Online UPS ( PAC Only ) Average Turn Over of Last 3 Years 11 Lakh (s) Experience with Gov. Required 15 Year (s) Online UPS ( 1 ) ( Under PAC ) Make emerson Model emersonsuper400d10kavups Technical Specifications * As per GeM Category Specification Specification Specification Name Values Allowed Values GENERIC Rating in KVA (KVA) 10.0 KVA * Technology IGBT-PWM with inbuilt isolation transformer MOSFET-PWM with inbuilt isolation transformer
IGBT- PWM with inbuilt isolation transformer
IGBT-PWM without inbuilt isolation transformer Input Power Three phase 300 V - 450V sinewave
50Hz single phase 160V - 260V sinewave
50Hz
Three phase 300 V - 450V sinewave
50Hz Output power Single phase 230V +/-1% sinewave 50 Hz Single phase 230V +/-1% sinewave 50 Hz
1/4 3 Phase 400V +/-1% with alternative user setable setting of 380V +/-1% 50 Hz Backup time (Minutes) 30 15
30
60
90
120
180
240 Minimum VAH (VAH) 8112 400-640000 Warranty for UPS (Years) 1 1
2
3
4
5 Movable trolly for Batteries Without With
Without
Without trollery but with rack Warranty for battery 2 1
2 Degree of Protection IP20 IP21
IP20 Cabling 5 meters for input and out put Without With
Without Paralleling kit for synchronising Without With
Without Installation and Commissioning Yes * CONSTRUCTIONAL Minimum thickness of M.S.Sheet Enclosure duly painted (mm) 1.2 * Type of Battery SMF-VRLA conforming to JISC:8702(Pt.I
II&III) * FUNCTIONAL Maximum overshoot and Under shoot of output rated voltage 4 * Voltage Regulation from no load to full load (%) </= 3% * 20% Overload limit for minimum 10 minutes Yes * Overall Efficiency (%) >/=90% * Total Harmonic Distortion(THD) (%) Maximum 3% * 50% Overload limit for minimum 1 minutes Yes * PROTECTION Protection for under voltage at battery terminal at 10.5V per 12 V battery. Yes * Protection of Over voltage
Short Circuit & over load at UPS output terminal Yes * 2/4 METERING AND INDICATIONS Digital Metering in UPS for AC Input Voltage
Output AC Volt age
Current
Frequency
Battery Voltage and Current Yes * Indicators for mains presence
Battery charging and discharging
Output Over Load
Low Battery Voltage Yes * REPORTS AND CERTIFICATION Damp Heat : in accordance with IS:9000(part 5/sec.2)1981 at Temperature of 40 degree C
two cycles of (12+12) hours each 2007) Yes * Dry Heat Test : in accordance with IS:9000 (part 3/sec.5)1977 (reaffirmed 2007) at 55 degree C for 16 hrs Yes * Cold Test : in accordance with IS:9000 (Part 2/Sec.4)1977 (Reaffirmed 2007) at -10 degree C for 4 hrs. Yes * Availability of the Type Test Report from Central Govt. NABL/ILAC Accredited lab covering all technical requirements. Yes * Type Test Certificate No. - * Type Test Certificate date - * Name of Lab - * Address of Lab - * As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes * * Bold specifications are the golden parameters. 3/4 Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Dhadhal Vanrajsinh Apabhai 380001
NYAY SANKUL MIRZAPUR COMPLEX DISTRICT AND SESSION COURT AHMEDABAD RURAL 1 15