EE, South 24 Pgs Elect Divn
57/2 DH Road
Remodelling of existing 24 beded Hybrid CCU at Diamond harbour Govt. Medical College and Hospital, South 24 Pgs to combat probable 3rd surge of Covid-19 cases - Arrangement for maintaining negative pressure and Air-conditioning work
2021_WBPWD_356849_1
WBPWD/EE/S24PED/eNIT18_3/21-22
Open Tender
A/C ORG
Item Rate
15 days
Diamond Harbour
Please refer Tender documents.
3 documents required · 3 mandatory
₹40,542
South 24 Pgs Elect Divn
7 Apr 2022
21 Dec 2021
6 Jan 2022
21 Dec 2021
4 Jan 2022
24 Dec 2021
23 Dec 2021
Amount
SITC of Single Skin Centrifugal Cabinet Type Fan complete with DIDW- forward/backward curved Direct/belt driven centrifugal blower Rotaion of fan 1435 RPM, Epoxy/ galvanized steel sheet cabinet with service access doors, Inlet & outlet drilled flanges 2.5 KW, 4 pole, IE - 2, IP -55 Standard 3Ph/415V/50 hz Motor with Fixed base, common base frame with spring isolators,Flange at inlet and outlet are provided to facilitate duct connection necessary hanging/supporting members,water prof VFD Panel for Fan's Speed control etc . Sound level-65 dba. Capacity 65 mmwg Static pressure,2500 CFM [Make : Fan-Air / Zeco / Edgetech]
SITC of 10 Micron Pre Filter with Frame, it will be fitted on Centrifugal Exhust fan & on the Fresh air Damper (Make: Spectrum/ Priyanka Engg./ AFI)
SITC of 0.3 Micron Hefa Filter,it will be fitted on Centrifugal Exhust fan.(Make: Spectrum/ Priyanka Engg. Spectrum/ AFI)
SITC of Motorized Duct Damper for out side Fresh air Control & AC Machine Air Control.(Make: Primier/ AFI/ Spectrum / System-Air)
Fabrication and erection of duct fabricated out of 24 SWG GI sheet complete with necessary flange connections, FRP flexible connections, GI brackets / hanger supports, to suit site condition & design layout. Exhaust Ducting,Supply ducting,Exhaust rille, (Make: TATA,SAIL,JINDAL)
Supply & Pasting Al. Foil face 9mm thick Nitrile rubber insulation on duct by adhesive gum.
SITC of 16A Limit switch for control the Fresh air Motorized Damper(Fresh air damper Will be Closed when open the Door.Fresh Air Damper will be Open when Close the Door)
Fan Lifting & Shifting Charges
SITC of Discrite Powder Coaed Al. Grill without VCD (Make:Primier/AFI/Air Primier/ System-Air)
Supply & Fixing of Bird Screen as per direction of E.I.C.
Supply and fixing of UVC EMIITTER for the above fan's for prevention of fungus , The minimum UV intensity in the coils shall be 700-800 UW-SEC/CM2. The unit shall be UL.Listed (UL-1995) and it should be suitable to fix the same in Fan's Duct.
Supplying, fabrication & fixing 2 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making Base Frame table type for installation of Exhuast Fan incl. drilling 2 nos holes in each channel. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm as per direction of E.I.C.
SITC of indoor & outdoor unit of High-wall Split Air Conditioner having following specification: Cooling capacity not less than 6400 Watt BEE levelling - 3-Star or more Capacity - 2.0 TR IS Compliance - IS-1391 Refrigerant - R410A/R32 Compressor - Rotary/Scroll Evaporator & Condenser Coil - Copper Operating outdoor temperature - 50ºC and above Power supply - 230V, 50Hz (±tolerance as per applicable standard) [Make: O.General / Mitsubishi Electric / Mitsubishi Heavy Duty]
Lifting & shifting incl. Erection & Commissioning Charges for 1.8/1.5/1.0 TR Hi Wall Split Air Conditioner as per direction of E.I.C.
Copper Refrigeration pipe line for Liquid Line (1/4" OD with 0.6 mm thick) with proper supports & brackets for 1.8/1.5/1.0 Tr Hi wall Split air Conditioner(make: Ryoku/Uniflow)
Copper Refrigeration pipe line for Suction Line (5/8" OD with 0.6 mm thick) with proper supports & brackets for 1.8/1.5/1.0 Tr Hi Wall Split & Hi Wall Split air Conditioner (make: Ryoku/Uniflow)
Supply & Fixing Pipe Insulation for Liquid Line (1/4" OD with 9 mm thick) with proper insulating for 1.8/1.5/1.0 Tr Hi Wall Split air Conditioner(make: Accroflex/Suprime)
Supply & Fixing Pipe Insulation for Suction Line (5/8" OD with 9 mm thick) with Proper insulating for 1.8/1.5/1.0 Tr Hi Wall Split air Conditioner (make: Accroflex/Suprime)
Control Cabling from Condensing Unit to Control Panel 3 Core 2.5 sq. mm. Communication Cable 1.8/1.5/1.0 Tr Hi Wall Split Conditioner (Make : Polycab/KEI/Finolex)
Supply & layingSoft Drawn PVC Drain Pipe 19mm dia with proper supports & brackets as per direction E.I.C. (Make: Suprime/Oriplast)
Supply and Installation of M.S. angle Bracket, making a hole incl. fixing accessories for providing condensing unit and cooling unit mending the good damages.
Note: 1) All the above rates should be quoted inclusive of all taxes & duties, District charges, Riverine charges and LWC as applicable, with cost of maintenance, servicing, supply & replacement of spares for 3 (three) years from the date of commissioning. 2) Total is rounded off to the nearest rupees.
NAYEE DISHA PROJECTS
Lyric International
Auto-Tech Projects Pvt.Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .