Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹10.8 LAccepted-AOC 1017 A SUBHASH NAGAR BEHIND KHALSA SCHOOL BAREILLY UP | BAREILLY | UTTAR PRADESH | 243001 | L-1 | Accepted-AOC Over all rates are reasonable and lowest. | |
| 2 | L-2₹14.7 L+₹2.9 L (24.4%)Rejected-Finance 24 C VAIBHAV SUNCITY VISTAR BAREILLY UP 243001 | BAREILLY | UTTAR PRADESH | 243001 | L-2 | Rejected-Finance Over all rates are higher than L-1. | |
| 3 | L-3₹18.4 L+₹6.6 L (55.4%)Rejected-Finance | L-3 | Rejected-Finance Over all rates are higher than L-1. | |
| 4 | L-4₹18.9 L+₹7.1 L (59.6%)Rejected-Finance 129 A NICHLI CHOWKI DEVI NAGAR SECTOR 32 PANCHKULA HARYANA 134109 | PANCHKULA | HARYANA | 134109 | L-4 | Rejected-Finance Over all rates are higher than L-1. |
Tender Value
Refer Docs
EMD Value
₹38,000
Closing Date
29 Jan 2021, 6:00 pmClosed
Garrison Engineer, Air Force, Bareilly
Garrison Engineer, Air Force, Bareilly, 243002
REPAIRS/ MAINT/ SERVICING AND MINOR OVERHAULING OF DG SETS VARIOUS CAPACITIES ALONGWITH LT PANEL, AMF PANEL, TROLLEY MOUNTED DG SETS ETC. INCLUDING ALLIED SERVICE/ PARTS AT AFS, BAREILLY.
2021_MES_408756_1
8572 / E8
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
Bareilly
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer, Air Force
₹38,000
Yes
11 May 2021
1 Jan 2021
1 Feb 2021
1 Jan 2021
29 Jan 2021
15 Jan 2021
Amount
Repair/ overhauling of DG Set engine of capacity 100 KVA to 125 KVA make Kirloskar/ Cummins 1500 RPM, water / air cooled by dismantling/strip opening of the DG Set for overhauling by decarbonising/ cleaning cylinder head, valves, rocker arms, plungers, head gaskets, packing sets, turbo chargers by replacing the piston oil/ lubrication, compression rings complete, top cover head and cam shaft, rocker arms gaskets; machining of heads, valves seat if required for all the cylinders and repairs to lubrication and cooling system by rectifying defects, replacement of the defective parts, damaged metal clamps, rubber hoses, dampers, packing pads, gaskets, manifolds, vibration dampers, pipe lines and minor corroded accessories complete and testing of the DG set complete all as specified and as directed. Note : Repair work shall be got carried out by respective OEM/ Authorized dealer only. All the spare parts shall be of OEM only and shall be measured and paid for separately as 'Supply only' under item no 2.01 to 2.15 herein after
Supply only of Piston, Piston ring with piston pin complete all as specified and as directed.
Supply of Liner with packing 'O' ring complete all as specified and as directed.
Supply of LE Bearing complete all as specified and as directed.
Supply of Small end Bush complete all as specified and as directed.
Supply of Engine Gasket set complete all as specified and as directed.
Supply of Head gasket set complete all as specified and as directed.
Supply of Thrust Washer complete all as specified and as directed.
Supply of Barrel plunger and cup complete all as specified and as directed.
Supply of Main bearing complete all as specified and as directed.
Supply of Oil seal rear complete all as specified and as directed.
Supply of Oil seal front complete all as specified and as directed.
Supply of Valve guide complete all as specified and as directed.
Supply of Valve seat complete all as specified and as directed.
Supply of Valve seal complete all as specified and as directed.
Supply of Valve complete all as specified and as directed.
M&L for carrying out 'B' check for DG Set 320 KVA, 6 cylinder Kirloskar water cooled type as per manufacturer's recommendation/ particular specification including replacement of necessary spares and replacement of filters such as fuel filter, SLO By-pass filter, air filter and lub oil filter complete sets and cleaning of coolant tank with blower and labour for filling/ topping up and replacement of Engine oil/ coolant and tuning of engine for DG set all as specified and as directed.
All as per Item No. 3 herein before but for DG Set 200 to 250 KVA 6 cylinder Kirloskar water cooled type complete all as specified and as directed.
All as per Item No. 3 herein before but for DG Set 160 to166 KVA Cummins/Kirloskar diesel engine 6 cylinder complete all as specified and as directed.
All as per Item No. 3 herein before but for DG Set 100 KVA to 125 KVA Kirloskar/ Cummins diesel engine any model complete all as specified and as directed.
All as per Item No. 3 herein before but for DG Set 30 KVA to 75 KVA Kirloskar/ Cummins diesel engine any model complete all as specified and as directed. NOTE FOR ITEM NO. 03 TO 07 :- The Servicing/ Maintenance/ Repair has to be carried out by respective OEM/ Authorized dealer only. All the spares shall be of OEM only. Engine oil as required shall be issued by the Deptt free for filling under Schedule 'B'
M&L for taking down & cleaning the radiator intercooler of LT DG set 30 to 75 KVA, 440 Volts by checking and removing the deposited dust, oil welt and carbons and cleaning with forced water with cleaning agents and testing for leaks at inter connectors/ couplers/ flexible connectors/ flexi clamps and making necessary minor repairs to arrest leakages of coolant and fixing back after repair/ cleaning all as directed by Engineer-in-Charge.
M&L for taking down & cleaning the radiator intercooler of LT DG set 100 to 166 KVA, 440 Volts by checking and removing the deposited dust, oil welt and carbons and cleaning with forced water with cleaning agents and testing for leaks at inter connectors/ couplers/ flexible connectors/ flexi clamps and making necessary minor repairs to arrest leakages of coolant and fixing back after repair/ cleaning all as directed by Engineer-in-Charge.
M&L for taking down & cleaning the radiator intercooler of LT DG set 200 to 320 KVA, 440 Volts by checking and removing the deposited dust, oil welt and carbons and cleaning with forced water with cleaning agents and testing for leaks at inter connectors/ couplers/ flexible connectors/ flexi clamps and making necessary minor repairs to arrest leakages of coolant and fixing back after repair/ cleaning all as directed by Engineer-in-Charge.
M&L for taking out FIP from DG Sets of capacity 200 KVA to 320 KVA carrying out servicing through authorized service centre of respective OEM including replacement of unserviceable Plunger - 06 Nos, Delivery valves – 06 No, Bearing - 02 Nos, Bearing Bush – 02 Nos, Needle valve– 06 Nos with spares from respective OEM complete including grinding of nozzles complete and re-fixing the same all as directed.
M&L for taking out FIP from DG Sets of capacity 100 KVA to 166 KVA carrying out servicing through authorized service centre of respective OEM including replacement of unserviceable Plunger - 06 Nos, Delivery valves – 06 No, Bearing - 02 Nos, Bearing Bush – 02 Nos, Needle valve– 06 Nos with spares from respective OEM complete including grinding of nozzles complete and re-fixing the same all as directed.
M&L for taking out FIP from DG Sets of capacity 30 KVA to 75 KVA carrying out servicing through authorized service centre of respective OEM including replacement of unserviceable Plunger - 04 Nos, Delivery valves – 04 No, Bearing - 02 Nos, Bearing Bush – 02 Nos, Needle valve– 04 Nos with spares from respective OEM complete including grinding of nozzles complete and re-fixing the same all as directed.
Complete cleaning work to oil cooler of water cooled diesel engine of 30 KVA to 320 KVA DG set Cummins/Kirloskar make with and including replacement of following spares complete all as specified and as directed. :- (i) Element tube oil cooler- 02 Nos (ii) ‘O’ Ring – 02 Nos (iii) Retainer ‘O’ Ring -02 Nos (iv) Gasket - 01 Set (v) Hose - 01 Set (vi) Clamp hose -02 Nos
S&F in replacement of Water circulating pump/ water body suitable for 200 KVA to 320 KVA capacity DG Sets of Kirloskar/ Cummins make all as directed by Engineer-in charge.
S&F in replacement of Water circulating pump/ water body suitable for 100 KVA to 166 KVA capacity DG Sets of Kirloskar/ Cummins make all as directed by Engineer-in charge.
S&F in replacement of Water circulating pump/ water body suitable for 30 KVA to 75 KVA capacity DG Sets of Kirloskar/ Cummins make all as directed by Engineer-in charge.
S&F in replacement of shut down valve for 200 to 320 KVA DG set of Kirloskar/ Cummins make including necessary electric connection to AMF panel and engine control panel board all as specified and as directed.
S&F in replacement of shut down valve for 100 to 166 KVA DG set of Kirloskar/ Cummins make including necessary electric connection to AMF panel and engine control panel board all as specified and as directed.
S&F in replacement of shut down valve for 30 to 75 KVA DG set of Kirloskar/ Cummins make including necessary electric connection to AMF panel and engine control panel board all as specified and as directed.
Replacement of burnt asbestos rope from silencer with 20mm dia asbestos rope including applying plaster of paris complete all as specified and as directed
S&F in repairs grooved belt A-47 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt A-50 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt A-52 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt B-35 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt B-38 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt B-39 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt B-42 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt C-48 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt B-46 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt SPA-1250 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
S&F in repairs grooved belt A-58 of make:-Fenner/ Yule/ Dunlop/ Conti Tech complete all as specified and as directed.
M&L for dismantling of fuel tank by disconnecting fuel pipe from DG Set of 200 KVA to 320 KVA capacity and refixing same after thorough cleaning and removing all sediments from the tank, scraping the external surfaces and applying two spray coats of synthetic enamel paint and replacement of fuel pipe of existing size, necessary welding work all as directed by Engineer in charge. [Note: Quoted rate is included for opening of DG set canopy for removing of Fuel tanks which are provided at bottom base plate of DG sets].
All as per Item No. 23 herein before but for DG Sets of 100 KVA to 166 KVA capacity
All as per Item No. 23 herein before but for DG Sets of 30 KVA to 75 KVA capacity
S&F in replacement of Solenoid coil 24 volts DC operated with lead and fixing clamps all as directed by Engineer-in-Charge.
S&F in replacement of Solenoid coil 12 volts DC operated with lead and fixing clamps all as directed by Engineer-in-Charge.
M&L for replacement of hose pipe set complete with clamps and other fitting as required at site for 200 to 320 KVA DG set of Make: Kirloskar/ Cummins all as directed by Engineer-in-Charge.
All as per Item No. 28 herein before but for DG Sets of 100 KVA to 166 KVA capacity
All as per Item No. 28 herein before but for DG Sets of 30 KVA to 75 KVA capacity
S&F diesel fuel inlet/out let of wire braided flexible hose pipe of 20mm dia with clamps/ clips for Cummins/Kirloskar make DG set complete all as specified and as directed.
M&L for disconnecting & opening of alternator and removing existing stator, rotor, AVR, Diode etc from DG sets of cap 30 KVA to 75 KVA for rewinding of stator, rotor and exciter etc and reassembling and refixing same all as directed by Engineer-in-Charge. Note: Rewinding of stator, rotor and exciter will be measured and paid separately.
M&L for rewinding of stator complete with supper enameled copper wire as per existing size for DG sets of cap 30 KVA to 75 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for rewinding of rotor main winding complete with supper enameled copper wire as per existing size for DG sets of cap 30 KVA to 75 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for rewinding of rotor exciter winding complete with supper enameled copper wire as per existing size for DG sets of cap 30 KVA to 75 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for disconnecting & opening of alternator and removing existing stator, rotor, AVR, Diode etc from DG sets of cap 100 KVA to 166 KVA for rewinding of stator, rotor and exciter etc and reassembling and refixing same all as directed by Engineer-in-Charge. Note: Rewinding of stator, rotor and exciter will be measured and paid separately.
M&L for rewinding of stator complete with supper enameled copper wire as per existing size for DG sets of cap 100 KVA to 166 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for rewinding of rotor main winding complete with supper enameled copper wire as per existing size for DG sets of cap 100 KVA to 166 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for rewinding of rotor exciter winding complete with supper enameled copper wire as per existing size for DG sets of cap 100 KVA to 166 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for disconnecting & opening of alternator and removing existing stator, rotor, AVR, Diode etc from DG sets of cap 200 KVA to 320 KVA for rewinding of stator, rotor and exciter etc and reassembling and refixing same all as directed by Engineer-in-Charge. Note: Rewinding of stator, rotor and exciter will be measured and paid separately.
M&L for rewinding of stator complete with supper enameled copper wire as per existing size for DG sets of cap 200 KVA to 320 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for rewinding of rotor main winding complete with supper enameled copper wire as per existing size for DG sets of cap 200 KVA to 320 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for rewinding of rotor exciter winding complete with supper enameled copper wire as per existing size for DG sets of cap 200 KVA to 320 KVA and making the alternator serviceable all as directed by Engineer-in-Charge.
M&L for Replacement of Auto Voltage Regulator with wire connection and connecting to existing field coil 24 volt DC for DG set of capacity 200 KVA to 320 KVA, Kirloskar/ Cummins make complete all as specified and as directed.
M&L for Replacement of Auto Voltage Regulator with wire connection and connecting to existing field coil 24 volt DC for DG set of capacity 125 KVA to 166 KVA, Kirloskar/ Cummins make complete all as specified and as directed.
M&L for Replacement of Auto Voltage Regulator with wire connection and connecting to existing field coil 12 volt DC for DG set of capacity 63 KVA to 100 KVA, Kirloskar/ Cummins make complete all as specified and as directed.
M&L for Replacement of Auto Voltage Regulator with wire connection and connecting to existing field coil 24 volt DC for DG set of capacity 30 KVA to 50 KVA, Kirloskar/ Cummins make complete all as specified and as directed.
S&F in Replacement of alternator 24 Volts (for charging of battery) complete all as specified and as directed. Make:- Lucas - TVS or approved by GE.
S&F in Replacement of alternator 12 Volts (for charging of battery) complete all as specified and as directed. Make:- Lucas - TVS or approved by GE.
M&L for repair/ replacement of DG Set canopy door hinges including repair to locking system by welding as per existing at site complete all as specified and as directed by Engineer-in-Charge.
M&L for rewinding of self starter of capacity 24 volts by taking out old burnt out copper winding wire and rewinding with supper enameled copper wire of same gauge including replacement of unserviceable pinion, bush, solenoid coil, carbon brushes and tension spring complete including commissioning and testing all as specified and as directed.
M&L for rewinding of self starter of capacity 12 volts by taking out old burnt out copper winding wire and rewinding with supper enameled copper wire of same gauge including replacement of unserviceable pinion, bush, solenoid coil, carbon brushes and tension spring complete including commissioning and testing all as specified and as directed.
M&L for replacement of slip ring made out of brass or copper moulded in epoxy compound with lead etc. complete for 30 KVA to 320 KVA DG Set of Kirloskar/ Cummins make.
M&L for replacement of Engine starting control Relay for on and off of 200 to 320 KVA DG set. Make: Kirloskar/ Siemens/ BCH.
M&L for replacement of Engine starting control Relay for on and off of 100 to 166 KVA DG set. Make: Kirloskar/ Siemens/ BCH.
M&L for replacement of Engine starting control Relay for on and off of 30 to 75 KVA DG set. Make: Kirloskar/ Siemens/ BCH.
S&F RPM meter showing hour run on same dial 90mm dia size, rang 0-2500 RPM with adaptor including cable connection suitable for 30 to 320 KVA capacity Kirloskar make DG set all as specified and as directed. [Make: Pricol].
M&L for disconnecting & opening of alternator for servicing from 200 to 320 KVA DG Set including coupling alignment and replacement of ball bearing & bearing bush -02 Nos and cleaning of insulation with Bectrol red and varnishing of windings all as directed by Engineer-in-Charge.
M&L for disconnecting & opening of alternator for servicing from 100 to 166 KVA DG Set including coupling alignment and replacement of ball bearing & bearing bush -02 Nos and cleaning of insulation with Bectrol red and varnishing of windings all as directed by Engineer-in-Charge.
M&L for disconnecting & opening of alternator for servicing from 30 to 75 KVA DG Set including coupling alignment and replacement of ball bearing & bearing bush -02 Nos and cleaning of insulation with Bectrol red and varnishing of windings all as directed by Engineer-in-Charge.
Supply and replace Battery lead of 2m long with thimble and terminal heavy duty made out of brass complete all as directed.
Supply and replace Battery lead of 60cm long with thimble and terminal heavy duty made out of brass complete all as directed.
Re-conditioning of unserviceable battery 12 Volts 120/150/180 AH, 25 plates by replacing the dead cells and providing proper electrolyte solution including washing the corroded terminal with ammonia solution complete all as directed by Engineer-in-Charge.
Supply and replace control panel governor PCB plate suitable for DG sets of capacity 30 KVA to 320 KVA make and model as per existing including testing and commissioning complete all as specified and as directed .
Supply and replace DG Base Card suitable for DG sets of capacity 30 KVA to 320 KVA make and model as per existing including testing and commissioning complete all as specified and as directed.
Supply and replace ampere transformer of control panel suitable for DG sets of capacity 30 KVA to 320 KVA make and model as per existing including testing and commissioning complete all as specified and as directed.
Supply and replace EMS 907 digital display of control panel suitable for DG sets of capacity 75 KVA to 125 KVA make and model as per existing including testing and commissioning complete all as specified and as directed.
Supply and replace EMS 907 digital display of control panel suitable for DG sets of capacity 200 KVA to 320 KVA make and model as per existing including testing and commissioning complete all as specified and as directed.
Supply and replace control panel without digital display suitable for DG Sets of any make/ type/ capacity as per existing, making all electric and electronic connections and testing & commissioning complete all as specified and as directed.
M&L for carrying out repairs to AMF (Automatic Mains Failure) control panel with 24 Volts DC system suitable for 20 to 320 KVA DG Set including replacement of unserviceable internal wiring of panel, cleaning of panel, tightening of loose nuts and bolts and replacement of corroded nuts and bolts etc. complete all as directed. [Note: Spare part shall be measured and paid separately under respective items of this BOQ]
S&F in repairs 4 pole contactors AC operated rating at 415 Volts, AC1 160 Amps rating with 2NO + 2NC auxiliary contacts with operatabe coil voltage 24 volts to 415 volts AC/DC with front/ side mounted Add On blocks as per site requirement. [Make: Cat No. CS97020 (MCX 32) of make: L&T or equivalent in Havells/ Legrand/ GE/ Schneider]
S&F in repairs 3 pole contactors AC operated rating at 415 Volts, AC3 185 Amps rating with 2NO + 2NC auxiliary contacts with operatabe coil voltage 24 volts to 415 volts AC/DC with front/ side mounted Add On blocks as per site requirement. [Make: Cat No. CS94139 (MNX 185) of make: L&T or equivalent in Havells/ Legrand/ GE/ Schneider]
S&F in repairs 3 pole contactors AC operated rating at 415 Volts, AC3 225 Amps rating with 2NO + 2NC auxiliary contacts with operatabe coil voltage 24 volts to 415 volts AC/DC with front/ side mounted Add On blocks as per site requirement. [Make: Cat No. CS94140 (MNX 225) of make: L&T or equivalent in Havells/ Legrand/ GE/ Schneider]
S&F in repairs MCCB with adjustable thermal and adjustable magnetic setting of capacity 160 Amps, 415V, 4 pole, 35 KA breaking capacity complete all as directed. [Cat part No. IHLCNF0160 of Make: Havells or equivalent in L&T/ ABB/ Indo Asian/ HPL]
S&F in repairs MCCB with adjustable thermal and adjustable magnetic setting of capacity 200 Amps, 415V, 4 pole, 35 KA breaking capacity complete all as directed. [Cat part No. IHLCNF0200 of Make: Havells or equivalent in L&T/ ABB/ Indo Asian/ HPL]
S&F in repairs MCCB with adjustable thermal and adjustable magnetic setting of capacity 250 Amps, 415V, 4 pole, 35 KA breaking capacity complete all as directed. [Cat part No. IHLCNF0250 of Make: Havells or equivalent in L&T/ ABB/ Indo Asian/ HPL]
S&F in repairs MCCB with adjustable thermal and adjustable magnetic setting of capacity 315 Amps, 415V, 4 pole, 35 KA breaking capacity complete all as directed. [Cat part No. IHLCNF0315 of Make: Havells or equivalent in L&T/ ABB/ Indo Asian/ HPL]
S&F in repairs MCCB with adjustable thermal and adjustable magnetic setting of capacity 400 Amps, 415V, 4 pole, 35 KA breaking capacity complete all as directed. [Cat part No. IHLCNF0400 of Make: Havells or equivalent in L&T/ ABB/ Indo Asian/ HPL]
S&F in repairs On load change over switch, open execution type with advanced Neutral 415 Volts of rating 125 Amp TPN complete all as specified and as directed. [Cat part No. IHCNFO0125 of Make: Havells or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs On load change over switch, open execution type with advanced Neutral 415 Volts of rating 200 Amp TPN complete all as specified and as directed. [Cat part No. IHCNFO0200 of Make: Havells or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs On load change over switch, open execution type with advanced Neutral 415 Volts of rating 320 Amp TPN complete all as specified and as directed. [Cat part No. IHCNFO0320 of Make: Havells or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs under or over voltage relay suitable for 03 phase AC supply, 415 volts complete all as specified and as directed.
S&F in repairs electronic timer suitable for 12/24 volts DC supply for 0-30 seconds as per OEM of DG set complete all as specified and as directed.
S&F in repairs electronic timer suitable for 12/24 volts DC supply for 0-180 seconds as per OEM of DG set complete all as specified and as directed.
S&F in repairs engine starting relay with sequence timer and master timer suitable for 24/12 volts DC supply as per recommendations of the OEM of DG sets complete all as specified and as directed.
S&F in repairs Battery charging transformer Engine starting relay with sequence timer and master timer suitable for 24/12 volts DC supply as per recommendations of the OEM of DG sets complete all as specified and as directed.
S&F in repairs battery charging indicator lamp complete all as specified and as directed.
S&F in repairs Auto/Manual/Test switch complete all as specified and as directed.
S&F in repairs LED type indicating lamp for DG and Mains side complete all as specified and as directed.
M&L for complete rewiring of 30 to 75 KVA DG set as per OEM recommendations and as given in circuit diagram as per existing size/ gauge of wire with and including replacement of all unserviceable connectors, fuses, minor electric parts and necessary testing and commissioning complete all as specified and as directed.
All as per Item No. 93 herein before but for DG Sets of 100 KVA to 166 KVA capacity
All as per Item No. 93 herein before but for DG Sets of 200 KVA to 320 KVA capacity
S&F in repairs Aluminium Lugs of size 400 sq.mm x 3.5 core.
S&F in repairs Aluminium Lugs of size 300 sq.mm x 3.5 core.
S&F in repairs Aluminium Lugs of size 240 sq.mm x 3.5 core.
S&F in repairs Aluminium Lugs of size 185 sq.mm x 3.5 core.
S&F in repairs Aluminium Lugs of size 95 sq.mm x 3.5 core.
S&F in repairs Aluminium Lugs of size 70 sq.mm x 3.5 core.
S&F in repairs Aluminium Lugs of size 50 sq.mm x 3.5 core.
S&F in repairs off load change over switch AC -21 (Side handle) in sheet steel enclosure 415 Volt AC, 50 Hz of rating 630 Amp TPN complete all as specified and as directed. [Cat part No. IHBFFE0630 of Make Havells or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs off load change over switch AC -21 (Side handle) in sheet steel enclosure 415 Volt AC, 50 Hz of rating 400 Amp TPN complete all as specified and as directed. [Cat part No. IHBFFE0400 of Make Havells or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs off load change over switch AC -21 (Side handle) in sheet steel enclosure 415 Volt AC, 50 Hz of rating 200 Amp TPN complete all as specified and as directed. [Cat part No. IHBFFE0200 of Make Havells or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs off load change over switch AC -23 (Side handle) in sheet steel enclosure 415 Volt AC, 50 Hz of rating 100 Amp TPN complete all as specified and as directed. [Cat part No. CSCSOF100CO4 of Make C&S or equivalent in Indo Asian/ HPL/ L&T].
S&F in repairs off load change over switch AC -23 (Side handle) in sheet steel enclosure 415 Volt AC, 50 Hz of rating 32 Amp TPN complete all as specified and as directed. [Cat part No. CSCSOF32CO4 of Make C&S or equivalent in Indo Asian/ HPL/ L&T].
Supply and filling of coolant suitable for DG set of capacity 30 KVA to 320 KVA of make Kirloskar/ Cummins/ Tata as per recommendations of the OEM of DG sets complete all as specified and as directed.
M&L for attending, identifying and rectification of minor faults pertaining to DG sets and connected accessories/ machinery, repairing/ making serviceable on day to day complaint basis or as per requirement by engaging competent technicians complete all as specified and as directed.
S&F in replacement Fuel indicating assembly complete of DG Set of capacity up to 320 KVA complete all as specified and as directed.
M&L as in replacement of fuel pipe line as per existing size and make suitable for 30 KVA to 320 KVA DG Set complete all as specified and as directed.
M&L as in replacement of maintenance free Battery 12 Volts, 180 AH complete all as specified and as directed. [Make: Exide/ Amaron/ Tata]
S&F as in replacement Battery charger 180-270 volt, 50 Hz, single phase AC current input and 12/24 volts 20 Amp DC output suitable to charge the batteries ranging from 60 AH to 220 AH, boost and float type with full charge cutoff mode complete with all protections i.e. short circuit, over load, reverse polarity, surge protection with voltmeter, ammeter, indication display. [Make: Sinetrac, model- 12-24BC 20A or equivalent to Elnix / Subtech/ Elak].
S&F as in replacement of new self starter of capacity 24 volts model and make as per existing suitable to DG set of 1500 RPM, 6 cylinder, water or air cooled type complete including taking out carefully old unserviceable self starter and necessary commissioning and testing as per manufacturer's recommendation all as specified and as directed. [Make: Lucas/ Bosch]
S&F as in replacement of new self starter of capacity 12 volts model and make as per existing suitable to DG set of 1500 RPM, 6 cylinder, water or air cooled type complete including taking out carefully old unserviceable self starter and necessary commissioning and testing as per manufacturer's recommendation all as specified and as directed. [Make: Lucas/ Bosch]
Visit of the OEM Engineers for the rectification of any fault pertaining to DG Sets and connected accessories/ machineries i.e.. change of controller, sensor, thermostat, malfunction of harness wiring etc and making serviceable as per requirement complete all as specified and as directed. NOTE: Spare part shall be measured and paid separately .
SHRI SIDHI VINAYAK INFRASTRUCTURE DEVELOPERS
Pal Engineering Services
SONI ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .