Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.8 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹49.7 L+₹14.4 L (40.6%)Rejected-Finance | L2 | Rejected-Finance highest | |
| 3 | L3₹50.6 L+₹15.3 L (43.3%)Rejected-Finance VILL BHOL KHAS PO LARTI TEH JAWALI DISTRICT KANGRA HP | MANDI | HIMACHAL PRADESH | 175013 | L3 | Rejected-Finance highest |
Tender Value
₹26.0 L
EMD Value
₹46,570
Closing Date
28 Feb 2022, 11:00 amClosed
Executive Engineer
Jal shakti division, fatehpur
Sub Head Laying Jointing and Testing of Rising Main GI pipe (Medium Calss) and S/E of submersible pumping machinery (Booster Stage) and centrifugal pumping machinery stage -1 (Zone-I) and Zone II along with its allied accessories.
2022_HPIPH_57032_1
EE/JSD/FTR/EA-I/2021-16343-80
Open Tender
Civil Works
Item Rate
90 days
Fatehpur
As per notice inviting tender
8 documents required · 8 mandatory
₹400
Yes
Fatehpur
₹46,570
Yes
4 Aug 2024
21 Feb 2022
28 Feb 2022
21 Feb 2022
28 Feb 2022
21 Feb 2022
Amount
Excavation in foundation treanches(Pipe & Pits) up to all depths in all classification of earth work such as pick work,jumper work,saturated soil including bailing or pumping out water,blasting soft /hard rock where blasting is prohibited in all lifts including trimming & dressing of sides leveling of beds to correct grade i/c shoring/strutting planking,timbering & dewatering wherever required stacking the usable & unusable material/soil separately & after laying,jointing & testing of pipes,returning the useable soil in trenches in 15cm layers including consolidating of such deposited layer by raming & watering & then disposing of all surplus excavated soil/unusable material as directed with in all leads & lifts including restoration of unmetalled surface to its original condition & including cost of diversion for traffic,night signals,fixing caution boards,crossing over trenches for access to houses,fencing etc.complete in all respects with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Laying, jointing and testing in trenches to be levelled to grade, BIS marked GI flanged pipes confirming to BIS:1239 (latest with upto date ammendments) of following dia (Medium class) duly flanged after 5th pipe with intermediate butt welded joints dully welded in three layer (two layer outer side & one layer inner side including the cost of flanges, bends/short pieces made from parent tubes of diferent degrees cutting welding and jointing with flanges conforming to tables as specified below of BIS: 6392 (latest with upto date ammendments) welded at both ends as per BIS:816 (latest with upto date ammendments) with electrodes confirming to BIS 814 (The earth work in trenches will be measured & paid for separatly) & provided with nuts and bolts BIS: 1369 (latest with upto date ammendments) of required sizes 4 mm thick champion make compressed asbestos fiber gasket or synthetic rubber gasket confirming to BIS:2712 (latest with upto date ammendments) & approved specifications as per site conditions including flushing, cleaning & hydraulic testing complete in all respects with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge..
125 mm Dia ( Medium Class) dully flanged Table -5 Booster stage (T/well to C/ tank)
125 mm Dia ( Medium Class) dully flanged Table -5 (Collection tank to OHSR at Node No-103)
80 mm Dia ( Medium Class) dully flanged Table -17 RD /00 to 600= 600mtr)
80 mm Dia ( Medium Class) dully flanged Table -5 (RD 600 to 1780= 1180mtr)
Supply of submersible pumping set of SABAR/Calama/KSB/ Crompton/SU/Johnston make conforming to BIS; 8034-1976 (latest) suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with uptodate ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:- (Stage-I(Booster) T/well to c/tank)
Location of site :-The site is located at a distance of 15 Kms.from Nurpur Road Railway Station.
The altitude of place in which :-Altitude of place is 500 Metres above Mean Sea Level.
the Motor is intended to work
Type of current :-A.C.Three phase supply with frequency 50 cycles per second.
Rated Voltage :-415 Vvolts (+/-) 10%
Characterstics of water :-(a).Temperature = 20oC (f) PH =_____ (b).Turbidity =Upto 10NTU (g) Total solids____Mg/Litre (c ) Hardness =_mg/Litre (as CaCo3) (h) others____ (d).Alkalinity =__Mg/Litre(as CaCo3)
40.00 Metres.
L.W.L.in T/ -Well :- Metres
Maximum draw down :- Metres
Centre line level of Pump :- 464 Metres
Discharge level of highest point:- 525Metres
Nos.of Pumps required :-2 No.Pump. (One will be act as standby)
Capacity :- 11.73 L.P.S.
Total head in Metres :- 68.79 Metres
Length of Rising Main :- 60 Metres
Dia of Rising Main :-125 mm.dia G.I..pIpe,(Medium Class)
No.of working hours per day :-8 Hours.
Limits of pump operation :- ( - ) 15% ( + ) 10% of total head.
H.P.of Motor/Drive unit :-Required 15.00 H.P.of Pump at ( + ) 10% and ( - ) 15% of total head. BHP.with following margins/multiplying factor at duty point,whichever is higher. a).Upto 2 H.P. =1.5 (d) 10 to 20 H.P. =1.2 b).2 to 5 H.P. =1.4 (e) 20 to 100 H.P. =1.15 c) 5 to 10 H.P. =1.3 (f) Above 100 H.P. =1.10
Test Run :-8 Hours continueously for 7 days.
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for centrifugal pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump of rating 22.50 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of 22.50 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
MCB /MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
Incommer MCCB with for proper short circuit capability for both the starters make L&T/Schnieder/ABB
On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Output contactors in the output of VFD to run the pump
Transporatation and Carrage Charges for panel till site
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Supply of software with license to monitor data at Laptop/Mobile in form of Software and Mobile Application for 3 users
Level Sensor to indicate the water level of tank remotely
Cloud GateWay for Data Cluding to Server
Cable for Communication for Water Level Sensor
Installation and Commissioning
Supply & fixing of double flanged acctuator cast iron sluice valve heavy size one dia higher tha pump size to delivery of pump class PN 1.6 of Kirloskar/Kilburn/Leader make conforming to BIS 14846-2000 laest with up to date ammendments having seat pressure of 16.32kg/cm2 complete in all respect with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Supply of Kirloskar/ Kilburn/Leader make Cast iron double flanged accutator swing check type reflux valve class PN 1.6 having bye pass arrangement ( to be provided on delivery side) of size of one size higher than the delivery size of pump and shall be suitable for withstanding nominal seat presure of 16.32 Kg/Cm2 as per BIS 5312-1984 Part-I (latest edition) complete in all respect with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Supply of Kirloskar/ Kilburn/Leader make Cast iron class PN 1.6 double flanged swing check type reflux valve having bypass arrangement equal to dia of Risng main i.e. 125mm shall be suitable for withstanding nominal seat pressure of 16.32 Kg/Cm2 as per BIS 5312-1984 ( Latest edition) complete in all respect with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 6.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Supply & errection of floor/wall mounted power shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments of GEC/Siemen/ Havells L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of requirement KVAR according to 100 BHP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including Standard/ L&T/Kilburn/Indo asian make ICTP switches conforming to BIS 4064- 4064-1978 or latest with HRC fuses. (range to be specified by the tenderer).
Supply of standarad make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
L/J G.I. pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe 100 mm dia
Delivery pipe 100 mm dia
Errection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
CENTRIFUGAL PUMP SETS:- Stage-II (Zone-I) Supply of horizontal spindle, horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir make conforming to BIS: 1520-1980 (latest with upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels, casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton/Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and shall be suitable for operation as per data given below.
Location of site :-The site is located at a distance of 5 Kms.from Nurpur Road Railway Station.
The altitude of place in which :-Altitude of place is 500 Metres above Mean Sea Level. the Motor is intended to work
Type of current :-A.C.Three phase supply with frequency 50 cycles per second.
Rated Voltage :-415 Vvolts (+/-) 10%
Characterstics of water :-(a).Temperature = 20oC (f) PH =_____ (b).Turbidity =Upto 10NTU (g) Total solids____Mg/Litre ©. Hardness =__Mg/Litre(as CaCo3) (h). Others_____ (d).Alkalinity =__Mg/Litre(as CaCo3)
Depth of Well Assembly :- Metres.
L.W.L.in Collection Tank :- 522 Metres
Maximum draw down :- Metres
Centre line level of Pump :- 522 Metres
Discharge level of highest point:- 561 Metres
Nos.of Pumps required :-2 No.Pump. (One will be act as standby)
Capacity :- 8.13 L.P.S.
Total head in Metres :-57.35 Metres
Length of Rising Main :- 1870 Metres
Dia of Rising Main :-125 mm.dia G.I..pIpe, (GI medium Class(PE)
No.of working hours per day :-8 Hours.
Limits of pump operation :- ( - ) 15% ( + ) 10% of total head.
25 H.P.of Pump at ( + ) 10% and ( - ) 15% of total head. BHP.with following margins/multiplying factor at duty point,whichever is higher. a).Upto 2 H.P. =1.5 (d) 10 to 20 H.P. =1.2 b).2 to 5 H.P. =1.4 (e) 20 to 100 H.P. =1.15 c) 5 to 10 H.P. =1.3 (f) Above 100 H.P. =1.10
Test Run :-8 Hours continueously for 7 days.
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for centrifugal pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump of rating 15 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of 15 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
MCB /MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
Incommer MCCB with for proper short circuit capability for both the starters make L&T/Schnieder/ABB
On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Output contactors in the output of VFD to run the pump
Transporatation and Carrage Charges for panel till site
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Supply of software with license to monitor data at Laptop/Mobile in form of Software and Mobile Application for 3 users
Level Sensor to indicate the water level of tank remotely
Cloud GateWay for Data Cluding to Server
Cable for Communication for Water Level Sensor
Installation and Commissioning
Supply of fixing of double flanged acctuator cast iron sluice valve heavy size one dia higher tha pump size to delivery of pump class PN 1.6 of Kirloskar/Kilburn/Leader make conforming to BIS 14846-2000 laest with up to date ammendments having seat pressure of 16.32kg/cm2 complete in all respect complete in all respect with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Supply of Kirloskar/ Kilburn/Leader make Cast iron double flanged accututor swing check type reflux valve class PN 1.6 having bye pass arrangement ( to be provided on delivery side) of size of one size higher than the delivery size of pump and shall be suitable for withstanding nominal seat presure of 16.32 Kg/Cm2 as per BIS 5312-1984 Part-I. complete in all respect with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Supply of Kirloskar/ Kilburn/Leader make Cast iron class PN 1.6 double flanged swing check type reflux valve having bypass arrangement equal to dia of Risng main i.e. 125mm shall be suitable for withstanding nominal seat pressure of 16.32 Kg/Cm2 as per BIS 5312-1984 ( Latest edition) complete in all respect with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 6mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Supply & errection of floor/wall mounted power shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments of GEC/Siemen/ Havells L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of requirement KVAR according to 15.00BHP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including Standard/ L&T/Kilburn/Indo asian make ICTP switches conforming to BIS 4064- 4064-1978 or latest with HRC fuses. (range to be specified by the tenderer).
Supply of standarad make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
Laying of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement complete in all respects with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Suction Pipe 100 mm dia GI pipe Medium Class
Delivery pipe 100 mm dia GI pipe Medium Class
Common Header 125 mm dia GI pipe Medium Class
Errection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
CENTRIFUGAL PUMP SET:- (Stage-II (Zone-II):- Supply of horizontal spindle, horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir make conforming to BIS: 1520-1980 (latest with upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels, casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton/Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and shall be suitable for operation as per data given below.
Location of site :-The site is located at a distance of 5 Kms.from Nurpur Road Railway Station.
The altitude of place in which :-Altitude of place is 500 Metres above Mean Sea Level.
the Motor is intended to work
Type of current :-A.C.Three phase supply with frequency 50 cycles per second.
Rated Voltage :-415 Vvolts (+/-) 10%
Characterstics of water :-(a).Temperature = 20oC (f) PH =_____ (b).Turbidity =Upto 10NTU (g) Total solids____Mg/Litre ©. Hardness =__Mg/Litre(as CaCo3) (h). Others_____ (d).Alkalinity =__Mg/Litre(as CaCo3)
Depth of Well Assembly :- Metres.
L.W.L.in Collection Tank :- 522 Metres
Maximum draw down :- Metres
Centre line level of Pump :- 522Metres
Discharge level of highest point:-563Metres
Nos.of Pumps required :-2 No.Pump.(one will be act as standby)
Capacity :- 3.60 L.P.S.
Total head in Metres : 71.98Metres
Length of Rising Main :- 1780 Metres
Dia of Rising Main :-80 mm.dia G.I..pIpe(medioum),(PE)
No.of working hours per day :-8 Hours.
Limits of pump operation :- ( - ) 15% ( + ) 10% of total head.
25 H.P.of Pump at ( + ) 10% and ( - ) 15% of total head. BHP.with following margins/multiplying factor at duty point,whichever is higher. a).Upto 2 H.P. =1.5 (d) 10 to 20 H.P. =1.2 b).2 to 5 H.P. =1.4 (e) 20 to 100 H.P. =1.15 c) 5 to 10 H.P. =1.3 (f) Above 100 H.P. =1.10
Test Run :-8 Hours continueously for 7 days.
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for centrifugal pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump of rating 10 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of 10 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens
MCB /MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release.
Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
Incommer MCCB with for proper short circuit capability for both the starters make L&T/Schnieder/ABB
On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc.
Input Choke which should be installed at the input of VFD starter, so that there should be proper protection in case of any voltage surge and distortions in signal
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes.
Output contactors in the output of VFD to run the pump
Transporatation and Carrage Charges for panel till site
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon.
Supply of software with license to monitor data at Laptop/Mobile in form of Software and Mobile Application for 3 users
Level Sensor to indicate the water level of tank remotely
Cloud GateWay for Data Cluding to Server
Cable for Communication for Water Level Sensor
Installation and Commissioning
Supply of fixing of double flanged acctuator cast iron sluice valve heavy size one dia higher tha pump size to delivery of pump class PN 1.6 of Kirloskar/Kilburn/Leader make conforming to BIS 14846-2000 laest with up to date ammendments having seat pressure of 16.32kg/cm2 complete in all respects with in all leads & lifts as per directions and to the entire satisfaction of Engineer-In-Charge.
Supply of Kirloskar/ Kilburn/Leader make Cast iron double flanged accututor swing check type reflux valve class PN 1.6 having bye pass arrangement ( to be provided on delivery side) of size of one size higher than the delivery size of pump and shall be suitable for withstanding nominal seat presure of 16.32 Kg/Cm2 as per BIS 5312-1984 Part-I
Supply of Kirloskar/ Kilburn/Leader make Cast iron class PN 1.6 double flanged swing check type reflux valve having bypass arrangement equal to dia of Risng main i.e. 250mm shall be suitable for withstanding nominal seat pressure of 16 Kg/Cm2 as per BIS 5312-1984 ( Latest edition)
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 4mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 2.5 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Supply & errection of floor/wall mounted power shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments of GEC/Siemen/ Havells L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of requirement KVAR according to 100 BHP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including Standard/ L&T/Kilburn/Indo asian make ICTP switches conforming to BIS 4064- 1978 or latest with HRC fuses. (range to be specified by the tenderer).
Supply of standarad make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
Laying G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe 65mm dia
Delivery pipe 65 mm dia
Common header = 80 mm dia
Providing and lying double loop earthing with coper plate 600x600 x3 thick electrode and copper strip of 25x3 complete including providing of material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, Copper /GI wire/ Strips of required capacity conforming to BIS 8034-1978 latest with upto date ammendments for above motor & other electriacl equipments including all civil works. (for both machineries)
Errection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
rajeev singh guleria
VIVEK KUMAR
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .