| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 LAccepted-AOC | L1 | Accepted-AOC work awarded | |
| 2 | L2₹19.4 L+₹18,460 (0.96%)Rejected-Finance | L2 | Rejected-Finance Rejected being L2 firm | |
| 3 | Not Admitted-Fee/PreQual/Technical PLOT NO F28 COMPLETE COOLING SOLUTIONS LLP PHASE 8 INDUSTRIAL AREA SAS NAGAR MOHALI PUNJAB 160055 | S A S NAGAR | PUNJAB | 160055 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 4 | Not Admitted-Fee/PreQual/Technical SHOP NO 5 BACHAT BHAWAN UNA TEHSIL UNA HP 174303 | UNA | UNA | HP | 174303 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹36,800
Closing Date
23 Dec 2020, 6:00 pmClosed
Executive Engineer, Electrical Division, HP.PWD Ma
Executive Engineer, Electrical Division, HP.PWD Mandi
Providing Fire Alarm and Public Addressable System at Combined Office Building at Thunag, District Mandi HP
2020_PWD_43328_1
PW/MED/TA/NIT/ e-notice/20-21-5567-73 dt 03.12.20
Open Tender
Electrical Works
Item Rate
365 days
Thunag
Please refer to bid document
10 documents required · 10 mandatory
₹500
Executive Engineer, Electrical Division, HP.PWD Ma
₹36,800
8 Oct 2021
18 Dec 2020
24 Dec 2020
18 Dec 2020
23 Dec 2020
18 Dec 2020
Amount
Supply installation and Commissioning of UL 864 Listed and FM approved 10th edition 32 bit 2 Loops Analog addressable Fire Alarm System having the toatal panel capacity of 125 devices [Detector or device any combination]in each loop. The panel shall have a backit 2"-x-4.3/4" backit LCD Screen and the four way navigation push button at the top of the FACP. The panel shall have the capacity of strong up to 5000 events.The panel shall have multiple levels of password protection, automatic environmentalbe compensation for smoke detectors, Degrade mode operation, Polarity-insensitive detection circuits.support single-person Walk test, connectivity to aleased- line/city tie module. The panel shall disconnect back up, battery on the addressable FACP when its voltage drop below 19 VDC . The panel shall have a built in power supply of 170 Watts and battery charger. Battery chrger shall be able to charge the system batteries up to 33 AH .tHE PANEL SHALL HAVE 240 v ac POWER SUPPLY, 24 v smf BATTERIES SUFFICIENT FOR 24 HOURS IN STANDBY AND 30 MINUTES IN ALARM COMPLETE AS PER SPECIFICATION. The panel shall have the capacity of connecting additional 15 panels or network terminals with redundancy in the network . The panel shall have the capacity of connecting maxinum 8 remote terminals or 8 remote display. The panel shall be approved by UL 864 10 th Edition listed ULC,FM,CSFM And NYC Fire Department complete the work upto the entire satisfaction of Engineer In Charge. MAKE:- Siemens Fire Finder / Honey Notifier / Tyco / Bosch.
Supply, Installation and Commissioning Of UL Listed and FM Approved repeater Panel. The panel shall be able to give location of all fire and fault and isolation conditions of addressable units main Fire Alarm panel via the address codes and also having remote System control capabilities. The panel shall have have a 160 Characters backlit LCD Screen Panel will show all details of above panels, complete the work upto the entire satisfaction of Engineer in Charge. MAKE:- Siemens Fire Finder / Honey Notifier / Tyco / Bosch.
Supply Installation and Commissioning of UL and FM approved intelligent Addressable Multicriteria Detector having responsiveness of photoelectric,thermal [Rate of rise and fixed ] Builts in isolation [In built fault isolator in detector]ionization technology and false alarm resistance along with standard base. The detector shall be Polarity insensitive dust resistant photoelectric chamber, Automatic environment compensation ,Field programmable as rate of rise or fixed temprature. The detector shall have Tri-Color detector-Status light emitting diode [LED] with 360 degree view. The detector shall be approved by UL,ULC,FM,CSFM and NYC Fire Department complete the work upto the entire satisfaction of Engineer In Charge. MAKE:- Siemens Fire Finder / Honey Notifier / Tyco / Bosch.
Supply Installation and Commissining of UL Listed and FM Approved intelligent Addressable Heat Detector having responsiveness of thermal [Rate of rise and Fixed ], Built-in isolation, ionization technology and false resistance along with standard base The detector shall be Polarity insensitive Automatic environment compensation, field programmable as rate of rise or fixed temprature. The detector shall have Tri-Color detector-Status light emitting diode [LED] with 360 degree view. The detector shall be approved by UL,ULC,FM,CSFM and NYC Fire Department complete the work upto the entire satisfaction of Engineer In Charge. MAKE:- Siemens Fire Finder / Honey Notifier / Tyco / Bosch.
Supply Installation and Commissining of UL Listed and FM Approved single action Manual Pull Station MCP shall be Built in isolation polarity insensitive, shock and vibration resistant,inbuilt isolator MCP shall be approved by UL,ULC,FM,CSFM and NYC Fire Department complete the work upto the entire satisfaction of Engineer In Charge. MAKE:- Siemens Fire Finder / Honey Notifier / Tyco / Bosch.
Supply Installation and Commissining of UL Listed and FM Approved intelligent Addressable Out put with one input module with Built in isolation having facility to activate sounders,AHU Tripping etc. Module shall be polarity insensitive, inbuilt isolator approved by UL,ULC,FM,CSFM and NYC Fire Department complete the work upto the entire satisfaction of Engineer In Charge. MAKE:- Siemens Fire Finder / Honey Notifier / Tyco / Bosch.
Supply of UL Listed and FM approved Line Isolator for isolating the section of Circuit incase of Short in the Addressable Loop wiring complete in all respect. Make Siemens Cerberus/Schneider Electric [ESMI]/Honey Well XLS3000
Supply Installation and Commissining of IEC60849 approved Glow Type EXIT/Stair/Emergency Exit Sign Board as finalized by Engineer in charge on both side showing marking [Runing Man,Arrowand Exist] and hanged with the ceiling with chain and faster complete the work up to the entire satisfaction of Engineerr in Charge. Make PES/HEINRICH/OMEX/COOPER/AGNI/Falcon / Cystom.
Supply and Erection of PVC Insulated Two core FR Copper conductor cable ISI Marked in PVC Pipe recess/ Surface complete in all respect Make Finolex/Polycab/Plaza
Supply Installation and Commissining of Universal Power supply 24 V/5A shall be operated at 100-240 V AC, Out put Voltage 26 V to 29 V DC
Supply ,Installation, Testing,and Commoissioning of voice controller 12 Analog inputs [With 48v Phantom power per channel ] 8 Analog output,configurable signal processing,Rich palette of processing and logic objects,48 channel, low Latency,Fault Tolerant Digital Audio Bus, Clear front Panel LED indication,Bi-Directional Locate Functionality,12 Control inputs and 6 Logicoutputs for GPIO integration input impedance 3.5 Komega Maximum input level +20dBu with 0dbinput gain+8dbu with 12 db gaininput noise [e.i.n] <128dbu typicalwith 150 omega source,Maximum output Level+19dbu Frequency Response 20 Hz-20Khz[+0.5db/-1db].Dynamic Range 108dbTypical22Hz-22KHz unweighted. Make JBL / Bosch / honey Well / Siemens.
Supply ,Installation, Testing,and Commoissioning Of 6W Ceiling/Wall Loudspeaker component 100 mm[4inch]Full range Frequency Range [-10 db ]60 Hz-18 Khz coverage 130 degree conical ,Sensitivity [2.83v@1m]:93 db [1khz-8khz] Termination Bare wire, Nominal Driver, impedance 8 Ohms Driver Power capacity;20W,70V/100V, Transformer Taps 6W,3W.1.5W.[0.75W at 70V only] Make JBL / Bosch / honey Well / Siemens.
Supply ,Installation, Testing,and Commoissioning Of Amplifier 4 Channel 300 W per Channel: Digital Signal Processing 96 KHZ-32 bit floating point Voltage Gain [At maximum level setting]4/8 Omega 70Vrms and 100 Vrms operation 34 db, Frequency response [8 Omega,20 Hz-20 Hz-2-0 Knz>108db, load impedance stereo/DualMode 2 Omega-16 Omega,70Vrmsand 100 Vrms Make Marti9n Audio/D&B AudioTechnica/Crown
Supply, Installation and Commissioning of 2 core 1.5 sqmm speaker cable. Make Finolex/Polycab/Plaza
Supply and Erection of PVC Pipe 25 Mm dia ISI marked [Medium] recessed in wall/ceiling etc the cosrt of PVC Bends. Inspection bends Iron Hooks,Iron hooks and cement concrete etc complete in all respect in all respect upto the entire satisfaction of engineer in charge of work Make BEC/Diplast/Polyplast/Polycab
Supply Installation Testing and Commissioning of 15U Standard Rack to place all equipment Make Valrack,Comrack,HCL
Vowels Technology and Services
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .