Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.0 LAdmitted-Finance | ₹8.0 L | L1 | Admitted-Finance |
| 2 | L2₹8.5 LAdmitted-Finance | ₹8.5 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Nev Tech L2 | DIAMOND ENGINEERING WORKS L1 |
|---|---|---|---|---|---|
| 1.00WIRING | |||||
| 1.01Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. | |||||
| 1.01 | Group C | 43 | Point | 1,500 ₹64,500 | 1,500 ₹64,500 |
| 1.02Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. | |||||
| 1.02 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire | 110 | Meter | 270 ₹29,700 | 100 ₹11,000 |
| 1.02 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | 190 | Meter | 300 ₹57,000 | 160 ₹30,400 |
| 1.02 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire | 80 | Meter | 410 ₹32,800 | 230 ₹18,400 |
| 1.02 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire | 35 | Meter | 500 ₹17,500 | 390 ₹13,650 |
| 1.02 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire | 100 | Meter | 650 ₹65,000 | 380 ₹38,000 |
| 1.02 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire | 25 | Meter | 900 ₹22,500 | 820 ₹20,500 |
Updated dates
Tender Value
₹7.8 L
EMD Value
₹15,600
Closing Date
27 Mar 2026, 6:00 pmClosed
Director
NIT Calicut, NIT Calicut Campus PO, Kerala, 673601
Electrical Renovation of Concrete Lab
2026_NITC_899521_1
Engg/EMU/JE2/049/Concrete Lab/2025-26
Open Tender
Electrical Works
60 days
NIT Calicut, NIT Calicut Campus PO, 673601
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹15,600
Yes
15 May 2026
20 Feb 2026
30 Mar 2026
20 Feb 2026
27 Mar 2026
20 Feb 2026
WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
4 X 4 sq. mm + 2 X 4 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet (3Module) and 15/16 A modular switch, connections etc. as required.
Supplying and fixing extra conduit down rod of 20 mm dia, 2 X 10 cm length, wiring with 2 X 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
Group A
Supplying of following specification exhaust fan including connection etc. as required. Make:havells/almonard or Equivalent
Heavy duty 380mm sweep exhaust fan speed>1400rpm
MCCB, MCB & DB'S
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.
160 A,36KA,FPMCCB
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
16 way, Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
8 way (4 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Double pole
Triple pole
Four pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP/FP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V "C" curve TP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCCB and MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
12 way (160 MCCB + 36), Double door
Supplying and fixing following rating, following pole, 415 V, C curve MCB suitable for inductive load in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply and fixing of Rotary Handle
Supply and fixing of Rotary Handle Vary depth suitable for MCCB rating upto 160A including necessory arrangement, cutting, welding, shaping etc. as required for fixing on exixting panel .
CABLE TRAYS
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required.
300 mm width X 50 mm depth X 1.6 mm thickness
EARTHING
Supplying and fixing 12 SWG copper wire on surface or in recess for loop earthing as required.
LED LIGHT
LED Batten light (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
18- 22 Watt -Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
BLDC FAN
Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 230 CM/Min (Minimum)
MV CABLE LAYING
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
MV CABLE JOINTING & END TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 95 sq. mm (45mm)
MISC.CIVIL ITEMS
Supply and fixing Fan Hook
Supplying and fixing of 8/10 mm "S/U" type steel fan hook including chipping,welding, painting making good the damages etc. as required
LABOUR
Removing following items, handing over to EMU store safely as required.
Tube light and Light fixture with/with out rad/clamp
Cealing fan with rad, regulator from switch board, including stacking of fan leafs
Point wiring including cealing rose, conduit, wires, switches(modular/piano type) switch board, clamps etc. as required
submain wiring including conduit, wires, clamps etc. as required
Switch board of any size including wires, switches(modular/piano type) switch board, clamps, GI/plastic box etc. as required
2C,4C,3.5C armoured Al/Cu Cable of size less than 35 Sqmm etc. as required
SP Main switch board (HRC) of any size including wires, switch board, clamps etc. as required
SPN DB (Fuce type) of any size including wires, DB, clamps etc. as required
Three phase DB (Fuce type) of size less than 1Mtr.X0.5Mtr. including wires, DB, clamps etc. as required
CABLE
Supply of following size PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988
3.5x95 Sq.mm
PANEL BOARD AND ACCESSORIES
BUS BAR
Supplying and fixing of copper bus bar suitable for 160A MCCB switch from switch to the busbar in the existing panel board Including drilling the holes, nuts and bolts and insulation on the bus bar with colour code, hylum sheet for covering the busbar and other necessory arrangements to meet IS codes etc. as required.
Drawing and Approval
Submission of as fitted drawings and SLD of the work in Autocad DWG and PDF format along with physical copy of the same in the format and standard to get the approval from electrical inspectorate.(along with seal,signature and license details) etc as required.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
BOQ_945487.xls
BOQ • 0.40 MB