Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.2 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED L1 | |
| 2 | L2₹20.8 L+₹2.6 L (14.2%)Rejected-Finance 50 SARASWATI VIHAR SINGHAWALA AMBALA CITY | AMBALA CITY | L2 | Rejected-Finance Being rejected L2 | |
| 3 | L3₹21.2 L+₹3.0 L (16.5%)Rejected-Finance | L3 | Rejected-Finance Being rejected L3 | |
| 4 | L4₹24.6 L+₹6.4 L (35.2%)Rejected-Finance STREET NO 10 MALLOMAZRA ROAD BHAKHRA ENCLAVE PATIALA PB | PATIALA | PUNJAB | 140401 | L4 | Rejected-Finance Being rejected L | |
| 5 | L5₹24.8 L+₹6.6 L (36.3%)Rejected-Finance 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L5 | Rejected-Finance Being rejected L5 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
29 Nov 2021, 6:00 pmClosed
SHRI N N LANGHE EE GE SOUTH AMBALA
GE SOUTH AMBALA CANTT
CERTAIN MISC REPAIR MAINT OF ELECTRIC LOAD LINE MAIN DISTRIBUTION BOARDS SUB MAIN WIRING AND INTERNAL ELECTRIFICATION SYSTEM AND ASSOCIATED WORKS IN OTM ACCN OF 612 I BDE CAMP AND ALLIED MSL AD REGT 145 LT AD 140 LT AD 513 RKT REGT ALONGWITH WKSP COY
2021_MES_476205_2
GE(SOUTH)/AMB-34/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE SOUTH AMBALA CANTT
AS PER NIT
9 documents required · 9 mandatory
₹500
GE SOUTH AMBALA CANTT
₹60,000
Yes
18 Dec 2021
2 Nov 2021
1 Dec 2021
2 Nov 2021
29 Nov 2021
16 Nov 2021
2 Nov 2021 - 15 Nov 2021
Amount
Supply and fixing of load bank (MCCB distribution panel) double door type ready to use sub distribution panel 4 way, suitable for 3 phase four wire system including 1x 250 Amp incoming MCCB and and 4x63 Amps outgoing MCCB alongwith voltmeter and ammeter and suitable size copper bus bar. Enclosure made from 1.6mm thick CRCA sheet, IP 43 protection, painted with powder coating, incl all inetrnal wiring done with PVC insulated copper cable, wall mounted, double door type, compartmentlized for indoor application alongwith manufacturer test certificate and suitable for fixing of existing 3 phase energy meter including taking down existing distribution panel complete all as specified and as directed.
Supply and fixing of sheet metal enclosures vertical distribution board VTPN,(MCCB DB) 4 ways, double door , 415 volts with 250 amps rated bus bar IP 43 protection, with shrouded neutral bar and insulated bus bar and earth link, with and including MCCB 4 pole,160 AMPS ,25 KA as incomer and MCB s as out going complete with making suitable size of MS cabinet 2 mm thick dully grouted on the wall (flush) with opening arrangement including making connections with suitable size of lugs and making good the disturbed surface matching with existing surface including taking down existing MCCB DBs including MCBs complete all as specified and as directed.
Supply and fixing of sheet metal enclosures vertical distribution board VTPN,(MCCB DB) 4 ways, double door , 415 volts with 200 amps rated bus bar IP43 protection, with shrouded neutral bar and insulated bus bar and earth link, with and including MCCB 4 pole,125AMPS ,25 KA as incomer and MCB s as out going complete with making suitable size of MS cabinet 2 mm thick dully grouted on the wall (flush) with opening arrangement including making connections with suitable size of lugs and making good the disturbed surface matching with existing surface including taking down existing MCCB DBs including MCBs complete all as specified and as directed.
Supply and fixing of sheet metal enclosures vertical distribution board VTPN,(MCCB DB) 4 ways, double door , 415 volts with 200 amps rated bus bar IP43 protection, with shrouded neutral bar and insulated bus bar and earth link, with and including MCCB 4 pole,100 AMPS 16 KA as incomer and MCB s as out going complete with making suitable size of MS cabinet 2 mm thick dully grouted on the wall (flush) with opening arrangement including making connections with suitable size of lugs and making good the disturbed surface matching with existing surface including taking down existing MCCB DBs including MCBs complete all as specified and as directed.
Supply, installation, testing of SPN distibution board 12 way,double door, IP 43, as per IS 8623 including 200 amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles including taking down existing MCB DBs including MCBs complete all as specified and as directed.
Supply, installation, testing of SPN distibution board 8 way,double door, IP 43, as per IS 8623 including 200 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles including taking down existing MCB DBs including MCBs complete all as specified and as directed.
Supply, installation, testing of SPN distibution board 4 way,double door, IP 43, as per IS 8623 including 200 amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles including taking down existing MCB DBs including MCBs complete all as specified and as directed.
Supply and fixing of MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, 'B' curve 6 to 32 Amps, ISI marked complete all as specified and as directed.
Supply and fixing of MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, 'B' curve 40 to 63 Amps, ISI marked complete all as specified and as directed.
Supply and fixing of MCB single pole and neutral 240 volts, 16 to 32 Amps,10KA, 50 Hz, 'B' Series complete all as specified and as directed.
Supply and fixing of MCB single pole and neutral 240 volts, 40 to 63 Amps,10KA, 50 Hz, 'B' Series complete all as specified and as directed.
Supply and fixing in repair MCB four pole, 240 volts, 50Hz, breaking capacity 10KA, 100 Amp complete all as specified and as directed.
Supply and fixing in repair MCB four pole, 240 volts, 50Hz , breaking capacity 10KA, 40A to 63 Amps, B curve, complete all as specified and as directed.
Supply and fixing of channel for fixing of LED tube rod, aluminium housing body in CRCA body suitable for 18/20 watt LED tube, high efficient, AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and as directed. Note: Tube rod shall be measured and paid for separately.
Supply and fixing of 18 W/ 20W Polycarbonate LED tube light, environment friendly, high efficient, T8 with aluminium extrusion heat sink for optimum performance with high luminous efficiency and easy and taking down existing tube light and removal complete all as specified and as directed. Note: - Tube rod must be get approved from Engr in charge to check fesibilty i.e. one end contact or two end contact for fixing in existing LED fittings.
Supply and fixing of LED luminaries of capacity 20 watt integrated aluminium batten with including Oppel diffuser complete including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and as directed.
Supply and fixing of decorative surface mounted LED tube light fitting with high efficient diffuser mirror light, aluminium housing in CRCA body suitable and including 10 watt LED tube high efficient, AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and as directed.
Supply and fixing of bulk head light fitting, 10 watt, energy efficient with lamp 10 watt with provision of 2/3 core PVC copper conductor cable 0.5 Sqmm size from ceiling rose to light fitting complete including disconnecting and taking down old existing light fitting of any description and in any position complete all as specified and as directed.
Supply and fixing in repair lamp any type with LED lamp 9 Watt with B 22 base cap type wider spread LED bulb with Opal Diffuser complete all as specified and as directed.
Supply and fixing of recess/ surface mounted LED flat panel 2' x 2' with high efficient LEDs and glare free full decorative light fitting, 36 watt, energy efficient provided with including LED 36 watt with provision of 2/3 core PVC copper conductor cable 1.5 Sqmm size to light fitting and complete including disconnecting and taking down existing light fitting and removal complete all as specified and as directed.
Supply and fixing in repair security light made up of 25mm dia, 0.9 metre long GI pipe, light grade, bent to required length, fixed to wall with two clamps made of 20 x 3 mm mild steel flat minimum 15cm long, 4 nos 8mm dia bolts with nuts complete all as specified and as directed.
Supply and fixing of LED security light luminaire 30 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP65 protection, better optics for uniform distribution with multiplte LEDs not less than 2 W eachand having optical grade polycarbonate lens with all accessories internally pre wired and including connecting up with Two core 1.5 sq mm copper conductor cable from connector to ceiling rose to connection of light including disconnecting and taking down old unserviceable security light fitting of any description and in any position complete all as specified and as directed.
Supply and fixing of LED security light luminaire 45 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP65 protection, better optics for uniform distribution with multiplte LEDs not less than 2 W eachand having optical grade polycarbonate lens with all accessories internally pre wired and including connecting up with Two core 1.5 sq mm copper conductor cable from connector to ceiling rose to connection of light including disconnecting and taking down old unserviceable security light fitting of any description and in any position complete all as specified and as directed.
Supply and fixing of post top lantern LED 30W , cast aluminium spigot, with high effieient LED light, with poly carbonate diffuser, complete with high efficient LED lamp 30 W and accessories internally pre wired and including connecting up with three core 1.5 sqmm flexible copper conductor cable including disconnecting and taking down existing light fitting and removal complete all as specified and as directed.
Supply and fixing of LED security light luminaire 30 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP65 protection, better optics for uniform distribution with multiplte LEDs not less than 2 W each and having optical grade polycarbonate lens with 4 hours battery back up all accessories internally pre wired and including connecting up with Two core 1.5 sq mm copper conductor cable from connector to ceiling rose to connection of light including disconnecting and taking down old unserviceable security light fitting of any description and in any position complete all as specified and directed.
Disconnecting and taking down old existing wall fitting of any description and in any position and Supply and fixing wall mounting bracket typr wooden base with finished and disgnied cover of V/opal/spherical shape with and including 9 to 12 watt LED lamp of B22 base including connecting up with three core 1.5 sqmm flexible copper conductor cablecomplete all as specified and as directed.
Disconnecting and taking down old existing wall fitting of any description and in any position and Supply and fixing surface mounted type metal base with finished and disgnied diffuser of round/ square/ oval shape slim down lighter 12 watt LED including suitable capacity driver complete connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and as directed.
Disconnecting and taking down old existing wall fitting of any description and in any position and Supply and fixing surface mounted type metal base with finished and disgnied diffuser of round/ square/ oval shape slim down lighter 18 watt LED including suitable capacity driver complete connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed.
Dismantling/taking down carefully aluminium/ copper point wiring (light, fan, socket or power) complete, including fixtures and fittings such as switches, ceiling roses, pendants, regulators , sockets, light fittings etc., removing materials to stores for keeping in safe custody for taking credit and making good the disturbed surfaces of walls, ceilings etc. to match with the existing surface complete all as specified and as directed.
Material and labour for concealed point wiring using approved colour coding as per IS, with multi stranded copper conductor 1.5 sqmm (Nominal area), single core, FRLSH (FIRE Retardant Low Smoke and low Halogen), PVC insulated and unsheathed stranded cable drawn through and including non metallic, heavy duty PVC concealed conduit not less than 20mm dia and its fittings including all tees, bell mouth pieces and fixing accessories such as couplers, saddlers, pipe hooks etc, PVC junction boxes ISI marked with GI flush boxes / sunken boxes made out of 1.2mm thick of any module from 2 to 18 module confirming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly including modular cover plates with frame i.e. inner and outer plate extended upto 25 mm over sunken box for housing the modular switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light / fan / Bell point contorlled by one switch including 1.5 sqmm single core PVC insulated and unsheathed FRLSH (FIRE Retardant Low Smoke and low Halogen) copper cable, 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor upto common earth and connecting to common earth dolly with suitable size of lugs for one light point/ fan point/bell point controlled by one switch complete all as specified and as directed. NOTES : - (i) The quoted rates shall be deemed to be inclusive for cutting chases by chase cutter in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of point wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary accessories/fittings. (ii) Point wiring & earth wire shall be connected to each & every flush/sunken box. (iii) All screws, fasteners, bolts, nuts & washer shall be cadmium plated & the cost of which is deemed to be included in the quoted unit rates.
Description all as per item No 30.00 above but for socket out let point 5 Amps on same board complete all as specified and as directed.
Description all as per item No 30.00 above but for socket out let point 5 Amps on independent board complete all as specified and as directed.
Description all as per srl item No 30.00 above but point wiring for one socket out let 15 & 5 Amps (independent) controlled by one switch with using 2.5 Sq mm (nominal area) stranded copper conductor complete all as specified and as directed.
Material and labour for point wiring in existing conduit using approved colour coding as per IS, with multi stranded copper conductor 1.5 sqmm (Nominal area), single core, FRLSH PVC insulated and unsheathed stranded cable drawn through and including existing non metallic/mettalic heavy duty concealed/Surface conduit and including replacement of its fittings including all tees, bell mouth pieces and fixing accessories such as couplers, saddlers, pipe hooks etc, PVC junction boxes ISI marked with GI flush boxes / sunken boxes made out of 1.2mm thick of any module from 2 to 18 module confirming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly including modular cover plates with frame i.e. inner and outer plate extended upto 25 mm over sunken box for housing the modular switches, socket outlets, fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for one light / fan / Bell point contorlled by one switch including 1.5 sqmm single core PVC insulated and unsheathed FRLSH copper cable, 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor upto common earth and connecting to common earth dolly with suitable size of lugs for one light point/ fan point/Bell Point controlled by one switch complete all as specified and as directed. NOTES : - (i) Point wiring & earth wire shall be connected to each & every flush/sunken box. (ii) All screws, fasteners, bolts, nuts & washer shall be cadmium plated & the cost of which is deemed to be included in the quoted unit rates.
Description all as per item No 34.00 above but for socket out let point 5 Amps on same board complete all as specified and as directed.
Description all as per item No 34.00 above but for socket out let point 5 Amps on independent board complete all as specified and as directed.
Description all as per srl item No 34.00 above but point wiring for onesocket out let 15&5 Amps (independent) controlled by one switch with using 2.5 Sq mm (nominal area) stranded copper conductor complete all as specified and directed.
Supply and fixing of modular switches, bell push, 6 amps one module, 230V, 50 Hz supply, complete all as specified and as directed.
Supply and fixing of modular switches, one way, 6 amps one module, 230V, 50 Hz supply, complete all as specified and as directed.
Supply and fixing of modular switches, one way, 20 Amps, one module, 230 Volt, AC supply, complete all as specified and as directed.
Supply and fixing of modular socket outlet 6 amps, 5 pin, 2 in 1 combined, 2 module, 230 volt, complete all as specified and as directed.
Supply and fixing of modular socket outlet 6/16 amps, 2 in 1, combined 2 module, complete all as specified and as directed.
Supply and fixing of fan regulator step type one module / 2 module, 120w 230 Volts, 50 Hz, AC complete all as specified and as directed.
Supply and fixing of modular blanking plate 1 module complete all as specified and as directed.
Material and labour for concealed point wiring with 1.50 Sqmm single core PVC insulated , unsheathed cable FRLSH, 1100 volt grade with multi stranded copper conductor drawn through and including medium grade, ISI marked, PVC conduit not less than 25 mm dia with FRLSH )accessories, concealed and including provision of 1.50 Sqmm single core PVC insulated , unsheathed cable FRLSH 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken box or pressed steel terminal boxes made out of 1.6 mm thick mild steel sheet metal conforming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly and coated with two coats of anti corrosive paint over a coat of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover extended up to 25 mm over sunken box for housing the switches , socket outlets, fan regulators etc. with brass screws and brass washers and making good the disturbed surfaces as per existing for one light/fan point/bell point controlled by one switch. NOTES : - (i) The quoted rates shall be deemed to be inclusive for cutting chases by chase cutter in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of point wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary accessories/fittings. (ii) Point wiring & earth wire shall be connected to each & every flush/sunken box. (iii) All screws, fasteners, bolts, nuts & washer shall be cadmium plated & the cost of which is deemed to be included in the quoted unit rates.
Description all as per item No 45.00 above but for socket out let point 5 Amps on same board, complete all as specified and as directed.
Description all as per item No 45.00 above but for socket out let point 5 Amps on independent board, complete all as specified and as directed.
Description all as per item No 45.00 above but with 2.5 Sqmm cable for 3pin 15 Amps switch socket outlet (Power Point), complete all as specified and as directed.
Material and labour for concealed point wiring with 1.50 Sqmm single core PVC insulated , unsheathed cable FRLSH, 1100 volt grade with multi stranded copper conductor drawn through existing medium grade, ISI marked, PVC conduit not less than 25 mm dia with FRLSH )accessories, concealed on wall/ceiling and including provision of 1.50 Sqmm single core PVC insulated , unsheathed cable FRLSH 1100 volt grade with multi stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with suitable size of lugs, including mild steel sunken box or pressed steel terminal boxes made out of 1.6 mm thick mild steel sheet metal conforming to IS-5139(pt-I) of 1969 and IS:14772-2000 with earth dolly and coated with two coats of anti corrosive paint over a coat of red oxide primer both internally and externally including provision of new 3 mm thick plastic laminated sheet top cover extended up to 25 mm over sunken box for housing the switches , socket outlets, fan regulators etc. with brass screws and brass washers and making good the disturbed surfaces as per existing for one light/fan point/bell point controlled by one switch. NOTES : - (i) The quoted rates shall be deemed to be inclusive for cutting chases by chase cutter in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of point wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary accessories/fittings. (ii) Point wiring & earth wire shall be connected to each & every flush/sunken box. (iii) All screws, fasteners, bolts, nuts & washer shall be cadmium plated & the cost of which is deemed to be included in the quoted unit rates.
Description all as per item No 49.00 above but for socket out let point 5 Amps on same board, complete all as specified and as directed.
Description all as per item No 49.00 above but for socket out let point 5 Amps on independent board, complete all as specified and as directed.
Description all as per item No 49.00 above but with 2.5 Sqmm cable for 3pin 15 Amps switch socket outlet (Power Point), complete all as specified and as directed.
Supply and fixing of bell push 5 Amps, flush type, single pole, one way, 230 volt, AC supply, ISI Marked, complete all as specified and as directed.
Supply and fixing of switch piano 5 Amps, flush type, single pole, one way, 230 Volt, AC supply, ISI Marked, complete all as specified and as directed.
Supply and fixing of switch piano 15 Amps flush type one way 230 Volts, 50 Hz, AC supply, ISI Marked, complete all as specified and as directed.
Supply and fixing of socket outlet 5 pin, 2 in 1, 5 amps, 230 volt. flush type, ISI Marked, complete all as specified and as directed.
Supply and fixing of socket outlet 2 in 1, 5/15 amps and multi pin flush type, complete all as specified and as directed.
Supply and fixing of ceiling rose surface bakelite 65x50mm, 3 terminal complete all as specified and as directed.
Supply and fixing of fan regulator electronic step type, 230 Volts, AC supply, suitable for ceiling fan any type/make/sweep, complete all as specified and as directed.
Supply and fixing of door bell electric ,ding dong /musical type, single phase 230 volts, ISI marked complete all as specified and as directed.
Supply and fixing of lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings, complete all as specified and as directed.
Supply and fixing in repair sheet metal enclosure SP with two pin and earth plug and socket with one single pole, MCB 32 Amps, 'C' Curve, 240 Volts complete all as specified and as directed.
Supply and fixing in repair sheet metal enclosure SP with two pin and earth plug and socket with one single pole, MCB 20 Amps, 'C' Curve, 240 Volts complete all as specified and as directed.
Material and labour for concealed sub main wiring with two single core FRLSH PVC insulated unsheathed copper conductor cable 2.5 Sqmm drawn in and including rigid non metallic PVC medium grade 20 mm dia New concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLSH of 2.50 sqmm,green colour for earth continuity conductor including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 3 run of cable and 1 run of conduit shall be measured as 1 unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary aceessories/fittings.
Material and labour for concealed sub main wiring with two single core FRLSH PVC insulated unsheathed copper conductor cable 4 Sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLSH of 4 sqmm, green colour for earth continuity conductor including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 3 run of cable and 1 run of conduit shall be measured as 1 unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary aceessories/fittings.
Material and labour for concealed sub main wiring with two single core FRLSH PVC insulated unsheathed copper conductor cable 6sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLSH of 6 sqmm, green colour for earth continuity conductor including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 3 run of cable and 1 run of conduit shall be measured as 1 unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary aceessories/fittings.
Material and labour for concealed sub main wiring with four single core FRLSH PVC insulated unsheathed copper conductor cable 6 sqmm drawn in and including rigid non metallic PVC medium grade 32 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated, stranded copper conductor FRLSH of 6 sqmm, green colour for earth continuity conductor including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 5 run of cable and 1 run of conduit shall be measured as 1 unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary aceessories/fittings.
Material and labour for concealed sub main wiring with four single core FRLSH PVC insulated unsheathed copper conductor cable 10 sqmm drawn in and including rigid non metallic PVC medium grade 32 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated, stranded copper conductor FRLSH of 10 sqmm, green colour for earth continuity conductor including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 5 run of cable and 1 run of conduit shall be measured as 1 unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary aceessories/fittings.
Material and labour for concealed sub main wiring with four single core FRLSH PVC insulated unsheathed copper conductor cable 16 sqmm drawn in and including rigid non metallic PVC medium grade 32 mm dia concealed conduit with accessories on wall or ceiling with one additional PVC insulated, stranded copper conductor FRLSH of 16 sqmm, green colour for earth continuity conductor including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 5 run of cable and 1 run of conduit shall be measured as 1 unit. (ii) The quoted rates shall be deemed to be inclusive for cutting chases in wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface. The portion of sub main wiring at ceiling shall be in surface conduit of suitable size fixed on ceiling surface with using necessary aceessories/fittings.
Supply and fixing in reapir 3 pin plug top, 5 amp capacity, 240 VAC, heavy duty, ISI marked complete all as specified and as directed.
Supply and fixing in repair 3 pin plug top, 15 amp capacity, 240 VAC, heavy duty, ISI marked complete all as specified and as directed.
Taking out old unserviceable earthing and material & labour for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.0 mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron wire 4 mm as earthing lead (upto terminal point) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh, 50 mm thick precast RCC 1:2:4 type B1using 20 mm graded stone aggregate , reinforced with 8 mm dia dedormed /TMT bars 3 nos both way 12 mm dia round bar handle and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2009(Part-I) complete all as specified and as directed by Engineer-in-charge. Note :- (i) Earth lead wire and its protection pipe upto and including 7.50 mtr only from top of earth electrode are included under this item. (ii) On testing if the earth resistance is not obtained within permissible limit, earthing will be re-done at NO extra cost ,till the desired earth resistance is obtained. (iii) Any joint in earth lead from earth electrode to test point shall not be allowed/permitted.
Taking out old unserviceable earthing and material & labour for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.0 mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised iron strip 25 x 3 mm as earthing lead (upto terminal point) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40 mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, 50 mm thick precast RCC 1:2:4 type B1using 20 mm graded stone aggregate , reinforced with 8 mm dia dedormed /TMT bars 3 nos both way 12 mm dia round bar handle and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 2009(Part-I) complete all as specified and as directed by Engineer-in-charge. Note :- (i) Earth strip and its protection pipe upto and including 7.50 mtr only from top of earth electrode are included under this item. (ii) On testing if the earth resistance is not obtained within permissible limit, earthing will be re-done at NO extra cost ,till the desired earth resistance is obtained. (iii) Any joint in earth lead from earth electrode to test point shall not be allowed/permitted.
Supply and fixing in repair air termination, single pointed aluminium rod 12mm dia 300mm long complete all as specified and as directed.
Supplying and fixing in repair test terminal block made of gun metal or phosphorous bronz size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex head screw comeplete all as directed and specified.
Supplying and fixing in repair aluminium strip 25x3.15 mm with saddles and fixing screwes etc for roof conductors and down conductors above ground complete all as specified and as directed.
Supply and fixing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable circulat of size 10 Sqmm including all incoming and outgoing connection with proper size of thimble including taking down existing unserviciable cable complete all as specified and directed.
Supply and fixing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable circulat of size 16 Sqmm including all incoming and outgoing connection with proper size of thimble including taking down existing unserviciable cable complete all as specified and directed.
Supply and fixing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections 10 Sqmm 4 core including all incoming and outgoing connection with proper size of thimble including taking down existing unserviciable cable complete all as specified and directed.
Supply and fixing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections 16 Sqmm 4 core including all incoming and outgoing connection with proper size of thimble including taking down existing unserviciable cable complete all as specified and directed.
Supply and fixing of house service bracket (hook type) complete with 3.0 M long GI Pipe 40mm dia medium grade pipe, two 90 degree bends. MS hook, stay or guy including fixing clamps etc and taking down old/ existing house service bracket complete all as specified and as directed.
Supply and fixing of LED based bollard light 10 watt with aluminium pipe housing with glare free PMMA Diffuser, IP 65 of height not less than 800 mm alongwith connected works i.e. excavation, PCC etc. complete including taking down existing old light fittings complete all as specified and directed.
Supply and fixing in repair loop in - loop out box of size 125 x 150x 100 mm PVC waterproof IP 55 with 2 way bottom entry for cable alongwith all fittings and fixtures complete all as specified and as directed.
Repair/replacement of unserviceable electrical fitting and fixture and emergent fault rectification in elctrical circuit incl no light , earth leakage, short cicuit, neutral break I mains /sub mains/internal circuits of existing system of main building / block ,making continious electric supply including carrying out minour repairs etc as required to make system in order / functional by replacing, copper cable , copper thimbles, glands, earthing wire complete all as specified and as directed as required at site by Engineer-in-Charge. NOTE : - (a) Items reqd for replacement such as switchs, sockets for power/light/ fan/ bell/geyser points including complete will be measured and paid under respective items of BoQ. (b) Contractor rep/supervisor will report to MES Service Centre alongwith reqd sufficient skilled/unskilled manpower between 930 Hrs to 1030 Hrs on all working days. for carrying out necessary execution. (c) Contractor will attend emergent nature of work i.e. no light, short circuit after working hours/holiday. The rate of the is deemed to be included in above quoted rates.
Supply only switch piano 5 Amps, flush type, single pole, one way, 230 volt, AC supply, ISI Marked, complete all as specified and as directed.
Supply only switch, single pole two way 6 Amps, 230 volts AC circuit complete all as specified and as directed.
Supply only switch piano 15 Amps flush type one way 230 Volts, 50 Hz , AC supply, complete all as specified and as directed.
Supply only bell push 5 Amps, flush type, single pole, one way, 230 volt , AC supply, complete all as specified and as directed.
Supply only socket outlet 3 pin 6 amps, 230 volt. flush type, ISI Marked, complete all as specified and as directed.
Supply only socket outlet 2 in 1, 6 pin 5 /16 Amp and multi pin flush type, complete all as specified and as directed.
Supply only ceiling rose surface bakelite 65x50mm, 3 terminal complete all as specified and as directed.
Supply only fan regulator/ Dimmer electronic step type ,230 Volts, AC supply, suitable for ceiling fan any type/make/sweep, complete all as specified and as directed.
Supply only door bell electric ,ding dong /musical| type, single phase 230 volts, complete all as specified and as directed.
Supply only lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings, complete all as specified and as directed.
Supply only switch modular 6 amps, one way single module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and as directed.
Supply only switch modular 16 amps, one way single module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and as directed.
Supply only socket modular 6 amps, 5 pin combined universal socket 2 module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and as directed.
Supply only socket modular 6/16 amps, 2 in 1, combined universal socket 2 module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and as directed.
Supply only fan regulator/ Dimmer step type one module / 2 module, 120W, 230 Volts, 50 Hz, AC complete with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and as directed.
Supply only bell push modular with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and as directed.
Sipply only Fan condenser 2.5 mfd complete all as specified and as directed.
Supply only PVC insulated, unsheathed cable 4.00 Sqmm three core 1100 volt grade with multi stranded copper conductor complete all as specified and as directed.
Supply only PVC insulated, unsheathed cable 2.5 Sqmm single core 1100 volt grade with multi stranded copper conductor complete all as specified and as directed.
Supply only Cable PVC copper conductor flexible twin core 0.75mm complete all as specified and directed.
Supply only MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, 'B' curve 6 to 32 Amps, ISI marked complete all as specified and as directed.
Supply only MCB single pole, 240 volts, 50Hz , breaking capacity 10KA, 'B' curve 40 to 63 Amps, ISI marked complete all as specified and as directed.
Supply only MCB single pole and neutral 240 volts, 16 to 32 Amps,10KA, 50 Hz, 'B' Series complete all as specified and as directed.
Supply only MCB single pole and neutral 240 volts, 40 to 63 Amps,10KA, 50 Hz, 'B' Series complete all as specified and as directed.
Note : - Amount of credit of Rs. 1,02,669.00 for retrieved materials is mentioned in Schedule of Credit Page Nos. 19 of tender documents in pdf form which will be deducted offline while acceptance of tender.
R N Enterprises
sheetal engineering
gurchan singh & sons.
M/S Sonu Traders
JS CONSTRUCTION COMPANY
J V ELECTRICALS
Gupta Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .