Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.4 LAdmitted-Fee/PreQual/Technical/Finance | L1 | Admitted-Fee/PreQual/Technical/Finance |
| Sl No | Description | Qty | Unit | INTIMATE REFRIGERATION AND AIR CONDITIONS L1 |
|---|---|---|---|---|
| 1.00SITC of Air conditioning system | ||||
| 1.00 | OD55185/2025-2026:-SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF MODULAR TYPE16HP VRF ODU. THE OUTDOOR UNIT SHALL BE FACTORY ASSEMBLED, WEATHER PROOF
CASING, CONSTRUCTED FROM HEAVY GAUGE MILD STEEL PANELS AND COATED WITH BAKED ENAMEL FINISH. THE UNIT SHOULD BE COMPLETELY FACTORY WIRED TESTED WITH ALL NECESSARY CONTROLS. OUTDOORS UNITS OF THE VRF /VRV SYSTEM SHALL BE COMPACT AIR-COOLED TYPE. ALL THE COMPRESSORS OF THE OUTDOOR UNITS MUST BE HERMETICALLY SEALED BLDC INVERTER SCROLL/TWIN ROTARY TYPE. OEM SHOULD USE THERE ON MAKE COMPRESSORS IN VRF /VRV SYSTEM WHICH IS TO BE SUPPLIED. SYSTEM COP SHALL NOT BE LESS THAN – 3.4 AT AIR CONDITION AND SUITABLE TO OPERATE AT HEAT LOAD PROPORTIONAL TO INDOOR TEMPERATURE REQUIREMENT.ALUMINUM FINS OF CONDENSER COIL SHALL HAVE ANTI CORROSIVE EPOXY RESIN OCEAN BLACK COATING ALONG WITH HYDROPHILIC COATING PRE-COATED AT FACTORY. THE ANTI-CORROSIVE TREATMENT SHOULD HAVE BEEN TESTED FOR AT LEAST 2500 HRS OF STANDARD SALT
SPRAY TEST AND MUST HAVE A CERTIFIED LIFE OF MINIMUM 20 YEARS SUPPORTED BY CERTIFICATE FROM REPUTED INTERNATIONAL INSTITUTION IS MANDATORY. THE
TREATMENT SHOULD BE SUITABLE FOR AREAS OF HIGH POLLUTION AND SALT LADEN AIR. MODULAR SYSTEM TO BECONFIGURED AS PER MENTION MODULES GIVEN IN BRACKET. MAKE: DAIKIN/LG/MITSUBISHI | 1 | no | 4,21,067 ₹4,21,067 Lowest |
| 1.00 | OD55186/2025-2026:-SUPPLY, INSTALLATION, TESTING& COMMISSIONING OF LG 4-Way CASSETTE TYPE 3TR VRF INDOOR UNIT.ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THATCONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTE CONTROLLERS. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE /50HZ. UNIT SHALL BE PROVIDED WIRELESS REMOTE CONTROLLER AND IT SHOULD FACILITATE ON/ OFF FUNCTION, CHANGE OF TEMPERATURE SETTINGS, FAN SPEED SETTING, OPERATION MODE SETTING. 4 WAY CASSETTE MAKE: DAIKIN/LG/MISTHUBISHI | 2 | no | 46,543 ₹93,086 Lowest |
| 1.00 | OD55187/2025-2026:OD109888/2023-2024 -SUPPLY, INSTALLATION, TESTING& COMMISSIONING OF LG 4-Way CASSETTE TYPE 2TR VRF INDOOR
UNIT.ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THATCONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE
LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTE CONTROLLERS. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE /50HZ. UNIT SHALL BE PROVIDED WIRELESS REMOTE CONTROLLER AND IT SHOULD FACILITATE ON/ OFF FUNCTION, CHANGE OF TEMPERATURE SETTINGS, FAN SPEED SETTING, OPERATION MODE SETTING. 4 WAY CASSETTE MAKE: DAIKIN/LG/MISTHUBISHI | 2 | no | 44,145 ₹88,290 Lowest |
| 1.00 | OD55188/2025-2026:SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF VRF LG 1-way CASSETTE TYPE 1.5TR INDOOR UNITS WITH WIRELESS REMOTE CONTROLLER.THE INDOOR UNIT SHALL BE OF THE ONE-WAY CASSETTE TYPE INDOOR UNITS AS PER THE REQUIREMENTS SPECIFIED IN THE BOQ / DRAWINGS. ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THAT CONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTECONTROLLERS. ALL INDOOR UNITS SHOULD HAVE INBUILT DRAIN PUMP WITH MINIMUM 700MM VERTICAL LIFT HEAD. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE / 50HZ.) MAKE: DAIKIN/LG/MISTHUBISHI | 1 | no | 39,785 ₹39,785 Lowest |
| 1.00 | OD55189/2025-2026:SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF VRF LG 1-way CASSETTE TYPE 1TR INDOOR UNITS WITH WIRELESS REMOTE CONTROLLER.THE INDOOR UNIT SHALL BE OF THE ONE-WAY CASSETTE TYPE INDOOR UNITS AS PER THE REQUIREMENTS SPECIFIED IN THE BOQ / DRAWINGS. ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THAT CONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTECONTROLLERS. ALL INDOOR UNITS SHOULD HAVE INBUILT DRAIN PUMP WITH MINIMUM 700MM VERTICAL LIFT HEAD. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE / 50HZ.) MAKE: DAIKIN/LG/MISTHUBISHI | 1 | no | 37,496 ₹37,496 Lowest |
| 1.01 | OD55184/2025-2026:SUPPLY AND INSTALLATION OF INDOOR UNITS REMOTE CONTROLLER | 6 | no | 2,507 ₹15,042 Lowest |
| 1.01 | OD55183/2025-2026:-SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF Y JOINTS INDOOR SIDE | 5 | no | 10,464 ₹52,320 Lowest |
| 1.01 | OD55210/2025-2026:Supply and providing the following size soft drawn copper pipe for extending the pipe between out door and indoor unit, including insulating the pipe using rubberized foam sleeve 10mm thick, brazing, leak testing etc.:- 1/4 inch (6.35 mm) and 1/2 inch (12.7 mm) 22 gauge | 10 | metre | 799 ₹7,990 Lowest |
| 1.01 | OD55220/2025-2026:SITC of hard drawn copper refrigerant piping including all accessories including joints properly brazed insulated with chemically crosslinked nitrile rubber fire retardant grade class O 13 mm Thickness necessary supports as required of size 9.52 mm dia. | 30 | metre | 954 ₹28,620 Lowest |
Tender Value
₹9.3 L
EMD Value
₹23,347
Closing Date
20 Jul 2026, 6:00 pmClosed
Assistant Executive Engineer
Assistant Executive Engineer,PWD Electrical sub division,Tvpm
DEPOSIT-Neuro and Nephro SAT-SITC of Air conditioning system in the Neuro and Nephro Lab at Golden Jubilee block fifth floor at SAT Hospital, Thiruvananthapuram-Electrical AC Work
2026_PWD_858319_2
ESDT/ET-50/2026-27
Open Tender
Electrical Works
Item Rate
120 days
PWD Electrical sub division Thiruvananthaouram
please refer tender documents
6 documents required · 6 mandatory
₹2,060
₹23,347
22 Jul 2026
13 Jul 2026
22 Jul 2026
13 Jul 2026
20 Jul 2026
13 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SITC of Air conditioning system | |||||
| 1.001 | OD55185/2025-2026:-SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF MODULAR TYPE16HP VRF ODU. THE OUTDOOR UNIT SHALL BE FACTORY ASSEMBLED, WEATHER PROOF
CASING, CONSTRUCTED FROM HEAVY GAUGE MILD STEEL PANELS AND COATED WITH BAKED ENAMEL FINISH. THE UNIT SHOULD BE COMPLETELY FACTORY WIRED TESTED WITH ALL NECESSARY CONTROLS. OUTDOORS UNITS OF THE VRF /VRV SYSTEM SHALL BE COMPACT AIR-COOLED TYPE. ALL THE COMPRESSORS OF THE OUTDOOR UNITS MUST BE HERMETICALLY SEALED BLDC INVERTER SCROLL/TWIN ROTARY TYPE. OEM SHOULD USE THERE ON MAKE COMPRESSORS IN VRF /VRV SYSTEM WHICH IS TO BE SUPPLIED. SYSTEM COP SHALL NOT BE LESS THAN – 3.4 AT AIR CONDITION AND SUITABLE TO OPERATE AT HEAT LOAD PROPORTIONAL TO INDOOR TEMPERATURE REQUIREMENT.ALUMINUM FINS OF CONDENSER COIL SHALL HAVE ANTI CORROSIVE EPOXY RESIN OCEAN BLACK COATING ALONG WITH HYDROPHILIC COATING PRE-COATED AT FACTORY. THE ANTI-CORROSIVE TREATMENT SHOULD HAVE BEEN TESTED FOR AT LEAST 2500 HRS OF STANDARD SALT
SPRAY TEST AND MUST HAVE A CERTIFIED LIFE OF MINIMUM 20 YEARS SUPPORTED BY CERTIFICATE FROM REPUTED INTERNATIONAL INSTITUTION IS MANDATORY. THE
TREATMENT SHOULD BE SUITABLE FOR AREAS OF HIGH POLLUTION AND SALT LADEN AIR. MODULAR SYSTEM TO BECONFIGURED AS PER MENTION MODULES GIVEN IN BRACKET. MAKE: DAIKIN/LG/MITSUBISHI | - | no | - | - |
| 1.002 | OD55186/2025-2026:-SUPPLY, INSTALLATION, TESTING& COMMISSIONING OF LG 4-Way CASSETTE TYPE 3TR VRF INDOOR UNIT.ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THATCONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTE CONTROLLERS. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE /50HZ. UNIT SHALL BE PROVIDED WIRELESS REMOTE CONTROLLER AND IT SHOULD FACILITATE ON/ OFF FUNCTION, CHANGE OF TEMPERATURE SETTINGS, FAN SPEED SETTING, OPERATION MODE SETTING. 4 WAY CASSETTE MAKE: DAIKIN/LG/MISTHUBISHI | - | no | - | - |
| 1.003 | OD55187/2025-2026:OD109888/2023-2024 -SUPPLY, INSTALLATION, TESTING& COMMISSIONING OF LG 4-Way CASSETTE TYPE 2TR VRF INDOOR
UNIT.ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THATCONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE
LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTE CONTROLLERS. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE /50HZ. UNIT SHALL BE PROVIDED WIRELESS REMOTE CONTROLLER AND IT SHOULD FACILITATE ON/ OFF FUNCTION, CHANGE OF TEMPERATURE SETTINGS, FAN SPEED SETTING, OPERATION MODE SETTING. 4 WAY CASSETTE MAKE: DAIKIN/LG/MISTHUBISHI | - | no | - | - |
| 1.004 | OD55188/2025-2026:SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF VRF LG 1-way CASSETTE TYPE 1.5TR INDOOR UNITS WITH WIRELESS REMOTE CONTROLLER.THE INDOOR UNIT SHALL BE OF THE ONE-WAY CASSETTE TYPE INDOOR UNITS AS PER THE REQUIREMENTS SPECIFIED IN THE BOQ / DRAWINGS. ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THAT CONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTECONTROLLERS. ALL INDOOR UNITS SHOULD HAVE INBUILT DRAIN PUMP WITH MINIMUM 700MM VERTICAL LIFT HEAD. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE / 50HZ.) MAKE: DAIKIN/LG/MISTHUBISHI | - | no | - | - |
| 1.005 | OD55189/2025-2026:SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF VRF LG 1-way CASSETTE TYPE 1TR INDOOR UNITS WITH WIRELESS REMOTE CONTROLLER.THE INDOOR UNIT SHALL BE OF THE ONE-WAY CASSETTE TYPE INDOOR UNITS AS PER THE REQUIREMENTS SPECIFIED IN THE BOQ / DRAWINGS. ALL INDOORS HAVE ELECTRONIC EXPANSION VALVE THAT CONTROLS THE FLOW OF REFRIGERANT IN RESPOND TO THE LOAD VARIATIONS OF ROOM ACCORDING TO SET TEMPERATURE, WHICH CAN SET BY REMOTECONTROLLERS. ALL INDOOR UNITS SHOULD HAVE INBUILT DRAIN PUMP WITH MINIMUM 700MM VERTICAL LIFT HEAD. ELECTRICITY CHARACTERISTICS FOR INDOOR UNIT SHALL BE 240 VOLTS/ 1PHASE / 50HZ.) MAKE: DAIKIN/LG/MISTHUBISHI | - | no | - | - |
| 1.006 | OD55184/2025-2026:SUPPLY AND INSTALLATION OF INDOOR UNITS REMOTE CONTROLLER | - | no | - | - |
| 1.007 | OD55183/2025-2026:-SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF Y JOINTS INDOOR SIDE | - | no | - | - |
| 1.008 | OD55210/2025-2026:Supply and providing the following size soft drawn copper pipe for extending the pipe between out door and indoor unit, including insulating the pipe using rubberized foam sleeve 10mm thick, brazing, leak testing etc.:- 1/4 inch (6.35 mm) and 1/2 inch (12.7 mm) 22 gauge | - | metre | - | - |
| 1.009 | OD55220/2025-2026:SITC of hard drawn copper refrigerant piping including all accessories including joints properly brazed insulated with chemically crosslinked nitrile rubber fire retardant grade class O 13 mm Thickness necessary supports as required of size 9.52 mm dia. | - | metre | - | - |
stage.html
html • 0.02 MB
finance_1454882.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
sbd.pdf
Tender Documents • 1.63 MB
nit.pdf
Tender Documents • 0.02 MB
mom.pdf
Tender Documents • 11.27 MB
BOQ_1454882.xls
BOQ • 0.32 MB
acsc.pdf
Tender Documents • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .