Executive Engineer, Electric (R&B) Division, Rajkot
Providing & Erecting On Grid Solar Rooftop System on Various Government Building of Jamnagar District.
364885
12 of 2026-27
Open
Electrical Works
Works
Rajkot
11 documents required · 11 mandatory
₹3,600
Executive Engineer, Electric (R&B) Division, Rajkot.
₹1.5 L
7 Nov 2026
7 Nov 2026
7 Nov 2026
23 Nov 2026
7 Nov 2026
90 days
Name of work :- Providing & Erecting On Grid Solar Rooftop System on Various Government Building
of Jamnagar District.
Sr. Qty Unit Item of work Net Rate Per Amount
1A 18.00 KW Supply, Installation, Testing & Commissioning of following size of 46648.87 PER
Grid Tied Solar Power Plant with KW
Solar Panels (ALMM approved): Frame Material : Anodized
Aluminum alloy Frame With Twin Wall Profile, Front Cover : High
Transmission Low-Iron Tempered Glass (AR Coated), High
efficency and positive power tolerance Pmax: 0/+5, Module
Efficiency should be approx. 19.5%-22%, Normal operating
temperature 45'C, Junction Box with Waterproof IP67 & MC4
Compatible and Enclosed with Bypass diodes, 100%
Electroluminescence test to ensure error free Modules, Thep.
temp. co-efficient of the PV module shall equal or better than -
0.45%/degree C. Solar PV modules of minimum fill factor 75% to
be used. Unit Production:- More than 4.5 Unit /kw /day
(Actual)(1Year Avg) With 10 year Product warranty and 25 year
Linear Power Warranty includes all mechanical and electrical
parameters of the Solar panel. Modules must be complied to the
DCR(Domestic content requirements). The Ration of AC to DC is
5:6 for the Installation capacity which are given in AC KW.
Solar Inverter: MPPT Range: MPPT Range: 80-1000 V , Max
efficiency: 97.5% - 98.9%, O/p Frequency: 50/60Hz, Operating
Altitude (m) ≤4000, O/p Power Factor: ~1, O/P THDi: <3%,
Operating Tempreture Range: -25~60°C, Integrated protection of
Inverter are Anti-islanding Protection, Input Reverse Polarity
Protection, Insulation Resistor Detection, Ground fault protection,
Residual Current Monitoring Unit, Output Over Current Protection,
Output Short Circuit Protection, Output Over Voltage Protection,
PV array string fault Protection. Protection Degree: IP65, User
Interface LCD & APP, Datalogger & Communication: GPRS (Sim
Module Mounting Structure: The mounting (Rectangular pipe /
square pipe / circular pipe) with requisite cross bars, nuts and
bolts, etc. shall be Hot deep galvanized with minimum 80micron
coating. The Rectangular / square /circular hollow pipe section
used for the structure should have a minimum thickness of
mm. other than above, the material thickness should be minimum
2.5 mm. A certificate of a structural engineer certifying the
strength and stability of the mounting structure to withstand the
weight and wind speed of 150 km/hour, shall be submitted by the
vendors. Hot Dipped Galvanized steel coils. suitable arrangement
for base plate for foundation , solar panel mounting, the structure
should be suitable for carry the load of solar panel,wiring,
sprinkler system etc. with necessary foundation work/wall mount, j
bolt, anchor fastner etc. the nut bolt used for installtion of stucture
should be (SS 304) quality.The ground clearance of the bottom
most edge of solar panel shall not be less than 300 mm to
mm or as per site’s technical/feasibility requirement.
a. Column –The minimum section (thickness) should be
60MM*40MM,b. Rafter - The minimum section (thickness) should
be 60MM*40MM,c. Purlin - The minimum section (thickness)
should be 40MM * 40MM Balane of System with necessary
Swichgears (Suitabel size and protection of ACDB & DCDB), inter
connecting wiring, earthing system as per the CEIG drawing
approval, lightining arrester system as per the CEIG drawing
approval, all liasoning work with various gov. dipartment like state
nodal agency,DISCOM & CEIG is included in agency scope
(Excluding All charges namely GEDA Application fees, Solar
connectivity Charges, Meter connectivity Charges, Meter testing
Charges and system stability/strenthning charges.) (NOTE: N
Type TOPCON Bifacial A-GRADE PANEL MUST BE
(A) Grid Tied Solar Power System: 1 - 6 kW (Single phase)
1B 21.00 KW (B) Grid Tied Solar Power System: 7 - 10 kW (3 - phase) 44081.45 PER
1C 167.00 KW (C ) Grid Tied Solar Power System: 11 - 25 kW (3 - phase) 42455.35 PER
1D 145.00 KW (D) Grid Tied Solar Power System: 26 - 50 kW (3 - phase) 42156.39 PER
Total Amount Put To Tender Rs.
Total Amount Put To Tender Rs.
Note : This Estimate has been prepared on the new SOR which is exclusive of GST hence GST additional will be
paid to the agency as per existing guidlines.
Deputy Executive Engineer Executive Engineer
Electrical R & B Sub Division Electrical (R&B) Division
Jamnagar Rajkot
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Additional Instruction.pdf
CMC RATES FOR 6 TO 10 YEAR.pdf
Eligibility Criteria for solar work FINAL (1).pdf
SBD.pdf
sch B.pdf
Tender for Supply and Installation.pdf
Contractor_Registration_Paripatra__1_.pdf
EMD GR.pdf
GR for single Tender.pdf
ONLINE_NOTICE(R-2)(dn).pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .