Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.8 LAccepted-AOC 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹28.2 L+₹17,480 (0.62%)Rejected-Finance H NO 698 SECTOR 10 PANCHKULA HARYANA 134109 | PANCHKULA | PANCHKULA | HARYANA | 134109 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹29.0 L+₹97,449 (3.48%)Rejected-Finance 44 NEAR DURGA MANDIR TRIPURI TOABA TRIPURI TOWN PATIALA 147004 PB | PATIALA | PUNJAB | 147004 | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹29 L+₹1.0 L (3.58%)Rejected-Finance | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹30.2 L+₹2.2 L (7.80%)Rejected-Finance 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
27 Apr 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE UTILITY AMBALA CANTT
GE UTILITY AMBALA CANTT 133001
REPAIR MAINT REPLACEMENT OF OH UG LT NETWORK INCLUDING MISC WORKS UNDER SECTOR A UNDER GE UTILITY AMBALA CANTT
2024_MES_648074_1
CA NO GE U AMB T 31 OF 2024-25
Open Tender
Civil Works
Works
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹92,000
22 May 2024
27 Mar 2024
29 Apr 2024
27 Mar 2024
27 Apr 2024
13 Apr 2024
27 Mar 2024 - 3 Apr 2024
Amount
Excavation in trenches n.exc 1.5 Mtr wide and n,exc 1.5 Mtr in depth loose/soft and greating out for underground cable/erection of poles, stays etc complete all as specified and directed.
All as per Srl item No.1.00 above but exceeding 1.5 mtr deep but not exc 3.0 mtr deep complete all as specified and directed.
Material & labour for sand cushioning for cables with river washed sand and punning to provide required cover as per SSR part I complete all as specified and directed.
Supply and laying bricks common burnt clay sub classs 'B' old size for cable protection complete all as specified and directed.
Description all as per item Ser No 5 here in before but except bricks complete all as specified and directed. Note : Old bricks retrieved from item No 12 here in after shall be used.
Material & labour for plain cement concrete in foundations, filling and mass concrete as foundation to poles, type D2, 1:4:8 using 40 mm graded stone agregate as foundations to poles complete all as specified & directed.
Material & labour for plain Cement concrete, filling and mass concrete,type C2, 1:3:6 using 20 mm graded stone aggregate complete all as specified & directed.
Material & labour for plain cement concrete as coping to poles, type B1, 1:2:4 using 20 mm graded stone aggregate complete all as specified & directed..
Returning, filling in (Soil) including spreading, levelling, watering and well ramming in layers not exc 25CM thick layers complete all as specified & directed.
Removal of excavated material n,exc 50 Mtr away and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified & directed.
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, will etc and locate the fault, rectify, the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminium conductor heavy duty 1100 volts including and testing for any size complete all as specified & directed.. (Excavation/earth work & sand cushioning, brick and joint shall be measured & paid for seprately).
Supply, fixing installing and testing of Hot Air Oven with blower/ fan to heatup silica gel granules removed from transformers which had turned pink and absorbed moisture upto 50 deg C to 150 Deg Cincl trays of size 10" x 10" minimum including taking down existing complete all as specified and directed.
Supply, laying, connecting and testing XPLE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc including taking out old unsv cable complete all as specified and directed. Note : (i) Earth work, sand , bricks removing , returning filling Aluminium thimbles/lugs will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates (iii) All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 25 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 35 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 50 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 70 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 95 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core120 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 150 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 185 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 240 Sqmm complete all as specified & directed.
Alll as per item ser No 13 here in before but for 3.5 core 300 Sqmm complete all as specified & directed.
All as per item ser No 13 here in before but for 3.5 core 400 Sqmm complete all as specified & directed.
Material & Labour for horizontal drilling hole of any size manully as per site requirement, drilling for laying pipes under the road for crossing electrical cables complete all as specified & directed. Note : Pipe will be measured and paid for seperately.
Supply & erection of Prestressed concrete pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white radium tape strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip including taking down existing complete all as specified & directed. Note: Earth work and PCC shall be measured and paid seperately (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply & erection (in true vertical position) Steel tubular swaged poles complete with cast iron base plate, finial taper plug bolts, nuts & screws all as specified of type 410 SP-31 ( 9.0 mtr length) complete all as specified in IS 2713 (Part-II) 1980 including one coat of red oxide primer and two coats of aluminium paint to exposed surfaces incl providing of two coats of black and white radium tape strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip and with black bituminus paint for embedded portion of pole including taking down existing complete all as specified & directed. Note: Earth work and PCC shall be measured and paid seperately (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply and fixing stay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv complete all as specified & directed. Note : The above quoted rates are included of excavation and PCC work.
Material and Labour for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primercoat, one under coat and one finishing coat of paint including taking down existing complete all as specified & directed.
Material & Labour for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm including taking down existing complete all as specified & directed.
Material & Labour for pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm hight and 65 mm dia with GI spindle two washer and one GI nut including taking down existing complete all as specified & directed.
Taking down old unserviceable ACSR conductor incl cutting, welding complete all as specified & directed.
Material & Labour for aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified & directed.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.5/4.0 x 10-50 Sqmm complete all as specified & directed.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 70-150 Sqmm complete all as specified & directed.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 185-300 Sqmm complete all as specified & directed.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XPLE cable of size 3.50 x 400 Sqmm complete all as specified & directed.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XPLE cable of size 3.5/4 x 25-50 Sqmm complete all as specified & directed. Note.Rate inclusive of earth work.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 70-150 Sqmm complete all as specified & directed.. Note.Rate inclusive of earth work..
Supply and fixing straight through joint heat shrinkable 1100 Volts for XPLE cable of size 3.5 x 185-400 Sqmm complete all as specified & directed. Note.Rate inclusive of earth work..
Material & Labour in replacement for one twin core cable flat or circular of size 10 sqmm 2 core 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm GI suspension wire, complete all as specified & directed.
Dismantling of old u/s earthing and material and labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick burried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 25x4 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm for steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20 mm bore nedium grade , funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified & directed.
Dismantling of old u/s earthing and material and labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick burried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm for steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20 mm bore nedium grade , funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified & directed.
Material & Labour for GI tubing 50 mm bore light grade, on poles, on walls, under floors, road crossing as reqd at site including taking down existing complete all as specified & directed. Note : Clamps, Nut bolts, saddle etc will be measured and paid seperately.
All as per Srl item No.44.00 above but 80 mm dia complete all as specified & directed.
Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl connection complete all as specified & directed.
Supply and fixing in replacement MCCB TPN 200 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl connection complete all as specified & directed.
Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl connection complete all as specified & directted..
Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl connection complete all as specified & directted..
Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl connection complete all as specified & directted..
Material & Labour for painting cleaning and repair of LT panel size upto 0.6 x 0.6 x0.6 mtr after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide primer including stand complete all as specified and directed. Note : (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates.
Material & Labour for painting cleaning and repair of LT panel size upto 1.2 x 1.2 x0.6 mtr after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding and painting on complete panel with two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as specified and directed. Note : (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates.
Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles , painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as specified and directed. Note : (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC
Material & Labour for cement base paint for Prestressed concrete pole 9 mtr including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etc incl incl reparing and painting on coping with cement base white paint complete all as specified and directed. Note : (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC
Material and Labour for detecting fault in cable of any type with fault locator equipment which is capable to supply as per cable of serviceable to cable complete all as specified and directed Note :- (a) The fault which is detected through cable fault locater will only be paid under this item (b) Charges of Cable fault locator and DG set including transportation charges deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single fault no delay on this account will be acceptable otherwise penality will leived Rs 500/- per day. (d) Necessary testing of cable after making joint will be deemed to be including in the cost of relevent item. However necessary earth work cable cutting, joint making joint will be paid under relevant item.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete all as specified & directed.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS complete all as specified & directed.
Re-streteching existing/retrieved ACSR conductor on LT pole and building conductor on insulator properly using new binding wire/jumper wire complete all as specified & directed. Note : (i) Each Run of line conductor shall be measured & paid for separetly.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm incl dismantling old thimbles of any type complete all as specified & directed.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185 sqmm incl dismantling old thimbles of any type. complete all as specified & directed.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm incl dismantling old thimbles of any type complete all as specified & directed.
Material & Labour for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations complete all as specified & directed.
Dismantling and taking down UNSV LED street light/security/flood lights upto 90 watt after disconnection electric supply and fix again after repairing of unsv AC/DC drivers incl proper connections complete all as specified & directted. Note : (i) Cost of repair and driver is incl in quoted rate. (ii) If repair is not possible then replacement of street/security light will be measured and paid seperately under relevent items.
Dismantling and taking down UNSV LED street light/security/flood lights upto 200 watt after disconnection electric supply and fix again after repairing of unsv AC/DC drivers incl proper connections complete all as specified & directed. Note : (i) Cost of repair and driver is incl in quoted rate. (ii) If repair is not possible then replacement of street/security light will be measured and paid seperately under relevent items.
Material and labour for new LED street light fittings of 70 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, TOP opening separare driver compartment with frame, IP 66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range -20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting, welding, drilling holes, nut bolts, washer including taking down existing old unsv street/security lights complete all as specified & directed.
All as per Srl item No.65 above but for 90 Watt LED street light complete all as specified & directed.
All as per Srl item No.65 above but for 100 Watt LED Flood lightcomplete all as specified & directed.
All as per Srl item No.65 above but for 200 Watt LED Flood light complete all as specified & directed.
Supply and fix 1100 volt grade heavy duty cable PVC insulated aluminium stranded conductor PVC sheathed suspended by insulating hanger not more than 1 mtr apart including 4mm suspension, cable size 10 sqmm twin core stranded conductor including taking down existing complete all as specified & directed.
Supply and fix or passing through pipe, 1100 volts grade heavy duty PVC insulated flat twin core cable of size 2.5 sqmm nominal cross section with connection in sintex box flood light including taking down existing complete all as specified & directed. Note : PVC pipe will be measured and paid seperately under relevent items.
Supply and fix of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc including taking down existing complete all as specified & directed..Note : PVC pipe will be clamed at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates.
Material & Labour for street light bracket made out of GI pipe medium grade 25 mm bore suitable to fit with LED street light approx length not less than 120cm bent to shape including new clamps made of MS flat of size 30x4 mm thick including cutting, welding holes, nut, bolts washers etc including two coat of aluminium paint over one coat of red oxide primer on MS work including taking down existing complete all as specified & directed.
Supply, fixing and testing of auto day/ night on and off photocell.LDR sensor switch 6amps for lighting on and off photocell, LDR sensor switch 6amps for lighting on and off water proof 220volt 50HZ,AC supply, model No Quick Sense QS-301 complete with all accessories internally pre-wired including connection with 1.5Sqmm copper conductor from main supply to sensor, sensor to fittings including taking down existing complete all as specified & directed.
Supply and fixing on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100/125 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches including taking down existing complete all as specified & directed.
Supply and fix of Lithium based Energy Efficient Integrated Solar Street Light of 25 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 64/66Wp , Lithium Battery 11.1/12.8V, 33.0AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700°K - 6500°K, Microcontroller based charge controller cum driver, automatic dimming function (first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10°C to (+)55°C, weight not more than 16-18kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 4-6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide including taking down existing complete all as specified & directed.
Supply & fixing of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32 Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Madel :Swadeep-02EC-8kW3P-VMS including taking down existing complete all as specified & directed. Note (i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years . (iii) The test certificate and warranty certificate must be provided by supplier.(iv) Cost of marking description on the box is incl quoted rate.
Supply & fixing of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Madel : Swadeep-02EC-5kW1P-VMS including taking down existing complete all as specified & directed. Note (i) Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years . (iii) The test certificate and warranty certificate must be provided by supplier.(iv) Cost of marking description on the box is incl quoted rate.
Material & Labour for Chemical spray (DC>2.26 having container 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc including taking down existing complete all as specified & directed.
Supplying and laying of synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 kv for lectrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 5.0m x 1m complete all as specified and diercted.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm incl taking down old unsv HT joint complete all as specified & directed.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm incl taking down old unsv HT joint complete all as specified & directed.
Material and Labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 50-95 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified & directed.
Material and Labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 120-185 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified & directed.
Supply fixing and testing in replacement of three phase multi functional meter, to measure electrical parameters such as voltage, current power factor, frequency, and energy consumption to measure real time data , enabling precise power quality assessment , load management complete including rewiring and making connections including taking down existing complete all as specified and directed. Make ; Secure meters Elite 440 or equivalent in schneider/ siemens/ L&T
Material and labour for vibratory compactive, precast cement concrete rubber moulded, coloured ( except grey colour), interlocking designer paver blocks in Milano shape, comfirming to IS-15658-2006 of 60 mm thickness, M-35 grade, as in path, harding standing, etc laid over and including 25 mm compacted sand cushioning, including 75 mm thick PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate including surface excavation over area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and removing excavated soil exc. 50 mtr but n. exc. 250 mtr including demolition of existing complete all as specified & directed.
Supply and fixing of Retro reflective sign board of size 600 X 750 sqmm made of ACP sheet of 3 mm thick. ACP Sheet will be fixed on MS frame of with legs of MS angle section 35 mm X 35 mm X 4 mm on PCC 1:3:6 type 750 mm above the ground level and 600 mm below the ground level. The background of board to be provided with red colour, letters and border with white retro reflective tape. Same description will be mentioned on both side of ACP Sheet.The size of letters and board will be complete fixing/grouting with nut/bolts/Anchor fastener with washers including taking down existing complete all as specified and directed.
Supply and Fix of MS clamp suitable for holding street light bracket on steel/PCC pole made out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia with flat washer 3mm thick -02 No for each including painting with aluminium paint over one coat of red oxide primer to the M.S clamps including taking down existing complete all as specified and directed.
Material & Labour for Air circuit Breaker, fixed type, spring operated, mannualy TPN, 4 Pole, 800 Amps, 415 Volt with Thermal magnetic release,(O/L, S/C, E/F protection & confirming to IEC - 60947-2 &3rated breacking capacity / making capacity 50 KA short time current including taking down existing complete all as specified and directed.
Note for item No 89 to 90 (i) The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) Panel drawing shall be got approved before placing of order from Engr-in-Charge. (iii) The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (iv) Cost of making description on the front door as per direction of Engr-in-Charge is encl in quoted rate. (v) Cable will be entered in panles through gland. (vi) Cost of marking descreption on the front door as per direction of Engr-in-Charge
Note:- Amount of credit of Rs 121669.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in PDFf form which will be deducted offline while acceptance of tender.
bharat contrectors
Mohinder Pal and Sons
R. P. Suppliers and Construction Co.
M/S Sonu Traders
Saurav Enterprises
KULWANT SINGH
M/s Friends Engineering Works
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .