GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
REPAIR MAINT OF CENTRAL PACKAGE AC PLANT AND MISC ITEMS UNDER GE UTILITY AMBALA CANTT
2022_MES_537190_2
CA NO GE U AMB T 18 OF 2022-23
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹54,000
19 Sept 2022
11 Aug 2022
3 Sept 2022
11 Aug 2022
1 Sept 2022
18 Aug 2022
11 Aug 2022 - 15 Aug 2022
Amount
Descaling the condenser by recommended chemical cleaning agent by soaking method, disconnecting condenser from the system, taking out nuts bolts, studs, 2 Nos valves and MS/GI pipe line from both side cover, cleaning each tube with nylon brush, flushing with alkaline solution connecting back both side cover including replacing leather gasket 4 mm thick suitable for AC plants installed as indicated below :-
Condenser at OT MH
Condenser at ICU MH
Condenser at Maternity ward
Condenser at Signal Center
Cleaning of Air cooled Condenser by recommended chemical cleaning agent and with high pressure water machine as under:-
Air cooled Condenser at Raina Auditorium
Air cooled Condenser at Cold Storage MH
Descaling the Chiller by recommended chemical cleaning agent, by soaking method, disconnecting condenser from the system by taking out nuts, bolts, studs, 2 Nos valves and MS/GI pipe line from both sides cover, cleaning each tube with nylon brush, flushing with alkaline solution, connecting back both side cover including replacing leather gasket 4 mm thick capacities of condensers suitable for AC plants installed as indicated below :-
Chiller at OT MH
Chiller at ICU MH
Chiller at Raina Auditorium
Descaling and cleaning of AHU by recommended chemical cleaning agent by soaking method, disconnecting condenser from the system by taking out nuts bolts, studs 2 No valves and MS/GI pipe line from both sides cover, cleaning each tube with nylon brush, flushing with alkaline solution connecting back both side cover including replacing leather gasket 4 mm thick suitable for AC plants installed as indicated below :-
AHU at OT MH
AHU at ICU MH
AHU at Raina Auditorium
Supply & charging of refrigerant gas R-22 in central/package type AC plants after detection & rectification of any leakage in the system by using CO2 gas and flushing the complete system thoroughly with Nitrogen gas including testing and commissioning complete all as directed. Note: (i) Gas to be brought by contractor at site from authorised dealer/manufracturer in company sealed cylinder (ii) The unit rate quoted is inclusive of cost of Nitrogen gas & CO2 gas required for leakage test & pressure test.
Description all as per item no. 5.00 here in before but R-407 gas.
Description all as per item no. 5.00 here in before but R-404 gas.
S & F suction and delivery external relief valve made of brass to prevent leakage from compressor.
M&L in replacement of sight/moisture indicator of AC plant as per existing size.
M&L in replacement of liquid line filter for following capacity of AC plant as per existing size.
Raina Auditorium AC plant for 23 TR Compresor.
OT MH AC plant for 12.5 TR Compresor.
ICU MH AC plant for 12.5 TR Compresor.
Maternity MH AC plant for 5 TR Compresor.
Signal Center AC plant for 7.5 TR Compresor.
Supply and fix in replacement of PVC pipe 1.5" dia for drainage of water from AC plant.
M&L in replacement of insulation pipe line with 25mm thick closed cell chemically cross linked fire retardant polyethylene foam instulation of density 30 Kg/Cum. The thermal conductivity of the material should not exceed 0.035 W/Mk at an average temp of 40 deg C, covered with aluminium face, application with rubber based adhesive pidilite SR 998 and 50 mm x 3 mm thick self adhesive tape on both longitudinal and traverse joints complete all as specified and directed by Engr-in-Charge.
M&L in replacement of insulation the Ducts with 13 mm thick closed cell chemically cross linked fire retradant polyethylene foam instulation of density 30 Kg/Cum. The thermal conductivity of the material should not exceed 0.035 W/Mk at an average temp of 40 deg C, covered with aluminium face, application with rubber based adhesive pidilite SR 998 and 50 mm x 3 mm thick self adhesive tape on both longitudinal and traverse joints complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement saddle for pipeline on wall size 22 mm long as per existing make & size/type.
Supply and Fix in replacement Butter Fly valve 100 mm dia.
Supply and Fix in replacement Butter Fly valve 80 mm dia.
Supply and Fix in replacement Butter Fly valve 50 mm dia.
Supply and Fix in replacement Y strainer of size 100 mm dia.
Supply and Fixing in replacement Y strainer of size 80 mm dia.
Supply and Fixing in replacement Y strainer of size 50 mm dia.
Supply and Fixing in replacement Gate valve brass of size 50 mm dia.
Supply and Fixing in replacement Gate valve brass of size 40 mm dia.
Supply and Fixing in replacement Gate valve brass of size 25 mm dia.
Supply and Fixing in replacement Float valve of size 25 mm dia Brass rod with float ball valve complete.
Supply and Fixing in replacement Float valve of size 20 mm dia Brass rod with float ball valve complete.
Supply & fix in replacement of V belts of following sizes:
Dismantling the rusted body of AHU of any capacity, blower motor, blower shaft , and other spares from AHU for repairing/ Over-hauling the Body of AHU by welding / blazing / fabrication and replacement of defective components to ensure the proper functioning of the AHU, Re-assemble after necessary repairs, Connecting, commissioning and testing complete all as specified and directed. Note- (i) The AHU shall be got repaired / Overhauled from specialized Firm or Agency as approved by the Engineer-in charge. (ii) Payment for replacement of parts/ components shall be made for separately as "Supply only" under relevant items of this schedule here-in-after. (iii) Cleaning and removing dust from inside of the duct is deemed to be included in the quoted rates.
Supply only the following material/spares/ components required for AHU / Blower shafts of AC Plants Note:- Fixing charges shall be deemed to be inclusive in the quoted rate against Serial item No. 27 here in before .
Galvanized steel sheet of 20 SWG
Galvanized steel sheet of 22 SWG
Galvanized steel sheet of 24 SWG
Nut bolts & screws.
Angle iron of size 30x3 mm
Main bearing/ bushing cat part no.NUP208 E.TVP2-208
Blower shaft bearing unit Cat Part No. UCP 208-24
Motor Shaft V-Belt Pully with two groove 4" dia
Blower Shaft V-Belt Pully with two groove 4" dia
Motor Shaft V-Belt Pully with two groove 6" dia
Blower Shaft V-Belt Pully with two groove 6" dia
Motor Shaft V-Belt Pully with two groove 12" dia
Blower Shaft V-Belt Pully with two groove 12" dia
Copper Tubing size 5/8" inch.
Copper Tubing size 3/4" inch.
Copper Tubing size 1/2" inch.
Copper Tubing size 1/4" inch.
Flair Nut size 5/8" inch.
Flair Nut size 3/4" inch.
Flair Nut size 1/2" inch.
Flair Nut size 1/4" inch.
Disconnecting from mains S & F in replacement of scroll compressor from the AC plant of Cap 12.5 TR, Installing and testing of company made Scroll Type compressor Model No. SZ 185S4RC Lubricant P.O.E 160 SZ suitable for Refrigerent 407C. Initially charging of Gas 407 and commisioning all as directed by Engg-in-Charge.
Disconnecting from mains S & F in replacement of scroll compressor from the AC plant of Cap 23 TR, Installing and testing of company made Scroll Type compressor Model No. SZ 185S4RC Lubricant P.O.E 160 SZ suitable for Refrigerent 407C. Initially charging of Gas 407 and commisioning all as directed by Engg-in-Charge.
Disconnecting from mains S & F in replacement of scroll compressor from the AC plant of Cap 5 TR, Installing and testing of company made Scroll Type compressor Model No. SZ 185S4RC Lubricant P.O.E 160 SZ suitable for Refrigerent 407C. Initially charging of Gas 407 and commisioning all as directed by Engg-in-Charge.
Disconnecting from mains S & F in replacement of scroll compressor from the AC plant of Cap 5 TR, Installing and testing of company made Scroll Type compressor Model No. CR72KQM or equiv Lubricant P.O.E 160 SZ suitable for Refrigerent R22. Initially charging of Gas R22 and commisioning all as directed by Engg-in-Charge.
Supply and fix in replacement of the following material/spares/ components required for AHU / Blower shafts of AC Plants Note:- Fixing charges shall be deemed to be inclusive in the quoted rate.
MCCB of capacity 32 Amp 25 KA ( 4P) and protection from short ciracuit and overload.
Voltmeter Digital type suitable for 0-500 volts.
Ammeter Digital type suitable for 0-15 Amps.
Indicator bulbs Red,Blue and yellow Phases.
On, Off switch to start and stop the motors (Set of Two)
Contactor 3TS47 AC 1-100A AC3 415 V 50Hz 30 KW/40 HP Raina Audi)
MNO 22E (2NO.+2NC 230 V)
25A MNX Contactor coil 230 V (2No.+2NC)
32A MNX Contactor coil 230 V (2No.+2NC)
Timer ETR 550 220 Volt
Over load relay MN 9-15A Ma
Over load relay MN 14-23A
Over load relay MN 6-10A
Add on Aux Contact block 2NO.+2NC M
Repair/Servicing of three phase Servo Voltage Stablizer including dismantling of the AVR, disconnect from AC supply, draining of transformer oil, lifting of AVR from oil tank with the help of chain pulley block and tripod and checking of any fault in the AVR assembly. Replacement of defective parts if any such as electronic control card for voltage regulation, Carbon Brushes, indicator, RC net work, Micro switch, Voltmeters, Rubber gasket & packing wherever required, oven baking of series transformers including re-varnishing & re-taping, Series transformer coil, servicing of AVR including cleaning of all contacts tightening of all nuts and bolts, thimbles, all inter connections, making adjustment of Electronic control circuits, indicators, output adjustment potentio meter, voltmeter etc. Filling and top up of transformer oil after dehyderation and filltering of old and used transformer oil at site and testing of AVR for satisfactory operation as required installed at AC plants as per detail given below:-
50 KVA Three Phase (ICU & Maternity MH)
30 KVA Three Phase (Signal Center)
25 KVA Three Phase (Cold Storage)
Supply only the following spares/components required for replacement of defective spare parts of the Voltage stabilizer/AVR. Note:-Fixing charges shall be deemed to be inclusive in the quoted rate against Serial item No 34 here in before.
Carbon Brushes
Electronic Control Card for voltage regulation
Auto variable transformer Coils
Indicator bulbs Red,Blue and Green Phases.
Rubber Gaskets & packings.
Servo Motors
Voltmeter suitable for 0-500 volts 96x96 sqmm. Make: AE or Equivalent.
Supply only Transformer oil for Voltage stabiliser installed at AC Plants Note:- Transformer oil should be brought by the contractor in sealed barrel procured from the authorised dealer and produced the test certificate.
M & L earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt and connected to earth GI Strip 25x4mm means of bolts, nuts, check nuts and washers of galvanised iron or steel, thimbles and other end of the earth wire connected to DB and protected by galvanised iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No. 3 of MES schedule Pt I of 2009. Note: RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I, 80mm thick reinforced with XPM weighting not less than 4 Kg/Sqm in lieu of CI cover. Earthing shall be tested after execution. Payment shall only be made after satisfactory result.
Material and labour for earth continuity conductor fix to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe, fix to pole or any other indicated situation or loop earthing etc as required 25x4mm galvanised iron strip.
S&F CT Fan blade set 100 TR Delta cooling Tower with cupling.
S&F Branch header pipe tie rod set with flaper complete all as specified and directed. OT plant/ICU.
S&F Honey comb fins of size 24"x12"x6" inches for cooling tower complete all as specified and directed.
Supply and fix in replacement of Touch screen and PLC controler Digital type panel capacity 37.5 TR with accessories complete (OT MH AC Plant) all as specified and as ditected by Engr-in-Charge.
M&L in replacement of sencier chiller unit water cooled type for following capacity of AC plant as per existing size. Make: Danfoss/Syenergy.
Raina Auditorium AC plant for 70 TR.
OT MH AC plant for 37 TR.
ICU MH AC plant for 37 TR.
Disconnecting from mains and Taking out existing unserviceable compressor sealed unit from the split type AC of Cap 8.5 TR and Supply, Installing and testing of company made new compressor with 02 year guarantee including cleaning and removing dirt/dust from the cooling coil , condenser coil with necessary modification, cap tube etc. and charging of Gas F-22/R-34 and commosioning complete all as directed by Engr-in-Charge.
Description all as per item No 44.00 here in before but split type AC of capacity 5.5 TR.
Description all as per item No 44.00 here in before but split type AC of capacity 3 TR.
Disconnecting from mains and Taking out existing unserviceable Blower motor from the split type AC of Cap 8.5 TR and Supply, Installing and testing of company made new blow motor with 02 years guarantee including cleaning and removing dirt/dust from the cooling coil , condenser coil with necessary modification complete all as directed by Engr-in-Charge.
Description all as per item No 47.00 here in before but split type AC of capacity 5.5 TR.
Supply and installation Rotational moulded polythylene water storage tanks (cylindrical vertical with closed top) capacity 2000 Ltrs hoisted complete all as specified and directed.
S & F in Replacement of panel air filters, dry type, washable, rated air flow capacity 1600 CFM 99.9%, down to particle 20 micron of Suitable sizes or nearest for AHU of central AC plant.(NTS,NAD UTKROSH) suitable for Raina Audi, OT MH,ICU MH, Maternity MH and ICU Signal centre supplied as per ground size.
Taking down old unserviceable water flow switch of any size, supply and fixing testing of water flow switch of suitable size including suitable wiring with control panel complete all as specified and directed.
M & L Sub main wiring with two single core PVC insulated unsheathed cable 1100 volts FRLS grade with multi strand copper conductor and drawn into and including rigid 25 MM PVC conduit along with continuous earthing wire, in green colour completely on surface/concealed and connected to common earth dolly size on :- 16 Sqmm (3 run of 16 Sqmm and one run of 16 Sqmm for earth wire) complete all as specified and directed.
Supply and fix in replacement finned strip heater having terminal at one end and two holes at another end for installation, 240 volt, 3 KW complete all as specified and as directed.
Supply and Fix in replacement finned strip heater having terminal at one end and two holes at another end for installation, 240 volt, 2 KW complete all as specified and as directed.
Supply and Fix in replacement finned strip heater having terminal at one end and two holes at another end for installation, 240 volt, 1.5 KW complete all as specified and as directed.
Rewinding of electric motor and replacement of bearings and other parts of motor including servicing of capacity 7.5 HP , 3 phase, 50 HZ, 415 volt comprising following activities :-
Disconnecting & removing the electric motor from the installed position and loading / unloading transporting to contractor’s workshop for repairs and refixing the same in its own position in running condition.
Dismantling existing burnt winding from the motor, preparing for rewinding complete with super enameled copper winding wire of existing gauge including all insulating materials such as insulation paper, sleeves, tape, varnish etc and painting with two coats of super enamel paint over a coat of primer and greasing of bearings.
Loading/unloading/transporting motor/pump set to the site, installing in position, alignment, electric connection, commissioning and testing in actual working condition for 8 hours continuously.
Motors shall be handed over during the currency of contract on as required basis.
Description all as per item No 56 above but capacity of motor 2 HP to 5 HP.
Description all as per item No 56 above but capacity of motor upto 2 HP.
Disconnecting dismatiling of centrifugal monoblock pump set of following capacities of any RPM and dismantling defective parts and installing new parts such as impeller, nut, glant, impeller key, gland packing water deflector bush bearings sleeve, gaskets, volute, suction and delivery flange, stud, nuts and all other petty items required to make the pumpset functional and reassembling the pumpset including installation commissioning and testing all as specified and as directed.
for pump of capacity 2 HP to 7.5HP
for pump of capacity upto 2HP
Material and labour for testing of terminal connecting plate suitable for 7.5HP/5HP/3HP/2HP of monoblock pumpset complete all as specified and as directed.
Dismantling of worn out part of FRP cooling tower of AC Plants, cleaning of water tanks and body of cooling tower to make the cooling tower functional and serviceable in all respect including rectification of minor leakages from the cooling tower with M Seal/adhesive complete all as specified and directed by Eng-in-Charge.
Supply & fix in replacement side cover jalli of cooling tower for any capacity as per existing size and pattern all as specified and directed by Engr-in-Charge.
Supply & fix in replacement of sprinkler and other accessories like Aluminium distributor, PVC pipes,pvc spray nozzle of existing size, supporting fastener etc.of cooling tower complete as per existing make, type and design complete all as specified and directed by Engr-in-Charge for undermentioned cooling towers.
Cooling tower at OT MH
Cooling tower at ICU MH
Cooling tower at Maternity ward
Cooling tower at Signal Center
Supply & fixing in replacement MS class "B" pipe line of size 100 mm bore including welding work in the duct for OT and Raina auditorium complete all as specified and directed by Engr-in-Charge.
Desciption all as per item No 64 above but 80mm dia pipe for OT, ICU & Raina Audi
Desciption all as per item No 64 above but 50mm dia pipe for Maternity, Signal & ICU
Supply & fix in replacement GI Pipe Medium grade of size 50 mm bore including fittings such as bend, Tee etc, work in the duct all as specicfied and directed by Engr-in-Charge.
Desciption all as per item No 67 above but 40mm dia pipe.
Desciption all as per item No 67 above but 25mm dia pipe.
Painting to all pipelines of AC plants by removing pealed old paint with scrapper painting two coat of synthetic enamel paint of Ist quality as per standred shade and colour complete all as approved and directed by Engr-in-Charge.
Supply & fix in replacement water pressure gauge 100mm dia range 0-100 Lbs/sqr inch complete all as specified and directed by Engr-in-Charge.
Supply & fix in replacement water tempreture gauge range 0-50 degree centigrade complete all as specified and directed by Engr-in-Charge.
Supply & fix in replacement chiller water temp sensor for AC Plants at OT,Raina Audi, ICU as per exisiting size and make complete all as specified and directed by Engr-in-Charge.
S&F in replacement expansion valve suitable for following AC Plants all as specified and directed by Engr-in-Charge:-
OT MH 12 TR (one compressor) with Gas -22. Make: Danfoss/Sporlo.
ICU MH 12 TR (one compressor) with Gas 407. Make: Danfoss/Sporlo.
Maternity MH 5TR (one compressor) with gas. Make: Danfoss/Sporlo.
Signal center 7.5 TR with gas (one compressor). Make: Danfoss/Sporlo.
Raina Audi 23 TR (one compressor).
S&F in replacement top protector cover to the CT fan motor at the top of the cooling tower made of GI sheet 20 SWG, conical shape including iron flat of required size complete to protect the CT fan motor from rain water all as specified and directed by Engr-in-Charge.
S&F 3 way Modulating (motrised) valve suitable for following AC Plants as per existing size, type and making system functional by changing control wiring and control system all as specified and directed by Engr-in-Charge.
Raina Audi
Disconnecting from mains and overhauling of existing air compressor from the Air manifold system OT MH of Cap 225 litre,max working pressure 175 PSIG,size 457x1475 and hydraulic test pressure 290 PSIG and replacing of unserviceable and non functional parts with new items including piston, connecting rod, oil, greasing, oil strainer, air filter,inlet/outletvalve, suction/delivery pipe, gasket,crank,belt, repairing and Overhauling of 7.5 HP pump, 3 phase starter, vacuum pump, oil strainer and air filter, cable,silencer etc all as directed by Engg-in-Charge. Note- Replacement of parts rate included in the Quoated rate.
Cheking and testing of Complete oxygen gas supply line for leakage and rectify the defects by tighting the joint and minor repairs, at OT MH all as directed by Engr-in-Charge.
Supply and fix in replacement Manifiold NRV as per existing make & size/type.
Supply and fix in replacement Oxygen regulator as per existing make & size/type.
Supply and fix in replacement isolation valve 22 mm with fiting as per existing make & size/type.
Supply and fix in replacement Alarm 1 line as per existing make & size/type.
Supply and fix in replacement Alarm 2 line as per existing make & size/type.
Supply and fix in silver oxygen manifold flexible tail pipe of length 1 meter size 1/2 inch for N2O and O2 supply as per existing size.
Supply anf Fix 0.5 HP pump along with pvc tubing flexible pipe used for cleaning the plant of size 20 mm dia and length 20 m
S&F by replacing old unsv with new high pressure switch (HP switch )up to 260 PSI No and 190PSI NC including removing of refrigerent in empty cylinder and checking of pressure testing leak testing vaccum the system of 700 micron charging the refrigerent in the system complete all as specified and as directed by the engr in charge Make:Danfoss
S&F by replacement old unsv with new low pressure switch (lP switch )up to 25 PSI No and 45PSI NC including removing of refrigerent in empty cylinder and checking of pressure testing leak testing vaccum the system of 700 micron charging the refrigerent in the system complete all as specified and as directed by the engr in charge.
Supply,installation,testing and commissioning of cooling/heating thermostats(proportional thermostats) for various Air Handling units as by replacing old thermostats, as per specifications incl al accessories, mountings, wiring between thermostat & unit ,terminations etc, complete in all respect as required and as per specifications.Complete all as specified and directed by Engineer-in-Charge.
Supply,installation,testing and commissioning of industrial Humidistat for various Air Handling units by replacing old unsv humidistat as per specifications incl all accessories, mountings,wiring between humidistat & unit ,terminations etc, complete all as specified and directed by Engineer-in-Charge.
Supply,installation and replacement of old heater battery with new heater battery complete with tubular heater, control wiring,controls etc for 15 KW capacity with minimum 2 banks (1x9 KW+1x6 KW).Complete all as specified.
Replacing unsv existing Microprocessor based control display device with new Microprocessor based control display device suitable for 60 TR(minimum nominal capacity) capacity compressor complete with accessories as per specifications.
Replacing the existing size non- return valve with dual plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled/hot water circulation including insulation.
Supply and Fixing in replacement of existing 7.5 HP ,3 phase 4 pole condenser/chiller induction motor with new heavy duty 7.5 HP 3 phase 4 pole copper winding 1440 rpm squirrel cage IE2 foot mounted condenser/chiller induction motor with minimum 1 year warranty suitable for Raina Auditorium / OT at MH site requirement matching existing impeller diameter.
Supply and Fixing in replacement of existing 5 HP 3 phase 4 pole condenser/chiller induction motor of 5 HP with new heavy duty 5 HP 3 phase 4 pole copper winding 1440 rpm squirrel cage IE2 foot mounted condenser/chiller induction motor with minimum 1 year warranty suitable for OT/ICU/Maternity AC Plant at MH Ambala site requirement matching existing impeller diameter.
Supply and Fix in replacement HP/LP pressure cut out switch complete all as specified and as directed.
Supply and Fix in replacement Water Flow switch 220 V AC 10 Amps for Condenser/Chilled Water complete all as specified and as directed.
Supply and fixing for Display Board for electric shock treatment chart/ Maintenance Chart/ Description Chart of size 850x600 mm made out of CRCA sheet 2 mm thick with square pipe 35 mmx35 mm fixed around sheet by welding and making hanging arrangements on top of the board. Board shall be painted with two coats of stove enamelled paint (navy Blue) over a coat of red oxide primer and writing the detail with fluoroscent reflective tape (as per sample) by digital computerized printing style complete all as specified and as directed.
Supply & Fixing synthetic insulating rubber mat of size 2 metre x 1 metre x 19 mm (ISI Marked) suitable for control panels of AC Plants complete all as specified and as directed.
Taking down old unserviceable MCB/ MCCB from LT Panel and supply and fix new MCB/ MCCB of following size and capacity
MCCB rating 100 Amps, 4 pole, 415 volts breaking capacity 25 KA complete all as specified and as directed.
MCB TPN rating 40 Amps, 4 pole, C-type, 415 volts breaking capacity 9 KA complete all as specified and as directed.
MCB TPN rating 63 Amps, 4 pole, C-type, 415 volts breaking capacity 9 KA complete all as specified and as directed.
MCCB rating 200 Amps, 3 pole, 415 volts breaking capacity 35 KA complete all as specified and as directed.
MCB rating 6-32 Amps, single pole, 220 volts breaking capacity 10 KA complete all as specified and as directed.
Taking out old unserviceable Timer Switches from LT panel / starter and supply and fix new timer switch range 0 to 60 second complete all as specified and directed.
Supply & Fixing of HEPA Filter size 500 x 500 x 300mm (NS) flanged type of aluminium construction having efficiency 99.97% down to 0.3 micron including taking down of damaged filter complete all as specified and directed.
Note :- Amount of credit of Rs. 215320.00 for retrieved materials is mentioned in Schedule of Credit mentioned in tender documents in pdf form which will be deducted offline while acceptance of tender.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .