Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical KUNNATH CHALI THALAMUNDA KOODALI | KOODALI | KANNUR | KERALA | - | Rejected-Technical L2 |
| Sl No | Description | Qty | Unit | sajithvc L1 | Madhusuthanan K P L2 |
|---|---|---|---|---|---|
| 1.00ELETRIFICATION | |||||
| 1.00 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group C | 98 | point | 1,541.86 ₹1,51,102.28 Lowest | 1,576.54 ₹1,54,500.92 |
| 1.00 | 1.4:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. | 2 | point | 2,081.47 ₹4,162.94 Lowest | 2,128.29 ₹4,256.58 |
| 1.00 | 90.3.20.3:Supply & installation of light fittings on TW round block
Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture | 52 | each | 1,235.04 ₹64,222.08 Lowest | 1,262.82 ₹65,666.64 |
| 1.00 | 1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required. | 4 | each | 115.39 ₹461.56 Lowest | 117.99 ₹471.96 |
| 1.00 | OD181229/2024-2025:Supply and providing the following types and power rated lamps in the existing fittings as required. B22 LED bulb 9W | 4 | each | 128.71 ₹514.84 Lowest | 131.61 ₹526.44 |
| 1.01 | OD181238/2024-2025:Supply ,Conveyance, installation, testing and commissioning of 12 W LED Bulkhead Light fittings Lumen output - 600, Housing - High pressure die cast aluminum directly on wall including giving connections with required length of 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.(LUKER STYX ECO BULKHEAD LIGHT 12W LBKOVSL12/equivalent) | 3 | each | 669.25 ₹2,007.75 Lowest | 684.3 ₹2,052.9 |
| 1.01 | OD181350/2024-2025:Supply ,conveyance, installation, testing and commissioning of 2 feet LED mirror light fittings directly on wall including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.( Philips Mirrormodel no.31165/equivalent) | 2 | each | 1,915.94 ₹3,831.88 Lowest | 1,959.04 ₹3,918.08 |
| 1.01 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply | 35 | each | 2,179.6 ₹76,286 Lowest | 2,228.63 ₹78,002.05 |
| 1.01 | 90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell | 4 | each | 190.69 ₹762.76 Lowest | 194.98 ₹779.92 |
Tender Value
₹10.6 L
EMD Value
₹26,597
Closing Date
5 Jun 2025, 3:00 pmClosed
Assisstant Executive Engineer
Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery
GENERAL-Construction of PWD Complex at Kannur - Phase II - Electrification of First Floor.-Electrification-General Electrical Work
2025_PWD_766960_1
PWD/BLDG/TR/20850/2024_6_1_1/1
Open Tender
Electrical Works
Item Rate
180 days
KANNUR
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹26,597
8 Dec 2025
29 May 2025
7 Jun 2025
29 May 2025
5 Jun 2025
29 May 2025
Amount
ELETRIFICATION
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.4:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD181229/2024-2025:Supply and providing the following types and power rated lamps in the existing fittings as required. B22 LED bulb 9W
OD181238/2024-2025:Supply ,Conveyance, installation, testing and commissioning of 12 W LED Bulkhead Light fittings Lumen output - 600, Housing - High pressure die cast aluminum directly on wall including giving connections with required length of 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.(LUKER STYX ECO BULKHEAD LIGHT 12W LBKOVSL12/equivalent)
OD181350/2024-2025:Supply ,conveyance, installation, testing and commissioning of 2 feet LED mirror light fittings directly on wall including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.( Philips Mirrormodel no.31165/equivalent)
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
OD181522/2024-2025:Supply and providing every additional length of down rod of suitable size heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required.
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.14:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD181242/2024-2025:Supply and providing test joint for the earthing system using 2Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe ete as required. 2 x 25 x 3 mm GI strip
OD181228/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required. 25 x 3 mm GI strip
OD181233/2024-2025:Supply and laying bare earthing conductors of the following sizes laid 0.6 m below ground level including excavating trench of suitable size and refilling etc. as required (in ordinary soil). 3.15 mm copper conductor (10 SWG)
OD181230/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required. 25 x 6 mm brass bolt & nut
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
OD181227/2024-2025:Supply and fixing 63 A, HRC Fuse with HRC Fuse link with connections, in existing meter board
OD181225/2024-2025:Supplying and fixing 63 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD181240/2024-2025:Supply and fixing Digital multi function meter to read: V,A,F,PF-3 Phase accuracy class 1 LED
OD181241/2024-2025:Supply and fixing 2A, HRC Fuse with HRC Fuse link with connections, in existing meter board
OD181236/2024-2025:Supply and providing Blue colour LED indicators, AC/DC 22.5mm cut out dia
OD181239/2024-2025:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia
OD231497/2024-2025:Supply and fixing of Danger 415 V, 150 x 100 mm aluminium anodised legend plates as required.
OD181232/2024-2025:Supply and fixing 50 mm dia 6Kgff/cm2 PVC pipe including fixing the pipe with clamp/clips at 60cm spacing. etc as required (For Service Pipe)
OD181751/2024-2025:Supply and providing suitable Iron Hook grouted on wall for binding the service wire
OD231498/2024-2025:Supply and Installation of ABC stored pressure type 6 Kg capacity Fire Extinguisher with pressure indication complete conforming to IS 15683 with initial charging and Installation brackets etc as required
OD181559/2024-2025:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength.
OD181653/2024-2025:SITC of 6L capacity Water Purifier of power rating of 20 W with 6 Stages of purification having water storage capacity of 6 litres. Water Flow Rate:550 to 650 ml/minute suitable to operate with 230±10 V AC / 50 Hz ac supply.( Eureka Forbes Aquaguard Aura UV E-boiling, Ultra Filtration, RO treatment,Active Copper, Mineral Guard Technology, Water Purifier (Black & Copper), 6 Liter Aquaguard /equivalent)
OD181741/2024-2025:Supply, Installation, Testing and Commissioning of BIS certified 3.0KVA On-line UPS with following specification including the cost for minor electrical work for connectivity of UPS a. Input Voltage range : Single Phase 3 Wire, 230V/45-55Hz AC,voltage range 160-260V b. Output capacity : 3.0 KVA/72V c. Output Waveform : True Sine wave d.Isolation Transformer : With out e.output voltage : Single Phase 230V AC ,Voltage Regulation +/-1% f. Switching Device : IGBT Technology (IGBT power modules with 100A or above) g.Metering : "Digital meter with LCD display,AC input voltage, AC output voltage, Frequency, Battery DC " h. Power factor : 0.9 to Unity i. Over load capacity : 100%-125%, j. Indicators : "Mains ON, UPS ON, Battery ON, charging, overload etc k. Battery : "C10 6 Nos Tubular Battery-65AH Prefrably:Exide /Amaron, (12V each of same rating) l.Warranty : 3 year for battery and 3 year for UPS m. Efficiency : 90% or above n. Battery rack : Painted MS angle iron rack Suitable for the battery supplied. o.Certification : For UPS Manufacturer ISO 9001,ISO:14001 p.Certification For Battery Manufacturer ISO 9001, ISO:14001,Rohs,OHSAS,Minimum experience-10 year or above.
Madhusuthanan K P (BID ID -2221290)
Bidder Name
sajithvc
Madhusuthanan K P
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1250298.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .