The Superintending Engineer
Work of shifting of existing control room and erection, control wiring, yard light, control room electrification, Colony Electrification etc work in new control room at 66kV Kaprada S/S under Vapi AM Division.
331689
TCNS/TR/ETRM-35/2026-27
Open
Electrical
Works
Navsari
19 documents required · 18 mandatory · 1 optional
₹1,180
Gujarat Energy Transmission Corporation Limited
₹45,836
5 Aug 2026
5 Aug 2026
5 Aug 2026
27 Aug 2026
5 Aug 2026
SCHEDULE B-1: MAIN ERECTION
Sr. Description of work/Supply Unit Qty. Rate Amount
1 Laying of any size of 11KV/22KV XLPE/PILC cable Mtr 360 138.00
including excavation of trench 300mm wide & 600mm
deep including laying and filling up sand of 100mm
layer from bottom & bricks on three side of cable &
refilling the trench with Murram/soil & ramming etc.
Required bricks, sand, etc. will have to be supplied by
the contractor. Rates are inclusive of shifting of cable
drum to the site from S/S site store. Drum should be
handled only by jacking to avoid damage to cables.
2 Laying of any size of 11/22KV XLPE/PILC cable in Mtr 3250 63.00
ready made cable trench or in open space. Rates are
inclusive of shifting of cable drum to the site from S/S
site store. Drum should be handled only by jacking to
avoid damage to cables. SOR PART-D14
3 Erection of 66KV Equipment/Lighting Mast/ VHF Mast MT 6.31 2491.00
structure including punching of nut bolts. Rates are
inclusive of minor required fabrication and shifting of
same up to erection site from its s/s Store. SOR PART-
4 Installation of earthing strip/ MS round bar in any kind Mtr 400 43.00
of soil except SR/HR Soil as per earthing Philosophy
1)Including digging of 600mm depth and 400mm wide
2) Cutting,bending,laying and fixing of Earthing grid
3) 75x10MM/50x6mm GI strips: Fixing of two bolt at
each stright joints and lap welding, removing oxide
films formed during welding, applying two coats of red
oxide and black powder after welding and applying zinc
rich paints on welded joints.
4)25/32/36/40MM dia MS Rod: Lap welding at each
stright & cross joints, removing oxide films formed
during welding, applying two coats of red oxide and
black powder after welding and applying zinc rich
paints on welded joints.
5) Including supply of red oxide paint, black powder,
HDGI Nuts & bolts as per specification.
6) Back filling of the trench with yellow/ Normal soil.
Structure & Equipment earthing:
1) Including digging of 600mm depth and 450mm wide
2) Cutting, bending as per required shape, laying and
fixing of risers from Grid to structures and Equipments.
3) Lap welding, removing oxide films formed during
welding, applying two coats of red oxide and black
powder after welding and applying zinc rich paint on
welded joints including supply of HDGI Nuts & bolts for
all connections including suporting to structures etc as
per specification.
4) Back filling of the trench with yellow/ Normal soil.
SOR PART-D24-a(b)50x6 mm GI strip/MS round bar
up to and including 25mm
5 Providing Bore type earthing with drilling of minimum No 10 871.00
20 following mentioned depth in Rocky (HR/SR) Soil
as per e of GETCO.1) Work includes inserting
20/25mm dia MS Rod (for 66k MS Rod (for EHV S/S)
in bore depth and to be connect-grid at junction point
by proper welding at both end.2) This includes cutting,
fabrication & welding of flat.3) Refilling and
compression of surrounding areas with Ne ground
enhancement material etc. wherever applicable Soil
strata and earthing design calculation.4) Required G.I.
Earthing strip/ MS rods will be supplied by GETCO
Free of Cost.5) Earthing material like Normal/yellow
soil, ground enhancement material (0.5CMT/Meter
depth),water,etc. shall be supplied by contractor. SOR
PART-D26 (f) 3 Mtr depth
6 (a) Supply, installation, testing and commissioning of No 19 13893.00
maintenance free treated earth electrodes, suitable for
Normal Soil as per drawing no-GETCO/E/STD/P-
021(1 of 2) R3 dated-29.05.2020 and techanical
specifications GETCO/E/TS-Maintenance free earth
pits/R1 dated 04.06.15 for 66/11KV substation with
gound enhancement materials/back filling/grounding
compound as per IEEE 80-2000 clause 14.5(d) and as
per part-7 of IEC-62561 using Copper bonded earth
electrode (With 250 micron copper coating) having
24mm dia(Min) and 3000mmlength which shall be
capable of handling STC of 25 KA-1 sec. work also
includes providing BB masonary Inspection
chamber(Manhole) incl.light type CI cover.
7 Erection of Control Panel relay panel or C/R panel or Per 8 691.00
RTCC panel including grouting of panel, jointing with No.
adjoining panels including required fabrication of entry
of control cables and complete vermin proofing. Job
includes supply of required bolts,nuts etc.and shifting
of panel from S/S site store to work site. joining panels
& entry of control cables and complete vermin proofing.
SOR Part H1- d)66kV
8 Erection of 11KV CB panel of any make including Per 15 2076.00
grouting, jointing with adjoining panels & horizontal, No.
vertical levelling including required fabrication in
control panel or required stone cutting in flooring for
entry of power cable, control cable, including
interpanel wiring and complete vermin proofing. Job
includes supply of required bolts, nuts etc. and shifting
of panel from S/S site store to work site. SOR Part H2
9 -DO- but for LT panel GETCO including fixing of all Per 1 968.00
switches bus bars etc. SOR Part H3 No.
9 -DO- but Erection of Battery charger of any make as Per 1 968.00
per manufacturer's instruction manual including No.
grouting, vermin proofing. SOR Part H4
10 Erection of 100AH, 110Volt D.C. battery set on Per 1 6227.00
wooden/FRP stand as per instruction manual of Set
supplier, including first filling of battery electrolyte,
proper connection of cells and applying,
charging/discharging cycles as per manufacturer's
instruction manual and instruction of EIC. SOR Part
11 Erection of station transformer of 22KV or 11KV/430V, Per 1 2214.00
63/100KVA on its plinth, grouting of foundation bolts, No.
fixing of channels, danger board etc. including
connection with power cable/LV cable terminations
including shifting from S/S site store to plinth as per
instruction of EIC.SOR Part H6
12 Erection of support structure for 11kV Power cable No 2 998.00
termination at 11kV bushing for 10/15/20MVA power
transformer as per Drawing No.:- GETCO/E/06S-
STD/11kV STR-A2-02. 1) Material for supporting
structure will be supplied free of cost by GETCO.2)
Necessary wooden clamps with required nut-bolt-
washers & HDPE rubber piece for packing etc. as per
drawing shall be supplied by the contractor.3) Job also
includes miNo.r fabrication if required as per instruction
of EIC. SOR PART D
13 Erection of support structure for Station transformer as No. 1 2196.00
per GETCO drawing no. GETCO/E/06S/STD/11KV
STRA3-03. Necessary wooden clamps as per drawing
with required nut-bolts-washers & HDPE rubber piece
for packing etc. shall be supplied by contractor. Job
also includes erection of required 11KV LA and DO
fuse and minor fabrication if requires as per instruction
of EIC. DO fuse and 11kV LA will be supplied by
GETCO free of cost. SOR PART D34
14 Providing & fixing Set of following Items on erected Set 2 27303.00
11kV support structure system for power cable of
66/11kV Transformer as per GETCO drawing
No..GETCO/E/06S-STD/SPL-028A, R3, DT-
26.10.2016 and instruction of EIC.
1) Allu. alloy bus bar of size 120X20X2000 mm with
heat shrinkable anti tracking tubing : 03 Nos.
2) 11kV SRI of PCD 127 mm - 12 No.
4) Copper laminated fusion welded flexible jumper of
size 75 X 10 X 600 mm having 2000 Amp capacity :
(4) Bi Metalic Plate (Al/Cu): 03 No.
(5)11kV Heat Shrinkable anti tracking Sleeve on Al Bus
bar of all three Phase: 06 mtrs
(6) Including required GI/SS nut-bolt and washer of
good Quality for fitting support structure.
(7) All live parts shall be coverd with heat shrinkable
MV insulated tape/ sleeve.SOR PART- D-35
15 Fabrication for erection of any L.S. 2 4992.00
Equipment/Structure/panel or anywhere in s/s & F.B. (Max.)
at other end as per Inst. Of E.I.C.SOR Part D-31
16 Erection of 11kV D.P. Structure as per GETCO No. 12 2196.00
Drawing No.: GETCO/E/06S-STD/11 kV STR-A1-01.
1) Job includes erection of 11kV A/B Switches, 11kV
Pl, jumpering between 11kV cable to 11kV bus, etc. on
erected structure.
2) Material for DP structure, AB switches, Pl and
conductor for jumpers will be supplied free of cost by
3) Necessary wooden clamps with required nut-bolt-
washers & HDPE rubber piece for packing etc. to hold
11kV power cable as per drawing shall be supplied by
the contractor.
4) Job also includes minor fabrication if rquired as per
instruction of EIC.
17 Erection of 11kV D.P. Structure as per GETCO No 12 2196.00
Drawing No.: GETCO/E/065-STD/11 KV STR-A4-04.
1) Job includes erection of 11kV A/B Switches, 11kV
LA, jumpering between 11kV cable to 11kV bus, etc.
on erected structure.
2) Material for DP structure, AB switches, Pl and
conductor for jumpers will be supplied free of cost by
3) Necessary wooden clamps with required nut-bolt-
washers & HDPE rubber piece for packing etc. to hold
11kV power cable as per drawing shall be supplied by
the contractor.
4) Job also includes miNo.r fabrication if rquired as per
instruction of EIC.
18 Stringing of Single ACSR Dog bus between 11kV D.P. Set of 12 4786.00
Structure (A1) to cross boundry structure (A4) in all 3-
respect.1) Job includes fixing of all fittings and Phase
accessories on erected DP structures.2) Single
tension hardware suitable for ACSR Dog Cond.- 6 set
shall be supplied by the contractor.3) Necessary
ACSR DOG conductor, 11kV Insulators will be
supplied by GETCO free of cost.SOR PART-D38
19 Providing of M15 Grade Concrete for various Cmt 10 5276.00
equipment structure, Guy, 11kv DP, M.K. Box, Neutral
channels, cable support channel, grouting of Pole/
Flood light structure with cement, sand & metal in
proportion of 1:2:4 respectively. 1) Work includes
muffing and with smooth cement mortar (1:6) finish.
2) Necessary sand, metal, water & cement shall be
supplied by the contractor. SOR PART D39
20 Excavation in Hard Rock for excavation of Earthing Cmt 15 525.00
Pits/trnchs, Yard Light Poles only. SOR PART D40
21 Loading, Transporting & Unloading of all material for Job 4 51720.00
66kV substation like Structure, indoor & out door SS
Equipments, DP Structure, earthing materials, battery
set, fire wedge, GI/MS scrap, all other required
materials, etc. in all respect for substation & opposite
end feeder bay from Store (Any store either const. div
or R&M store within respective Zone) to substation
This job also include crediting balance material as
respective construction divison store at no extra cost.
22 Supply & laying of 1 CoreX25mm2, armroured Copper Mtr 50 199.00
Cable, multi-strand flexible of approved make ISI
marked in ready made trench or PVC pipe from Battery
Charger to Battery Set including termination at both
side as per inst. of EIC. SOR PART D42
23 Providing and fixing of various type of sign Board, Job 1 24957.00
sticker, Big Sign Board, earthing pit board, earthing pit
Board & Single line diagram etc as per instruction of
IEC. Sticker of red, white, black Letters are to be
utilised for various sign board. SOR PART D43.
Earthing Pit Board Size:- 6" x 6" -30 Nos.
Safety Slogan Board, Hard Sheet board size 2' x 2'and
4mm thick (Gujarati Language)- 2 Nos.
Safety Slogan Board, Hard Sheet board size 3' x 2'and
4mm thick (Gujarati Language) with red and Yellow
colour.-03 Nos.
Single line diagram size 5' x 3' Digital with Alluminium
frame with fitting and as per approved diagram given
Big sign board size 5' x 4' and 2mm thickness
indicating sub station name digital with S.S. rod with
hole & as per approved symbol with fitting charge.-
Switch yard sign Board 12" X 6" with 2 mm Thickness
black & white Gujarati language.-25 Nos.
Safety Slogen Board size 2" x 6" in side control room.-
Various type of control room equipment sticker size-24
cms x 5cms.--18 Nos.
Safety picture board size :- 3' x 3' (Laminated for O/D
Name plate board of transformer size :- 2' x 1'- 04 Nos.
Cable marker size:- 6" x 6", Radium, fixed on 750mm
long M.S.Rod for fixing arrengement.- 30 Nos.
24 Providing and fixing of Radium sticker for out door and sq. 4000 2.00
Indoor equipments identification like LA, ISOlator, Inch
Circuit breaker, transformer, CT,PT,MK box, C&R
panels , 11KV panel board etc. SOR PART - D44
25 Providing and Fixing of fire stand from 75mm Gl pipe Job 1 4992.00
A class ISI mark heavy duty having 5ft width and 4ft
height as per inst of Engr. In charge work includes
cutting,drilling,welding of pipe as required. Fabrication
and supply of 16mm dia meter hook required size for
buckets. 4 Nos.of fire buckets are to be provided fire
stand should grouted with excavation of pit size
300mm x 300mm-2 Nos. of 600mm depth with 1:3:6
mix muffing 300mm in height including leveling of
stand. The fire stand is to be painted with post box red
colour of approval quality as per instruction of EIC. All
required approved material including
cement,sand,metal etc are to be provided by
contractor. SOR PART D45
26 Providing, Fabrication and erection of VHF set entena Job 1 1498.00
support pipe on control room by providing 25mm dia.
GI pipe of length 20 feet.including providing & fixing of
4 nos. of guy from GI wire 10 SWG. This job includes
painting of GI pipe by good quality paint white and red
alterlatively SOR PART D46
27 Labour charge for fixing of 11KV XLPE Indoor/Outdoor No 10 748.00
cable kit of any make for size 95 to 300mm2. Cable kit
provided by GETCO.
28 Providing & Fixing of RAYCEM/MSEAL/CABSEAL No 40 6139.00
make heat shrinkable type 11KV XLPE Indoor/
Outdoor cable Termination kit suitable for 11KV, 3C x
95 sqmm to 300 sq.mm XLPE power cable. SOR
29 Providing & Fixing of Aquaguard Total Reviva Water No 0 6889.00
R.O. Plant including Commissioning & Testing and
also with required peripherals for installation of plant
as per site condition
(1) Dimension: 320 X 275 X 410 mm
(2) Weight : 8 KG
(3) Water flow : 8 to 12 LPH
(4) Input power : 230V AC
(5) RO membrence : TFC spiral
You have to provide guarantee for the 12 month from
the installation. SOR PART D50
30 Providing and fixing of ISI mark Rubber Matting sheet sq.mtr 60 4492.00
Suitable for 11KV Class As per following specification.
Reference IS:15652-2006 with latest amendment.
Suitable for Voltage Class :B
Max Use Voltage : 11KV
AC proof voltage : 22KV
Dielectric strength : 45KV
Leakage current : < 10 micro ampere
Make : Vardhman or equivelent ( Rubberhouse India)
Thickness :2.5 mm.
Surface :Chequred on one side and other side plain.
Contractor has to supply Rubber Matting sheet as per
IS:15652-2006 with latest amendment specification
and shall submit test certificate for routine test as per
relevant IS SOR PART D51
31 Providing & fixing of reputed make ISI mark Fire No
Extingusher.with leatest ammendment in standards as
per following capacity.Note: Contractor shall submit
Test certificate for routine test as per relevant IS. SOR
a) Chemical powder 9kg Capacity No 2 6301.00
b) CO2 type - 6.5Kg No 2 7047.00
c) CO2 type - 22.5Kg No 2 17817.00
d) Mechanical foam type - 50Ltr Mtr 1 14499.00
32 Dismantling of any size of 11KV/22KV XLPE Mtr 2500 69.00
/PILCcable including excavation of trench 300mm wide
& 600mm deep including laying and filling up sand of
100mm layer from bottom & bricks on three side of
cable & refilling the trench with Murram/soil & ramming
etc. Required bricks,sand,power cable marker
/C.I./G.I. plate etc.will have to be supplied by the
contractor. Rates are inclusive of shifting of cable drum
to the site from S/S site store. Drum should be handled
only by jacking to avoid damage to cables. SOR PART-
33 Dismantling of any size of 11/22KV XLPE/PILC cable No 1000 31.50
from ready made cable trench or in open space. Rates
are inclusive of shifting of cable drum to the site from
S/S site store. Drum should be handled only by jacking
to avoid damage to cables. SOR PART-D14 (50%)
34 Dismantling of 66KV Control Panel, relay panel or C/R Per 8 345.50
panel or RTCC panel including grouting of panel, No.
jointing with adjoining panels with providing required
B/N including required fabrication for joining panels &
entry of control cables and complete vermin proofing.
SOR Part H1d (50%)
35 Dismantling of 11KV CB panel of any make including No 15 1038.00
grouting, jointing with adjoining panels & horizontal,
vertical levelling including required fabrication in
control panel or required stone cutting in flooring for
entry of power cable, control cable, including
interpanel wiring and complete vermin proofing. Job
includes supply of required bolts, nuts etc. and shifting
of panel from S/S site store to work site. SOR Part H2
36 Dismantling of LT panel board of any make as per No 1 484.00
manufacturers instruction manual including grouting,
vermin proofing etc.SOR Part H3 (50%)
37 Dismantling of Battery charger of any make as per Set 1 484.00
manufacturers instruction manual including grouting,
vermin proofing etc.SOR Part H3 (50%)
38 Dismantling of 100AH, 110Volt D.C. battery set on Per 1 3113.50
wooden/FRP stand as per instruction manual of No.
supplier, including first filling of battery electrolyte,
proper connection of cells and applying,
charging/discharging cycles as per manufacturer's
instruction manual and instruction of EIC.SOR Part
39 Dismantling of station transformer of 22KV or Per 1 1107.00
11KV/430V, 63/100KVA on its plinth, grouting of No.
foundation bolts, fixing of channels, danger board etc.
including connection with power cable/LV cable
terminations including shifting from S/S site store to
plinth as per instruction of EIC.SOR Part H6 (50%)
40 Steel chair, “S” Type , over hanging arm with cushion Nos 4 1850
with cane seat / back 1” X 16 gauge round pipe frame.
41 Steel rack of size 30’’x36”x15” with three partitions, Nos 3 2100
prepared with 20 gauges.
42 Steel Table of size 54”x30”x30” one side three Nos 1 8750
drawers, one side shelf 1x 18 gauge square pipe with
Nova pan pre laminated top.
43 Computer Table made from pre laminated Board size Nos 2 7200
with Key Board facility and Drawer with looking facility
with continues printer out facility and Mouse Tray and
also with special Tray for CPU and UPS having I.D.
X 21 inch X 2.5.FT.
44 Steel revolving Chair, revolving & tilting, low back high Nos 4 4600
type seat with foam rubber 3” in seat 2” in back with
good quality raxine cover, Five legs, Chromium plated
45 Steel cup board of size 78” x 36” x 19” four partition, Nos 2 9200
Door and shelves 20 Gauge, Body 22 Gauge, color
Olive green as per drawing attached.
TOTAL - 1 ( SCHEDULE B-1 )
SCHEDULE B - 2 : CONTROL WIRING
Sr. Rate Amount
Description of work/Supply Unit Qty.
1 Preparing of complete schedule of wiring for line/ Bay 7 1996.00
transformer bay for 66KV bays in triplicate. necessary
drawing will be provided by the GETCO. Schedule should be
approved by EE. or DE in charge.
2 Laying of Up to 7 Core Control Cable , 1.1KV PVC, Per 6050 6.00
armored copper/ aluminum control cable in readymade cable RMtr
trench and inside Hume pipe including binding / clamping of
cable with GI wire or saddles as per the requirement including
the supply and fixing of identification tags at both ends in
between if required to following size (Cable will be supplied
by GETCO at free of cost). SOR Part H7a
3 As above but for, Above 7 Core Control Cable . SOR Part Per 2890 10.00
4 Dismantling of Up to 7 Core Control Cable , 1.1KV PVC, Per 4000 3.00
armored copper/ aluminum control cable in readymade cable RMtr
trench and inside Hume pipe including binding / clamping of
cable with GI wire or saddles as per the requirement including
the supply and fixing of identification tags at both ends in
between if required to following size (Cable will be supplied
by GETCO at free of cost). SOR Part H7a (50%)
5 Dismantling as above but for, Above 7 Core Control Cable Per 2000 5.00
. SOR Part H7b (50%) RMtr
6 Laying of Up to 7 Core Control Cable , 1.1 KV PVC Per 800 21.00
armored copper /aluminum cable in ground by digging trench RMtr
of suitable width and 450 mm depth in any type of soil
including supply and fixing of identification tag on both end
and at distance every 100 mtrs . SOR Part H8a
7 As above but for, Above 7 Core Control Cable. SOR Part Per 500 26.00
8 Dismantling of Up to 7 Core Control Cable , 1.1 KV PVC Per 500 10.50
armored copper /aluminum cable in ground by digging trench RMtr
of suitable width and 450 mm depth in any type of soil
including supply and fixing of identification tag on both end
and at distance every 100 mtrs . SOR Part H8a (50%)
9 Dismantling as above but for, Above 7 Core Control Cable. Per 500 13.00
SOR Part H8b (50%) RMtr
10 Providing and fixing 'B' class G.I. pipes of following size for
cable protection including fixing with the structures.( Non
SOR) including required 'L' & 'T' band,coupling for CT,PT,
Transformer, M.K.Box cabling on structure including required
fabrication.(weight of pipe-25kg/meter)
11 {a} 40mm dia SOR Part H10a Mtr 200 255.00
12 {b} 50mm dia SOR Part H10b Mtr 120 284.00
13 Termination of Control Cable at Panel / M.K./ Equipments End 210 199.00
including supply of required size of brass double
compression cable glands, ring type lugs, printed ferrules,
PVC Binding Tape, Buttons etc. for Up to 7 Core Control
Cable. SOR Part H11-a
14 As above but for Above 7 Core Control Cable., SOR Part End 50 349.00
15 Providing & installation and commissioning of remote control Job 2 6489.00
switch board for ON/OFF control of all 11kv panel at operator
table with supply of good quality metal sheet box (18 SWG)
size 450 x 450 x 125 mm with door, 20 nos standard ISI make
and rating industrial push botton, indication lamp(LED) with
installing accept/ reset arrangement with required ISI marked
copper flexible wire size 2.5 Sq. mm including complete
wiring in PVC pipe and fixing on wall as per inst. of EIC.only
19/27 core x 2.5 sqmm cable supply by GETCO.
16 Providing and fixing of all weather proof, cold rolled sheet No 7 21549.00
steel junction box for CVT & PT, CT terminations with 30 Nos.
of disconnecting type, 'Elmex' make CATDM 4 or equivalent
type connectors and required nos. of fuses, links, internal
wiring having 6 sq.mm. multi strand Cu cable with ring type
lugs etc.as per instruction of Engineer-in-charge,as per
drawing enclosed SOR Part H13
TOTAL - 2 ( SCHEDULE B - 2 )
SCHEDULE B - 3 : YARD LIGHTING
Sr. Rate Amount
Description of work/Supply Unit Qty.
1 Providing & fixing of all weather proof, cold rolled sheet No 2 24732
steel AC Panel - 2 for Yard-Light AC supply having
(1) 63A 4P MCB : 01 NO
(2) MCX-12A contactor : 01 NO
(3) Digital Timer : 01 NO
(4) 20A TPN MCB : 06 NOS
(5) Indication lamp " 03 NOS
(6) Push Butten : 02 NOS
(7) Terminal Connector as per site requierment and other
detail as per drawing enclosed including grouting &
Necessary fabrication of GI Angle or fixing on GI Structure
and earthing with main grid as per instruction of EIC.a SOR
Part D53 (01 for Yardlight, & 01 for ACDB)
2 Supply & laying of following size Control/L.T power cable in Mtr 150 292
readymade cable trench or by excavating in any type of soil
cable trench size 1 ft. wide 2.5 ft. depth and refilling the
same as per the direction of EIC. Item Includes the cable
laying upto termination box with clamps & proper clamping
of cable on gantries by GI pipe & glands as per direction.
Item includes providing & supply of bircks, sand as per
requirement. The L.T power cable to be provided by
contractor as under :As per ISI 1554 (Part-I). 3.5 Core x
mm2 Alluminium cable -Armoured, from distribution X'mer
to Main Distribution Board near dist. X'mer and from MDB
to indoor LT panel board (LTPB) - both 2 runs. SOR Part
3 Supply & laying of following size Control/L.T power cable of Mtr 300 175
FINOLEX or equivalent ISI make in readymade cable
trench or by excavating in any type of soil cable trench size
300mm wide and 600mm depth and refilling the same as
per the direction of EIC. Item Includes the cable laying up
to termination box with clamps & proper clamping of cable
on gantries by GI pipe & glands as per direction. Item
includes providing & fixing of bricks, sand as per
requirement to protect cables . The L.T power cable to be
provided by contractor as under :As per ISI 1554 (Part-I).
Core x 25 mm2 Aluminum cable -Armored, from LT panel
board (LTPB) to Yard Light AC MK (AC Panel-2)., AC Panel
1 in C.R. and yard AC BoxSOR Part D56
4 - - do - - 4/7 C x 4mm2 Copper cable - Armoured, from Mtr 800 19
yard-light AC panel-2 to all yard-light fixture junction boxes
on LM & street light pole & Station transformer to Colony &
LT panel to watchman cabin. Note:- cable laying work either
in ready made cable trench or by excavating in any type of
soil if required (Only laying. Cable will be supplied by
GETCO)SOR Part D57
5 - - do - - 4C x 2.5mm2 Copper cable - Armoured, from yard- Mtr 300 19
light AC panel-2 to all junction boxes on post top lantern
Note:- cable laying work either in ready made cable trench
or by excavating in any type of soil if required (Only laying.
Cable will be supplied by GETCO)SOR Part D58
6 Providing & fixing of 'B' class ISI marked GI. Pipe of Mtr 40 180
32/40mm dia for cable looping & road crossing with
necessary elbo/band for each pole & J.Box for yard lighting
& for control-room flud lights wiring work with fixing on wall
with shadles if required as per inst. Of EIC.SOR Part D59
7 Providing & erection of 7.0 mtr. long swaged type welded No 12 9983
GI tubular street light pole on the foundation in any type of
soil as per inst. of EIC. Confirming to relevent IS and as per
attached drawing no. GETCO/E/STD/LTG.POLE-R2 DT-
24-12-2019. SOR Part D60
8 Providing & erection of 4.5 mtr. long swaged type welded No 20 6988
GI tubular street light pole on the foundation in any type of
soil as per inst. of EIC. Confirming to relevent IS and as per
attached drawing no. GETCO/E/STD/LTG.POLE-R2 DT-
24-12-2019. SOR Part D61
9 Supply and fixing of Pole/Wall/Structure mounted FRP No 35 748
junction box standard make of required size with clamp,
providing 1 SPN MCB G class of 16 A having short ckt
breaking capacity of 10KA peak of standard ISI make like
L&T/ANCHOR/MDS /HAVELLS & 2 Nos. of stud type
connector of standard make like Connectwell. The cable
glands & lugs are also included for both incoming & out
going cablesAmp. of standard make like MDS/HAVELLS &
2 Nos. of stud type connector of standard make like
Connectwell. The cable glands & lugs are also included for
both incoming & out going cables.SOR Part D62
10 Earthing to tubular pole/luminaries,by coil type earthing at No 15 400
10 SWG, GI wire in earth pit of 1.5 mtr. Depth in any type
of solil by using salt/ coke (charcole) 16 kgs each &
remaining filling with BC soil & clamping the earth wire with
pole & Junction box.SOR Part D63
11 Providing and fixing of Single Piece Cast Alluminium with No 20 7487
full frame with Acrylic Cover integrated luminaries
Energy Efficient flood light luminaries on swaged pole / GI
structure by providing required fabrications, of
Philips/CGL/Bajaj/GE/Osram make, suitable for 1 x
Watt HPSV/T with allied accessories such as Capacitor
igniter, ballast, control gear box etc, 4 core 2.5 sq mm
double insulated flexible stranded wire should be used from
control gear fitting to junction box.SOR Part D64
12 Providing & fixing of LED street light fixtures (1/120W) ( No 12 9593.00
CGL cat no. LSTO120/CDL 120W or equipment under cat-
II or above as per R&B SOR) 4-core 2.5 mm2 double
insulated flexible strended wire should be used from control
gear fitting to approved SMC type unction box as per
instructin of EIC. SOR Part-D-66
13 Providing & fixing of 1 x 40W LED Post Top Lantern No 5 7556.00
Fixtures (CGL Cat No. LPTO-40/CDL 40W or equivalent
under Cat-II or above as per R&B SOR) complete fitting in
all respect and 4 core X 2.5 mm2 double PVC flexible
copper cabel from control gear fitting to SMC junction box
as per instriction of EIC. ( 4 no are to be provided on main
gate & 3 No are to be provided on 4 Mtr Tubular pole)SOR
14 Providing & fixing of all weather proof MAIN AC Distribution No 1 20650.00
Box -SOR PART-D-54
TOTAL - 3 ( SCHEDULE B - 3 )
SCHEDULE B - 4 : CONTROL ROOM INDUSTRIAL ELECTRIFICATION
Sr. Rate Amount
Description of work/Supply Unit Qty
1 Providing and fixing of DBS as AC Panel - 1 for CR of ISI No 1 6738
marked Powder coated Pearl DBS of ivory color , wall
mounting, Double door Distribution board of L&T, Heggar or
higher make fitted with 63Amp Phase Bus bar, Earth / Neutral
Bars and inter connecting wires with removable bottom gland
plates for all power cable entry from bottom with DIN Channel
,incoming contact and INO - 63Amp TPN MCB 'C' Series
,6Nos-20A SP MCB C Series and 13N0 -IOA SP MCB C Series
All MCBs are L&T, Anchor or Higher make only. Complete in
all respect and as per instruction of EIC. SOR Part D68
2 Supply & laying of following size Control/L.T power cable of Mtr 40 175
FINOLEX or equivalent ISI make in readymade cable trench or
by excavating in any type of soil cable trench size 300mm wide
and 600mm depth and refilling the same as per the direction of
EIC. Item Includes the cable laying up to termination box with
clamps & proper clamping of cable on gantries by GI pipe &
glands as per direction. Item includes providing & fixing of
bricks, sand as per requirement to protect cables . The L.T
power cable to be provided by contractor as under :As per ISI
1554 (Part-I). 4 Core x 25 mm2 Aluminum cable -Armored, from
LT panel board (LTPB) to Yard Light AC MK (AC Panel-2)., AC
Panel 1 in C.R. and yard AC Box. SOR Part D56
3 Supplying & Laying Sub-main lines of 3X2.5 mm2 ( two Rmtr 500 125
for P & N and one for Earthing) copper PVC insulated wier of
ISI brand in suitable standard make steel conduit pipe having
minimum 1.5 mm thickness of approved brand with ISI brand
with clmpes with it's associated accessories for various circuits
amanating from AC panel 1.as per inst. of E.I.C. SOR Part D69
4 Point wiring for control room tube lights, fans, exhaust fans, Point 95 1298
fency lights, water tight bulck head lights with PVC insulated
660 V grade standard copper wire in ISI make Gl conduct pipe
20 mm dia and 1.6 mm wall thickness size fitted with sadles on
the wall/ceilingt Size of wire shall be with 3C x 1 .5 sq.mm PVC
insulated copper wire for phase and neutral and earth wire [
Green] and 5 Amp Anchor/Roma or any equivalent switch as
per specification with 16 guage M.S. box. The box shall be
covered with 3 mm thick decorative mat finish hylum sheet. The
work is all inclusive of supply and fixing of required materials
as afore said [ like Gl conduct pipe , sadles , swithces , Steel
box , ceiling Rose , flexible copper wire etc] to complete point
wiring with each fixture to be earthed by SWG-12 stranded
copper conductor having green color as per direction and
instructions of E.I.C.. SOR Part D70
5 Providing, fixing & termination for emaregency D.C. supply Job 1 4492
arrangment. This job includs supply & laying of 2C x 2.5 mm2
Copper arrmoured cable from battery chargers to SBDC, fixing
& providing SBDC & complete wiring with supply of wire & D.C.
lamp (110V D.C., 100 watt-4 Nos.) in standard steel conduit
pipe as per inst. of E.I.C. SOR Part D71
6 Providing and Fixing points wiring in Gl. Conduct pipe size 20 Point 10 1213
mm dia and 1.6 mm wall thickness with singal PVC insulated
2.5 Sqmm. copper wire of ISI standard good quality using
1.5mm thick suitable size ISI mark ( 2+3 pin in socket ) Anchor
brand 15 Amp. 250 Volt plug socket as seperate
plug point with shock proof accessories incl. indication lamp ;
erected on separate decorative mat finish hylum sheet board
on wall with providing adequate green earthing wire as per
specification and instruction of Engineer Incharge.
7 ---- Do ---- as above but with singal PVC insulated 3Cx1.5 sq. Point 10 814
mm.copper wire of ISI mark plug socket for 5A domestic use
separate plug point as per direction and instruction of E.I.C.
8 ---- Do ---- as above but looped on same board i.e. no separate Point 20 199
board, plug socket for 5A domestic use as per direction and
instruction of E.I.C. SOR Part D74
9 Providing & Fixing of Ceiling Fan of 1400mm sweep No 19 1797
Bajaj/Crompton / Orient/ usha / Cinni make (ISI approved)
flexible wiring by using twin core double PVC 48/0.2 mm copper
flexible cord of suitable & approved make and size from ceiling
rose upto fan terminal & supply and fixing of energy saver
regulators , extra GI pipe of required size and length for
lowering of fan if required as per instruction of EIC. SOR Part
10 Providing & fixing of 50 W LED Lighting Fixture (CGL Cat No. No 24 5059
LCTLR-50-FO-CDL 50W or equivalent under Cat-II or above
as per R&B SOR) 4 coe 2.5 mm2 double insulated flexible
strended wire should be used from control gear fitting to
approved SMC type junction box as per inst. of EIC.SOR PART
11 Providing and fixing of 41.5W LED Lighting Fixture (CGL Cat No 20 3154
No. LPFC-36-CDL 41.5W or equivalent under Cat-II or above
as per R&B SOR) Ref-CE(p)/SE(SS)/V/7213 dt.30.05.17 SOR
12 Providing and fixing of 40W (1x4) LED Lighting Fixtures as per No 2 3417
drawing ( in porch area) (CGL Cat No. LCTLSN-40-CDL (1x4)
40W or equivalent under Cat-II or above as per R&B SOR) as
per instruction of EIC PART D-77
13 Providing & fixing of 30W LED Street Light Bulkhead (CGL Cat No 6 2678
No. LSTO-30-CDL 30W or equivalent under Cat-II or above as
per R&B SOR) on out side C/R building and inside cable trench
in C/R including wiring from ceiling rose to fixture with suitable
size of PVC insulated ISI marked copper wire only as per
instructin of EIC.SOR PART D-78
14 Providing and fixing of heavy duty exhaust fan in battery room No 1 3494
size 18" of Make GEC/KHAITAN/ CROMPTON/ HAVELLS incl.
M.S. lourex shutter of Fan & necessary wall finishing works and
applying bird proof net on outside wall with required
arrangement for rain water sealing and necessary conection
from ceiling rose as per Direction and instruction of EIC. SOR
15 Same as item No.1 but with Fixing of Electric bell with bell No 1 149
switch near officer's table. All materials must be ISI mark and
approved by Engineer I/C SOR Part D80
16 Providing and fixing of 18W LED Lighting Fixture (CGL Cat No. No 6 1281
LCTL-18-CDL 18W or equivalent under Cat-II or above as per
R&B SOR) as per instructin of EIC. SOR Part D81
TOTAL - 4 ( SCHEDULE B - 4 )
SCHEDULE B - 5 : COLONY INDUSTRIAL ELECTRIFICATION
Description Qty Rate UNIT Amount
PART -B Electrical BOQ Type
Providing and fixing of DBS as AC panel-
1 for CR of ISI marked powder coated
pearl DBS or ivory color, wall mounting,
Double door Distribution board of L&T
Heggar or higher make fitted with 63 Amp.
Phase bus bar , earth, neutral bars & inter
connecting wires with removable botton
1 gland plates for all power cable entry from 1.00 1.00 6738.00 No
bottom with DIN Channel, incomming
contact and 1 No- 63 Amp TPN MCB "C"
series. 6 No - 20A SP MCB "C" Series and
13 no-10 Amp, SP C Series. All MCBs are
L&T , Anchor or Higher make only.
Complete in all respect and as per
instruction of EIC. Sor 25-26 Part D-68
Providing and fixing of open type full point
wiring inside OVEL shape PVC Pipes with
2.5 sq.mm Multistranded Copper Flexible
double PVC Insulated wire of standard
brands like POLYCAB/AVOCAB etc for
Phase & Neutral and 1.5 sq.mm Green
2 Colour for earthing. All accessories like
Switch Board, switches, Pendent
Holders.Bracket Holders, Cellig Rose etc.
shall be of standard brands like
SSK/ANCHOR etc make.Sor 25-26 Part
As per Item No.124 but for 5 pin 5 Amp.
3 Point wiring, Sor 25-26 Part D-83
As per Item No. 124 but for 5 pin 15 Amp.
4 Point wiring, Sor 25-26 Part D-84
As per Item No.124 for Call Bell including
5 fixing of Reputed Brand Call Bell. Sor 25- 4.00 4.00 300.00 Point
Circuit charges for individual circuit with
2.5 sq.mm copper wire in GI Conduit Pipe
as per Drg. And Instructions of Engineer
(1) Two No of power point looped in one
(2) 8 No of light/fan/holder/ looped in on
(3) 5 Amp plug point is to be considered
as 2 No of light point. Sor 25-26 Part D-86
Providing and fixing of reputed brand (
CGL/ORIENT/USHA) White Coloured
Celing Fan with 1200 mm Sweep with all
7 required accessories Fan is to be 8.00 8.00 1597.00 No
purchased from authorised dealer only
inspection is to be arranged prior
purchasing.Sor 25-26 Part D-87
Providing and fixing of 18W LED Lighting
Fixture (CGL Cat No. LCTL-18-CDL 18W
8 or equivalent under Cat-II or above as per 16.00 16.00 1281.00 No
R&B SOR) as per EIC, Sor 25-26 Part D-
Providing and Fixing of Distribution Board
12 Way, SPN fitted with 1 No. of 25 Amp.
MCB, 1 No. D.P. ELCB 32 Amp and
9 required No of MCB's. The DP, MCB, 4.00 4.00 2995.00 No
ELCB should be of standard company like
L&T, Siemen, MDS etc. Sor 25-26 Part D-
Installation of C.I. Plate Type Earth Pit for
earthing of various Installations of
quarters. CI Plate weighing 10 Kg is to be
burried inside earth Pit Size 0.5M x 1.5M
to be filled with Black Cotton Soil, Sand,
Salt, Charcoal etc( 16 Kg each). 10 SWG
10 Flexible Multistranded Coppe Wire to be
laid inside good quality heavy duty 19 mm
PVC Pipe from earth Pit to main
distribution board as per Inst. of EIC. Job
includes supply of all required material by
the contractor.Sor 25-26 Part D-89
Providing & fixing of surface mounted 12-
way distribution box of
L&T/STANDARD/MDS/INDOASIA make
for electric power supply to staff quatrs. It
includs providing and fixing of one 32A
TPN, three 16A DP switch of
11 L&T/STANDARD/MDS/INDOASIA with
fixing and commissioning of energy meter
provided by DISCOM, if required with
complete wiring with 2.5mm2 copper,
insulated wire of POLYCAB/AVOCAB
make.Sor 25-26 Part D-90
Providing & fixing of Wall Mounted Fan
Crompton / Orient/ PSPO / Usha / Cinni
(must be ISI approved).including wiring
from ceiling rose to Fan terminals of by
12 using twin core flexible PVC to PVC 48 /
0.2 mm copper cord of suitable &
approved size & fixing of Fan regulator.Sor
25-26 Part D-91
Providing and laying of 2 core, 2.5 sq. mm
PVC armoured copper cable of standard
ISI make , inside hume pipe / cable trench
/ in ground, from control room / transformer
distribution board to junction box of quarter
& main switch of watchman cabin.Cable is
to be laid in ground by preparing 300mm
13 wide and 450mm deep trench. Cable is to
be laid on sand bed and covered by RCC
Hume Pipe Halves for protection of cables.
Job also includes fixing of appropriate size
saddles on the wall for dressing cables as
per instructions of E.I.C. Sor 25-26 Part D-
Providing and fixing Auto door shutter lift
of ISI Make (Otis, Omega,Schneider) or its
equivalent with lift use license, 2 years
waranty including transportaion and
following specifications [1] GEAR LESS
LIFT DRIVE (MRL) comprising of High
Starting torque Lift 3 phase 440 V A. C.
Permanent Magnet Synchronous motor of
proper rating with high efficiency shall be
used. [2] Micro processor based / PLC,
ACVVVF, vector control drive with encoder
feedback closed loop system shall be used
for lift car and door operation which shall
be full collective selective operation hall
call demand response, UP/DOWN hall
stops, Main, Up/ Down Contactor with
overload and phase reversal relay and
safety controls.[3] Car with M S platform
with bracings of adequate size and to
sustain the impact load cabin + passenger
with safety factor of fire for steel and side
panels of Stainless steel of sheet of grade
304 duty. Car ceiling will be S.S. finishes
with aesthetic appearance with LED ceiling
lights. Car flooring shall be of anti skid PVC
14 with choice of colour of engineer in charge.
Car doors shall be of stainless steel grade
304, hairline finish with centre opening /
telescopic automatic doors. Car panel will
also be S.S. 304 finished with emergency
stop device, mechanical door safety
device, facility of auto/ attended mode. All
car panel buttons and all floor switches
must be with brail language as per lift
act.[4] All landing doors must be fire rated
for 2 hour shall be fully automatic centre
opening/ telescopic opening made of
hairline finish steel grade of 304 with key
holes and infrared curtains with Unlocking
facility from outside [5] Appropriate battery
operated emergency light in the car along
with alarm switch shall be provided. Also,
Emergency Light & Fan should start
immediately without any Time Delay as
soon as power fails.[6] Digital scrolling
indicator system for up-down arrow along
with floor position indicator shall be
provided inside the car and at all floors.[7]
Full height infra red curtain with multiple
cross / crossing light beams shall be
provided.[8] Automatic Rescue Device
(ARD) shall be provided accordingly of
passenger capacity with Manual Rescue
Operation ( Manual Cranking Facility). [9]
Audio visual indication in the lift car
showing over loading shall be provided
such that doors kept open till excess load
is removed.[10] Spring buffers/PU Buffers
shall be provided.[11] Car fan as per
passenger capacity with automatic sleep
timer shall be provided.[12] Voice
annunciator with suitable music shall be
provided in lift car. [13] Self diagnostics
system for operational and safety
parameters shall be provided in control
panel.[14] Mechanical over speed
governor with governor calibration as per
actual site parameters and submission of
calibration certificate submission, door key
holes in the floor doors, fireman switch
shall be provided.[15] Lift machine hoisting
arrangement in the lift machine room and
monkey ladder for lift pit should be
provided by the lift agency, along with the
other steel structure works, foundations for
the machine etc…[16] In the hoist way
fascia plate shall be provided without any
extra cost, where ever required as / if
directed by engineer in charge.[17]
Permanent wiring with necessary safety
devices like RCCB in all circuit, Over
Voltage Under Voltage protection and THD
eliminator in circuit for lift machine room
and lift well with proper numbers of light
points, with fixtures, exhaust fan and plug
points shall be provided by the agency.
Only 3 phase Power Supply shall be made
available by department in lift machine
room. Necessary Earthing as per Lift
Act/Rules shall be arranged by Lift
Agency.[18] Any civil/ electrical works for
additional and alteration in lift shaft and
machine room related to erection of lift
shall be made by lift agency without any
extra cost. (granite/marble fixing around all
landing door openings are not in lift
agency’s scope.)[19] Agency has to
provide all working drawings and
documents and liaison services for
obtaining all necessary permission from lift
inspector and other authorities. [20]
acrylic transparent licence/display A4 size
holder in lift car[20A] As per statutory
requirement of Govt. Of Gujarat lift &
escalator act 2000, lift agency has to
provide 1. Car top safety barricade2. Push
& talk communication system.3. Fireman's
switch operation at Ground Floor.
4.carrying out third party lift inspection
during/after lift erection and provide report
by third party authorized by concern
licensing authority 5.agency has to
provide third party insurance upto
completion of free maintenance period and
submit the document for the same. [21]
Car Panel Operating Buttons with floor
position indicator/buttons must be of Auto
Glow type clearly visible when view from
inside cabin.[22] For Physically
Handicapped person Full Length
Handrails of hairline finish steel grade of
304 should be provided at appropriate
height on the Rear & Side Wall Panels in
Lift Car.R&B Electric SOR 2021-22
Chapter 13 Item no 13-1-C-B
Providing & fixing of 'B' class ISI marked
GI. Pipe of 32/40mm dia for cable looping
& road crossing with necessary elbo/band
15 for each pole & J.Box for yard lighting & for 20.00 20.00 180.00 Mtr
control-room flud lights wiring work with
fixing on wall with shadles if required as
per inst. Of EIC. Sor 25-26 Part D-59
Electrical BOQ in Rs.
Part Item Erection in Rs.
B Control Wiring
D Control Room Elect
E Colony Electrification
Grand Total in Rs.
Grand Total in Rs.
SIGNATURE OF CONTRACTOR SUPERINTENDING ENGINEER (TR)
(With rubber stamp/seal of the company) GETCO, CO, Navsari.
All erection work is to be carried out strictly as per the manual of OEM (Original equipment manufacturer), FQP and
instruction of E.I.C.
All equipment erection charges are inclusive of shifting dragging handling of the respective equipment up to S/S
erection site from its S/S site store but exclusive of GST / service tax.
Contractor has to ensure safe shifting dragging erection of all equipments to comply with labour laws I.E. rules etc.
All erection charges are inclusive of fixing of clamp connectors, all necessary accessories to the respective
Transformer erection charges cover shifting, dragging, handling etc. for its bushings, radiators, conservator tank and
allied accessories and oil filling with filtration.
STORAGE CUM ERECTION INSURANCE :- Bidder shall note that storage cum erection insurance is to be taken at
his own cost and amount of material for erection to complete the scope of sub-station work is to be considered Rs
Bidder shall have to take the comprehensive Marine cum Erection (MCE) insurance policy against any loss,
damage, theft, pilferage, fire etc. for the complete period of storage, erection and commissioning up to the time of
taking over the line or S/S by GETCO.
All the required tools and tackles like compression jointing machine for conductor, earth wire, cutting machine,
welding set, drill machine, etc are to be arranged by the contractor at his cost.
Contractor should complete transportation within one job as per above schedule. No extra payment will be given in
any case other than this job.
For power transformer oil filteration the filter machine shall be arranged by Contractor at his own cost.
Earthing pit activities should be done in such a way in presence of GETCO supervisor that final earthing pit
resistance should be record as per standard. All expenditure like sufficient watering to maintain earth resistance up
to the mark should be born by contractor.
All the brought out items get to be approved from DE/EE invariably.
The execution of bore are to be carried out as per soil strata in consultation with E.E. .
The Classification of hard rock strata should be got approved from E.E. invariably.
Contractor has to make arrangement for site engineer and skill labors for maintaining all activities and records as
Sign & Seal of Contractor Page 65/66
Regd. Corporate Office: GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED, Sardar Patel VidyutBhavan, Race Course, Vadodara-390007
Corporate Identity No. (CIN): U40100GJ1999SGC036018 Phone: (0265) 2310582-86, Fax: (0265) 2337918, 2338164, Web site: www.getcogujarat.com
per FQP. also assisting to staff/Engineer in charge to take IR values, Earth pits values, name plate detail, oil
samples etc all activities relative to commissioning of project.
Contractor has to make arrangement for skill labors for assisting to commissioning engineer, PLCC staff/engineer,
SMS/testing staff/Engineer as an when require as per instruction of Engineer in charge.
After completion of project successful bidder has to submit all the records like battery charging report, control wiring
schedule, earth pit lay out, earthing grid layout, power cable lay out, yard light pole and Ckt lay out etc in hard and
soft copy for handing over the project.
For Colony & Yard lighting and Control Room Industrial Electrical wiring works the rates quoted shall be inclusive of
providing and fixing / Installation ,testing and commissioning of complete Control Room lightings, Ceiling Fans,
Exhaust Fans etc..
All items / materials shall be installed / erected in accordance with specified manuals /technical guide lines of the
manufacturer and as per instruction of EIC.
Cable laying, Circuit distribution and Fixture fixing shall be carried out as per GETCO Standard Drg. No.
GETCO/E/06S-STD/S-013 (R0) Sheet 1 to 3 of 3 and as per Instruction of Engineer In charge.
Control Room Wiring, Fixing of fixture, Ceiling fan & Exhaust fan etc shall be carried out as per Standard Drawing
No. GETCO/E/6S-STD/S-015 (R0) Sheet No 1 & 2 of 2. and GETCO/E/6SSTD/S-013 (R0) Sheet No 1 of 3 and as
per instruction of Engineer In charge.
For entire control Room, Office & store etc. building wiring is to be done by Providing and fixing of ISI Marked MS
conduit pipes 20mm dia. & 1.6 mm wall thickness size (Minimum Size) and PVC insulated stranded copper wire of
FENOLEX/ANCHOR make as per relevant IS.
Total tilting angle for the flood light luminaries provided on pole is considered as maximum of 45 degree, looking to
the tilting angle 20 degree available with luminaries it self & supporting pipe should be fabricated & welded
accordingly. Also arm for fixing of Flood light luminaries shall be fix as per required angle & direction as per
instruction of EIC.
EE/DE will decide the make of luminaries, fan, cable, MCB, Switches etc. and same is to be inspected at authorize
Yard lighting G.I.Tubular pole should be inspected at the cost of contractor.
Successful bidder has to appoint site engineer to maintain site register and FQP as per ISO
All work should be done according to ISO & FQP and all requier documents including filled FQP, testing results, etc
should be submitted while handing over the s/s.
The above rates are with supply of cement by the contractor.
Sign & Seal of Contractor Page 66/66
Regd. Corporate Office: GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED, Sardar Patel VidyutBhavan, Race Course, Vadodara-390007
Corporate Identity No. (CIN): U40100GJ1999SGC036018 Phone: (0265) 2310582-86, Fax: (0265) 2337918, 2338164, Web site: www.getcogujarat.com
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2. Schedule B for TCNS-ETRM-35 CR Shifting Kaprada SS.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .