Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹36.6 CrAdmitted-Finance 241 SWAMI NARAYAN NAGAR 1 OPP SWAMIVIVEKANA ASHRAM BEHIND HALAR HOUSE JAMNAGAR JAMNAGAR GUJARAT 361001 UDYAM GJ 10 0002177 | JAMNAGAR | GUJARAT | 361001 | +11.25% | ₹36.6 Cr | L1 | Admitted-Finance |
| 2 | L2₹40.0 CrAdmitted-Finance | +21.33% | ₹40.0 Cr | L2 | Admitted-Finance |
| 3 | L3₹49.1 CrAdmitted-Finance | +49.00% | ₹49.1 Cr | L3 | Admitted-Finance |
| 4 | Rejected-Technical | - | - | - | Rejected-Technical Technically rejected |
Tender Value
₹32.9 Cr
EMD Value
₹25 L
Closing Date
3 Jun 2026, 3:00 pmClosed
DGM Electrical
MMRCL Transit Office, E Block, BKC Mumbai- 51
Supply Installation, Testing, Commissioning of Panels, DB, Cables, Earthing, etc. for Extension of LT Power supply to Kiosk, Retail for Mumbai Metro line 03 stations in Aqua Line
2026_MMRCL_276992_1
MMRC/Sys/Elect/NFBR/Power Supply/R1/2026
Open Tender
Supply, Erection and Commissioning
Percentage
270 days
Mumbai
Please refer Tender documents.
9 documents required · 9 mandatory
₹23,600
Mumbai Metro Rail Corporation Limited
₹25 L
Yes
9 Jun 2026
9 May 2026
4 Jun 2026
9 May 2026
3 Jun 2026
9 May 2026
Cable Laying :Supply, laying, testing and commissioning at the site of 1100 V grade, copper conductor, XLPE insulated, armoured, Flame retardant low smoke zero halogen (FRLSZH), type cables conforming to IS-7098-1 and tender technical specification following sizes: All the items / parts mentioned in relevant clauses of the technical specifications and not specifically mentioned in BOQ shall be deemed to be included in the quoted rates, unless specifically excluded. The cable runs shall be measured up to the outer end of the boxes without any allowances for over lap in joints. The rate shall include all the above mentioned material, labour, etc. for laying as required. The cost includes of supports with suitable clamps, saddles, hooks, bolts etc. including the cost of proper dressing of cables, and providing identification tags at regular intervals, etc.
4-core, 300 sqmm
4-core, 240 sqmm
4-core, 150 sqmm
4-core, 120 sqmm
4-core, 95 sqmm
4-core, 70 sqmm
4-core, 50 sqmm
4-core, 25 sqmm
4-core, 16 sqmm
4-core, 10 sqmm
4-core, 6 sqmm
3-core, 4 sqmm
Cable Termination : Supply and providing terminations conforming for XLPE insulated, FRLSZH and armoured cables of sizes given below including the cost of supplying, fixing and crimping copper lugs, double compression weather proof brass glands IP 66, insulation LSZH sleeves etc, earthing of glands through earth tags and LSZH shrouds as per tender technical specifications and as required This also includes making holes in gland plate complete.
4-core, 300 sqmm
4-core, 240 sqmm
4-core, 150 sqmm
4-core, 120 sqmm
4-core, 95 sqmm
4-core, 70 sqmm
4-core, 50 sqmm
4-core, 25 sqmm
4-core, 16 sqmm
4-core, 10 sqmm
4-core, 6 sqmm
3-core, 4 sqmm
CABLE TRAYS (PERFORATED TYPE) : Supply & installation of Prefabricated type, perforated hot dip galvanized cable trays made of minimum 2mm thick MS sheet and shall be capable of being subject to temperature up to 500 degree centigrade for 1 hour and shall not support combustion under the same temperature. Each section of cable tray shall be electrically bonded with minimum 6 sq mm cross section area earth bonding strap. GI Cable tray system shall include horizontal and vertical bends, reducers, tees, coupling plate and nut bolts / washers, securing the support to the structure by dash fasteners, minor civil work, etc. duly suspended from the ceiling with 10/12mm Dia vertical G.I rods supported by minimum 40 mm X40mm X5mm hot dipped G.I angle and/or equivalent Unistrut channel supporting arrangement etc including installation on wall dully supported on suitable brackets as required confirming to tender technical specification & approved by the employer.
Fire Sealants :Fire sealant compound of approved make. Fire stopping materials must meet and be acceptable for use by all building codes and NFPA codes wherever applicable, confirming tender technical specification
Earthing & Bonding System: Supply, laying and testing of unarmoured, stranded copper conductor, Low Smoke Zero Halogen, green coloured cables of following sizes, conforming to BS 7211 and tender technical specifications, for earthing, including termination of the same by copper lugs at both end.
1 x 6 sq. mm
Earthing & Bonding System: Supply and laying of hot dipped GI strips of the following sizes for provision of Earthing System confirming to tender technical specification Earthing strips for interconnecting the MET, panels, DBs, Cable trays, etc. of the following sizes in built up cable tray/wall complete with holes & fixing, jointing/terminating accessories as per specifications as required. (Quantity shall be paid as per the actual measurement as executed)
75 mm x 10 mm GI strip (600 mtrs converted in to KG)
50 mm x 6 mm GI strip
25 mm x 6 mm GI strip
Industrial Metal Box :
Supply,installation,testing and commissioning of 10 A FP MCB, 10 KA in sheet steel enclosure and suitable for termination of Cu. conductor in incoming and outgoing side, confirming to tender technical specification (For Retail Shop)
Supply,installation,testing and commissioning of 20 A FP MCB,10 KA in sheet steel enclosure and suitable for termination of Cu. conductor in incoming and outgoing side, confirming to tender technical specification (For Retail Shop)
Spare of 10 A, 4P MCB Qty- 8 Nos.
Spare of 20 A, 4P MCB Qty- 9 Nos.
Spare of 63 A, 4P MCB Qty- 2 Nos.
Spare of 100 A, 4P MCCB Qty- 2 Nos. (36KA,TMD)
Spare of 125 A, 4P MCCB Qty- 2 Nos. (36KA, TMD)
Spare of 150 A, 4P MCCB Qty- 2 Nos.(36KA,TMD)
Spare of 200 A, 4P MCCB Qty- 2 Nos.(36KA,TMD)
NFBR Panel DHAV- South Side Incomer 800 A ACB -Qty = 1 nos. ACBs shall be horizontal draw-out type, fully interlocked & rated for an operational voltage Ue = 415 V AC, insulation voltage Ui = 1000 V, and rated impulse withstand voltage Uimp = 12 kV for the main circuit. Class-II front fascia, suitable for indoor mounting, and shall conform to IS 13947 / IEC 60947-2. Shunt trip and closing coils suitable for 24 V DC / 240 V AC shall be provided. The ACBs shall satisfy Ics = Icu = Icw (1 second). Outgoing 10 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 100 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 2 Nos 125 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 1 Nos 200 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 2 Nos
NFBR Panel VIDN- South Side-1 Incomer 1600A -ACB ACBs shall be horizontal draw-out type, fully interlocked & rated for an operational voltage Ue = 415 V AC, insulation voltage Ui = 1000 V, and rated impulse withstand voltage Uimp = 12 kV for the main circuit. Class-II front fascia, suitable for indoor mounting, and shall conform to IS 13947 / IEC 60947-2. Shunt trip and closing coils suitable for 24 V DC / 240 V AC shall be provided. The ACBs shall satisfy Ics = Icu = Icw (1 second). Outgoing 32 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 63 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 100 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 2 Nos 200 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 2 Nos 320 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 1 Nos 400 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 1 Nos
NFBR Panel STZM- South Side-1 Incomer 1600A -ACB ACBs shall be horizontal draw-out type, fully interlocked & rated for an operational voltage Ue = 415 V AC, insulation voltage Ui = 1000 V, and rated impulse withstand voltage Uimp = 12 kV for the main circuit. Class-II front fascia, suitable for indoor mounting, and shall conform to IS 13947 / IEC 60947-2. Shunt trip and closing coils suitable for 24 V DC / 240 V AC shall be provided. The ACBs shall satisfy Ics = Icu = Icw (1 second). Outgoing 32 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 63 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 100 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 2 Nos 200 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 2 Nos 250 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 1 Nos 400 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 1 Nos
NFBR Panel MNK- North Side-1 Incomer 2500A -ACB ACBs shall be horizontal draw-out type, fully interlocked & rated for an operational voltage Ue = 415 V AC, insulation voltage Ui = 1000 V, and rated impulse withstand voltage Uimp = 12 kV for the main circuit. Class-II front fascia, suitable for indoor mounting, and shall conform to IS 13947 / IEC 60947-2. Shunt trip and closing coils suitable for 24 V DC / 240 V AC shall be provided. The ACBs shall satisfy Ics = Icu = Icw (1 second). Outgoing 40 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 2 Nos 100 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 3 Nos 200 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 3 Nos 400 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 3 Nos
NFBR Panel MIDC- South Side-1 Incomer 2500A - ACB ACBs shall be horizontal draw-out type, fully interlocked & rated for an operational voltage Ue = 415 V AC, insulation voltage Ui = 1000 V, and rated impulse withstand voltage Uimp = 12 kV for the main circuit. Class-II front fascia, suitable for indoor mounting, and shall conform to IS 13947 / IEC 60947-2. Shunt trip and closing coils suitable for 24 V DC / 240 V AC shall be provided. The ACBs shall satisfy Ics = Icu = Icw (1 second). Outgoing 32 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 40 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 63 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 100 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , MFM etc Qty- 2 Nos 200 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , MFM etc Qty- 3 Nos 400 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , MFM etc Qty- 3 Nos
NFBR Panel SEEPZ- South Side-1 Incomer 2500A - ACB, ACBs shall be horizontal draw-out type, fully interlocked & rated for an operational voltage Ue = 415 V AC, insulation voltage Ui = 1000 V, and rated impulse withstand voltage Uimp = 12 kV for the main circuit. Class-II front fascia, suitable for indoor mounting, and shall conform to IS 13947 / IEC 60947-2. Shunt trip and closing coils suitable for 24 V DC / 240 V AC shall be provided. The ACBs shall satisfy Ics = Icu = Icw (1 second). Outgoing 10 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 40 A, 4P MCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , etc Qty- 1 Nos 100 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB ,MFM etc Qty- 3 Nos 200 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , MFM etc Qty- 2 Nos 250 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB , MFM etc Qty- 1 Nos 400 A, 4P MCCB adjustable thermal magnetic type with ON-OFF LED type indicating lamps, complete in all respect with control MCB, MFM etc Qty- 3 Nos
Distribution Boards: Design, manufacture, supply, installation, testing and commissioning of indoor, wall-mounted, metal enclosed, dead-front type MCB Distribution Boards, suitable for 415V, 3-phase, 4-wire, 50 Hz AC system, complete in all respects. Distribution Boards shall be factory-built, type-tested and shall conform to IS 8623 / IEC 61439, IS 13032, IS/IEC 60898, IS/IEC 60947, IS/IEC 61008/61009, National Electrical Code, NBC 2016 and CEA (Measures relating to Safety and Electric Supply) Regulations, latest editions. Enclosure shall be fabricated from minimum 2.0 mm thick CRCA / electro-galvanized steel sheet, epoxy powder coated (minimum 60 microns, shade RAL 7035), with hinged, gasketed, lockable doors and minimum IP42 degree of protection. Distribution Boards shall be provided with tinned copper busbars for phases, neutral and earth, rated for full load current and short-circuit withstand capacity not less than 25 kA for 1 second, colour coded as per standards. Separate neutral and earth busbars shall be provided. Incoming shall be through FP MCCB and outgoing feeders shall be protected by SP / DP / FP MCBs of required ratings with minimum 10 kA breaking capacity, complete with minimum 20% spare ways, as specified. Complete with double earthing using GI flat 50 mm × 6 mm, removable Al gland plates (minimum 3mm thick) , internal FRLSZH copper wiring, terminations, mounting accessories and all associated works as specified and mentioned in technical specifications. Testing shall include continuity, insulation resistance test with 500 V megger (minimum 100 MΩ) and functional checks. Item rate shall be inclusive of all materials, labour, testing, commissioning and making good works, required to complete the installation in all respects as per drawings and Engineer’s instructions. Please refer techncial specifications for more details.
Rubber Mat : Supply & Laying of non skid Electro mat 1mtr wide and 2.0 mm thick 1.1KV grade IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities.
Fire Suppression system (Panel Flooding System): Supply, fixing, testing and commissioning of UL 521, UL listed Polymer Tube Detection based Clean Agent Fire Suppression System for Electrical Panels, consisting of the following components: Direct Low Pressure Clean Agent system above 2.5 LBS capacity, complete with Clean agent (NOVEC 1230 or equivalent), D.O.T/TC approved Cylinder, nickel plated brass valve with slip on union connector, isolation valve, plug pressure switch port and 195 psi Pressure gauge fittings, operating pressure 195 psi (13.45 Bar) at 70 Deg F, supplied complete with Bolt Pattern Bracket and: INCLUDING Fill Port Outlet Port End of Line Adaptor End of line Adopter Pressure switch Flexible 4/6mm UL 521, UL listed Polymer Detection Tube 195 Deg C rated complete with all necessary fittings & supports' make each entire system functional - 2 Nos. Note: The items indicated above are notable items. The vendor to include all allied and implied items in required quantity at no extra cost. Spare of Fire Suppression system (Panel Flooding System) as recommended by OEM and approved by the Employer.
Labour Charges
Supervisor per station 1 No, total 6 station and 240 days
Skilled per station 6 Nos, total 6 stations and 240 days
Semi Skilled per station 4 Nos, total 6 stations and 240 days
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.19 MB
TenderdocuemtnsforRetailelectwork.pdf
Tender Documents • 1.87 MB
SHEandW.pdf
Tender Documents • 5.46 MB
GeneralConditionsofContract.pdf
Tender Documents • 5.31 MB
BOQ_323523.xls
BOQ • 0.46 MB
PowersupplyAddendumNo2.pdf
PDF • 0.06 MB
RevisedNIT.pdf
PDF • 0.18 MB
AddendumNo1.pdf
PDF • 0.08 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].