Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.0 LAccepted-AOC 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | ₹28.0 L Quoted ₹29.0 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹29.4 LRejected-Finance 4 14 168 TRISHERIYU SALVIWADO PATAN PATAN GUJARAT 384265 UDYAM GJ 18 0001893 | PATAN | GUJARAT | 384265 | ₹29.4 L | L2 | Rejected-Finance Being L2 |
| 3 | Rejected-Technical | - | - | Rejected-Technical NOT RECOMMENDED DUE TO FIRM NOT ENLISTED WITH APPROPRIATE CATEGORY b(ii) AS PER NIT |
| 4 | Rejected-Technical KUCHHADI VADI VISTAR PORBANDAR GUJARAT 360579 | PORBANDAR | GUJARAT | 360579 | - | - | Rejected-Technical NOT RECOMMENDED DUE TO FIRM NOT ENLISTED WITH APPROPRIATE CATEGORY b(ii) AS PER NIT |
| Sl No | Description | Qty | Unit | SURESH ELECTRICALS L1 | shree chamunda enterprise L2 |
|---|---|---|---|---|---|
| 0.00Schedule 'A' | |||||
| 1.00 | Material & Labour for Dehydration/Filtration of transformer oil at site by means of centrifuging machine in order to improve dielectric strength of oil as per IS-355. Break down voltage should not be less than 50 KV, complete all as specified and directed by Engr-in-Charge. | 935 | Litre | 50 ₹46,750 | 36 ₹33,660 |
| 2.00 | Material & Labour for Transformer oil having di-electric strength of 60 KV as per IS complete for top up/ replacement, complete all as specified and directed by Engr-in-Charge. (Oil should be supplied in sealed barrel of Power/Transol brand)
Note: oil shall be filled in the transformers/stabilizers to be repaired or installed at site at different locations. | 100 | Litre | 190 ₹19,000 | 191 ₹19,100 |
| 3.00 | Material and labour for painting of the transformer 400 KVA, RMU, VCB complete by removing old paint by scrapping and providing spray painting with synthetic enamel paint (Suitable for existing colour) of approved make duly marking/writing MES/SM No., complete all as specified and directed by Engr-in-Charge. | 4 | Each Job | 17,500 ₹70,000 | 15,301 ₹61,204 |
| 4.00 | Supply only Gasket for LT/HT Bush suitable for 400 KVA transformers, including taking down old unserviceable gasket, complete all as specified and directed by Engr-in-Charge. | 6 | Each | 500 ₹3,000 | 531 ₹3,186 |
| 5.00 | Supply & Fixing Breather suitable for 400 KVA distribution transformers, complete including taking down, complete all as specified and directed by Engr-in-Charge. | 2 | Each | 600 ₹1,200 | 606 ₹1,212 |
| 6.00 | Supply and fixing in replacement Silica Gel (Moisture absorbent chemical) for breather of transformer, complete all as specified and directed by Engr-in-Charge. | 2 | Kilogram | 250 ₹500 | 241 ₹482 |
| 7.00 | Supply and fixing in replacement of LT bush with rod of brass complete cork washer with nuts bolts and washers of brass of suitable size for 400KVA Transformer, complete all as specified and directed by Engr-in-Charge. | 3 | Each | 1,950 ₹5,850 | 1,981 ₹5,943 |
| 8.00 | Supply and fixing in replacement of HT bush with rod of brass complete cork washer with nuts bolts and washers of brass of suitable size for 400KVA Transformer, complete all as specified and directed by Engr-in-Charge. | 3 | Each | 2,000 ₹6,000 | 2,131 ₹6,393 |
| 9.00 | Supply and fixing in replacement Oil Temp Gauge suitable for 400KVA transformer, complete all as specified and directed by Engr-in-Charge. | 2 | Each | 5,000 ₹10,000 | 5,031 ₹10,062 |
Updated dates
Tender Value
₹28.6 L
EMD Value
₹57,500
Closing Date
28 Jan 2026, 6:00 pmClosed
GE (I) CG PORBANDAR
COAST GUARD DHQ NO 1, OPP BIRLA FACTORY
REPAIR MAINTENANCE OF EXTERNAL ELECTRIC SUPPLY EXTERNAL WATER SUPPLY AND OTHER MISC ITEMS AT CGDHQ NO 15 UNDER GE (I) CG PORBANDAR
2025_MES_745450_1
8145A/E8
Open Tender
Electrical and Maintenance Works
180 days
OKHA
AS PER NIT
10 documents required · 10 mandatory
₹500
GE (I) CG PORBANDAR
₹57,500
Yes
27 Mar 2026
2 Jan 2026
30 Jan 2026
2 Jan 2026
28 Jan 2026
16 Jan 2026
Material & Labour for Dehydration/Filtration of transformer oil at site by means of centrifuging machine in order to improve dielectric strength of oil as per IS-355. Break down voltage should not be less than 50 KV, complete all as specified and directed by Engr-in-Charge.
Material & Labour for Transformer oil having di-electric strength of 60 KV as per IS complete for top up/ replacement, complete all as specified and directed by Engr-in-Charge. (Oil should be supplied in sealed barrel of Power/Transol brand) Note: oil shall be filled in the transformers/stabilizers to be repaired or installed at site at different locations.
Material and labour for painting of the transformer 400 KVA, RMU, VCB complete by removing old paint by scrapping and providing spray painting with synthetic enamel paint (Suitable for existing colour) of approved make duly marking/writing MES/SM No., complete all as specified and directed by Engr-in-Charge.
Supply only Gasket for LT/HT Bush suitable for 400 KVA transformers, including taking down old unserviceable gasket, complete all as specified and directed by Engr-in-Charge.
Supply & Fixing Breather suitable for 400 KVA distribution transformers, complete including taking down, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement Silica Gel (Moisture absorbent chemical) for breather of transformer, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of LT bush with rod of brass complete cork washer with nuts bolts and washers of brass of suitable size for 400KVA Transformer, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of HT bush with rod of brass complete cork washer with nuts bolts and washers of brass of suitable size for 400KVA Transformer, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement Oil Temp Gauge suitable for 400KVA transformer, complete all as specified and directed by Engr-in-Charge.
Preventive Maintenance and Servicing, 11/0.433 KV, 400 KVA Step down Transformer Indoor and Oil Cooled type by disconnecting carefully electric connection on primary & secondary side, Checking both side HT bushing, bushing rod, opening top cover of the transformer by unscrewing nuts, bolts, washers etc., rectify the oil leakages issues, if noticed any from the entire body of the transformer, during servicing and re-fixing the top cover of transformer according to previous system. Servicing of the transformer must be done through OEM or authorised personnel including maintaining and submitting the inspection and testing records of each transformer to the Engr-in-Charge. Note 1. :- Inspection of transformer shall involve :-(a) Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts etc. (b) Checking all brazing’s, joints, tap heads, gaskets and connection joints. (c) Checking all terminations / connections inside/outside the transformer. (d) Checking of off load tap changer assembly, checking the moving and fixed contacts for contact wear and connection to winding. (e) Conducting the test on core and windings as per IS like ratio, magnetic imbalance, short circuit, IR Value, High Voltage Test etc. in presence of Engr-in-Charge. Note 2. : Spares used bushes studs HT/LT, bushing rod HT/LT, transformer oil, filtration of oil, buchholtz relay, Gaskets set, Off Load Change over switch etc., will be measured and paid separately under respective item of BOQ. Note 3 :- The rates quoted against the item is deemed to be included for cost of Labour for lifting/transporting to civil workshop and vice-versa, if required as per site requirement.
Attending any breakdown immediately power transformer/RMU/VCB of 400 to 630A capacity by OEM service engineer to check and repair/replace any spares related break down and make the power transformer serviceable within 24hrs, complete all as specified and directed by Engr-in-Charge. Note: - (i) Spares will be paid separately under the relative items. (ii) Checking of all electrical connection and proper tightening is inclusive of this job. (iii) Proper care shall be taken to isolate the supply, taking shutdown if required from PGVCL and it shall be ensured that repairs are carried out on No LIVE switchgears are inclusive of Job
Comprehensive maintenance/Overhauling of HT panel/RMU (01 Incoming and 2x Outgoing) of 630A capacity, 11KV, Indoor type, SF6, insulated compact with short circuit peak making current 50 KA and short breaking current 20 KA fully arc proof metal enclosed free standing floor mounting manually operated fixed type SF 6 insulated, 02 Nos, detection of defective components, replacement of worn-out parts and servicing/cleaning of mechanical components through authorised service centre of RMU manufacturer /OEM or skilled RMU repairing agency, re-insertion of trolly in HT panel, testing, complete all as specified and directed by Engr-in-Charge. Note: (i) Worn out parts shall be measured & paid separately under respective items. (ii) Replacement of mechanical indication in the front in the mimic for open & close breaker / isolator / earth switch and manual push button for emergency trip etc., all are inclusive of job and all as specified and as directed. (iii) Disconnect the HT cables in test position, check the megger value of RMU terminals with body by suitable HT megger of range 5000 volts and check the serviceability of Earthing connection by earth megger, note down the reading all are inclusive of this job.
Supply and fixing in replacement of Following parts/items( Srl no. 13.01 to 13.03) for HT panel / RMU as per existing make and model and directed at site, complete all as specified and directed by Engr-in-Charge.
Motor cut off Limit switch Make: BCH / L&T / C&S
Closing coil 24V DC Assembly
Shunt trip coil 24V DC
Comprehensive maintenance/overhauling of HT, 11KV, VCB (01 Incoming and 02x Outgoing), detection of defective components, replacement of worn-out parts and servicing / cleaning of mechanical components through authorised service centre of VCB manufacturer /OEM or skilled VCB repairing agency, re-insertion of trolly in HT panel, testing, complete all as specified and directed by Engr-in-Charge. Note: (i) Worn out parts shall be measured & paid separately under respective items. (ii) Replacement of small piece of wire of 1.5 sqmm in control of max up to 05 Mtr and replacement of unserviceable indicator lamps as per colour code all as directed are inclusive of this job, (iii) Rack out/down he HT VCB kept in test position, check the megger value of VCB terminals with body by suitable HT megger of range 5000 volts and check the serviceability of Earthing connection by earth megger, note down readings are inclusive of this job.
Supply and fixing in replacement of Following parts/items for VCB 11 KV 630 A as per existing make and model and directed at site. :-
Spring charging Handle
Auxiliary Contactor
charging motor
Closing coil 24 Volt DC
Tripping coil 24 Volt DC
Master Trip Relay 110 volt DC
Auxiliary Relay 110 volt DC
Protection Relay (over short Circuit /earth fault) 110 volt DC
Dismantling cross-arms of M.S. channel or angle sections etc., complete all as specified and directed by Engr-in-Charge.
Supply and fixing of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete with joints to match, complete all as specified and directed by Engr-in-Charge.
Supply and fixing Switch Air break, Gang operated, TP suitable for horizontal or vertical operation, mechanically operated mounted on 9 insulators and steel frame with operating mechanism and operating rod of 20mm bore, medium grade, GI pipe worked from ground level with locking arrangement for 200 Amps rating 11 KV working pressure connecting Electrical connections, including taking down old unsv air break switch, complete all as specified and directed by Engr-in-Charge.
Supply & Fixing in replacement of HT 11 KV drop out fuse assembly with insulator and base including fuse tube, fuse carrier top connectors incoming and outgoing connectors as specified and as directed by EIC. (Note: Rate include taking down existing unserviceable/ Faulty DO fuse assembly and fix the new one and make the incoming and outgoing connections and switch on the supply through the new DO fuse assembly all as directed by EIC)
Material & Labour Lightening arrestor, expulsion type consisting of multiple spark gaps in series with one or more nonlinear resister to limit voltage surge on AC power circuit to interrupt power flow current suitable for outdoor installation and exposed direct to sun with ambient temperature below - 10 degree C to 50 degree C suitable for surge discharge capacity 65 KA, transmission class, 11000 volts grade conforming to IS-4350 and all fittings including taking down existing unsv DO fuse, complete all as specified and directed by Engr-in-Charge.
Supply & Fixing in replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull & bones in signal red colour & fixed with MS clamps, bolts & nuts of required size for HT 25x20 cm size, complete all as specified and directed by Engr-in-Charge.
Material & Labour Earthing for poles and other machinery/eqpt using GI strip as earth lead and MS galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32x6mm as Earthing lead with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame, charcoal, common salt 15cm at round the earth plate watering pipe 20mm med grade/galvanized and 40mm dia GI pipe light grade for GI strip protected steel with funnel complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009, including taking dwon old unserviceable Earthing, complete all as specified and directed by Engr-in-Charge.
Excavation in trenches not exceeding 1.5 Metre wide and not exceeding 1.5 Metre in depth and getting out in soft soil for taking up or laying of cable/erecting of pole /stay, complete all as specified and directed by Engr-in-Charge.
Returning filling in including spreading levelling watering and well ramming in layers not exc. 25 cm thick each, complete all as specified and directed by Engr-in-Charge.
Removing excavated material to a distance not exceeding 50 Metre and depositing where directed at a level not exceeding 1.5 Metre above the starting point of any type of soil, complete all as specified and directed by Engr-in-Charge.
Material & Labour for cutting existing road/hard standing not exc 45 x 45 cm in wide & depth getting out excavated material for laying cable/GI tube, returning filling & well ramming watering finish surface 10 cm from top using PCC 1:2:4; including removal of surpluses soil, complete all as specified and directed by Engr-in-Charge.
Taking out UNSV HT UG cables of any sizes from trenches, complete all as specified and directed by Engr-in-Charge.
Supply, Laying, Connecting, testing, commissioning and Jointing HT underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armour fixed electric power cable (heavy duty), with aluminium conductor, laid in trenches, ducts, fixed on poles/walls with proper size saddles and clamp laid under roads/path/drain/culverts or encased in GI pipe fixed, 11000 volts grade cross sectional area 95 sqmm 3 core, complete all as specified and directed by Engr-in-Charge.
Supply, Laying, Connecting, testing, commissioning and Jointing HT underground XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty), with aluminium conductor, laid in trenches, ducts, fixed on poles/walls with proper size saddles and clamp laid under roads/path/drain/culverts or encased in GI pipe fixed, 11000 volts grade cross sectional area 185 sqmm 3 core, complete all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement of Cable jointing kit for 11 KV (Earthed) grade cable for Indoor type termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to185 Sqmm, complete all as specified and directed by Engr-in-Charge.
Ditto-as per item no. 30 But for cable size 50 to 95 Sqmm, complete all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement of Cable jointing kit for 11 KV (Earthed) grade cable for Outdoor type termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to185 Sqmm, complete all as specified and directed by Engr-in-Charge.
Ditto-as per item no. 32 But for cable size 50 to 95 Sqmm, complete all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement of Cable jointing kit for 11 KV (Earthed) grade cable for Straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm, complete all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement of Cable jointing kit for 11 KV (Earthed) grade cable for Straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm, complete all as specified and directed by Engr-in-Charge.
Material & Labour for concrete graded stone aggregate using 20mm grade using for laying to cover the area of MRS, Transformer, complete all as specified and directed by Engr-in-Charge.
Material & Labour for Site Clearance, cleaning away all grass, vegetation, saplings, Scrubs, brush wood, under growth roots and trees not exceeding 30 cm girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearance in soft/loose soil, complete all as specified and directed by Engr-in-Charge.
Supplying and laying in replacement of synthetic Rubber insulated mats 2.5mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and directed by Engr-in-Charge.
Taking out UNSV LT UG cables of any sizes from trenches, complete all as specified and directed by Engr-in-Charge.
Supply & Laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, complete all as specified and directed by Engr-in-Charge. of cross-sectional area.
16 sqmm 4 core
50 Sqmm 3.5 Core
95 sqmm 3.5 core
120 sqmm 3.5 core
240 Sqmm 3.5 Core
Supply and fixing in replacement of Multi standard Copper Conductor cable of size 1.5 Sqmm 3 Core, inclusive of all tees, bends, elbows, reducers and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. for interconnection of cable light/looping box to street light fitting etc., complete all as specified and directed by Engr-in-Charge.
Material and Labour for DWC pipe laying in trenches/ under floor/on walls for protection of UG cables of following sizes, complete with coupler and connected accessories, including taking down old unserviceable DWC Pipe, complete all as specified and directed by Engr-in-Charge. Note: (i) Cutting of floor/ road and making good with PCC deemed to be included in item rate of Following Size:-
Material & Labour Cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material (heat shrinkable) and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable, including taking down old unserviceable cable jointing kit. of following sizes- Make-Denson/Siemen
25 sqmm to 50 sqmm
70 sqmm to 150 sqmm
150 sqmm to 240 sqmm
Supply & Fixing in replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull & bones in signal red colour & fixed with MS clamps, bolts & nuts of required size for LT 20x15 cm size, complete all as specified and directed by Engr-in-Charge.
Ditto (item No 45) for HT, 25x20cm size, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of MCB/MCCB FP, 415 V fixed type, including taking down of old unsv panel after disconnecting Existing cables and reconnecting the cables with proper lugs and glands complete all as specified and directed of following:-
MCCB 4 pole 63 Amps of Breaking capacity 16KA.
MCCB 4 pole 100 Amps of Breaking capacity 25KA.
MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA
MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA
MCCB 3 Pole, 415 V, fixed type, 200 Amps with breaking capacity 36 KA
MCCB 3 Pole, 415 V, fixed type, 250 Amps with breaking capacity 36 KA
MCB 6 TO 32 Amps SP, 240 V breaking capacity 10 KA
Comprehensive maintenance and repair of APFC panel by replacement of worn out spare parts and cleaning of the serviceable contactors and tightening/ checking of all internal electrical connections and accessories to maintain PF not less than 0.99 by adjusting/ calibrating the APFC relay of any type, complete all as specified and directed by Engr-in-Charge. Note: Defective parts if any will be measured and paid separately
Supply and fixing in replacement of Heavy duty gas filled Capacitor 5 KVAR, 440V, 3 phase, 50 Hz.
Supply and fixing in replacement of Heavy duty gas filled Capacitor 10 KVAR, 440V, 3 phase, 50 Hz.
Supply and fixing in replacement of Heavy duty gas filled Capacitor 3 KVAR, 440V, 3 phase, 50 Hz.
Supply and fixing in replacement of 8 Steps APFC Relay, microprocessor based and connected items all as directed by Engr-in-Charge.
Servicing of Servo Stabilizer oil cooled automatic type of capacity 100 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel level, supply system, Lubrication system, cooling system, rectification of defect if any and including replacement of following, complete all as specified and directed by Engr-in-Charge.
Material & Labour for apply two coat of epoxy paint on LT Panels of any size, including preparation of rusted surface of poles by means of sand paper/scrubbing of dust etc., and apply one coat of epoxy based primer before painting, complete all as specified and directed by Engr-in-Charge. Note: Minor repair/ replacement of hinges suitable for screw fasteners and fixed in original position deemed to be included in unit rate.
Material & Labour for bore Earthing 150mm bore for Earthing with galvanised steel pipe electrode, 40mm bore, medium grade, 3 metres length, top edge of GI pipe 15 cm above GL, connected with Earthing lead of 25X4 mm GI strip to the Earthing test point and filling of charcoal dust, salt etc., and testing on completion, including taking down old unserviceable Earthing, complete all as specified and directed by Engr-in-Charge. Note: IR Value should be less than 5 Ohms.
Supply & Fixing in replacement of Aluminium lugs long barrel of size 120 to 240 sqmm, complete all as specified and directed by Engr-in-Charge.
Supply & Fixing in replacement of Aluminium lugs of size 50 to 95 sqmm, complete all as specified and directed by Engr-in-Charge.
Supply & Fixing in replacement of Aluminium lugs of size 16 to 35 sqmm, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of On-Load Changeover Switch with enclose 200 Amps, 4 Pole, 415 Volt with cable entry, connecting the cables with proper lugs and glands, complete all as specified and directed by Engr-in-Charge.
Supply & Fixing in replacement of Gear box with all assembly complete of Height mast 15Mtr height, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of Contactor ML-3, 3 pole of cap 40 Amps, complete all as specified and directed by Engr-in-Charge.
Comprehensive maintenance / servicing and repair of raising lowering system comprising double drum winch, for 12.5 Metre height HDG Octagonal high mast poles and greasing gear box, panel and make connection, complete all as specified and directed by Engr-in-Charge.
Taking down the old and rusted GI bracket and supply fixing GI bracket of 40mm dia duly painted with two coat of supper enamelled paint over a coat of red oxide including suitable clamps nuts bolts and washers etc., complete all as specified and directed by Engr-in-Charge.
Material & Labour for preparing old rusted surface of 9/11Mtr PCC pole by means of sand paper/scrubbing of dust etc., and apply one coat of primer on surface of poles and applying two coats of OBD paint on Pole and numbering of poles with synthetic enamel paint white in 100mm high letters over 150x150 mm black base, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of time switches 415 V, three Phase integrated model with max Load 5-8 KW of 20 Amp rating with suitable MCBs and contactor fitted inside enclosure confirming to protection of IP66 with Hinged Lid, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of time switches 240 V, Single Phase integrated model with max Load 3-5 KW of 25 Amp rating with suitable MCBs and contactor fitted inside enclosure confirming to protection of IP66 with Hinged Lid, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement thermoplastic cable junction box for street lights of size 205 x 255 x 112mm including bus bar/terminal for cable connection with IP-66 protection, complete all as specified and directed by Engr-in-Charge. Make : Hensel Cat No.DK 2525 G or its equivalent in Legrand /sintex
Material & Labour for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm, including taking down old unserviceable cable, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of LED street light of capacity 60 Watt, LM6 high pressure die cast aluminium housing, IP 66 protection ,THD<20%, PF>0.95, Operating Voltage 140-270V AC, 50HZ, complete all as specified and directed by Engr-in-Charge. Make: Wipro Cat Part No LR02-671-XXX-57-G3 or equivalent in Philips/Crompton Greaves
Supply and fixing in replacement of LED flood light 200 Watt LM6 high pressure die cast aluminium housing, IP 66, Nominal Lumen output 14000 lm, Colour temperature 5700K, THD<10%, PF>0.95, Operating Voltage 140-270V AC, 50HZ, complete all as specified and directed by Engr-in-Charge. Make: Wipro Cat part No- LF30-112-60L-57-XX or equivalent in Philips/Bajaj
Supply and fixing in replacement of LED Bollard light Cool white 6500 K of wattage 11 watt with integrated mounting base plate and driver complete with including PCC (1:2:4) foundation of suitable size for mounting of light fitting including, complete all as specified and directed by Engr-in-Charge. Make : Wipro Cat No. LB14-131-XXX-65-08 or equivalent in Philips /Bajaj
Supply and fixing in replacement LED Bollard Light Cool White of wattage 11 Watt 6500 K with integrated mounting base plate and driver complete with housing dark grey RAL 7043 IP 65 protection, Resistant to corrosion and Better optics for uniform distribution including PCC (1:2:4) foundation of suitable size for mounting of light fitting, complete all as specified and directed by Engr-in-Charge. Make: Wipro Cat No: LB13-131-XXX-65-05 or equivalent in Philips/Bajaj
Supply and fixing in replacement of LED Landscape 35 watt, 5700K, 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete, complete all as specified and directed by Engr-in-Charge. Make-Wipro Cat No:LF09-431-XXX-57-XX or equivalent in Philips/Bajaj
Supply and fixing in replacement LED High Bay light fittings surface mounted 140W to 150W, CCT 5700K, fixed output, wide beam Innovative thermal sink design, flat with slight inclination and thermal fins in the middle with hook mounting arrangement and Suitable for 10 to 30 meter height, complete all as specified and directed by Engr-in-Charge. Make : Wipro /Philips / Osram
Comprehensive maintenance / servicing and repair of search light 150W, system by replacement of worn out parts, and cleaning of the serviceable contactors and tightening/ checking of all internal electrical connections and accessories/ relay/ single phase preventer/ motors etc., complete all as specified and directed by Engr-in-Charge.
Servicing of DG set ('C' Check) of Cap 100/125 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect if any and including replacement of following, complete all as specified and directed by Engr-in-Charge. (a) Lub oil filter. (b) Lubrication oil. (c) Fuel filter. (d) Coolant top up. Make of DG set: Ashok Leyland/ Kirloskar Note: Defective parts if any other than listed at (a) to (d) above will be measured and paid separately.
Supply only parts/ Items of DG set 100/125 KVA (Make : Ashok Leyland/ Kirloskar)
Oil Filter
Fuel Filter
Air Filter
Coolant
Engine Oil
Servicing of DG set ('C' Check) of Cap 20/25/30 KVA by Rep of authorised service centre as per manufacturer manual and checking of fuel supply system, Lubrication system, cooling system, battery ignition system and rectification of defect if any and including replacement of following, complete all as specified and directed by Engr-in-Charge. (a) Lub oil filter. (b) Lubrication oil. (c) Fuel filter. (d) Coolant top up. Make of DG set: Ashok Leyland/ Kirloskar Note: Defective parts if any other than listed at (a) to (d) above will be measured and paid separately
Supply only parts/ Items of DG set 20/25/30 KVA (Make : Ashok Leyland/ Kirloskar)
Oil Filter
Fuel Filter
Air Filter
Coolant
Engine Oil
Servicing/Calibration of old AMF Panel and rectification of defect if and including Repair/ Replacement of Unserviceable items, complete all as specified and directed by Engr-in-Charge.
Relay Card Start/Stop, complete all as specified and directed by Engr-in-Charge.
4ST relay, complete all as specified and directed by Engr-in-Charge.
Materials and labour for scraping removing and cleaning old rusty paint from enclosure of DG set 20 KVA to 125 KVA capacity any make by cleaning agents & painting the above DG set complete with Polyurethane (PU) paint, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair Door locking arrangement and Hinges as per existing canopy of DG Set 125/100 KVA DG Sets, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair Door locking arrangement and Hinges as per existing canopy of DG Set 30/25/20 KVA DG Sets, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair 4 pole power contactor MCX-13, 50 Hz, complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair power Relay MNX - A1,/MNX - A2, 50 Hz, complete all as specified and directed by Engr-in-Charge.
Cleaning of following reservoir : Cleaning 4 stage cleaning process such as Sludge removal, high pressure cleaning, vacuum cleaning, anti-bacterial spray and Material & Labour for scraping/removing old date of cleaning of service tanks and writing with white paint "CLEANED ON" (date) using 10" (25cm) size letter on painted black base, complete all as specified and directed by Engineer-in-Charge.
UG Sump 200000 ltr capacity
UG Sump 100000 ltr capacity
UG Sump up to 40000 ltr capacity
OHT 100000 ltr capacity
Taking up/down CI/DI pipes with connection from trenches including connected fittings/accessories complete of 100mm bore size and removing the pipes and reused to site, complete all as specified and directed by Engineer-in-Charge.
Supply, laying and jointing in trenches DI pipes class K-7 of standard length spigot and socketed end push type joint with rubber gasket as jointing material, internal cement mortar coating an external surface with bituminous paint of size 100mm dia ISI, complete all as specified and directed by Engineer-in-Charge.
Taking down and Supply, lay and joint in replacement in trenches 150mm bore, ductile iron (DI) pipe Class "K-7", of standard length spigot and socketed end push type joint with rubber gasket as jointing material, internal cement mortar coating and external surface with bituminous paint of size 150mm (6") dia ISI including specials, complete all as specified and directed by Engineer-in-Charge.
Taking out unserviceable foot valve 80/100mm dia from the UG sump and Supply & Fixing new foot valve 80mm dia ball type including rubber gasket, bolts, buts, complete all as specified and directed by Engineer-in-Charge.
Taking out unserviceable sluice valve and Supply & fixing in replacement of sluice valves flanged type class PN 1.6, complete all as specified and directed by Engineer-in-Charge. of following size:-
100mm dia bore
150mm dia bore
80mm dia bore
Taking out unserviceable valve and Supply & fixing in replacement of non-return sluice valve flanged type class PN 1.6, complete all as specified and directed by Engineer-in-Charge. Of following size:-
80mm dia bore
100mm dia bore
150mm dia bore
Taking out unserviceable air release valve and Supply & fixing in replacement of air release valve flanged double ball type Cast Iron body class PN 10 of 50mm size, complete all as specified and directed by Engineer-in-Charge.
Taking up or down steel tubing/PPR/Old UPVC and connections, including cleaning for re-fixing or removal to store of following sizes
25/32mm bore
50mm bore
80mm bore
Supplying and laying of CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings in trenches complete all as specified as per site requirement complete of sizes of nominal dia:-
Supplying and laying of CPVC Schedule 80 pipes & plain CPVC Schedule80, 75mm ID fittings in trenches, complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing in replacement of CPVC Gate /ball valves as per requirement of the site of the following
Material & Labour for bends (any type, radius and angle) tapers any type (straight bend, increasing, decreasing or double socked etc) tee pieces, single branch, junction, double branch, cross (all sockets or socket and spigot) collars, caps plugs suitable for the pipe upto 300mm bore, complete all as specified and directed by Engineer-in-Charge.
Material & Labour for Construction of brick masonry valve pit complete including necessary excavation and earth work complete all as specified with internal dimension 150x150x110cm (type 'B') including MS sheet cover 3mm thick welded with hinges on angle iron frame 50x50x6mm with hold fast grouted in 100mm thick PCC (1:2:4) type B-1 coping on top of brick wall including necessary locking arrangement, complete all as specified and directed by Engineer-in-Charge.
Taking down/up the Unsv Submersible Pump 12.5/15 HP including disconnecting delivery system etc and reassembling after replacement of necessary spares including greasing and oiling and painting of 2 coats of synthetic enamel paint using spray machine, complete all as specified and directed by Engineer-in-Charge. [NOTE: Replacement of worn out spares will be measured and paid separately].
Dismantling the centrifugal Pump 12.5/15 HP including disconnecting suction and delivery etc and reassembling after replacement of necessary spares including greasing and painting of 2 coats of synthetic enamel paint using spray machine, complete all as specified and directed by Engineer-in-Charge. [NOTE: Replacement of worn out spares will be measured and paid separately].
Dismantling of electric motor 3 phase, 415 Volt capacity 12.5/15 HP, incoming disconnection electric connections, dismantling slots, taking out burnt windings and rewinding the motor with super enamelled copper wire as per existing size including insulating material and varnishing, greasing, painting with super enamelled paint as per colour cod assembling the motor after rewinding and mounting at its own position, replacing the old nut, bolts and testing, complete all as specified and directed by Engineer-in-Charge.
Taking down/up the Unsv Submersible Pump upto 5 HP including disconnecting delivery system etc and reassembling after replacement of necessary spares including greasing and oiling and painting of 2 coats of synthetic enamel paint using spray machine, complete all as specified and directed by Engineer-in-Charge.
Supply and replace following worn out spares of Centrifugal/mono-block pump 12.5/15 HP sets.
Bearing as per existing Size
Rubber bush for coupling
Gland packing
Supply and fix in replacement Automatic star delta starter for 12.5/15 Hp centrifugal mono block pump set/ submersible, 415 V 50 Hz three phase as per existing specification, complete all as specified and directed by Engineer-in-Charge.
Material and labour for rubber gasket (Tyton) joints suitable for 100mm bore CI/DI pipe and fittings including jointing material, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of following spares for RO water Plant 10000 Ltr/Hr :-
Micron Cartridge Filter (Spun Type 5 Micron)
Micron Cartridge Filter (Bag Type 20 Micron)
Multiport Valve
Pressure Gauge
Anti-sealant chemical
Dozing pump
Supply and fixing in replacement of following spares for RO water Purifier 50 LPH Cap:-
Sediment/Carbon Filter
Pre-filter box with candle
Supply & Fixing in replacement of Pressure Pump Sensor For Pressure Pump, complete all as specified and directed by Engineer-in-Charge.
Spray Painting of Pump & Motor any type, any capacity upto 20 HP as per colour code (Shade) of MES specification after cleaning the dust particle of existing motor & Pump, complete all as specified and directed by Engineer-in-Charge.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.29 MB
BOQ_834714.xls
BOQ • 0.44 MB
8145AT.pdf
Tender Documents • 3.95 MB
Download all tender documents and submit your bid