Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹12.6 Cr
EMD Value
₹12.6 L
Closing Date
23 Oct 2026, 3:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
NBCC Bhawan
NBCC Bhawan
Construction of the Residential Building of Canara Bank at Plot Nos. 222 and 223, Dollars Colony, RMV Extension, Bengaluru.
NBCC/RBG/South/CNB/Bengaluru/Karnataka/2026/48~EW2bee0ca2936e7a7fbf28a54a
NBCC/RBG/South/CNB/Bengaluru/Karnataka/2026/48
Open Tender-Domestic
Civil Works - Buildings
NBCC Bhawan
₹11,800
₹12.6 L
9 Oct 2026
9 Oct 2026
23 Oct 2026
9 Oct 2026
23 Oct 2026
Abstract of Cost - Civil/Plumbing/Fire/Electrical Works
Location:- Dollars Colony, RMV Extension, Bengaluru.
S.No. Description DSR Amount NDSR Amount Total DSR+NDSR
2 Internal Plumbing Works 3907760.90 2314845.10 ₹ 62,22,606.00
3 External Plumbing Works 2969277.62 749428.90 ₹ 37,18,706.52
4 Internal Fire Fighting Works 597185.24 263558.49 ₹ 8,60,743.72
5 Internal Electrical/LV Works 6813097.96 4311234.17 ₹ 1,11,24,332.13
6 External Electrical Works 2189146.56 8410032.60 ₹ 1,05,99,179.16
7 15 KLD STP Equipments Works 0.00 1720215.80 ₹ 17,20,215.80
Grand Total - (Project Cost) ₹ 12,57,65,506
Grand Total - (Project Cost) ₹ 12,57,65,506
Digitally signed by DEEPAK
Project :- Construction of the Residential Building at Plot Nos. 222 & 223,
Dollars Colony, RMV Extension, Bengaluru. K.A
COST SUMMARY - CIVIL WORKS
S. No. Sub-Head
AS PER DSR 2023
1 Earthwork 12,00,088.94 -
2 Concrete & RCC Works - Foundation & Plinth 1,77,28,868.22 -
3 Concrete & RCC Works - Superstructure 2,88,95,160.57 -
4 Masonary Work 62,31,548.05 -
7 Steel Works 20,80,045.39 -
8 False Ceiling 5,32,780.90 -
9 Finishing 96,68,249.06 -
10 Site Development Works 19,44,224.12 -
12 Rain Water Harvesting 5,57,168.40 -
13 Horticulture Works 1,58,637.07 -
Total (DSR + NSR): 9,15,19,723.08
Project :- Construction of the Residential Building at Plot Nos. 222 & 223, Dollars Colony, RMV Extension, Bengaluru. K.A
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
1.0 Earthwork: -
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth
2.31 1.1 up to 30 cm measured at a height of 3 m above ground level and removal of rubbish up to a distance Sqm 260.00 20.11 5,228.06 -
of 50 m outside the periphery of the area cleared.
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas
(exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and
disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-in-charge - In all
Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or stacked
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers
2.25 1.3 not exceeding 20cm in depth consolidating each deposited layer by ramming and watering, lead upto Cum 1,038.00 223.93 2,32,438.65 -
50m for all lift.
Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport
2.25 A) 1.4 upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20cm in Cum 260.00 800.32 2,08,082.91 -
foundation trenches, plinth, sides of foundation etc. complete for all lift.
Supplying and filling in plinth with sand under floors, including, watering, ramming consolidating and
dressing complete.
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/
Lindane emulsifiable concentrate of 20%.
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment
(excluding the cost of chemical emulsion):
Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per
2.35.2.1 a) linear metre including drilling and plugging holes etc.: With Chlorpyriphos/ Lindane E.C. 20% with 1% Metre 152.00 61.07 9,282.10 -
Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart
including drilling 12 mm diameter holes and plugging with cement mortar 1: 2 (1 cement : 2 Coarse
sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Total Carried Over to Summary: - 12,00,088.94 -
2.0 Concrete & RCC Works - Foundation & Plinth: -
Providing and laying in position cement concrete of specified grade excluding the cost of centering
and shuttering - All work up to plinth level:
1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources: 8 graded stone aggregate 40
mm nominal size derived from natural sources)
Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4 (1 cement: 2 coarse
sand (zone-III) derived from natural sources: 4 graded stone aggregate 20 mm nominal size derived
from natural sources) along with approve crystile admixure as per manufacturer's specifications.
Providing & applying a coat of approved quality residual petroleum bitumen of grade VG-10 using
4.13 2.3 using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and Sqm 44.00 166.98 7,346.94 -
finally with a piece of cloth lightly soaked in kerosene oil.
Providing and laying in position ready mixed or site batched design mix cement concrete for
reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural
sources, Portland Pozzolana/ Ordinary Portland/ Portland Slag cement, admixtures in recommended
5.33 2.4 proportions as per IS: 9103 to accelerate/ retard setting of concrete, to improve durability and -
workability without impairing strength; including pumping of concrete to site of laying, curing,
carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as
per direction of the engineer-in-charge; for the following grades of concrete.
5.33.1 a) All works upto plinth level. -
5.33.1.1 i) Concrete of M25 grade with minimum cement content of 330 kg /cum. Cum 118.00 10,859.14 12,81,379.06 -
5.33.1.2 ii) Concrete of M30 grade with minimum cement content of 350 kg /cum. Cum 413.00 11,031.60 45,56,052.63 -
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and
binding all complete up to plinth level.
5.22.6 a) Thermo-Mechanically Treated bars of grade Fe-500 D or more. Kg. 78,606.00 123.22 96,85,694.41 -
5.9 2.6 Centering and shuttering including strutting propping etc and removal of form for: -
5.9.1 a) Foundations, footings, bases of columns etc for mass concrete Sqm 654.00 448.03 2,93,011.65 -
5.9.2 b) Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. Sqm 227.00 962.55 2,18,499.62 -
5.9.3 c) Suspended floors, roofs, landings, balconies and access platform Sqm 23.00 1,059.38 24,365.74 -
5.9.5 d) Lintels, beams plinth beams, girders, bressumers and cantilevers Sqm 387.00 841.33 3,25,596.45 -
5.9.6 e) Columns, pillars, piers, abutments, posts and struts Sqm 101.00 1,098.28 1,10,926.48 -
Making plinth protection 50mm thick of cement concrete 1: 3: 6 (1 cement: 3 coarse sand (zone III)
derivd from natural sources: 6 graded stone aggregate 20 mm nominal size) over 75mm bed by dry
4.17 2.7 brick ballast 40mm nominal size, well rammed and consolidated and grouted with fine sand, Sqm 52.00 856.07 44,515.78 -
including necessary excavation, levelling & dressing & finishing the top smooth.
Brick edging 7 cm wide 11.4 cm deep to plinth protection with common burnt clay F.P.S. (non
6.44 2.8 modular) bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 cement: 4 fine Metre 69.50 67.92 4,720.54 -
Total Carried Over to Summary: - 1,77,28,868.22 -
3.0 Concrete & RCC Works - Superstructure: -
Providing and laying in position ready mixed or site batched design mix cement concrete for
reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural
sources, Portland Pozzolana/ Ordinary Portland/ Portland Slag cement, admixtures in recommended
proportions as per IS: 9103 to accelerate/ retard setting of concrete, to improve durability and
workability without impairing strength; including pumping of concrete to site of laying, curing,
carriage for all floor to floor heights and all leads; but excluding the cost of centering, shuttering,
finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of
Note: Excess/ less cement used than as specified as per approved design Mix is payable/ recoverable
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
5.33.2 a) All works above plinth level upto floor V level -
5.33.2.1 i) Concrete of M25 grade with minimum cement content of 330 kg /cum. Cum 30.00 11,265.47 3,37,964.20 -
5.33.2.2 ii) Concrete of M30 grade with minimum cement content of 350 kg/cum. Cum 743.00 11,437.93 84,98,384.47 -
5.38 3.2 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof. Cum 13.00 406.33 5,282.28 -
Add for using extra cement or recovery for less cement consumed in the items of Design Mix over
and above the specified cement content therein.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and
binding all complete above plinth level. (SAIL, TISCO, RINL, JSW, Electrotherm)
5.22A.6 a) Thermo-Mechanically Treated bars of grade Fe-500 D or more. Kg. 1,11,538.00 123.22 1,37,43,518.10 -
5.9 3.5 Centering and shuttering including strutting propping etc and removal of form for: -
5.9.3 a) Suspended floors, shelves, roofs, landings, balconies and access platform Sqm 2,939.00 1,059.38 31,13,517.74 -
5.9.5 b) Lintels, beams plinth beams, girders, bressumers and cantilevers Sqm 1,544.00 841.33 12,99,020.46 -
5.9.6 c) Columns, pillars, piers, abutments, posts and struts Sqm 1,567.00 1,098.28 17,21,007.87 -
5.9.7 d) Stairs, (excluding landings) except spiral staircases Sqm 130.00 873.95 1,13,613.86 -
Total Carried Over to Summary: - 2,88,95,160.57 -
4.0 Masonry Work -
Providing and laying factory made Precast concrete solid blocks of 200 mm thickness of grade M10
made of C&D waste from approved manufacturer in foundation and plinth in:
26.68.1 a) Cement mortar 1:6 (1 cement : 6 coarse sand). Cum 20.00 8,439.91 1,68,798.16 -
Providing and laying factory made Precast concrete solid blocks of 200 mm thickness of grade M10
26.69 4.2 made of C&D waste from approved manufacturer in superstructure above plinth level up to floor V -
26.69.1 a) Cement mortar 1:6 (1 cement : 6 coarse sand). Cum 412.00 11,247.48 46,33,961.41 -
Extra for brick work/ block work/ AAC block masonry/ Tile brick masonry in superstructure above
floor V level, for each four floors or part thereof by mechanical means.
Providing and laying half block masonry with factory made Precast concrete solid blocks of 100 mm
26.71 4.4 thickness of grade M10 made of C&D waste from approved manufacturer in superstructure above -
plinth level up to floor V level:
26.71.1 a) Cement mortar 1:4 (1 cement :4 coarse sand) Sqm 446.00 1,255.78 5,60,075.71 -
Extra for brick work/ block work/ AAC block masonry/ Tile brick masonry in superstructure above
floor V level, for each four floors or part thereof by mechanical means.
Providing and laying Autoclaved Aerated Cement (AAC) blocks masonry with 100 mm/ 125mm thick
with Grade-1 AAC blocks of density 551 to 650 kg/cum conforming to IS:2185 (Part 3) in super
6.38 4.6 structure above plinth level up to floor V level in cement mortar 1:4 (1 cement: 4 coarse sand). The Cum 41.00 11,648.27 4,77,578.95 -
rate includes providing and placing in position 2 Nos. 6mm dia M.S. bars at every third course of
Providing and laying Autoclaved Aerated Cement (AAC) blocks masonry with 150 mm to 300 mm
thick with Grade-1 AAC blocks of density 551 to 650 kg/cum conforming to IS:2185 (Part 3) in super
structure above plinth level up to floor V level with RCC band at sill level and lintel level with
approved block laying polymer modified adhesive mortar all complete as per direction of Engineerin-
Charge. (The payment of RCC band and reinforcement shall be made for seperately)
Total Carried Over to Summary: - 62,31,548.05 -
5.0 Flooring: -
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the
manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand
& manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse
sand) jointing with grey cement slurry @3.3 kg/sqm including providing uniform grooves, grouting
the joints with white cement and matching pigments etc complete as per approved design, drawing.
The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the
notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing
the tiles gently and easily.
11.41A.2.5 a) Porcelain/ vitrified floor tile polished finish of size 1200 x 1200mm as per approved sample. Sqm 76.00 2,903.08 2,20,634.08 -
11.41A.1.4 b) Double charged vitrified tile polished finish of size 800 x 1600mm as per approved sample. Sqm 1,300.00 2,136.75 27,77,775.00 -
11.41A.3.1 c) Glazed Vitrified tiles Matt/ Antiskid finish of size 600 x 600mm as per approved sample. Sqm 433.00 1,912.07 8,27,926.31 -
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with
water absorption less than 0.08% and conforming to I.S. 15622, of approvedmake, in all colours &
11.46 5.2 shade, in skirting, riser of steps, over 12mm thick bed of cement mortar 1:3 (1 cement: 3 coarse Sqm 164.00 1,464.83 2,40,231.98 -
sand), jointing with grey cement slurry @3.3 kg/ sqm including grouting the joint with white cement
& matching pigments etc. complete.
Providing and laying Ceramic glazed floor tiles of size 300x300mm (thickness to be specified by the
manufacturer) of 1st quality confirming to IS: 15622 of approved make in colours such as White,
Ivory, Grey, Fume Red Brown, laid on 20mm thick cement mortar 1:4 (1 Cement: 4 Coarse Sand),
jointing with grey cement slurry @3.3 kg/ sqm including pointing the joints with white cement and
matching pigment etc. complete as per approved sample. (On inside walls and floors of Under
Ground and Over Head Water Tanks etc. complete).
Providing and laying Kota stone slab flooring over 20mm (average) thick base laid over and jointed
11.26 5.4 with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and -
polishing complete with base of cement mortar 1:4 (1 cement: 4 coarse sand)
Providing and laying Kota stone slab 20mm thick in risers of steps, skirting, dado and pillars laid on
12mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement
slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete.
Providing and laying Granite stone flooring in required sizes, design and patterns, in linear as well as
curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick
stone slab over 20 mm (average) thick base of cement mortar 1: 4 (1 cement: 4 coarse sand) laid and
jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching
shade including providing moulding, rubbing, curing and polishing etc. all complete as specified and
as directed by the Engineer-in-Charge.
Polished Granite stone slab of colour Black, Cherry/ Ruby Red or approved equivalent as per
approved sample. (Basic Rate Rs. 2152/- Per Sqm excl. taxes & CP).
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine
cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size
of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement: 4
coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing, moulding and polishing to edge to give high gloss finish etc complete at all
8.2.3 a) Granite stone slab of all colur and texture except black, cherry/ ruby red. -
i) Area of Slab upto 0.50 Sqm Sqm 69.00 6,184.91 4,26,758.47 -
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform,
8.5 5.8 vanity counter and similar location in marble/ granite/ stone work, including necessary holes for Each 49.00 1,118.16 54,789.91 -
pillar taps etc. including, rubbing and polishing of cut edges etc. complete.
Providing and fixing 1st quality ceramic glazed wall tiles confirming to IS: 15622 (thickness to be
specified by the manufacturer) of apporved sizes, make in all colours, shades except burgundy, bottle
green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over
12mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry
@ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade
Providing and fixing machine cut, mirror/ eggshell polished, Marble stone work for wall lining (veneer
work) including dado, skirting, risers of steps etc., in required design and pattern wherever required,
stones of different finished surface texture, on 12mm (average) thick cement mortar 1: 3 (1 cement :
8.11 5.10 3 coarse sand) laid and jointed with white cement slurry @ 3.3 kg/sqm including pointing with white -
cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all
complete as per Architectural drawings, and as directed by the Engineer-in-Charge.
8.11.1 a) 18mm thick Italian Marble Stone Slab, Perlato, Rosso verona, Fire Red or Dark Emperadore etc. Sqm 59.00 11,898.87 7,02,033.33 -
Cement plaster skirting (up to 30 cm height) with cement mortar 1:3 ( 1 cement : 3 coarse sand),
finished with a floating coat of neat cement.
Total Carried Over to Summary: - 88,53,202.06 -
6.0 Wood & PVC Work -
Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/
window/ Clerestory windows & other Frames/ Chowkhat comprising of virgin PVC polymer of K value
58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/ wheat
husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints
after applying PVC solvent cement and screwed with full body threaded star headed SS screws having
minimum frame density of 750 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge),
minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to
spread of flame of Class A category with property of being termite/ borer proof, water/ moisture
proof and fire retardant and fixed in position with M.S hold fast/ lugs/ SS dash fasteners of required
dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/ lugs or SS dash
fasteners shall be paid for separately). Frame size 65 x 125mm.
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought
framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length
including painting with enamel paint over a coat of wood primer, applying anti-termite/ bitumen
paint to the wooden surface in contact with walls/ columns etc. complete as directed at site. Clear
height/ lenghth/ width of the frame shall be measured for payment. (hold fast lugs or dash fastener
shall be paid for separately). Note:- Wood shall be as per approved sample and if the wood does not
meet the specification and standard due to any reason including non availability in market, suitable
deduction shall be made in this regard.
9.1.1 a) Second class teak wood. Cum 3.00 1,63,319.55 4,89,958.64 -
Providing and fixing wooden moulded beading to door and window frames with iron screws, plugs
and priming coat on unexposed surface etc. complete :
a) 50 x 20 mm of 2nd class teak wood Metre 287.00 310.47 89,105.88 -
Providing and fixing chowkhat in existing opening in brick/ RCC wall with dash fasteners/ Chemical
fasteners of appropriate size (3 nos on each vertical member of door chowkhat and 2 nos on each
vertical member of window chowkhats), including Cost of dash fasteners/ chemical fastener.
Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid decorative
type flush door shutter of 30 mm thick of required size comprising of virgin polymer of K value 58-60
(Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/ wheat husk) and
non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650
kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive
strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A
26.88.1 6.5 category with property of being termite/ borer proof, water/ moisture proof and fire retardant. WPC Sqm 90.00 5,340.26 4,80,623.18 -
to be laminated with PVC foil of minimum 14 microns thick of approved design pasted with hot melt
adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with
necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In-
Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately) (DSR
2023, Page No: 342, Item No-26.88.1)
Providing and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) decorative type,
core of block board construction with frame of 1st class hard wood and well matched teak 3 ply
veneering with vertical grains or cross bands and face veneers on both faces of shutters:
9.21.1 a) 35 mm thick including ISI marked Stainless Steel butt hinges (4 Nos.) with necessary SS screws Sqm 113.00 3,123.12 3,52,912.56 -
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of
flush door shutters (over all area of door shutter to be measured).
Providing & Fixing decorative high pressure 1mm thick laminate sheet of plain/ wood grain in gloss/
matt/ suede finish of approved make, shade and colour with high density protective surface layer and
reverse side of adhesive bonding quality conforming to IS: 2046 Type S, including cost of adhesive of
approved quality.
Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of
lever handles of approved quality and sample with necessary SS screws etc. complete.
Providing and fixing chrome plasted bright finished brass door latch of size 300 x 16 x 5mm with
necessary SS screws etc. complete.
Providing and fixing bright finished brass tower bolts, (barrel type) with necessary screws etc.
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
Providing and fixing bright finished brass 100mm mortise latch with one dead bolt and a pair of lever
handles with necessary screws etc complete (best make of approved quality).
Providing and fixing IS: 3564 marked aluminium extruded section body tubular type universal
9.84 6.13 hydraulic door closer with double speed adjustment with necessary accessories and screws etc. each 13.00 1,123.25 14,602.19 -
Providing and fixing bright finished brass hanging type floor door stopper with necessary screws etc
9.92 6.15 Providing and fixing chromium plated brass handles with necessary screws etc. complete. -
Providing and fixing non load bearing fixed frame for fire resistant glazed partition for 120 minutes
fire rating, made out to a profile of dimension 60 mm x 70 mm of 1.6 mm thick galvanised steel sheet
as per test evidence suitable for fixing fire rated glass for 120 minutes of both integrity & radiation
control (EW120) & minimum 20 minutes of insulation (EI20).The profile has to be fixed to the
supporting construction by means of anchor fasteners of size M10 x 80, every 150 mm from the
edges and every 500 mm (approx) c/c. Linear measurement of frame shall be measured for payment.
The frame shall be filled with mineral wool insulation of density minimum 96kg/ cum and finished
with a approved fire resistant primer or powder coating of not less than 30 micron in desired shade
as per NBC 2016, IS 16231 (Part 3):2016 and directions of Engineer - in- Charge.
Providing and fixing 60mm thick glazed fire resistance door of 120 minutes Fire rating confirming to
IS: 3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory approved by Engineer-in-
Charge, with suitable mounting on door frame, consisting of vertical styles, top rail & side rail 60mm
x 60mm wide and bottom rail of 110mm x 60mm made out of 1.6mm thick G.I. sheet (zinc coating
9.162 6.17 not less than 120 gm/ sqm) duly filled mineral wool insulation having density monimum 96 kg/ cum Sqm 9.00 13,730.41 1,23,573.69 -
and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm of approved make
(minimum 4 nos. each shutter or as approved), including applying a coat of approved fire resistant
primer or powder coating not less than 30 micron etc. all complete as per direction of Engineer-in-
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I.
beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/sqm) of size 20 x 33
mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c,
including applying a coat of approved fire resistant primer/ powder coating of not less than 30
micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per
NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-Charge with glass of required
9.164 6.18 thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and Sqm 1.00 49,901.57 49,901.57 -
minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of
fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be
tested in approved NABL accredited lab or by any other accreditation body which operates in
accordance with ISO/IEC 17011 and accredited labs as per ISO/IEC 17025 for testing and calibration
scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or
Providing and fixing panic bar/ latch (Double point) fitted with a single body, Trim Latch & Lock on
9.139 6.19 back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- Nos. 4.00 9,558.30 38,233.19 -
charge, all complete.
Providing and fixing factory made uPVC glazed/ wire mesh windows/ doors comprising of lead free
uPVC multi-chambered frame, sash and mullion/ coupler (wherever required) extruded profiles
having minimum wall thickness 1.70mm for Series R1 and R2 profiles and 2.10mm for series R3 and
R4 profiles confirming to EN: 12608 in any shape, colour and design duly reinforced with galvanised
mild steel section made of required shape and size as per CPWD specification, uPVC extruded glazing
beads, interlocks and inline sash adapter (wherever required) of appropriate dimension, EPDM
gasket, hardware, SS 304 grade fasteners of minimum 8mm dia with countersunk head, comprising of
matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367: Part 2 to 14,
plastic packers, plastic caps and necessary stainless steels screws etc. Profile of frame, sash & mullion
(if required) shall be mitred cut and fusion welded/ machanically jointed duly sealed at all corners,
including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap
between frame and adjacent finished wall shall be filled with weather proof silicon sealant over
backer rod of approved size and quality, all complete as per approved drawing confirming to CPWD
specifications & directions of Engineer-in-Charge. Section of steel reinforcement and cross sections of
uPVC profiles to be as per design approval by Engineer-in-Charge.
Glazing of plain/ toughened/ laminated/ double glass unit with/ without high performance coating as
per design requirement and confirming to IS: 3548 & IS: 16231 shall be paid seperately. -
Note: Structural design proof checked from a Government Engineering Institute, to be provided by
the manufacturer for: i) Sites with basic wind speed > 45m/sec as per IS 875 - Part 3. ii) Sites with -
structure height more than 20m for all wind speeds.
Two track two panels sliding window with Aluminium channel for roller track, wool pile, nylon rollers
with SS 304 body using R3 series with frame (55mm & above) x (40mm & above) & sash (30mm &
above) x (55mm & above) with zinc alloy (zamak) powder coated handle on every panel along with
multi-point locking system (Height upto 1.8m).
Casement windows single panel (top hung) with SS 304 friction hinges as per size and weight of sash,
multipoint locking sytem, zinc alloy (zamak) powder coated handles - Using R2 series with frame
(39mm & above) x (39mm & above) & sash (39mm & above) x (60mm & above). (Height upto 1.2
Two track two panels sliding door with Aluminium channel for roller track, wool pile, sinc alloy
(zamak) powder coated handle on every panel along with multipoint locking system, ajustable nylon
rollers with SS 304 body using R3 series with frame (55mm & above) x (40mm & above) & sash
(30mm & above) x (74mm & above). (Height upto 2.5m).
Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM
21.3 6.21 rubber/ neoprene gasket etc. complete as per the architectural drawings and the directions of 0
engineer-in-charge. (Cost of beading shall be paid in basic item):
21.3.3 a) With toughened float glass panes of 8.0 mm thickness (weight not less than 20kg/sqm). Sqm 372.00 1,925.56 7,16,309.72 -
Providing and fixing 22mm dia. stainless steel (SS pipe 316L grade) for curtain rods of wall thickness
MR 6.22 1.25mm with two brass brackets fixed with brass screws and wooden plugs etc. wherever necessary Rmt 172.00 804.82 - 1,38,428.42
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
Providing & Fixing 4mm Thick Non-Combustible Corrugated Composite Cladding consisting of
minimum 3mm thick corrugated aluminium core made of minimum 0.30mm thick aluminium coil
sandwiched between two Color Coated Aluminium Skins (each minimum 0.50mm thick). The
Non Combustible Corrugated Composite Panel Cladding sheet shall be coil coated, with high
performance resin coating of approved colour/ shade from Architect on exposed face of NCCP
MR-1 6.23 with a minimum warranty of 10 years and a minimum coating thickness of 25 microns and Sqm 62.00 19,345.00 - 11,99,390.00
polymer (Service) coating on unexposed face of NCCP as approved by Architect, The final color
combination will be decided by the architect in charge. Installation to be done in silicon free
rainscreen MFR system. The cost of the base frame and MFR system is included in the item. The non
combustible panels shall be tested for gross heat of combustion in accordance with ISO 1716, and
manufactured by an ISO 9001 (QMS), ISO 14001 (EMS), and ISO 45001 (OHSMS) certified company.
Providing and executing premium architectural WPC decorative Jali/ panel work, comprising 19
mm thick solid, single-extruded, high-density WPC boards in approved plain white finish,
precision CNC-cut/ routed to approved patterns, suitable for facades, shafts, ducts and partitions.
The boards shall have a minimum density of 700 kg/m³ and Class A1 flame-spread
performance, with inherent resistance to termites, borers, fungus, moisture, water, and fire, along
MR-2 6.24 with good dimensional stability. The panels shall be mounted on a rigid 25 × 25 × 2.0 mm M.S. Sqm 100.00 7,960.00 - 7,96,000.00
SHS support system, treated against corrosion and secured with SS 304 grade hardware,
including all required brackets, supports, cleats, cutting, CNC profiling, edge treatment,
fabrication, wastage, transportation, access/scaffolding, erection, alignment, finishing, labour and
associated accessories, complete to the satisfaction of the Engineer-in-Charge.
Providing and fixing single extruded PVC louvers of approved colour for ceilings, interior wall
panelling, etc. The louver base and PVC film shall be 100% manufactured in India. The wall
thickness of the louver should be minimum 2 mm while the base wall thickness should be
minimum 3 mm. The composition shall include virgin polymer, calcium carbonate, natural
MR-3 6.25 fibres (such as wood powder, rice husk, or wheat husk), and non-toxic additives. Having Class Sqm 143.00 6,765.00 - 9,67,395.00
A category resistance to spread of flame criteria, and tested for gross heat of combustion in
accordance with ISO 1716. Manufacturer Must have ASTM D635 for Fire test Report.
Additionally, the louvers must be termite/borer proof, water/ moisture proof, and fire-retardant.
Providing and fixing 8 mm thick fibre cement board / calcium silicate Premium grade soffit panels of
approved make, colour, texture and finish, fixed to a suitable GI/MS framework including perimeter
channels, intermediate channels, hangers, cleats, screws, jointing compound, joint tape, edge
finishing, necessary cut-outs/openings, scaffolding and all required accessories, complete as per
drawings and specifications and as directed by the Engineer-in-Charge.
Total Carried Over to Summary: - 67,73,822.22 36,05,213.42
7.0 Steel Work: -
Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer using structural steel etc as required - In gratings,
frames, guard bar, ladder, railings, brackets, gates and similar works all complete as per design and
drawing and instructions of Engineer-in-Charge.
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50mm including
16.70.1 7.2 strengthening with 2mm dia wire or nuts, bolts and washers as required complete as per the Sqm 24.00 1,162.83 27,907.99 -
direction of Engineer-in-Charge: Made of G.I. wire of dia 4mm.
Providing and fixing 1mm thick M.S. sheet door with frame of 40 x 40 x 6mm angle iron and 3mm
10.5.1 7.3 M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a Sqm 2.00 6,631.45 13,262.90 -
priming coat of approved steel primer. Using M.S. angles 40x40x6mm for diagonal braces.
Total Carried Over to Summary: - 20,80,045.39 -
8.0 False Ceiling: -
Providing and fixing false ceiling at all height including providing and fixing of frame work made of
special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm
(both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick
with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with
dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle
hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of
angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm
centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered
flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a
direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x
230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm
high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/ partition with
the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval,
including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall
screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered
and square edges of the board with recommended jointing compound, jointing tapes, finishing with
jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer
suitable for board, all as per manufacturer’s specification and also including the cost of making
openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably
fixed, all complete as per drawings, specification and direction of the Engineer in Charge but
excluding the cost of painting: With 12.5 mm thick tapered edge gypsum plain board conforming to
IS: 2095- (Part I) :2011 (Board with BIS certification marks).
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate
false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on
inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm
including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and
of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and
cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between
main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length
600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of
the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a
Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum)
sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230
mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture
in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures,
smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I.
slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners,
4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200
mm centre to centre along main ‘T’, bottom exposed with 24 mm of all T-sections shall be pre-
painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by
Engineer-in-Charge.
Note: Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall
be made for exposed frames/ opening (cut outs) having area less than 0.30 sqm. The calcium silicate
ceiling tile shall have NRC value of 0.5 (Minimum), light reflection > 85%, non-combustible as per B.S. Sqm 152.00 2,465.68 3,74,783.21 -
476 part IV, 100% humidity resistance and also having thermal condutivity <0.043 w/mK.
Total Carried Over to Summary: - 5,32,780.90 -
9.0 Finishing: -
18mm cement plaster in 2 coats under layer 12mm thick cement plaster 1: 5 (1 cement: 5 coarse
sand) finished with a top layer 6mm thick cement plaster 1: 6 (1 cement: fine sand).
Extra for providing and mixing water proofing material in cement plaster work in proportion
recommended by the manufacturers.
Extra for plastering exterior walls of height more than 10 m from ground level for every additional
height of 3 m or part thereof.
Providing and fixing chicken wire mesh 24 gauge & 12 mm mesh and 300 mm width for construction
joints, RCC and masonry joints and chasing in brick work for electrical conduits or water supply pipes
including cement slurry and pegs/nails with nailing machine as required before plastering etc.
5.30 9.5 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. Rm 547.00 89.57 48,995.74 -
15 mm cement plaster on the rough side of single or half brick wall of mix : 1:6 (1 cement : 6 coarse
13.16.1 9.7 6 mm thick cement plaster of mix 1:3 (1 cement : 3 fine sand) Sqm 2,444.00 343.26 8,38,935.02 -
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic
13.83 Compound ) content less than 50 grams/ litre of approved brand and manufacture, including
applying additional coats wherever required to achieve even shade and colour.
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile
Organic Compound ) content.
13.85.3 With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre Sqm 7,366.00 84.49 6,22,335.84
Finishing walls with textured exterior paint of required shade: New work (Two or more coats applied
13.45.1 9.9 @ 3.28 ltr/ 10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/ 10 sqm Sqm 3,011.00 255.46 7,69,196.80 -
with including preparation of surfaces etc. complete in all respect.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and
13.80 9.10 manufacturer, over the plastered wall surface to prepare the surface even and smooth complete Sqm 10,376.00 178.29 18,49,901.70 -
including preparation of surfaces etc. complete in all respect.
Material and labour for finishing with Deluxe Multi surface paint system for interiors and exteriors
using Primer as per manufacturers specifications :
Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @
13.48.2 a) 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and Sqm 230.00 230.06 52,913.80 -
manufacture including preparation of surfaces etc. complete in all respect.
Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied
13.48.3 b) @ 0.90 ltr/ 10 sqm over an under coat of primer applied @ 0.80 ltr/ 10 sqm of approved brand and Sqm 118.00 195.02 23,012.85 -
manufacture including preparation of surfaces complete in all respect.
13.37 9.12 White washing with lime to give an even shade: -
i) New work (three or more coats) Sqm 360.00 44.61 16,061.22 -
Polishing in high gloss/matt finish melamine clear polish on wood work in required color/wooden
shade texture with following process in the sequence as detailed below:
1. The surface to be polished is rubbed with sand paper 80/120 no. and then with sand paper of
2. Applying two coats of sealer with spray gun and allowing sufficient drying time for 1st coat and
2nd coat is allowed to dry for 8 to 12 hrs.
3. On drying of sealer coat, wet rubbing with emery cloth of finer grading with ample water to
remove excess sealer layer and make the surface further smooth after this wet rubbing, then surface
is applied with special grade melamine fillers to fill all the small and big holes/grooves etc. Filler coat -
to be allowed to dry for 4 to 6 hrs on which again a light wet rubbing is done this surface is further
allowed to dry for 12 hrs.
4. On this, 1st coat of melamine polish is applied with spray gun using melamine clear polish and
melamine thinner in required proportion. This 1st coat is allowed to dry for 24 hrs then this dry
surface is again fine wet rubbed smooth, which is further allowed to dry for 12 hrs. The final
melamine polish is applied with compressor pressure spray gun using melamine clear polish and
melamine thinner mixed in required proportion complete as per direction of Engineer-in-Charge.
(Final coat to be done in 1 or 2 layers without gap of time.)
Total Carried Over to Summary: - 96,68,249.06 75,856.23
10.0 Site Development Works: -
Preparation and consolidaion of sub grade with power road roller of 8 to 12 tonne capacity after
excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road
roller including making good the undulations etc. and re-rolling the sub garde and disposal of surplus
earth lead upto 50 metres.
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
Extra for compaction of earth work in embankment under optimum moisture conditions to give
atleast 95% of the maximum dry density (proctor density).
16.3 10.3 Supplying and stacking at site. -
16.3.1 90 mm to 45 mm size stone aggregate Cum 69.00 2,397.41 1,65,421.63
Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in
uniform thickness, hand picking, rolling with 3 wheeled road/vibratory roller 8-10 tonne capacity in
16.4 stages to proper grade and camber, applying and brooming requisite type of screening / binding Cum 69.00 1,196.14 82,533.44
material to fill up interstices of coarse aggregate, watering and compacting to the required density .
Construction of dry lean concrete sub base over a prepared sub-grade with coarse and fine aggregate
confirming to IS: 383, the size of coarse aggregate not exceeding 25mm, aggregate cement ratio not
to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to
16.8 10.4 be less than 150kg/cum, optimum moisture content to be determined during trial length Cum 35.00 4,739.82 1,65,893.65 -
construction, concrete strength not to be less than 10Mpa at 7 days, mixed in a batching plant,
transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne
vibratory roller, finishing and curing etc. complete as per the direction of Engineer-in-Charge.
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The
ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering
16.75 10.5 process and finally finished by floating, brooming with wire brush etc. complete as per specifications Cum 120.00 11,223.66 13,46,838.97 -
and directions of Engineer-in-charge. (The panel shuttering work shall be paid for separately).
Providing and laying factory made chamfered edge Cement Concrete grass paver blocks in footpath,
parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape,
made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick
16.91 10.6 compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into -
the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with
sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand.
complete all as per direction of Engineer-in-Charge.
16.91.2 a) 80mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern. sqm 75.00 1,424.73 1,06,854.75 -
Painting runway/ taxi track/ apron marking with adequate nos. of coats to give uniform finish with
road marking paint of superior make as approved by the Engineer-in-Charge, including cleaning the
surface of all dirt, scales, oil, grease and othger foreign material etc. and lining out complete. New
work (Two or more coats).
Total Carried Over to Summary: - 19,44,224.12 -
11.0 Waterproofing; -
Providing & applying terrace slab watrproofing system comprising of 1.2mm thick single-component
polyurethane (PU) membrane combined with 1mm thick PVC membrane on the RCC slab, ensurig
high elongation, tensile strength, and long-term durability, with all surface cleaned to expose hairline
cracks and aggregate texture prior to application.
Providing & applying eco-friendly epoxy primer and two coats of single-component PU waterproofing
MR-6 11.2 with 0.3mm PVC membrane, total thickness > 1.2mm on prepared concrete. Sqm 846.00 0 818.00 - 6,92,028.00
Providing and laying protective screeding for water proofing treatment with cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size).
Providing and laying integral cement based treatment for waterproofing on horizontal surface at all
22.1 11.4 depth below ground level for under ground structures as directed by Engineer-in-charge and -
i) Ist layer of 22 mm to 25 mm thick approved and specified rough stone slab over a 25mm thick
base of cement mortar 1:3 (1 cement : 3 coarse sand) including applying twice (at base and top of
mortar) cement slurry @ 2.2kg/sqm (each time) mixed with water proofing compound conforming to
IS:2645 in the recommended proportion over the levelling course (levelling course to be paid
seperately). Joints sealed and grouted with cement slurry mixed with water proofing compound.
ii) 2nd layer of 25mm thick cement mortar 1:3 (1 cement : 3 coarse sand) mixed with water proofing
compound in recommended proportions.
iii) Finishing top with stone aggregate of 10mm to 12mm nominal size spreading @ 8 cudm/sqm
thoroughly embedded in the 2nd layer.
i) Using rough Kota stone Sqm 60.00 1,731.57 1,03,894.07 -
Providing and laying integral cement based treatment for water proofing on the vertical surface by
fixing specified stone slab 22mm to 25 mm thick with cement slurry mixed with water proofing
compound conforming to IS:2645 in recommended proportions with a gap of 20mm (minimum)
22.2 11.5 between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed -
with water proofing compound and finishing the exterior of stone slab with cement mortor 1:3 (1
cement:3 coarse sand) 20mm thick with neat cement punning mixed with water proofing compound
in recommended proportion complete at all levels and as directed by Engineer-in-charge.
i) Using rough Kota stone Sqm 88.00 2,313.21 2,03,562.73
Bore Packing: All the borehole gaps between concrete surface and pvc pipe of various dia upto the
neck level shall be filled with non-shrink free flow grout - SmartCare GP Grout or approved equivalent
having dual shrinkage compensation property and than apply epoxy primer at perferi of the pipe than
apply two quote of FlexiSeal PU US or approved equiv. coating. Before the bore packing, surface of
the pvc pipe and concrete surface will be made rough and sand will be sprinkled with polymer
Providing & applying two coats of 2-component acrylic cementitious coating followed by food-grade
epoxy coating on the inner side of the tank.
Providing & applying two coats of 2-component acrylic cementitious coating followed by coal tar
epoxy coating on the inner side of the tank.
Providing and placing in position suitable PVC water stops confirming to IS: 12200 for construction/
22.4.1 11.9 expansion joints between two RCC members and fixed to the reinforcement with binding wire before Rmt. 80.00 374.34 29,947.12 -
pouring concrete etc. complete: Serrated with central bulb (225mm wide, 8-11mm thick).
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1: 2: 4 (1
cement: 2 coarse sand: 4 graded stone aggregate of 20mm nominal size) over PVC sheet 1m x 1m x
400 micron, finished with 12mm cement plaster 1:3 (1 cement: 3 coarse sand) and a coat of neat
cement, rounding the edges and making and finishing the outlet complete.
Total Carried Over to Summary: - - 11,59,251.66 21,31,463.00
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
12.0 Rain Water Harvesting: - -
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation
trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and
ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus
excavated soil as directed, within a lead of 50 m., All kinds of soil.
Providing and laying in position cement concrete of specified grade excluding the cost of centering
and shuttering - All work up to plinth level 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from
natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources).
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation
and plinth in:, Cement mortar 1:4 (1 cement : 4 coarse sand)
12 mm cement plaster finished with a floating coat of neat cement of mix 1:3 (1 cement: 3 fine sand)
Boring/ drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in
IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata
chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries
required for the job, all complete as per direction of Engineer -in-charge,beyond 90 metre & upto
150 metre depth below ground level., All types of soil, 300 mm dia.
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C.
top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone aggregate 20 mm
nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone-III) : 8 graded stone
aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3
coarse sand) finished with floating coat of neat cement and making channels in cement concrete
19.7.1.1 12.6 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) finished with a Nos. 9.00 14,590.31 1,31,312.79 -
floating coat of neat cement complete as per standard design :, Inside size 90x80 cm and 45 cm deep
including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover
and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :, With
common burnt clay F.P.S. (non modular) bricks of class designation 7.5.
Providing, laying and jointing of 160mm dia PVC pressure pipe of 10 kgf/ sqcm, specials couplings and
fittings to site of work. Lowering the same in to the trenches and laying true in alignment and
gradient including testing of the pipe line. (excluding the cost of trenching but including the cutting
of pipes for making up the length and making joints. Sanctioned Rate. 0
Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in
23.5 12.8 the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. Cum 34.00 1,724.94 58,648.01 -
Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over
23.6 12.9 the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction Cum 19.00 1,757.45 33,391.46 -
of Engineer-in-charge.
Development of tube well in accordance with IS : 2800 (part I) and IS:11189, to establish maximum
rate of usable water yield without sand content (beyond permissible limit), with required capacity air
compressor, running the compressor for required time till well is fully developed, measuring yield of
well by “V” notch method or any other approved method, measuring static level & draw down etc. by
step draw down method, collecting water samples & getting tested in approved laboratory, i/c
disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools &
accessories etc., all as per requirement and direction of Engineer-in-charge.
Total Carried Over to Summary: 5,57,168.40 78,285.00
13.0 Horticulture Work:
Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable
materials and then disposing of surplus soil, by spreading and neatly levelling within a lead of 50 m
2.1/ DSR 2025 (H&L) 13.1 and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or/ Cum 100.00 139.73 13,972.98 -
and manure before and after flooding trench with water (excluding cost of imported earth, sludge or
Supplying and stacking of good earth at site including royalty and carriage upto 5 km lead complete
(earth measured in stacks will be reduced by 20% for payment).
Supplying and stacking at site dump manure from approved source, including carriage upto 5 km lead
13.3 complete (manure measured in stacks will be reduced by 8% for payment): Screened through sieve of Cum 32.00 577.30 18,473.45 -
I.S. designation 4.75 mm.
Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-
Spreading of sludge, dump manure and/ or good earth in required thickness as per direction of
officer-in-charge (cost of sludge, dump manure and/ or good earth to be paid separately).
2.5/ DSR 2025 (H&L) 13.6 Rough dressing the trenched ground including breaking clods. Sqm 212.70 2.70 574.43 -
2.7/ DSR 2025 (H&L) 13.7 Fine dressing the ground Sqm 212.00 6.58 1,394.01 -
Grassing with selection No. 1 Doob grass including watering and maintenance of the lawn for 30 days
2.10.2/ DSR 2025 or more till the grass forms a thick lawn, free from weeds and fit for mowing including supplying
(H&L) good earth, if needed (the grass and good earth shall be paid for separately) - With Turf Grass.
Uprooting weeds from the trenched area after 10 to 15 days of its flooding with water including
disposal of uprooted vegetation.
Providing & laying of Selection no. 1 Doob grass turf with earth 50mm to 60mm thickness of existing
ground prepared with proper level and ramming with required tools wooden and than rolling the
13.10 surface with light roller make the surface smoothen and light watering the same and maintenance for Sqm 212.00 133.51 28,303.39 -
30 days or more till the grass establish properly, as per direction of the officer-in-charge.
Preparation of mounds of various size and shape by available excavated/ supplied earth in layers not
13.11 exceeding 20 cm in depth, breaking clods, watering of each layer, dressing etc., lead upto 50 meter Cum 12.00 817.48 9,809.74 -
and lift upto 1.5 m complete as per direction of Officer-in-charge.
Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or
sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1
2.14.2/ DSR 2025 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including
(H&L) removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra
good earth if needed to be paid for separately): Holes 90 cm dia, and 90 cm deep
DSR/ MR Item Ref. S. No. Description of Items Unit Quantity DSR Rate (INR) NDSR(INR)
Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the
excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and
mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction
2.13/ DSR 2025 by 20% : one part of stacked volume of sludge or manure after reduction by 8%), flooding with water,
(H&L) filling with earth if necessary, watering and finally fine dressing, leveling etc. including stacking and
disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed,
within a lead of 50 m, lift up to 1.5 m complete (cost of sludge, manure or extra earth to be paid for
Plantation of Trees, Shrubs, Hedge, ground covers and seasonal plants at site i/c watering and
13.14 removal of unserviceable materials as per direction of officer in charge (excluding cost of plant & -
7.11/ DSR 2025 Providing and stacking of Bottle palm ht. 210-240 cm bottom girth 30-35 cm well developed in big
(H&L) HDPE bag as per direction of the officer-incharge.
7.16/ DSR 2025 Providing and stacking of Cassia fistula (Amaltash) height 120-135 cm. in poly bag size 25 cm as per
(H&L) direction of the officer-in-charge.
7.27/ DSR 2025 Providing and stacking of Ficus benjamina (green) height 150-165 cm., bushy with healthy branches
(H&L) and lush green foliage in big size HDPE bag as per direction of the officer-in-charge.
7.34/ DSR 2025 Providing and stacking of Ficus nuda height 120-135 cm. with 6-8 branches and lush green foliage in
(H&L) gunny bag size 25 cm as per direction of the officer-in-charge.
7.44/ DSR 2025 Providing and stacking of Foxtail palm of ht. 240-270 cm bottom girth 35 - 40 cm well developed in
(H&L) big size HDPE bags as per direction of the officer-in-charge.
SHRUBS - - - -
8.28/ DSR 2025 Providing and stacking of Ficus panda of height 90-105 cm. with 10-12 branches and healthy foliage,
(H&L) well formed in cement pots of size 30 cm as per direction of the officer-in-charge.
8.24/ DSR 2025 Providing and stacking of Ficus reginald well branched, bushy of height 60-75 cm. in earthen pots of
(H&L) size 25 cm as per direction of the officer-in-charge.
Providing and stacking Duranta Golden, having ht. 15 cm to 20 cm bushy shape with fresh and
13.22 healthy leaves in 15 cm size of Earthen Pot/ Plastic Pot and as per direction of the officer-in-charge. each 34.00 26.83 912.24 -
6.30/ DSR 2025 Providing and stacking Tradescantia zebrina having in 15 cm size of Earthen Pot/ Plastic Pot and as
(H&L) per direction of the officer-in-charge.
Total Carried Over to Summary: 1,58,637.07 -
Project Name:- Construction of Building Of Canara Bank Residence Building
DETAILED ESTIMATE OF INTERNAL PLUMBING ESTIMATE
S. No. Description
Amount (in Rs.)
1 SANITARY FIXTURES & FITTINGS 10,47,371 8,25,324
2 INTERNAL WATER SUPPLY 27,73,457 86,022
3 SOIL, WASTE, VENT PIPES, RAIN WATER PIPES & FITTINGS. 86,933 14,03,499
GRAND TOTAL (DSR +NSR) 62,22,606.00
GRAND TOTAL (DSR +NSR) 62,22,606.00
Project Name:- Construction of Building Of Canara Bank Residence Building Banglore
Schedule Of Quantity
Total DSR Rate (in MR Rate MR Amount
S. No. DSR 2023 Description Unit DSR Amount (in Rs.)
Quantity Rs.) (in Rs.) (in Rs.)
1.0 SANITARY FIXTURES & FITTINGS
Providing and fixing white vitreous china
extended wall mounting water
closet of size 780x370x690 mm of approved
shape including providing &
fixing white vitreous china cistern with dual
flush fitting, of flushing capacity
3 litre/ 6 litre (adjustable to 4 litre/ 8 litres),
including seat cover, and cistern
fittings, nuts, bolts and gasket etc complete..
Providing and fixing white vitreous china
counter top type wash basin of approved make,
with single or three tap hole, including C.P.
waste coupling, bottle trap, brackets, fixing
with necessary nuts, bolts and washers, 15 mm
C.P. pillar taps, connection to water supply
1.2 MR-1A and waste pipe, including cutting and making Each 48 - 5,014.00 2,40,672.00
good the walls and floors wherever required,
complete in all respects.(Size: 415 x 600 x 175
mm, oval profile)
Providing and fixing Stainless Steel AISI 304
(18/8) kitchen sink as per IS:13983 with C.I.
brackets and stainless steel plug 40 mm,
1.3 17.10 including painting of fittings and brackets, -
cutting and making good the walls wherever
17.10.1 Kitchen Sink With Drain Board
Providing & Fixing of C.P WALL
MOUNTED SWIVEL SPOUT KITCHEN
SINK MIXER with all accessories as per
approved specifications, Material:
Brass,Size(mm):180(L) x 185(W) x
225(D),Spout Length(mm):135,Mounted :
Wall mounted,Series : Rivera , Origin Made In
Providing and fixing 8 mm dia C.P. / S.S. Jet
with flexible tube upto 1 metre long with S.S.
triangular plate to Eureopean type W.C. of
quality and make as approved by Engineer - in -
Providing and fixing CP Brass 32mm size
1.6 17.22A bottle trap of approved quality & make and as Each 48 1,182.26 56,748.26
per the direction of engineer in charge.
Providing and fixing C.P. brass long nose bib
1.7 18.50 cock of approved quality conforming to IS -
standards and weighing not less than 810 gms
18.50.1 15 mm nominal bore Each 937.65
1.8 17.34 Providing and fixing toilet paper holder -
17.34.1 C.P. brass Each 918.22 -
Supply & Installation of Twin Coat
Hook:Material:18-8 S, type-304, stainless
steel,Application:WC Cubicle
Area,Warranty:1 year , Origin Made In India
Providing and fixing C.P. brass angle valve
for basin mixer and geyser points of approved
quality conforming to IS:8931.
Providing and fixing unplasticised P.V.C.
connection pipe with PTMT Nuts, collar and
bush of approved quality and colour.
18.74.2 15 mm nominal bore with 45 cm length Each 216 139.27 30,082.39
Providing & fixing of C.P Towel ring, cost
inclusive of CP flange, fasteners, complete as
per manufacturer recommendation as per
approved specifications , Origin Made In India.
Providing & Fixing of C.P Towel rail with all
accessories as per approved specifications,
1.13 MR-4 with 600 mm length, SS 304, and making good Each 30 - 950.00 28,500.00
the walls wherever required. , Origin Made In
Total DSR Rate (in MR Rate MR Amount
S. No. DSR 2023 Description Unit DSR Amount (in Rs.)
Quantity Rs.) (in Rs.) (in Rs.)
Supply & Installation of S.STEEL SOAP
DISPENSER (HEAVY TRAFFFIC)
Container : 18-8 S, Type-304, Stainless Steel
Material : Non Corrosive Steel, Capacity : 400
ML, Dispense Volume : 2 ML , Origin Made
Providing and fixing white vitreous china
battery based infrared sensor operated urinal
of approx. size 610 x 390 x 370 mm having
pre & post flushing with water (250 ml & 500
1.15 17.80 ml consumption), having water inlet from back Each 9,116.21
side, including fixing to wall with suitable
brackets all as per manufacturers specification
and direction of Engineer-in-charge.
Providing and fixing 75 mm high, 50 mm deep
and 18 mm thick stone slab table rubbed, edges
rounded and polished, fixed in urinal
partitions by cutting a chase of appropriate
width with chase cutter and embedding the
stone in the chase with epoxy grout or with
cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 6 mm nominal
size) as per direction of Engineer-in-charge and
finished smooth.
8.10.2 Granite Stone of approved shade Sqm 4,629.22
Providing and fixing 600x450 mm beveled
edge mirror of superior glass (of approved
1.17 17.31 quality) complete with 6 mm thick hard board Each 48 1,837.08 88,179.72
ground fixed to wooden cleats with C.P. brass
screws and washers complete.
Providing and fixing P.V.C. waste pipe for
1.18 17.28 sink or wash basin including P.V.C. waste -
fittings complete.
17.28.2 Flexible pipe -
Providing and fixing C.P. brass long body bib
1.19 18.51 cock of approved quality conforming to IS -
standards and weighing not less than 690 gms.
18.51.1 15 mm nominal bore Each 24 912.80 21,907.14
Supply & Installation of Auto Closing System
Bib Cock, Range:Pressmatic Tap,Flow Rate
Bar:9.91,2.0 Bar:13.93,3.0 Bar:17.00 , Origin
Providing & Fixing of Soap Dish with all
accessories as per approved specifications of
1.21 MR-7 material 304 stainless steel with chrome plating Each 30 - 578.00 17,340.00
and making good the walls wherever required. ,
Origin Made In India
Supply, installation, testing and commisioning
of Shower system consisting of the following:-
Supply, installation, testing and commisioning
of 15mm C.P overhead shower with shower Each 36 1,358.00 48,888.00
Supply, installation, testing and commisioning
of one bath spout complete including cutting Each 36 2,210.00 79,560.00
and making good the walls wherever required.
Supply, installation, testing and commisioning
of 15mm dia single lever concealed mixer Each 36 - 3,519.00 1,26,684.00
complete in all respect.
TOTAL CARRIED OVER TO
Total DSR Rate (in MR Rate MR Amount
S. No. DSR 2023 Description Unit DSR Amount (in Rs.)
Quantity Rs.) (in Rs.) (in Rs.)
2 INTERNAL WATER SUPPLY -
Providing and fixing Chlorinated Polyvinyl
Chloride (CPVC) pipes, having thermal
stability for hot & cold water supply, including
all CPVC plain & brass threaded fittings, i/c
fixing the pipe with clamps at 1.00 m spacing.
This includes jointing of pipes & fittings with
one step CPVC solvent cement and the cost of
cutting chases and making good the same
including testing of joints complete as per
direction of Engineer in Charge.
Concealed work, including cutting chases and
making good the walls etc.
Providing and fixing Chlorinated Polyvinyl
Chloride (CPVC) pipes, having thermal
stability for hot & cold water supply, including
all CPVC plain & brass threaded fittings,
2.2 18.7 including fixing the pipe with clamps at 1.00 m -
spacing. This includes jointing of pipes &
fittings with one step CPVC solvent cement
and testing of joints complete as per direction
of Engineer in Charge.
Internal work - Exposed on wall -
a) 18.7.1 15mm nominal bore Mtr. 327.67 -
b) 18.7.2 20mm nominal bore Mtr. 382.74 -
Providing and fixing gun metal gate valve
2.3 18.17 with C.I. wheel of approved quality (screwed -
2.3.5 18.17.5 65mm nominal bore Each 1,990.40 -
2.3.6 18.17.6 80mm nominal bore Each 2,975.69 -
Providing and fixing ball valve (brass) of
2.4 18.18 approved quality, High or low pressure, with -
plastic floats complete :
18.18.1 15 mm nominal bore Each 464.84 -
18.18.2 20 mm nominal bore Each 96 528.40 50,726.85
18.18.3 25 mm nominal bore Each 19 530.18 10,073.34
Derrived 32 mm nominal bore Each 19 - 1,789.00 33,991.00
Derrived 40 mm nominal bore Each 3 - 2,382.00 7,146.00
Supplying, fixing, testing and commissioning
of butterfly valve of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked
complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of following sizes as
18.11.5 100 mm dia Each -
Providing and fixing motorized valve with
2.6 MR-9 sensor of approved quality, to complete the -
a) 40 mm dia ( Flushing Riser) Each 1 - 19,366.00 19,366.00
b) 50 mm dia ( Domestic Riser) Each 1 - 25,519.00 25,519.00
Providing and placing on terrace (at all floor
levels) polyethylene water storage tank, IS :
12701 marked, with cover and suitable locking
arrangement and making necessary holes for
inlet, outlet and overflow pipes but without
fittings and the base support for tank.
TOTAL CARRIED OVER TO
SOIL, WASTE, VENT PIPES, RAIN
WATER PIPES & FITTINGS.
Providing and fixing soil, waste and vent pipes
Supplying, Installation, Testing and
Commissioning of uPVC pipes type -B
conforming to IS 13592 (1992) for soil, waste
and vent pipes including all fittings rubber ring
type (plain or with access door) e.g. bends,
junctions, cowls, offsets, access pieces,
jointing with rubber ring joints with lubricant
etc. fixed with clamps to walls with cement
concrete 1:2:4 blocks complete in all respects.
(For Soil & Waste Pipe)
a) 75 OD mm Metre - 424.00 -
Total DSR Rate (in MR Rate MR Amount
S. No. DSR 2023 Description Unit DSR Amount (in Rs.)
Quantity Rs.) (in Rs.) (in Rs.)
Providing, laying, Jointing, Testing and
commissioning of uPVC pressure pipes of
6Kg/Sqcm pressure rating class 5 (IS : 4985-
2000) including fittings, tees, bends, clamps,
coupling and adaptors supports, and jointing
with solvent joint, testing and necessary earth
3.2 MR-11 work in excavation, backfilling, disposal of -
surplus earth with a lead upto 50m complete,
compaction and consolidation Including laying
cement concrete 1:2:4 alround UPVC pipe
including bed concrete and thrust blocks at
bends as per standard design (For Soil &
Supplying, Installation, Testing and
Commissioning of uPVC, P or S trap of self
cleansing design with / without vent. arm
Setting in cement concrete 1:2:4 mix complete
including cost of cutting & making good the
Wall / Floors wherever required.
Providing and fixing floor drain with jali size
110X50 size inlet and outlet including cutting
and making good the walls and floors
wherever required complete in all respects.
Providing and fixing 125 mm dia, 3 mm thick
Stainless steel grating with frame for floor
traps or drains of required pattern including
cutting and making good the floors complete.
Providing and fixing cast brass Cleanout plug
with suitable insert keys for opening in brass
cap, male threaded joint/reducer with G.I.
socket caulked to Pipe/fittings of CI pipe
including cost of lead joints etc. complete in all
Making khurras 45x45 cm with average
minimum thickness of 5 cm cement concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate of 20 mm nominal size) over
3.7 12.22 P.V.C. sheet 1 m x1 m x 400 micron, finished each 9 340.75 3,066.75
with 12 mm cement plaster 1:3 (1 cement : 3
coarse sand) and a coat of neat cement,
rounding the edges and making and finishing
the outlet complete.450 X 450mm -
Providing and fixing on wall face unplasticised
Rigid PVC rain water pipes conforming to IS :
13592 Type A, including jointing with seal
ring conforming to IS : 5382, leaving 10 mm
gap for thermal expansion, (i) Single socketed
12.41.1 75 mm diameter Metre 284.25 -
Providing and fixing to the inlet mouth of rain
3.9 12.44 water pipe cast iron grating 15 cm diameter Each 9 62.49 562.45
and weighing not less than 440 grams.
TOTAL CARRIED OVER TO
Project Name :- Construction of Canara Bank Residence Building Banglore
Detailed estimate of Internal Plumbing Services
S. No. Description
Amount (in Rs.)
1 EXTERNAL SEWERAGE AND STORM WATER DRAINAGE 20,53,367 7,39,107
2 EXTERNAL WATER SUPPLY 4,38,429 10,322
3 RAIN WATER HARVESTING PIT (1 Nos.) 4,77,482
GRAND TOTAL (DSR +NSR) ₹ 37,18,706.52
GRAND TOTAL (DSR +NSR) ₹ 37,18,706.52
Project Name :- Construction of Canara Bank Residence Building Banglore
Schedule Of Quantity
DSR Rate (in DSR Amount (in MR Rate MR Amount
S. No. DSR 2023 Description Unit Total Quantity
EXTERNAL SEWERAGE AND STORM
Excavating trenches of required width for
pipes, cables, etc including excavation for
sockets, and dressing of sides, ramming of
bottoms, depth upto 1.5 m, including getting
out the excavated soil, and then returning the
1.1 2.10.1 soil as required, in layers not exceeding 20 cm
in depth, including consolidating each
deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed,
within a lead of 50 m :
All kinds of soil
Pipes, cables etc. exceeding 80 mm dia. but
not exceeding 300 mm dia
Supplying and laying of following size DWC
SN8 pipe ISI marked along with all
accessories like socket, bend, couplers etc.
conforming to IS 16098, Part II complete with
1.2 MR-1 fitting and cutting,jointing etc.direct in ground
(75 cm below ground level) including
excavation and refilling the trench but
excluding sand cushioning and protective
covering etc., complete as required.
Providing and laying cement concrete 1:5:10
(1 cement : 5 coarse sand : 10 graded stone
1.3 19.2 aggregate 40 mm nominal size) all-round
DWC pipes including bed concrete as per
standard design :
Derrived 300 mm dia. DWC & RCC Pipe Metre 170.5 1795.00 306047.50
Derrived 450 mm dia. DWC & RCC Pipe Metre 55 2099.00 115445.00
Providing and laying non-pressure NP2 class
(light duty) R.C.C.
pipes with collars jointed with stiff mixture of
cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints
etc. complete :
Constructing brick masonry manhole in
cement mortar 1:4 ( 1cement : 4 coarse sand )
with R.C.C. top slab with 1:1.5:3 mix
(1cement : 1.5 coarse sand (zone-III) : 3
graded stone aggregate 20mm nominal size),
foundation concrete 1:4:8 mix (1 cement :
4coarse sand (zone-III) : 8 graded stone
aggregate 40 mm nominalsize), inside
plastering 12 mm thick with cement mortar 1:3
(1 cement: 3 coarse sand) finished with
floating coat of neat cement andmaking
channels in cement concrete 1:2:4 (1 cement :
2 coarse sand : 4 graded stone aggregate 20
mm nominal size) finished with a floating coat
of neat cement complete as per standard
Inside size 90x80 cm and 45 cm deep
including C.I. cover with frame (light duty)
455x610 mm internal dimensions, total weight
19.7.1.1 of cover and frame to be not less than 38 kg Each 50 14590.31 729515.50
(weight of cover 23 kg and weight of frame 15
kg) : 19.7.1.1 With common burnt clay F.P.S.
(non modular) bricks of class designation 7.5
19.8 Extra for depth for manholes :
19.8.1 Size 90x80 cm
With common burnt clay F.P.S. (non modular)
bricks of class designation 7.5
DSR Rate (in DSR Amount (in MR Rate MR Amount
S. No. DSR 2023 Description Unit Total Quantity
Providing and fixing square-mouth S.W. gully
trap class SP-1 complete with C.I. grating
brick masonry chamber with water tight C.I.
1.10 19.4 cover with frame of 300 x300 mm size (inside)
the weight of cover to be not less than 4.50 kg
and frame to be not less than 2.70 kg as per
standard design :
19.4.2 150 x 100mm size P-type
With common burnt clay F.P.S. (non modular)
bricks of class designation 7.5
Making connection of drain or sewer line
with existing manhole
including breaking into and making good the
walls, floors with cement concrete 1:2:4 mix (1
cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) cement
plastered on both sides with cement mortar 1:3
(1 cement : 3 coarse sand), finished with a
floating coat of neat cement and making
necessary channels for the drain etc. complete :
19.21.2 For pipes 250 to 300 mm diameter Each 2 1053.84 2107.68
19.21.3 For pipes 350 to 450 mm diameter Each 2 1517.75 3035.50
TOTAL CARRIED TO SUMMARY 2053366.72 739106.50
2 EXTERNAL WATER SUPPLY
Providing and fixing Chlorinated Polyvinyl
Chloride (CPVC) pipes, having thermal
stability for hot & cold water supply including
all CPVC plain & brass threaded fittings This
includes jointing of pipes & fittings with one
step CPVC solvent cement, trenching, refilling
& testing of joints complete as per direction of
Engineer in Charge.
18.9.3 25 mm nominal dia Pipe Metre 34.5 406.04 14008.49
18.9.5 40 mm nominal dia Pipe Metre 57.5 643.28 36988.76
18.9.6 50 mm nominal dia Pipe Metre 57.5 907.43 52177.11
18.9.7 65 mm nominal dia Pipe Metre 86.25 1913.00 164995.93
18.9.8 80 mm nominal dia Pipe Metre 28.75 2475.05 71157.62
Providing and fixing in position garden
hydrant hose outlet consisting of 25mm ball
valve full bore type with lever and female
screwed ends, tested to 20 Kg/cm2 of
approved quality, including G.I. elbow, G.I.
threaded hose receiver etc. complete.
Providing and fixing enclosed type water
meter (bulk type) conforming to IS : 2373 and
2.3 18.60 tested by Municipal Board complete with
bolts, nuts, rubber insertions etc. (The tail
pieces if required will be paid separately) :
18.60..1 100 mm dia nominal bore Each 1 4144.58 4144.58
Constructing masonry Chamber 30x30x50
cm inside, in brick work in cement mortar 1:4
(1 cement :4 coarse sand) for stop cock, with
C. I. surface box 100x100 x75 mm (inside)
with hinged cover fixed in cement concrete
slab 1:2:4 mix (1 cement : 2 coarse sand : 4
graded stone aggregate 20 mm nominal size),
i/c necessary excavation, foundation concrete
1:5:10 ( 1 cement : 5 fine sand : 10 graded
stone aggregate 40mm nominal size ) and
inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12mm thick, finished
with a floating coat of neat cement complete as
per standard design :
With common burnt clay F.P.S.(non modular)
class designation 7.5
DSR Rate (in DSR Amount (in MR Rate MR Amount
S. No. DSR 2023 Description Unit Total Quantity
Constructing masonry Chamber 60x60x75
cm inside, in brick work in cement mortar 1:4
(1 cement : 4 coarse sand) for sluice valve,
with C.I. surface box 100mm top diameter,
160 mm bottom diameter and 180 mm deep (
inside) with chained lid and RCC top slab
1:2:4 mix (1 cement : 2 coarse sand : 4 graded
2.5 18.33 stone aggregate 20mm nominal size ) , i/c
necessary excavation, foundation concrete
1:5:10 (1 cement : 5 fine sand : 10 graded
stone aggregate 40 mm nominal size) and
inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12 mm thick, finished
with a floating coat of neat cement
complete as per standard design :
With common burnt clay F.P.S.(non modular)
class designation 7.5
Constructing masonry Chamber 60x45x50
cm inside, in brick work in cement mortar 1:4
(1 cement : 4 coarse sand) for water meter
complete with C.I. double flap surface box
400x200x200 mm (inside) with locking
arrangement and RCC top slab 1:2:4 mix (1
cement : 2 coarse sand : 4 graded stone
2.6 18.37 aggregate 20 mm nominal size) , i/c necessary
excavation, foundation concrete 1:5:10 ( 1
cement : 5 fine sand:10 graded stone aggregate
40 mm nominal size) and inside plastering
with cement mortar 1:3 (1 cement : 3 coarse
sand) 12 mm thick, finished with a floating
coat of neat cement complete as
per standard design :
With common burnt clay F.P.S.(non modular)
class designation 7.5
TOTAL CARRIED TO SUMMARY 438428.89 10322.40
RAIN WATER HARVESTING PIT (1
Boring/ drilling bore well of required dia for
casing/ strainer pipe, by suitable method
prescribed in IS: 2800(part 1), including
collecting samples from different strata,
preparing and submitting strata chart/ bore log,
including hire and running charges of all
equipment tools plants and machineries
required for the job, all complete as per
direction of Engineer-in-charge upto 90 m
depth below ground level.
23.1.2 Rockey Strata including Boulders
Supplying, assembling, lowering and fixing in
vertical position in bore well, unplasticized
PVC medium well casing (CM) pipe of
3.2 23.3 required dia, conforming to IS: 12818,
including required hire and labour charges,
fittings and accessories etc all complete for all
depths as per direction of Engineer-in-charge.
23.3.1 100 mm nominal size dia. Metre 100 768.10 76810.05
Supplying, assembling, lowering and fixing in
vertical position in bore well, unplasticized
PVC medium well screen (RMS) pipe with
3.3 23.4 ribs, conforming to IS: 12818, including hire
and labour charges, fittings and accessories etc
all complete for all depths as per direction of
Engineer-in-charge
23.4.1 100 mm nominal size dia. Metre 100 784.38 78438.10
Supplying , filling , spreading and levelling
stone boulders of size range 5 cm to 20 cm , in
3.4 23.5 recharge pit in the required thickness for all Cum 7 1724.94 12074.59
leads and lifts all complete as per direction of
engineer - in - charge .
DSR Rate (in DSR Amount (in MR Rate MR Amount
S. No. DSR 2023 Description Unit Total Quantity
Supplying , filling , spreading and levelling
stone boulders of size range 5 mm to 10 mm ,
in the recharge pit over the existing layers of
boulders in required thickness for all lead and
lifts all complete as per direction of engineer -
Supplying , filling , spreading and levelling
coarse sand of size range 1.5 mm to 2 mm , in
3.6 23.7 the recharge pit in required thickness over Cum 7 1757.45 12302.12
gravel layer for all leads and lifts all complete
as per direction of engineer - in - charge .
Gravel packing in tube well construction in
accordance with IS: 4097, including providing
gravel fine/medium/coarse in required grading
and sizes as per actual requirement all
complete as per direction of Engineerin-
Development to tube well in accordance with
IS: 2800(part 1) and IS:11189 to establish
maximum rate of usable water yield without
sand content ( beyond permissible limit) with
required capacity air compressor, running the
compressor for required time till well is fully
developed measuring yield of well by “V”
notch method or any other approved method,
3.8 23.12 measuring static level & draw down etc. by Hour 12 1239.67 14875.99
step draw down method collecting water
samples & getting tested in approved
laboratory, i/c disinfection of tube well, all
complete including required hire & labour
charges of air compressor tools & accessories,
etc. all, as per direction of engineer - in -
Providing and fixing suitable size threaded
mild steel cap or spot welded plate to the top
of bore well housing/ casing pipe removable as
per requirement all complete for bore well of :
Providing and fixing M.S clamp of required
dia to the top of casing/ housing pipe of tube
3.10 23.14 well as per IS:2800 (part 1), including
necessary bolts & nuts of required size
DSR Rate (in DSR Amount (in MR Rate MR Amount
S. No. DSR 2023 Description Unit Total Quantity
Providing and fixing Bail plug/ Bottom plug of
3.11 23.15 required dia to the bottom of pipe assembly of
tube well as per IS: 2800 (part 1)
TOTAL CARRIED TO SUMMARY 477482.00
Project Name:- Construction of Building Of Canara Bank Residence
Building Banglore
SUB HEAD DESCRIPTION AMOUNT DSR AMOUNT NDSR
SUB HEAD -1.0 PIPING, HYDRANT , SPRINKLER
AND ACCESSORIES SYSTEM FOR BUILDINGS
B SUB HEAD-2.0 FIRE FIGHTING PUMPS 1,22,828.16 78,148.53
GRAND TOTAL FOR DSR AND NON DSR 8,60,743.72
GRAND TOTAL FOR DSR AND NON DSR 8,60,743.72
SQ - 1 Fire Fighting
Project Name:- Construction of Building Of Canara Bank Residence Building Banglore
FIRE FIGHTING ESTIMATE
ITEM CODE RATE AMOUNT
S.NO. NO. DSR 2025 DESCRIPTION OF ITEMS UNIT
QUANTITY DSR NDSR DSR NDSR
A. SUB HEAD -1.0 PIPING, HYDRANT , SPRINKLER AND
ACCESSORIES SYSTEM FOR BUILDINGS
1 27.7 Providing Laying Testing and Commissioning of C class
Heavy duty MS Pipe Conforming to IS : 1239 / 3589
including Fittings like elbows , tees , flanges , tapers ,
nuts , bolts , gaskets etc and fixing the pipe on the wall
/ ceiling with suitable clamp / support frame and
painting with two or more coats of synthetic enamel
paint of required shade complete as required .
2 27.9 Supplying and Fixing Single Headed Internal Hydrant -
Valve with instantaneous gunmetal coupling of 63 mm
dia with cast iron wheel ISI marked conforming to IS :
5290 ( Type A ) with blank gunmetal material cap and
chain as required .
2.1 27.9.1 Single Headed Gunmetal 4 Set 9,357.12 37,428.48
3 27.11 Supplying Fixing Testing and Commissioning of -
butterfly valve of PN 1.6 Rating with Bronze Gunmetal
Sheet duly ISI marked complete with nuts , bolts ,
washers , gaskets conforming to IS : 13095 of following
sizes as required .
4 27.12 Supplying, fixing, testing & commissioning of double
flanged sluice valve of rating PN 1.6 with non rising
spindle, bronze/gun metal seat, ISI] marked complete
with nuts, bolts, washers, gaskets and conforming to IS
780 of following sizes as required : -
5 27.13 Supplying and Fixing orifice plate made out of 6 mm
thick stainless steel ( Grade 304 ) with orifice of
required size to be fitted between flange and landing 6,548.16
valve of external and internal hydrants to reduce
pressure at the outlet to the level of 3.5 kg / sqcm
complete as required .
6 27.14 Providing Installation Testing and Commissioning of -
Non Return Valve of following sizes conforming to IS :
5312 complete with rubber gasket , GI Bolts , Nuts ,
washers etc as required .
7 27.15 Providing Installation Testing and Commissioning of
stainless steel y-strainer fabricated out of 1.6 mm
thick stainless steel, grade 304, sheet with 3mm dia
holes with stainless steel flange. -
8 27.16 Supplying and Fixing 63 mm dia 15 m Long RRL Hose
pipe with 63 mm dia male and female coupling duly
bound with GI wire , rivet etc . Conforming to IS : 636 (
Type A ) as Required . -
8.1 27.16.1 Gunmetal Material 5 Set 6,218.70 31,093.50
9 27.17 Supplying and Fixing First aid hose reel with MS -
Construction Spray painted in Post office red
conforming to IS : 884 complete with the following as
20 mm nominal internal dia water hose thermoplastic -
( Textile Reinforced ) Type - 2 as per IS : 12585
20 mm nominal internal dia gunmetal globe valve and -
Drum and Brackets for fixing the equipments on wall -
Connections from Riser with 25 mm dia stop gunmetal
valve and MS Pipe and socket -
SQ - 2 Fire Fighting - Internal
ITEM CODE RATE AMOUNT
10 NO. 27.18 TOTAL
S.NO. DSR 2025 Supplying and DESCRIPTION
Fixing 63 mmOF diaITEMS
Gunmetal Material UNIT
FF WORKS Short Branch Pipe with 20 mm nominal internal
diameter size nozzle conforming to IS : 903 suitable for
instantaneous connection to interconnect hose pipe
coupling as required -
10.1 27.18.1 Gunmetal Material 4 Set 2,900.16 11,600.64
11 27.19 Supplying and Fixing of Fire brigade connection of Cast
iron body with gunmetal male intantaneous inlet
coupling complete with cap and chain as required for
suitable dia ms pipe connection conforming to IS : 904
14 27.20 Supplying and Fixing Air Vessel made of 250 mm dia 8
mm thick ms sheet 1200 mm in height with air release
valve on top and flanged connection to riser drain
arrangement with 25 mm dia gunmetal wheel valve
with required accessories pressure gauge and painting
with synthetic enamel paint of approved shade as
16 27.22 Providing and fixing of pressure switches in MS pipe line
including connection extra as required. 1 Each 1,903.80 1,903.80
21 NS-1 Providing and fixing of Fire Hose Cabinet size not less
than 2.1 x 1.2 x 0.90 mtr made out of M.S. sheet not
less than 1.5 mm thick having central opening and 4
mm thick glazed glass doors (Two nos.) suitably
marked on the outside 'with the letters "FIRE HOSE"
including necessary locking arrangement and painting
in PO red colour suitable to accommodate, internal
hydrant valve, 2 nos 15 mtr long Hose pipe, branch
pipe, nozzle and fire man's axe. It shall be fixed inside 4 Each - 20,146.69 80,586.77
23 NS-2 Providing and fixing standard firemans axe with
heavy rubber handle. 4 Each - 850.10 3,400.38
24 NS-3 Providing and fixing dial type pressure gauge with
isolation cock and copper pipe on main header Dial
diameter 100 mm celebration 0-16 / sq. cm. 4 Each - 4,019.27 16,077.06
25 NS-4 Providing and fixing Fire Extinguishers (CO2 type
powder ) 4.5 Kg Capacity complete with all
accessories as per manufacturers specifications. 3 Each - 5,625.85 16,877.54
26 NS-5 Providing and fixing Fire Extinguishers (A, B, C type
powder ) 4 Kg Capacity complete with all accessories
as per manufacturers specifications. 3 Each - 2,649.65 7,948.96
27 NS-6 Providing and fixing Fire Extinguishers mechanical
foam type type capacity 9 ltr. complete with all
accessories as per manufacturers specifications. 3 Each - 5,072.14 15,216.41
28 NS-7 Providing and fixing 25 mm dia Inspector Test Valve 25
mm with drain arrangement complete with all
accessories as per manufacturers specifications. 3 Each - 8,242.61 24,727.82
29 NS-8 Providing and fixing Fire Extinguishers Clean Agent
capacity 2 Kg. complete with all accessories as per
manufacturers specifications. 3 Each - 6,858.33 20,575.00
TOTAL CARRIED TO SUMMARY SHEET FOR SUB HEAD A - 4,74,357.08 1,85,409.96
SUB HEAD-2.0 FIRE FIGHTING PUMPS -
4 Supplying, installation, testing and commissioning of
electric driven Terrace Fire Pump suitable for
automatic operation and consisting of following, -
complete in all respects, as required : ( Terrace Fire
Horizontal type, multistage, centrifugal split casing -
pump of cast iron body and bronze impeller with
stainless steel shaft, mechanical seal conforming to IS :
Suitable HP squirell cage induction motor TEFC type -
suitable for operation on 415 volts, 3 phase 50 Hz AC
supply with IP 55 class of protection for enclosure,
horizontal foot mounted type with Class-'F' insulation,
conforming to IS : 325.
M.S.fabricated Common base plate, coupling, coupling -
guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered -
and with anti vibration pads.
NS-9 ELECTRICAL INSTALLATION FOR FIRE PROTECTION
SQ - 3 Fire Fighting - Internal
ITEM CODE RATE AMOUNT
S.NO. NO. DSR 2025 b. 1 No. 32 amps TPN MCB,
DESCRIPTION OF 5.5
ITEMSKW STAR DELTA UNIT
FF WORKS starters with single phase preventer and outgoing
feeder to terrace pump motor. The compartment
shall contain CT operated ammeter of 0-32 amps ,
Single Phase Preventor and indicating lamps with
MCBs for `ON'/OFF`TRIP' status of pump motors.
Cable 3C X 6 Sqmm XLPE CU and Earthing.
Note:Contractor shall include in his rates for providing
level controllers, pressure switches, wiring, cabling
from level controller / pressure switch to panel etc. N0S 78,148.53
complete as required to operate the system
automatic/manual. Pump shall be protected against
TOTAL CARRIED TO SUMMARY SHEET FOR SUB HEAD A 1,22,828.16 78,148.53
SQ - 4 Fire Fighting - Internal
Project Name:- Construction of Residential Building of Canara Bank at Plot No.
222,223, Dollars Colony, RMV Extension - Bengaluru, KA.
INTERNAL ELECTRICAL WORKS (AS PER DSR 2025)
S.NO NAME OF SUB-HEAD
DSR 2025 items Non Scheduled items
1 SUBHEAD- I: DISTRIBUTION BOARD 2,83,388.04 -
2 SUB-HEAD - II : INTERNAL WIRING 43,23,722.46 -
3 SUB-HEAD III - FANS & LIGHT FIXTURES: - 41,39,644.17
4 SUB HEAD - IV : LIGHTNING PROTECTION SYSTEM 2,04,240.12 82,260.00
5 SUB HEAD - V: LIFT 19,20,017.32 -
6 SUB HEAD-IX:FIRE ALARM & CCTV SYSTEM 81,730.02 89,330.00
Project Name:- Construction of Residential Building of Canara Bank at Plot No. 222,223, Dollars Colony, RMV Extension - Bengaluru, KA.
SCHEDULE OF QUANTITIES FOR SUPPLY, ERECTION, TESTING AND COMMISSIONING
INTERNAL ELECTRICAL WORKS (AS PER DSR 2025)
AS PER DSR-2025 AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT QTY.
RATE (RS.) AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
1 SUBHEAD- I: DISTRIBUTION BOARD
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/
1 2.3 recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V,
2 2.4 on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder
painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for
6 2.10 inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc.
Supplying and fixing following rating, double pole, single phase and neutral, 240 volts, residual current circuit breaker
7 2.14 ( RCCB), having a sensitivity current upto 30 milliamperes in the existing MCB DB complete with connections, testing
and commissioning etc as required.
Supplying and fixing following rating, four pole, three phase and neutral, 415 volts, residual current circuit breaker (
8 2.15 RCCB), having a sensitivity current upto 30 milliamperes in the existing MCB DB complete with connections, testing
and commissioning etc as required.
Total carried over to Summary 2,83,388.04 0.00
SUB-HEAD - II : INTERNAL WIRING
1 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulate copper
conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate,
suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated
copper conductor single core cable etc. as required.
Wiring for group controlled (looped) light point/f point/exhaust fan point/ call bell point ( without independent switch
etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit,
and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
3 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper
conductor, single core cable in surface/ recessed medium class PVC conduit as required
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including
4 1.31 providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. Each 291.00 621.30 1,80,798.30
(For light plugs to be used in residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including
5 1.32 providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as Each 114.00 751.26 85,643.64
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug
6 2.18 top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover Each 49.00 2,058.84 1,00,883.16
for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in
recess etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/
7 1.12 recessed medium class PVC conduit alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable Metre 400 425.22 1,70,088.00
for loop earthing as required.Make:KEI,Worldcab,RR Kable,Bonton
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/
8 1.13 recessed medium class PVC conduit alongwith 2 Nos 4 sq. mm FRLS PVC insulated copper conductor single core Metre 100 669.18 66,918.00
cable for loop earthing as required.Make:KEI,Worldcab,RR Kable,Bonton
9 1.38 Supplying and fixing of call bell / buzzer suitable for single phase,230 volt complete as required. Each 12.00 127.68 1,532.16
3 SUB-HEAD III - FANS & LIGHT FIXTURES:
LED Down lighter (SMD Type) (System lumen efficacy ≥120 <135 lm/Watt )
Supplying, installation, Testing & Commissioning of LED Recessed /
surface Down lighter (Round / square/ Rectangular) SMD type of following
body material with PMMA and prismatic diffuser and construction as per IS :
10322 with driver as per the requirement with Driver efficiency >85%,
Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range
-15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with
Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 ,
UGR (Unified Glare Rating) < 19, Flicker free (flicker should
be below 5 %), life time (LED,Driver & electrical circuitry), life time of
minimum 50000 Burning Hours with , 70% of initial Lumen maintained
till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per
ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum
power consumption should not more than the specified rating and Fixture
shall be of relevant BIS standard and trade mark certificate ( T.C.).
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on
housing. OEM must have its own in house NABL lab setup for all
testing facilities for LED fixtures. "complete in all respect i/c
connections with 1.5 sq mm FRLS, PVC insulated copper conductor
single core cable and earthing etc. as required with Minimum 5 year OEM
warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80
Test report from NABL lab for all testing required for LED fixtures as
per BIS shall be submitted. Shape size and CCT shall be as approved by
Engineer-in-Charge as per requirement. (Thermal management: heat sink
of aluminum housing such that LED junction temperature shall not rise
Powder coated die cast /Extruded aluminum Body including trim .
Supply installation testing and comissioning 4ft LED (Light Emitting Diode) tube light system power: 20W, luminous
3 NDSR-1.3 flux of luminaire 2000lm or more, colour temperature of min 5700K , CRI>80, 230V constant current driver, luminaire Each 326.00 1,142.03 3,72,300.95
profile powder coated in white. Protection class I, L = 1175 mm (min),
Supply installation testing and comissioning LED Tube, Wall / Surface / Celling Mounted, 10W(MIRROR LIGHT),
luminous flux of luminaire 900lm, IP 20,1200mm, Direct light emission, 230V, Electronic Control Gear, 5700K, Satin
Diffuser, L=600mm (Min)
Supply, Installation, Testing & Commissioning of LED bulkhead with LED (Light Emitting Diode) system power:
10W, luminous flux of luminaire 800lm, 5700K, cool white, CRI 80, 230V, Direct light emission, white housing, opal
diffuser, integral electronic control gear, Protection class I, IP65, IK08, L=215mm, B=132mm, H=55mm
8 NDSR-1.8 Supply, Installation, Testing & Commissioning of 15W LED WALL BRACKET LIGHT Each 60 1,713.04 1,02,782.47
10 NDSR-1.10 Supply, Installation, Testing & Commissioning of exhaust fan Each 36 2,595.52 93,438.61
Façade Lighting
SITC of 4 feet long RGBW LED Linear Grazer luminaire having made of Extruded anodized aluminum. The luminaire
shall have clear UV Protected polycarbonate finish lenses. The luminaire shall deliver total system lumen output of
2200lumens. The minimum lumen per channel shall be R – 600lm/ G1600lm/ B – 400lm & W – 1300lm. The
luminaire efficacy shall be minimum 65lm/w. Total system wattage shall not exceed 34W. The luminaire shall be
available in architectural optics with choice of beam angles of 10° x 60°, 30° X 60°, 60° X 60°. LEDs used shall be
SMD type only with special lenses. The luminaire shall be able to deliver 2.0fc at 24 ft from the luminaire with a beam
width of 4.1ft in the horizontal plane and 44.4 ft in the vertical plane.To Improve color consistency between all LED
luminaires in a family with the luminaire manufacturer should employ calibrated light measurement device during
manufacturing process which enable to define a common colour gamut for entire family of the LED luminaire using an
algorithm. This should ensure that the color consistency between luminaires is achieved without having to manually
adjust color points on each luminaire. The luminaire connections for data & power shall be done using only single cable
wherein the line voltage merges with control data and delivers both over a single standard cable thus simplifying the
NS-10 installation. The luminaire shall be programmable using 8-bit or 16-bit control with DMX512 protocol as per the Each 11 60,000.00 6,60,000.00
lighting sequence required for desired theme creation. The luminaire dimensions shall not be more than (Height x Width
x Depth) 45.05 x 1260.65 x 42.2 mm and nominal weight shall not be more than 2 kg. The luminaire operating
temperature shall be -40°C to 50°C. The luminaire input voltage shall be 100 – 277 VAC. The luminaire shall have
surge protection of 2KV (DM) & 4KV (CM). The Lifetime shall be ≥ 50000Hrs @ L80. The luminaire shall be
IP66 & IK07 compliant. The luminaire electrical cum data connections shall be done using waterproof
connectors. The luminaire shall be corrasion resistant & shall comply with ASTM B117 standard for >
1,500 hours. The luminaire shall be vibration resistant & shall comply with ANSI C136.31, 3G. The
lighting company/brand/make shall have the following data available online on their webpage product
Catalogues, Polar Diagrams, Cone Diagrams, IES Files, luminaire diagrams, wiring diagrams &
accessories details (if used). The luminaire shall have following approbations: UL/cUL, FCC Class A,
PSE, CE, CQC, RCM, EAC, BIS, UA. Luminaire manufacturer must have In-house NABL accredited
lab toofconduct
rectangular as per
RGBW LED2019 Standard,
architectural floodType test asmade
light having per IS10322,
of pressure"FAT"
die cast before dispatch
aluminium as per
powder coated finish. The luminaire shall have front cover as clear tempered glass. The luminaire shall deliver total
system lumen output of min. 2500lumens. The luminaire efficacy shall be minimum 54lm/w. Total system wattage shall
not exceed 47W. The luminaire shall have beam angle of 10°. LEDs used shall be SMD type only with special lenses.
The luminaire shall be able to deliver 85.3fc at 24 ft from the luminaire with a beam width of 4.1ft in the horizontal
plane and 4.1 ft in the vertical plane. To Improve color consistency between all LED luminaires in a family with the
luminaire manufacturer should employ calibrated light measurement device during manufacturing process which enable
to define a common colour gamut for entire family of the LED luminaire using an algorithm. This should ensure that the
color consistency between luminaires is achieved without having to manually adjust color points on each luminaire.The
luminaire connections for data & power shall be done using only single cable wherein the line voltage merges with
control data and delivers both over a single standard cable thus simplifying the installation. The luminaire shall be
programmable using 8-bit or 16-bit control with DMX512 protocol as per the lighting sequence required for desired
NS-11 theme creation. The luminaire dimensions shall not be more than (Height x Width x Depth) 183.7 x 337.8 x 171.2 mm Each 8 0 70,000.00 5,60,000.00
and nominal weight shall not be more than 4 kg. The luminaire operating temperature shall be -40°C to 50°C. The
luminaire input voltage shall be 100 – 277 VAC. The luminaire shall have surge protection of 2KV (DM) & 4KV
(CM). The Lifetime shall be ≥ 60000Hrs @ L80 with ambient temperature of 25°C. The luminaire shall be
IP66 & IK10 compliant. The luminaire electrical cum data connections shall be done using waterproof
connectors. The luminaire shall be corrasion resistant & shall comply with ASTM B117 standard for >
1,500 hours. The luminaire shall be vibration resistant & shall comply with ANSI C136.31, 3G. The
lighting company/brand/make shall have the following data available online on their webpage product
Catalogues, Polar Diagrams, Cone Diagrams, IES Files, luminaire diagrams, wiring diagrams &
accessories details (if used). The luminaire shall have following approbations: UL/cUL, FCC Class A,
CE, PSE, CQC, RCM. Luminaire manufacturer must have In-house NABL accredited lab to conduct
LM79 as per 2019 Standard, Type test as per IS10322, "FAT" before dispatch as per IS 10322 & IK
Test. The successful bidder must submit the NABL accreditation certificate for Luminaire
SITC of rectangular RGBW LED architectural flood light having made of pressure die cast aluminium with white
powder coated finish. The luminaire shall have front cover as clear tempered glass. The luminaire shall deliver total
system lumen output of min. 1900lumens. The luminaire efficacy shall be minimum 41lm/w. Total system wattage shall
not exceed 47W. The luminaire shall be available in architectural optics with choice of beam angles of 20°, 40°, 60°,
80°, and 10° x 40° (asymmetric). LEDs used shall be SMD type only with special lenses. The luminaire shall be able to
deliver 4.3fc at 24 ft from the luminaire with a beam width of 20.6ft in the horizontal plane and 20.6 ft in the vertical
plane. To Improve color consistency between all LED luminaires in a family with the luminaire manufacturer should
employ calibrated light measurement device during manufacturing process which enable to define a common colour
gamut for entire family of the LED luminaire using an algorithm. This should ensure that the color consistency between
luminaires is achieved without having to manually adjust color points on each luminaire. The luminaire connections for
data & power shall be done using only single cable wherein the line voltage merges with control data and delivers both
over a single standard cable thus simplifying the installation. The luminaire shall be programmable using 8-bit or 16-bit
NS-12 control with DMX512 protocol as per the lighting sequence required for desired theme creation. The luminaire Each 10 0 90,000.00 9,00,000.00
dimensions shall not be more than (Height x Width x Depth) 183.7 x 337.8 x 171.2 mm and nominal weight shall not
be more than 4 kg. The luminaire operating temperature shall be -40°C to 50°C. The luminaire input voltage shall be
100 – 277 VAC. The luminaire shall have surge protection of 2KV (DM) & 4KV (CM). The Lifetime shall be ≥
60000Hrs @ L80 with ambient temperature of 25°C. The luminaire shall be IP66 & IK10 compliant. The luminaire
electrical cum data connections shall be done using waterproof connectors. The luminaire shall be corrasion resistant &
shall comply with ASTM B117 standard for > 1,500 hours. The luminaire shall be vibration resistant & shall comply
with ANSI C136.31, 3G. The lighting company/brand/make shall have the following data available online on their
webpage product Catalogues, Polar Diagrams, Cone Diagrams, IES Files, luminaire diagrams, wiring diagrams &
accessories details (if used). The luminaire shall have following approbations: UL/cUL, FCC Class A, CE, PSE, CQC,
RCM. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79 as per 2019 Standard, Type
test as per IS10322, "FAT" before dispatch as per IS 10322 & IK Test. The successful bidder must submit the NABL
accreditation certificate for Luminaire manufacturer before supply of material. The LED Luminaire shall be BIS
registered. Successful bidder shall submit the following reports before supply of material for approvals LM79 as per
SITC of RGBW LED architectural flood light having made of pressure die cast aluminium with black powder coated
finish. The luminaire shall have front cover as clear tempered glass. The luminaire efficacy shall be minimum 47lm/w
(All channels full ON) & minimum 80lm/w for white light. Total system wattage shall not exceed 100W. The luminaire
shall be with 20° beam angle. If any other specific beam angle is required as per site condition the same shall be
arranged bby the luminaire manufacturer. LEDs used shall be SMD type only with special lenses. The SDCM should be
≤ 2 for white light. The luminaire shall be able to deliver 35.5 fc at 24 ft from the luminaire with a beam width of 8.8ft
in the horizontal plane and 8.4 ft in the vertical plane. To Improve color consistency between all LED luminaires in a
family with the luminaire manufacturer should employ calibrated light measurement device during manufacturing
process which enable to define a common colour gamut for entire family of the LED luminaire using an algorithm. This
should ensure that the color consistency between luminaires is achieved without having to manually adjust color points
on each luminaire. The luminaire connections for data & power shall be done using only single cable wherein the line
voltage merges with control data and delivers both over a single standard cable thus simplifying the installation. The
NS-13 luminaire shall be programmable using 8-bit or 16-bit control with DMX512 protocol as per the lighting sequence Each 10 1,10,000.00 11,00,000.00
required for desired theme creation. The luminaire dimensions shall not be more than (Height x Width x Depth) 285.22
x 647.25 x 196 mm and nominal weight shall not be more than 15 kg. The luminaire operating temperature shall be -
40°C to 50°C. The luminaire input voltage shall be 100 – 277 VAC. The luminaire shall have surge protection of 2KV
(DM) & 4KV (CM). The Lifetime shall be ≥ 60000Hrs @ L80 with ambient temperature of 25°C. The luminaire shall
be IP66 & IK09 compliant. The luminaire electrical cum data connections shall be done using waterproof connectors.
The luminaire shall be corrasion resistant & shall comply with ASTM B117 standard for > 1,500 hours. The luminaire
shall be vibration resistant & shall comply with ANSI C136.31, 3G. The lighting company/brand/make shall have the
following data available online on their webpage product Catalogues, Polar Diagrams, Cone Diagrams, IES Files,
luminaire diagrams, wiring diagrams & accessories details (if used). The luminaire shall have following approbations:
UL/cUL, FCC Class A, CE, PSE, CQC, RCM. Luminaire manufacturer must have In-house NABL accredited lab to
conduct LM79 as per 2019 Standard, Type test as per IS10322, "FAT" before dispatch as per IS 10322 & IK Test. The
successful bidder must submit the NABL accreditation certificate for Luminaire manufacturer before supply of material.
The LED Luminaire shall be BIS registered. Successful bidder shall submit the following reports before supply of
5/10feet leader/jumper cable capable for transmitting power & data together to the architectural façade lighing
Supply of two way protocol converter, the converter can allowing to integrate DMX luminaires with Ethernet lighting
network. It should accepts KiNET and Art-Net input via an Ethernet connection, and transmits DMX light data to up to
four universes of luminaires. The device can be powered over PoE or DC voltage. The unit should have DMX/RDM R
connector. The second 1Gb RJ45 Ethernet port can be used to connect any other application or the next protocol
converter device. Each DMX/RDM port is fully optically and galvanically isolated and can be configured as an in- or
output. All relevant industry standard protocols such as Art-Net, sACN, KiNET, RTTRpl (Blacktrax) are supported
NS-15 and can be processed and converted by the 6 onboard process engines supporting HTP, LTP, Crossfade, Backup, Nos. 1 12,000.00 12,000.00
Switch and Custom merging modes with soft patch functionality. The converter should have 4 x RJ45-DMX (ANSI
E1.11 – 2008 (R2018)), 4x 3-pin pluggable terminal block, 2 x gigabit RJ45, and power connectivity terminal. The
device operating temperature shall be -10 to +60°C, Storage temperature: -10 tot +70°C and Humidity (non-
condensing): 5 to 95% RH. The device housing shall be robust plastic housing, and dimension not greater than 160 x
90 x 40 mm. It shall comply EN55032 class A, EN55035, EN61000-3-2, IEC 62368-1.
Supply, Installation, Testing and Commissioning of Ethernet based controller with following key features - Easy to use
— Featuring Ethernetbased control and automatic lighting system discovery, - Hardware support for medium and large
environments - processing simultaneous light output data for up to 15,000 individually controllable LED nodes,
depending on configuration.
- Improved reliability — Solid-state drives reduce the number of moving parts
- Slimmer profile — Slimmer form factor offers convenient surface mounting, as well as the ability to install in server
racks and racknmount cases.
- Packaged with Light System Composer — Software allowing creation and managing dynamic light shows with fully
customizable effects, multi-layer editing, and unique color palettes.
- Versatile zone usage — Configure and control multiple playback zones, each with up to unique lightshow
- Simplified control access — with Controller Keypad is a wall mounted triggering device that controls light shows and
NS-16 fixture brightness at the touch of a button. Controller should support up to 10 keypads with 8 keys minimum each. Nos. 1 12,000.00 12,000.00
- Automatic playback control — Configure show scheduling based on a specific date, a day of the week, weekdays, or
The features are as follows -
Input Voltage 100 – 220VAC, auto-switching
Power Consumption 180W max
Supported LED Nodes Up to 15,000 LED nodes
Network Data Ethernet protocol* via standard Ethernet switch
Playback Output Light shows containing one or more visual effects
Operating Temperature 32 – 95° F (0° – 35° C)
Operating Humidity 0 – 90%, relative humidity, non-condensing
Certification UL / cUL, FCC, CE, CCC, C-Tick
Environment Indoor / Dry location".
SITC of Ethernet key pad. it must be a compact keypad that activates up to six DMX controller light shows with the
press of a button. The keypad housing will be made of medium matte white plastic. The Keypad shall use Power over
Ethernet (PoE) technology to eliminate the need for a separate power source, allowing for greater placement flexibility,
NS-17 increased reliability, and ease of installation. The operating temperature range shall be - 5 to 50 °C and Humdity shall Nos. 1 14,000.00 14,000.00
be 0 to 90%, non-condensing. The keypad light turns on when a button is pressed. The IP rating shall be IP20. The
device's total power consumption, including the module, shall not exceed 3W. It shall be supplied along with the
necessary communication modules.
4MP @ 25/30fps@1440P (2560 x 1440) Outdoor Bullet Camera with 2.8/ 3.6/6/8/12 mm
fixed lens (as per site requirement)
Unmanaged Network Switches (24 port) Minimum 4/8 nos. 10/100/1000 BASE-T Ethernet
Ports. Uplink port should have sufficient speed to avoid network congestion, preferably
NS-3 network should not be loaded more than 70% at any stage, fully IEEE 802.3 No. 1.00 8,200.00 8,200.00
compliant,Protocols and compliances , The switch should provide all standard protocols
and compliances AND Mounting Shall Be Rackmount, wall or desktop mounting options
1 Mtr Cat 6 patch cord with 23 AWG suitable for Gigabit connection, it should be suitable to
maintain the bending radius as per relevant code.
Supplying, Installation,Testing & Commissioning of 40 " LED Full HD TV Resolution 1920 x
1080 ,Contrast Ratio (Typical) 5000:1,Built-in Speaker (10W + 10W), Magic Clone (to
USB), Auto Source Switching & Recovery, Lamp Error Detection, Super Clear Coating,
NS-5 Temperature Sensor, Plug and Play (DDC2B), Pivot Display, Clock Battery, PIP/PBP, No. 1.00 40,000.00 40,000.00
Video Wall (10x10), Image Rotation, Button Lock, HDCP Support, Smart Scheduling,
Smart F/W update, Built-In MagicInfo Premium-Swith Mounting Brackets as per Technical
Specification complete in all respect.
Project- Construction of Residential Building of Canara Bank at Plot No.
222,223, Dollars Colony, RMV Extension - Bengaluru, KA.
EXTERNAL ELECTRICAL WORKS (AS PER DSR 2025)
S.NO NAME OF SUB-HEAD
DSR 2025 items Non Scheduled items
1 SUB HEAD -I SUBSTATION WORK 5,37,655.92 39,41,354.18
2 SUB-HEAD - II - DG SET WORK - 5,69,241.00
3 SUB HEAD- III : EARTHING 7,19,285.28 -
4 SUB HEAD-IV: CABLE & END TERMINATIONS 6,86,079.36 24,42,110.40
5 SUB HEAD-V : EXTERNAL LIGHTING 2,46,126.00 14,57,327.03
Project- Construction of Residential Building of Canara Bank at Plot No. 222,223, Dollars Colony, RMV Extension - Bengaluru, KA.
SCHEDULE OF QUANTITIES FOR SUPPLY, ERECTION, TESTING AND COMMISSIONING
EXTERNAL ELECTRICAL WORKS (AS PER DSR 2025)
FINAL AS PER MARKET RATE
S.NO DSR ITEMS DESCRIPTION OF ITEM UNIT QTY.
(RS.) AMOUNT (RS.) RATE (RS.) AMOUNT (RS.)
SUB HEAD -I SUBSTATION WORK
NDSR-2.3 HT Panel Main Switchgear Room
Design, manufacture, supply, delivery including supervision during installation, testing and commssioning of 1
panel, 11KV HT VCB switch board with following accessories: type tested Indoor Air insulated 11KV up to
630A, 26.3kA / 40kA (3sec), 3 Phase, metal clad, horizontal draw out type Switchboard with vacuum circuit
a. One No. incoming panel equipped with following:-
630A, 11KV, VCB 25 KA, TP, totally enclosed, air insulated metal clad housing, cassette mounted horizontal
isolation, horizontal drawout type, motorised spring charged, manually operated, trip free, vaccum circuit breaker
(VCB) having double isolation features and control devices complete with mechanical with continous tripping &
closing, coil suitable for 24V DC, shunt trip coil, OFF/ON indicators, mechanical operation counter & provided
with following:
Spring charge / discharge mechanical OFF push buttons for emergency trip (test / service position limit switches
with 6 NO/6 NC breaker auxiliary contacts in service position and The cubicle shall be of LSC 2B (Loss of
Service Continuity) and PM (Partition Class) classes as defined by IEC standard 62271-200. And it shall
comprise three high voltage compartments and one LV cabinet
CT chamber with single wound single phase, dual core cast resin CT, 15VA burden with core-1 for metering (CL-
1) and core-2 for protection (CL-5P10) and of 110/5+5A ratio.
Wireless communication energy sensor that monitors and measures energy and power in real-time is required so
that can count on operational efficiency and uptime.
Microprocessor based relay, IDMT, Time delay with 3 elements for over current (50-200%) and 1 element for
earth fault protection(10-40%) .-1 Set
Antipumping relay & master trip relay- 1 Set
Digital Ammeter with selector switch.-1 Set
A set of breaker ON/OFF/Trip/DC control supply/ Spring Charged indication lamp. 1 Set
Emergency trip push button on front door 1 Set
Limit switches with 6 NO/ 6 NC breaker auxiliary contacts 1 Set
Control:- T-N-C (Trip, Neutral, Close) breaker control switch. 1 Set
Space heater with thermostat for moisture absorption. 1 Set
Suitable for connection to 2 Runs x 3 core x 240 sq.mm. Cross linked polythelene (XLPE) 11KV cables or as
called for. 1 Set
HT Danger Plate 1 Set
Hooter low intensity 24 Volt with acknowledge and reset push button 1 Set
6-window microprocessor based annunciation panel with audio and visual indicator.
Over current & earth fault - 2 windows
Master trip operated - 1 window
Spare - 3 windows
Surge Arrestor, 10KA, Class II 1 Set
Thermal monitoring shall be fitted on HV field cable/busbar connections,The monitoring shall be done by a
battery less sensor that communicates wirelessly using Zigbee Green Power protocol.
Incoming as described above.
630A, 11KV, 25 KA, 3 phase, air insulated Electrolytic grade copper bus bars
c.Feeder panel for, equipped with following :-
1 nos. 630A, VCB 11KV 25 KA, TP, Totally enclosed, air insulated, metal clad housing, cassette mounted
horizontal isolation, horizontal drawout type, motorised spring charged, manually operated, trip free,each
vaccum circuit breaker having double isolation features and control devices complete with mechanical with
continous tripping & closing, coil suitable for 24V DC, shunt trip coil OFF/ON indicators mechanical operation
counter & provided with each feeder following:
Spring charge / discharge mechanical OFF push buttons for emergency trip (shrouded) test / service position
limit switches with 6 NO / 6 NC breaker auxliary contacts in service position.The busbars shall be rated for
continuous current, at 40°C ambient temperature. Temperature rise shall be as per IEC 62271-200.
The bus bars shall be sleeved for full voltage. Sleeve shall be heat shrinkable BTPM type of Reychem / equivelent
make. No PVC sleeving in bus bar for 11KV is acceptable
CT chamber with Dual core, single phase, Single ratio cast resin CT, 15VA burden with core-1 for metering (CL-
.2S) ,core-2 for protection (CL-5P10)
Digital Ammeter with selector switch, shrouded terminals, square size.The busbars shall be located in a separate
metal clad chamber and shall be air insulated. Bus bars shall be extendible on either side
Microprocessor based IDMT instantaneous relay with 3 O/C (50-200%) & one E/F protection (10-40%). To
maintain safety of the Indoor switchgear & Human resources in case of any internal ARC fault and also minimize
the damage, maintenance cost and downtime of the system, the system should have ARC flash protection system
with ACTIVE Arc flash protection
Antipumping relay & master trip relay
A set of breaker ON/OFF/Trip/DC control supply/Trip circuit healthy & R,Y, B phase indication lamps.
Required Auxiliary relays for WTI (Winding temperature indication with alarm & trip)
8-window annunciation panel with audio and visual indication
Over current & earth fault - 2 windows
Winding temperature trip alarm - 2 window
Master trip operated - 1 window
Spare window - 2 1 Set
Emergency trip push button on front door 1 Set/Panel
Limit switches with 6 NO/ 6 NC breaker auxiliary contacts 1 Set/Panel
Control:- T-N-C (Trip, Neutral, Close) breaker control switch. 1 Set/Panel
All control wiring with protection & test terminal block as required. 1 Set/Panel
Space heater with thermostat for moisture absorption. 1 Set/Panel
Cable box suitable for connection for 3C x 240sq.mm 11KV XLPE Al. conductor cable.1 set/pan
HT Danger Plate 1 Set/Panel
75X6mmAl earth bus to be provided for full length of the panel
Outgoing as described above.
HT Panel as described above (1 No.Incoming / 1 No Outgoing Panel) Set 1 6,60,299.51 6,60,299.51
DSR2025-24.8.2 250 kVA Transformer
Supplying, installation, testing and commissioning of
following capacity (continuous loading) BEE 4 Star
rated (Corresponding Level as per BIS amended upto
date of receipt of tender) , 11/0.433 KV step down, 3
Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil
Natural Air Natural) copper wound transformer
(Electrolytic grade 99.9% pure copper, Core made of
first grade Cold Rolled Grain Oriented (CRGO) Core
grade MOH or better, suitable for out door/indoor
applications with Offload Tap Changer/ On Load Tap
Changer (OLTC) ( below 500 KVA offload and above
500 KVA On Load Tap Changer) on HV side having
AVR relay and Remote Tap Changer Control (RTCC)
for automatic sensing of incoming voltage, automatic
operation of OLTC and facility for remote and manual
operation of OLTC HV side in range of +5% to -15%
in steps of 2.5%, having cable end boxes on HV side
suitable for 3x300 sq.mm XLPE cable of 11 KV grade,
including bus trunking arrangement on LV side
including supplying and laying of copper conductor
multicore control cable from transformer to HT
breaker/panel for safety tripping, complete with all
accessories and safety provisions as per relevant IS
Code including first filling of filtered dehydrated oil, i/c
supplying and grouting of suitable M.S. Channel with
all accessories and transformer shall be confirming to
IS : 2026 (Part 1 to Part 5), IS : 1180 and as per
CPWD specifications complete in all respects etc as
required at site. The maximum flux density in any part
of the core and yoke at rated voltage and frequency
shall be such that the flux density with + 12.5 percent
combined voltage and frequency variation from rated
voltage and frequency does not exceed 1.9 Tesla. The
permissible temperature-rise shall not exceed 35 0C
for oil and 40 dg. C up to 200 KVA and 40 0C for oil
and 45 0C for above 200 KVA for winding. Inside of
tank shall be painted with varnish or liquid resistant
paint. For external surfaces one coat of thermo setting
powder paint or one coat of epoxy primer followed by
two coats of polyurethane base paint shall be used
IS: 1180 (Part 3) shall be referred to for paint
thickness for normal to medium corrosive atmosphere.
For highly polluted atmosphere and special application
external paint work shall be as per direction of
Engineer-in-Charge. Design ambient condition : a) air
temperature 50 0C, b) Relative Humidity 90 % Max,
c) Seismic Zone as per location of site, d) Altitude as
per location/site. Noise level Shall not exceed limits as
per NEMA TR-1 with all accessories running
measured as per IEC 551 / NEMA standard. The
transformer should have QR code which should
contain drawing, test report OEM manual, Geo- Tag of
manufacturing location etc. Marking Each transformer
shall be provided with rating plate made of anodized
aluminium/ stainless steel material securely fixed on
the outer body, easily accessible, as per IS: 1180
Part-3. The entries on the rating plate shall be
indelibly marked.
Fitting and Accessories : The following fittings shall
be provided:- a) Two earthing terminals with the
earthing symbol b) Oil level gauge indicating oil level
at minimum, 30°C and maximum operating
temperature; c) Air release device (for non-sealed
type transformers) d) Rating and terminal marking
plates; e) Silica gel breather f) Drain-cum-sampling
valve (¾″ nominal size thread, IS 554) preferably steel
with plug for three phase transformers;
24.8.2 250kVA transformer Each 1 537655.92 537655.92
MR -1 Supply, Installation, testing and commissioning of 100 AH capacity, 24V DC maintenance free SMF Batteries in fully charged
condition, including painted MS stand & spill proof plastic trays etc.complete as required as per specifications.
MR-2 Supply, Installation, Testing & Commissioning of Battery Charger Unit with provisions of "Boost Charging" and "Float
Charging", suitable for 240V, single phase, AC, 50Hz supply system & 24V DC including providing required MCB for DC No 1 23,477.32 23,477.32
supply distribution to panel complete as required.
MR-3 Supply and fixing in position the approved "shock treatment charts" framed in teak wood frame and covered with glass in front
as required in two languages (Hindi & English)
MR-4 Supply & fixing of Mimic diagram for overall schematic of power distribution complete as required. Set 2 7,336.66 14,673.32
MR-5 Supply and fixing in position the best quality "Danger Boards" of approved shape and size as specified by Local Electricity
Authorities written in English and Local languages.
MR-6 Supply & Laying of non skid Electro mat 1 mtr wide and 3.0 mm thick 11 KV grade conforming to IS 15652 as required
including cutting to required length complete as per requirement of local electricity authorities.
MR-7 Supply of fire buckets 5 nos. 15 litre capacity duly filled with fine sand and fixed on an angle iron frame as per requirement of
local authorities. The fire buckets shall be painted red from outside and white from inside, including lettered as FIRE with Set 1 9,537.66 9,537.66
white colour with extra handle at bottom.
MR-8 Supply & Laying of non skid Electro mat 1mtr wide and 2.0 mm thick 11 KV grade IS 15652 as required including cutting to
required length complete as per requirement of local electricity authorities.
MR-9 Supply of Rubber hand gloves 11 KV grade, as per IS 4770-1968. Pair 5 1,760.80 8,803.99
MR-10 Supply of standard first aid box as approved by Indian red cross society/ St.John Ambulance Brigade and conforming to IS
MR-11 Supply & Installation of Earthing Trucks (Casette type) of same Make as HT Panel complete as required. Set 2 176079.87 3,52,159.74
MR-12 Supply, Receiving, shifting, laying, testing and commissioning of following 1100V grade PVC insulated armoured copper
conductor control cables on existing cable tray/ trench as per specifications including of all clamps/ saddles/screw and cable
identification tags etc. complete as required including termination of the following sizes of PVC insulated Copper conductor
cable including providing terminal lugs,single compression gland , crimping the joints ,providing insulation tape,effecting
terminal connections to the equipment.(For HT Panel controls, Transformer Protection, PLC controls.
A a. 2C X 2.5sq.mm Cu. Cable RM 60 513.57 30,813.98
C c. 2C X 1.5sq.mm Cu. Cable RM 60 418.19 25,091.38
NDSR-2.4 APPROVAL / LIASIONING WORK WITH STATUTORY AUTHORITIES :
(i) Charges for Liasioning with State Electricity Board for getting approvals, clearances for load sanction and
(i) obtaining connection etc. Complete for energising the installation with State Electricity Board power as required.
The charges shall broadly include but not limited to following and as per SCC.
MAIN LT PANEL as per IEC 61439-1&2 and IEC 61641 for 0.3 sec min
Suppy , installation, testing, Design, manufacture, supply inspection, Handling, Assembling, Affecting Proper
Connections, Testing and commissioning of 1.6/2mm CRCA sheet steel fabricated cubical type Main L.T. Panel
with PLC base (INTER LOCKING MAINS , D.G. Supply & Bus Couplar), Floor Mounting, Dust & Vermin
Proof, Front Operated Construction, Enclosure IP42 Class after proper treatment with 7 tank process with
top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and
lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq.
mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4
core Aluminium Bus Duct as required.
All ACB Shall have Zone selective interlocking and LCD display for Current, Voltage & Energy metering and
trip cause history, EDO Type with Microprocessor based release & Icu=Ics=Icw
The electronic trip unit shall have the following adjustable „pick-up‟ settings for protection characteristics where
specified. It shall be possible to configure protection characteristics based on adjustable time delay settings. a.
Overload Protection [L] (adjustability 40% to 100% of breaker rating), with option to deactivate protection for
special application. b. Short Circuit Protection [S] (1.5 times to 10 times overload setting), with time delay
adjustability up to 0.5s c. Instantaneous Protection [I] (similar in pickup range to short circuit settings) d. Ground
fault protection (G) - current adjustable up to 1 x In, with an option to deactivate protection, time delay
adjustability up to 1s.
All EDO ACB shall have ready to close indication on panel door.
There shall 96X96 display Meter for each outgoing for display of all parameters like V,I,Pf, load profile etc.
All ACB Shall have communication port to provide status (ON/OFF/TRIP) to software or BMS, Required
hardware need to consider.
Circuit breakers shall comply with definitions given by standard IEC 61000-4-4 (Electrical fast transients) on
Trip causeto Electromagnetic
context and recordscompatibility (EMC) at fingertips through mobile app / software or trip unit
should be accessible
display. Any additional mobile app/ software shall be offered by default without any additional cost. Following
breaker health and diagnostics information shall be available. a. Trip cause details and interrupted current at the
time of fault b. Last 30 trip records with time stamp c. Overload and ground fault pre alarm d. Trip counter e.
Real time RMS current measurements, unbalance current, maximum current etc.
All ACB shall have roatable terminal adobters on input and output side & adjustable Neutral (OFF, 50%, 100%)
All ACB release shall have Over temperature protection & Indication
All ACB release shall have continious rated triping and closing coils & Dual Core Rogowski CT for metering
and protections & No derating till 55 deg C
All Incomer ACB Should be should be communicable on software platform with on/off/trip status.
Cable alley shall have a sensor capable of monitoring the cable overheating situations leading to fire or fire
hazard. This is required to provide protection against fires arising out of cable alleys because of loose connections
or ageing. This sensor shall be capable of analyzing gas and particles in the air and sending alerts before any
smoke or insulator browning occurs.
All electronic components in the trip unit shall withstand temperatures up to 105 °C. If temperature exceeds
105°C, there shall be provision for a visible alarm on LED
ACB‟s electronic trip unit shall be equipped with a self-test continuously check healthiness connection between
the electronic trip unit, the current transformers and the actuator.The self-test will be of positive logic and visible
LED indication in case the self-test occurred correctly and the extinction of the LED in case the self-test failed.
All MCCB shall have Built-in μP based trip unit having protection functions LSIG. Variable current setting for
L,S,I and G and variable time delay setting for L,S and G. Neutral O/L protection possible with 3P MCCB (with
All meter at incomer level shall have minimum 128 sample per cycle,Acuuracy class 0.2s and compliance to
IEC 62053-22 for active energy and IEC 62053-24 for reactive energy measurement, should be capable of
Individual Harmonics measurement up to 63rd and compliance to relevant IEC standard IEC 61000-3. should be
capable for 4 quadrant measurement , Including Demand & should be capable of generating onboard alarms for
various critical conditions.
All MCCB shallVariable setting of LSIG type trip unit
Manufacturer should provide the Discrimination cordination study upto the bus fault level for all ACB/MCCB.
All starter feedrs shall have MPCB as S/C protection device with built in O/L relay and Contactor (As per type 2
Co-Ordination chart of OEMs)s need to be selected as per Type -2 coordination cahrt of respective OEMS.
GA drawings shall be got approved from Owners / Architects / Consultants before fabrication.The panel has to be
specifically fabricated as per the space available at Site. The Existing Column Positions Will also be Considered.
LT PANELS & DISTRIBUTION PANELS
The contractor shall consider the following details in their item rates, wherever required:
1 Supporting rigid steel framework.
2 Cubicle type, 14 gauge CRCA sheet steel enclouser, close door operation for all panel breaker.
3 Complete with interconnections and distribution bus bars.
4 Proper bonding to earth.
Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its
5 circuit diagram.
6 Providing cable clamps / supports within distribution boards cable alley.
7 TPN ACB‟s / MCCB‟s shall mean 3 pole ACB‟s / MCCB‟s with adequate size of neutral link.
8 All MCB‟s shall be of minimum 10 KA breaking capacity.
9 All motor feeders MCCBs shall be of motor duty.
10 Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.
11 Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.
12 IP 42 for indoor panels.
13 IP 54 for kitchen and laundry panels.
14 IP 55 for outdoor panels
15 All MCCB‟s shall be provided with operating mechanism for door interlock.
Current density of aluminium shall be 1 sq mm for 1.0 amps for rated current of bus bars and current density of
16 copper shall be 1 sq.mm for 1.25 amps for rated current of bus bars.
17 Tinned copper earth bus shall be provided through out the length of each board.
All measuring instruments (Meters) shall be of digital electronic with LED of approved make and compatible
19 All hinged door shall be earthed through 4.0 sq mm tinned braided copper wire.
20 All panels shall have provision of the following:
21 Pad locking of Switch board doors.
22 Pad locking of MCCB‟s handles in “OFF” Position.
23 Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided
24 All MCB‟s used for protection of resistive and lightly inductive load shall be type “B” characteristic and
inductive (motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D
characteristic.
25 All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier
26 All PTs / control transformer shall be provided with centre tap earth secondary.
27 All DOL & Star-Delta Starters shall be provided with SPPR (single phase preventor relay) and 2 nos. of
Aux.Contacts for Remote operation/monitor.
28 The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more than two nos. of
cables are terminated in the breakers.
29 Readymade 16 SWG Sheet steel Enclosure with cutout For MCBs
30 The breaking capacity of MCCB‟s are mentioned panel wise. All MCCB‟s shall be with thermal magnetic
releases upto 250 amps and miroprocessor based above 250 amps capacity, unless specified otherwise.
31 ACB shall comply with standards IS/IEC 60947-1 & 2
32 ACB shall have a rated operational voltage of 415V AC, rated insulation voltage of 1000 volts AC, rated impulse
voltage of 12kV.
33 ACB shall have a Ready to close mechanism preferably having a ready to close mechanical indication on front of
ACB. All EDO ACBs ready to close indication contact
34 ACBs upto 3200A shall be provided with top horizontal and bottom vertical terminal adapters on both sides for
proper cable connections/bus duct connections.
35 MCCB shall have a rated operational voltage (Ue) of 415V, insulation voltage (Ui) of 690 V (AC 50/60 Hz) &
impulse voltage (Uimp) of not less than 8kV.
36 MCCBs shall be current limiting type having a double break design
Protection Releases Microprocessor based (PRMB) & Thermal magnetic (PRTM) shall be as described below .
38 There should be provision of close-door operation for LT Panel
Over-current/long time protection range 40% - 100 % with Time setting
short circuit /short time protection range 100% - 1000 % with Time setting
Instantaneous short circuit Protection range 150% - 1200 % with Time setting
Earth Fault Protection range 20% - 100 % with Time setting
ZSI(Zone Selectivity Interlocking)
B Protection Release Microprocessor Based (PRMB-3) For MCCB
Overload protection
short circuit protection
C Protection Release Thermal-Magnetic Based (PRTM) For MCCB
Design, fabrication, assembly, wiring and supply of front operated dead front cubicle type compartmentalised as
per Form 4B, rear access free standing, dust and vermin proof (IP 42 ingress protection) main switchboards
suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for a symmetrical fault level at 415 volts,
fabricated from 2 mm thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and lockable doors
having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on
top and bottom and including lifting hooks and including GI earth strip of required size with 2 nos earthing
terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated
with seven tank process complete with interconnections etc as per specifications, as required and as below.
(Note:The contractor may select the next higher fault rating of MCCB if it is not readily available ,without any
extra cost ,as the figure indicated within the bracket are required maximum fault level of the panel).
NDSR-2.5 MAIN LT Panel
A INCOMER FROM TRANSFORMER
A From 250 KVA Transformer
1 No. 630A 4 pole microprocessor based EDO, ACB(50kA) with integral protection as per PRMB-1 mentioned
i) 1 set of 630/5A, 15 VA, class-.2S CTs for APFC relay
ii) 1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCBs.
iii) 1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
iv) 1 No. (0-630A) Ammeter with ASS with 3 nos. 1250/5A CT's
v) 1Set- of ON/OFF/Trip/ Spring Charged & Trip circuit healthy indicating lamps.
vi) 240 V AC Motor wound spring closing mechanism
vii) 1 - 24 volts DC shunt trip coil
viii) 6 nos NO/NC contacts for remote opening & closing
ix) Terminals to receive XLPE insulated Aluminium cables
x) Class – B transient voltage surge suppression devices suitable for 3 phases as per specification.
xi) Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485
B From 25 KVA DG SET-1
1 No. 150A 4 pole microprocessor based EDO, ACB with integral protection as per PRMB-1 mentioned in Premable
1 set of 150/1A, 15 VA, class-.2s CTs for Metering
1 set of 150/1A, 15 VA, class-5P10 CTs for Protection Relay
1 set of R,Y,B phase indicating lamps each with 3 nos. 2A SP MCBs.
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
1 No. (0-400A) Ammeter with ASS with 3 nos.150/5A CT's
Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485 port
240 V AC Motor wound spring closing mechanism
1 - 24 volts DC shunt trip coil
6 nos NO/NC contacts for remote opening & closing
Terminals to receive XLPE insulated Aluminium cables
Class – B transient voltage surge suppression devices suitable for 3 phases as per specification.
Multifunction meter with display of V,I,PF,Energy,Power, Harmonics up to 15th order & %THD with RS485 port
Emergency Push Button with Each Incomer
DG Sync as per PLC
Electrolytic high conductivity Aluminium three phase and neutral busbars with earthing rated at 800 amps
having a maximum current density of 1 amp per sq mm suitable to with stand symmetrical fault level of 50 kA at
415 volts. The neutral busbar is to be of 50% capacity.
D OUTGOINGS-Bus Section-1
iii) 2 No. 315A TP+NL MCCB(35KA) complete with:
3 nos 400/5A Class - .2S, 15 VA Burden CT's for metering
ON / OFF indicating lamps with MCB as backup protection.
Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of
Accuracy-1 as specified.
iv) 2 No. 160A TP+NL MCCB(50KA) complete with:
3 nos 160/5A Class - .2S, 15 VA Burden CT's for metering
ON / OFF indicating lamps with MCB as backup protection.
Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of
Accuracy-1 as specified.
v) 3 No. 100A TP+NL MCCB(50KA) complete with:
3 nos 100/5A Class - .2S, 15 VA Burden CT's for metering
ON / OFF indicating lamps with MCB as backup protection.
Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of
Accuracy-1 as specified.
v) 3 No. 63A TP+NL MCCB(50KA) complete with:
3 nos 100/5A Class - .2S, 15 VA Burden CT's for metering
ON / OFF indicating lamps with MCB as backup protection.
Digital Three Phase, four wire, multifunction Meter with V, A, KWH, 485 Communication Port, Class of
Accuracy-1 as specified.
LT PANEL DESCRIVED ABOVE Set 1 13,20,599.02 13,20,599.02
NDSR-2.7 MAIN PANEL
1 No. 315amps 4P MCCB(25KA) PRTM with Class-C transient voltage surge suppression device suitable for 3
phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B And ON/OFF phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th
order & %THD) with RS-485 Port.
Sets of 315/5A, CL-1, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
350A TP+100%N Aluminium Bus Bar with colour coded PVC Sleeves
4 Nos. 63 Amp 4P MCCB
15 Nos. 63 Amp 4P MCB
PROVISION OF SPACE FOR 30 NOS METER
LIGHT POWER, PANEL DESCRIVED ABOVE set 1 5,13,566.28 5,13,566.28
NDSR-2.8 LIFT PANEL
1 No. 63amps 4P MCCB(36KA) with thermal Magnetic release (PRTM) with Class-C transient voltage surge
suppression device suitable for 3 phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th
order & %THD) with RS-485 Port.
Sets of 60/5A, CL-.2S, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
100 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
2 Nos. 40 Amp TP MPCB
2 Nos. 40 Amp TP MCB
2 Nos.40 Amp DP MCB
Lift Panel as described above Set 1 1,62,873.88 1,62,873.88
NDSR-2.9 Capacitor Panel (75kVAR)
1 No 160A MCCB TP 50KA
1 Nos. 0 to 440 Volt digital voltmeter with Voltmeter Selector Switch & Protective SP MCB 10KA C Curve
(96mm square) (one for each Incoming Breaker).
3 No. 0 to 160Amp digital ammeter (96mm square) with CT's.
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).
8 Step Automatic Power Factor Correction relay (APFC relay).
160Amp TP busbars of aluminium alloy as per SLD.
1 Nos.125 Amp TP MCCB.
3 Nos. capacitor duty contactor (one for each 50 KVAR capacitor unit with APP type Capacitor bank)
2 Nos.63 Amp TP MCCB.
2 Nos. capacitor duty contactor (one for each 10KVAR ccapacitor unit with APP type Capacitor bank)
3 Nos. 40 Amp TP MCCB.
3 Nos. capacitor duty contactor (one for each 5KVAR capacitor unit with APP type Capacitor bank)
10 sets of push button stations Red and Green for manual operation of capacitor units with auto/manual selector
1 No. Indicating lamp for each 100 / 50/ 10 KVAR capacitor unit to indicate that the unit is 'ON'.
1 No. Toggle switch for changing automatic to manual operation of capacitor units.
Power factor meter.
Capacitor Panel Described as above set 1 2,20,099.84 2,20,099.84
NDSR-2.10 PLUMBING PANEL
1 No. 63amps 4P MCCB(25KA) with thermal Magnetic release (PRTM) with Class-C transient voltage surge
suppression device suitable for 3 phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th
order & %THD) with RS-485 Port.
Sets of 63/5A, CL-.2s, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
80A TPN Aluminium Bus Bar with colour coded PVC Sleeves
6 No. 63amps 4P MCB
6nos suitable starter
PLUMBING PANEL DESCRIVED ABOVE set 1 1,32,059.90 1,32,059.90
NDSR-2.11 EXTERNAL LIGHTING PANEL
1 No. 63amps 4P MCCB(16KA) with thermal Magnetic release (PRTM) with Class-C transient voltage surge
suppression device suitable for 3 phases as per specifications.
METERING & INDICATION for each Incomer
1 set of R,Y,B phase indicating lamps
Multifunction digital meter (consisting of Voltage, Current, Frequency, PF, kWh, kVA, harmonics upto 15th
order & %THD) with RS-485 Port.
Sets of 60/5A, CL-.2s, 15VA CTs for measuring.
Sets of phase indicating lamp with 2A control MCBs.
100A TPN Aluminium Bus Bar with colour coded PVC Sleeves
8 No. 40amps 4P MCB
EXTERNAL LIGHTING PANEL DESCRIVED ABOVE set 1 2,05,426.51 2,05,426.51
Total of Sub-Head - I carried to summary sheet 537656 3941354
SUB-HEAD - II - DG SET WORK
A 25KVA DG Set
Providing, Installing, Testing and Commissioning of 25KVA „Silent Type‟ Diesel Generating set along with
having Prime Power Rating, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for
0.85 Load Factor and consisting of the followings including making necessary civil foundation etc. complete as required:
Diesel Engines:
Diesel engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for delivering required
output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS
10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will
be fitted complete with all the required accessories.
Engine mounted Instrument Panel fitted with
and having digital display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Battery charging indication
(v) RPM indication
(vi) Over speed indication
(vii) Low lub. Oil trip indication
(viii) Engine Hours indication
Synchronous alternator rated at25KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40
Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and
self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class-F/H insulation.
Base Frame & Foundation:
Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary
reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation
arrangement as per recommendations of manufacturer.
Daily service fuel tank of 205 liters capacity respectively fabricated out of 2 mm thick M.S. sheet complete with all
standard accessories and fuel piping between fuel tank and diesel engine with MS class „C‟ pipes of suitable dia. Complete with valves,
level indications & accessories as required as per specifications.
Exhaust System:
Dry exhaust manifold with exhaust silencer and catalytic convertor.
Starting System:
24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial
excitation complete with suitable nos. of batteries (180 AH capacity lead acid type) as required as per
specifications.
NDSR-2.18 Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & Set 1 205000
alternator, extraction, discharging hot air in to the atmosphere as per specifications, For in house power 205000
Generation for Emergency loads suitable for 75KVA
NDSR-2.19 Supplying and fixing Exhaust gas piping of 1x100 dia. welded black MS, B Class pipe conforming to IS:3589 cut to required Set 1 254241
lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral
wool/Rockwool, 50 mm thick wire mesh & aluminum cladding etc., as required as per specifications. 254241
NDSR-2.20 AMF PANEL :-
Fabricating , supplying, installation, testing and commissioning of Automatic Mains Failure Control (AMF panel)
including auto by-pass panel, suitable for 25KVA, silent type DG set complete with relay, timers, set of CTs for metering & protection
and enery analyser to indicate currents, phase and line voltage, frequency, power factor, KWH, KVARH and provision for overload,
short circuit, restricted earth fault , under frequency, control cabling from AMF panel to diesel engine and elsewhere if required, all
complete and inter locking including the following:
(a) 1 No.150AMP., 4 Pole motorised molded case circuit breaker.
(b) Auto/Manual/Test/Off selector switch
(c ) 2 Nos. over voltage relay, 2 nos.reverse power relay and 2 nos. under voltage relay
(d) 3 Sets of Current Transformer 5P10 accuracy for protection and 15 VA class-I for metering
(e )Energy analyzer unit to indicate current voltage frequency power factor and KWH
(f) indication lamps for load on mains and load on set
(g) fuse for instruments
(h) Battery charger, complete with transformer/ rectifier, D.C voltmeter and ammeter, selector switch for trickle,
off and boost and current adjustment.
(i) Main supply failure monitor
(j) Supply failure timer
(k) Restoration timer
(l) Control unit with three impulse automatic engine start/stop and failure to start lockout.
(m) Impulse counter with locking and reset facility.
(n) ON/OFF/Control circuit switch with indicator
(o) Audio/Video annunciation for
(i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v)
Full load/maximum load warning
Total of Sub-Head - II carried to summary sheet 0 569241
SUB HEAD- III : EARTHING
1.0 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure Set 69840.96
5.2 with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. 8 8730.12
2.0 5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry Set 6 57120.84
enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ 9520.14
coke and salt as required.
3.0 5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry Set 8 136836.48
enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ 17104.56
coke and salt as required.
4.0 5.7 Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including Metre 150 10602
connection/ termination with GI thimble etc. as required.
5.0 5.10 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe FRLSom earth electrode including Metre 50 93366
connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
6.0 5.11 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection Metre 150 129105
with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
7.0 5.12 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe Metre 100 35682
from earth electrode including connection with G.I. thimble excavation and re-filling as required.
8.0 5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. Metre 80 1420.44 113635.2
9.0 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. Metre 200 327.18 65436
10.0 5.16 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. Metre 80 95.76 7660.8
Total of Sub-Head - III carried to summary sheet 719285.28 0
SUB HEAD-IV: CABLE & END TERMINATIONS
1.0 10.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as
b 10.1.2 Above 35 sq. mm and upto 95 sq. mm Metre 30 541.5 16245
c 10.1.3 Above 95 sq. mm and upto 185 sq. mm Metre 100 566.58 56658
d 10.1.4 Above 185 sq. mm and upto 400 sq. mm Metre 300 642.96 192888
2.0 10.5 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
in the existing RCC/ HUME/ METAL pipe as required.
b 10.5.2 Above 35 sq. mm and upto 95 sq. mm Metre 50 82.08 4104
c 10.5.3 Above 95 sq. mm and upto 185 sq. mm Metre 50 110.58 5529
d 10.5.4 Above 185 sq. mm and upto 400 sq. mm Metre 80 193.8 15504
3.0 10.6 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
in the existing masonry open duct as required.
b 10.6.2 Above 35 sq. mm and upto 95 sq. mm Metre 100 66.12 6612
c 10.6.3 Above 95 sq. mm and upto 185 sq. mm Metre 100 91.2 9120
d 10.6.4 Above 185 sq. mm and upto 400 sq. mm Metre 100 166.44 16644
4.0 10.8 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of
following size on cable tray as required.
a 10.8.1 Upto 35 sq. mm (clamped with 1mm thick saddle) Metre 100 60.42 6042
b 10.8.2 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) Metre 100 124.26 12426
c 10.8.3 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) Metre 50 157.32 7866
d 10.8.4 Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) Metre 50 257.64 12882
e 10.10 Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, Each 100 68172
bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. 681.72
6.0 22.4 Laying of one number XLPE power cable of 11 KV grade of following size in the existing masonry open duct as
a 22.4.2 Above 120 sq. mm and upto 400 sq. mm Metre 150 166.44 24966
7.0 11.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of
PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
11.0 NDSR-4(C) Supply of LT cable
Supply, following sizes of PVC sheathed PVC/XLPE insulated Aluminium conductor/copper conductor power/
multicore control armoured cable of 1.1 KV grade.
a NDSR-4.1 3.5C X 300 Sqmm Aluminium Cable Metre 100 5586 558613.3845
b NDSR-4.2 3.5C X 240 Sqmm Aluminium Cable Metre 100 4519 451938.3305
c NDSR-4.3 3.5C X 185 Sqmm Aluminium Cable Metre 100 3591 359056.1996
d NDSR-4.4 3.5C X 150 Sqmm Aluminium Cable Metre 100 2891 289064.4517
e NDSR-4.5 3.5C X 120 Sqmm Aluminium Cable Metre 100 2426 242550.0196
f NDSR-4.6 3.5C X 95 Sqmm Aluminium Cable Metre 100 1927 192660.7234
g NDSR-4.7 3.5C X 70 Sqmm Aluminium Cable Metre 50 1482 74100.27822
h NDSR-4.8 3.5C X 50 Sqmm Aluminium Cable Metre 50 1096 54804.85924
i NDSR-4.9 3.5C X 35 Sqmm Aluminium Cable Metre 90 832 74877.96431
j NDSR-4.10 4C X 25 Sqmm Aluminium Cable Metre 30 660 19808.98527
k NDSR-4.11 4C X 16 Sqmm Aluminium Cable Metre 50 524 26191.88052
l NDSR-4.12 4C X 10 Sqmm Aluminium Cable Metre 60 406 24387.06186
m NDSR-4.13 4C X 6 Sqmm Aluminium Cable Metre 50 333 16654.22095
n NDSR-4.14 3C X 10 Sqmm Aluminium Cable Metre 50 371 18561.75286
o NDSR-4.15 3C X 6 Sqmm Aluminium Cable Metre 50 289 14453.22258
p NDSR-4.16 2C X10Sqmm Aluminium Cable Metre 60 406 24387.06186
Total of Sub-Head - IVcarried to summary sheet 686079.36 2442110.397
SUB HEAD-V : EXTERNAL LIGHTING
1) Supply of following sizes XLPE insulated (Heavy duty) Cu conductor armoured cables suitable for working
voltage upto and including 1100 Volts complete as required and as per specifications.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
2 10.1 direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
in the existing RCC/ HUME/ METAL pipe as required.
4) Termination of the following sizes of XLPE insulated Aluminium/ Copper conductor cable including providing
terminal lugs,double compression gland , crimping the joints ,providing insulation tape,effecting terminal
connections to the equipment complete as required.
a NDSR-5.2 2 x 6 sq,mm, Al conductor cable Nos. 32 953.77 30,520.51
a. Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper RM 120
conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene
Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as
b. Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor RM 100
having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required.
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars,
7 15.14 jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as
8) Supply,fixing and laying of Heavy duty PVC pipes complete buried in floor with joints and other accessories as
a) NDSR-5.3 63 mm dia, 2mm thick RM 50 97 4,842.20
Including supply and installation of 6 ways-20A connector & 6A MCB mounted on 6mm thick painted M.S/GI
plate, insulated, and fixed inside the pole suitable for termination of armoured aluminium cable as required and
wiring to Luminaries from the 6A MCB, with 3x2.5 sq.mm. PVC insulated copper, stranded conductor
(P+N+PE) double sheathed wire including terminations.
4 meters high tubular pole with single arm of length 1 meter, smoothly curved making an angle of 10 deg to 15 Nos. 10
deg with the horizontal plane complete as required.
NDSR-5.4B Supply, erection, testing and commissioning of 6 M high Tubular pole as per Technical specifications and with following components :-
Including supply and installation of 6 ways-20A connector & 6A MCB 10KA C Curve mounted on 6mm thick painted M.S/GI plate,
insulated, and fixed inside the pole suitable for termination of armoured aluminium cable as required and wiring to Luminaries from the
6A MCB 10KA C Curve, with 3x2.5 sq.mm. PVC insulated copper, stranded conductor (P+N+PE) double sheathed wire including
6 meters high tubular pole with single arm of length 1.5 meter, smoothly curved making an angle of 10 deg to 15 deg with the Nos. 12 27,146 3,25,747.76
horizontal plane complete as required.
10) LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120
Supplying of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the
requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -
15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency
>85%,THD < 10% as per IEC 61000- 3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80, 5-Star Rating under voltage and
over voltage protection, EMI-EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the
width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver &
electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as
per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI
Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the
specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq
mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year
OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab
for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved
by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that
LED junction temperature shall not rise above 90°C).
11) LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt)
Supplying of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per
the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz,
Operating temp range -15 deg to 50 deg centigrade, internal surge rotection of 5 KV L,N,E as per IEC 61000-4-
5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , 5-Star Rating
under voltage and over voltage protection,EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as
per the application and the project requirementdeg., suitable tilt able fitting, life time (LED,Driver & electrical
circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80
extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) ,
SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the
specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq
mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year
OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all
testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by
Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED
NDSR-5.7 junction
250 watt temperature shall not rise above 90°C). Nos 4 4,175.06 16,700.23
12) NDSR-5.7 Supply,Receiving and fixing in position, effecting proper connections, testing and commissioning of 9W LED 6
13) NDSR-5.8 Supply,Receiving and fixing in position, effecting proper connections, testing and commissioning of 35 W GATE 4
14) NDSR-5.9 Supply, Installation & Commissioning of Solar PV stand alone Street Lighting System comprising of two 37 Wp / one 74 Wp SPV
module, one 12 V, 75 Ah Tubular Plate sealed maintenance free VRLA Gel Battery, one luminaries with inbuilt inverter, dusk to dawn
circuit for automatic switching on & off at dusk & dawn and 24 W LED Light, pole, one charge-regulator, module mounting structure, Nos 4 1,24,723.24 4,98,892.96
Pole mounted Battery box, cables and other fittings along with 5 (five) years guarantee / warranty period (25 years for SPV Module).
15) NDSR-5.10 Supply, installation Testing including civil foundation work & commissioning of fixed type high mast lighting
tower (16 mtr.) with 8 Nos. 300 watt LED flood light fittings for outdoor lighting application.
Total of Sub-Head - V carried to summary sheet 2,46,126.00 14,57,327.03
Project :- Construction of the Residential Building at Plot Nos. 222 & 223, Dollars Colony, RMV Extension,
15 KLD STP MBBR Equipments.
Sl.No DESCRIPTION Unit QTY NDSR NDSR AMOUNT
D/S/I/T/C of a fully functional Sewerage Treatment Plant, all complete, as per
instructions of E/I, including, but not limited to Co-ordinating with any and all
agencies at Site, and ensuring full compatibility with all other works for the same. If
any other items / materials are required, these shall be done without any extra cost.
Design, supply installation testing & commissioning of Sewage Treatment Plant
1 (excluding excavation, backfilling & disposal of surplus earth civil construction work)
for the following duty
Nature of effluent - Domectic Sewage from Toilets/Bathroomss Waste (Drawings &
3 Daily Average Flow - 15 m3/Day (15 KLD MBBR Process)
7 S.Solid - 300 - 450mg/l
8 Oil & Grease - 50mg/l
Sewage discharge after treatment
10 BOD5 - less than 10mg/l
11 COD - less than 40mg/l
12 S.Solid - less than 10mg/l
13 Oil & Grease - less than 5mg/l
All tank will be client scope
Sewage Treatment Plant shall include the following items:
14 Screen Chamber/ Oil & Grease Trap
15 Sewage Equalisation Tank/Sump
16 Sewage MBBR I Tank
17 Sewage MBBR II Tank
18 Secondary Tube Settler Tank
19 Clear/ Soft Water Tank
20 Treated Water Tank
21 Sludge Holding Tank
22 Filter Press - 12" x 12" hydraulic
23 Ultra Violet UV System
24 Chlorine Contact Tank
25 Air Blower, Pumps & Equipments.
26 Water Softner.
27 Ozonation System.
28 Piping Valves etc.
29 Electrical Panel, Cabling .
Supply, installation, testing & commissioning of 2 Nos Stainless Steel 304 perforated
30 corrugated bar screen with suitable lifting arragement ( Size 900 x 900 mm approx) Nos 2.00 ₹ 16,520.00 ₹ 33,040.00
Supply of MS hot dip galvanised puddle flange in accordance to BS to table D as
required to be provided (in the structrual slab & wall) of vrious diameter. Puddle
flanges shall be provided for all the structual component of the STP. The installation
of the puddle flanges shall be carried of by the civil contractor in accordance to civil
GA drawing (to be prepared by the BCD Registered STP contractor) at the required
levels & positionunder the supervision of BCD Registered STP contractor
Supply, installation, testing & commissioning of electronic type level indicator &
32 controller for automatic operation of the system with high/low level alarm complete Set 2.00 ₹ 20,355.00 ₹ 40,710.00
with auxillary NO/NC contcts for BMS connectivity/compatability
Supply, installation, testing & commissioning of sight tube (of 1.5 to 2.5 mtr length)
33 with isolation valve at top/bottom, demarcation on tube & for making the Nos 2.00 ₹ 25,960.00 ₹ 51,920.00
installation complete
Supply, installation, testing & commissioning of non clogging type pumps capabile of
handling solids upto 35mm having CI casing & Bronze impeller complete with all
accessaries, motor of required capacity. Pressure gauge on delivery line with
isolation cock , level controller (with wiring) to control the level of sump
automatically. Pumps shall have following duty.
Sludge Lifting Imhoff Tank To Eqilization Transfer Pump (2 Nos - 1 Working & 1
Flow Rate(Each) - 05- 6 m3/Hr (Sewage Lifting Submersible-Pumps)
(Solid handling size for this pump shall be 35 mm)
35 Sludge Lifting Eqilization Transfer Pump To MBBR I (2 Nos - 1 Working & 1 Stand by)
Flow Rate(Each) - 05- 6 m3/Hr (Sewage Lifting Submersible-Pumps)
(Solid handling size for this pump shall be 35 mm)
36 Sludge Transfer/Recirculation Pump (4 Nos - 2 Working & 2 Stand by)
MBBR I Tank To MBBR II, MBBR II To Clarifier Tank
Flow Rate(Each) - 05- 6 m3/Hr (Sewage Lifting Submersible-Pumps)
(Solid handling size for this pump shall be 35 mm)
37 Sludge Transfer/Recirculation Pump (2 Nos - 1 Working & 1 Stand by)
Clarifier Tank To Sludge Holding Tank
Flow Rate(Each) 05- 08 m3/Hr
38 Sump Pump With SS Body & SS impeller Pump (2 Nos - 2 Working)
Flow Rate(each) - 05-06 m3/Hr
(Solid handling size for this pump shall be 30 mm)
Cost shall be inclusive of uPVC pipe ( for piping submerged in effluent) with MS
39 piping (for piping non submerged effluent Lot 1.00 ₹ 91,037.00 ₹ 91,037.00
Provision of guide ropes to guide submersible pump from upper level to operational
level in sump basin with channels/angle sections shall be made by the STP
The above rate for pumps with CI casing & SS impeller, material of construction
Air diffusion system shall include the following:
2 Nos. Twin Lobe Rotary Air Blowers for Imoff, Equilization, MBBR I & II Clarifier &
SHT (One working & one standby) capable of delivering 10- 20 m3/hr of free air at
40 0.4kg/cm2 driven through “V” belt or directly coupled through flexible coupling to a Nos 2.00 ₹ 90,565.00 ₹ 1,81,130.00
TEFCmotor of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles A/C
Air piping shall comprise of pipes droppers/laterals with MS Header complete with
all fitting such as tees, crosses, plugs, sockets, Elbows, reducer,supporters & clamps,
Puddle flange etc cutting chases and making good.Contractor to submit detailed P& I
indicating there propasal
Non clog type air dispersion system capable of handling 3-5 cfm of air with oxygen
transfer efficiency of 3-4% per/meter water depth. Air dispersion grid shall be
42 assembled in modular form so that they can be replaced / repaired easily from plat 1.00 ₹ 25,960.00 ₹ 25,960.00
form at the top. (Imported fine bubble membrane diffusers for MBBR Tanks and
Coarse Diffusers for Imoff, Equilization, Clarifier & SHT.
43 Air dispersion system shall be provided for Imhoff Tank , Equilization tank, Tube
Setteler, Sludge holding tank & Aeration Tank (MBBR-I & MBBR-II)
Corase Bubbles Diffuser, Size : 150mm Nos 12.00 ₹ 1,504.50 ₹ 18,054.00
Fine Tublar Bubbles Diffuser, SIZE : 63mm X 1000mm, Moc : Epdm Nos 6.00 ₹ 2,165.30 ₹ 12,991.80
Supply, installation, testing and commissioning of MBBR Media Size 16/22 - 06 m3
to be installed in MBBR Tank and Clarifier Settling Media (Tube Settler Media-03 m3-
consider only 4 cum) be installed in Secondary settling tank alonwith suitable sludge
removal arrangement either by pumps or air lifting pumps
Clarifier Settling Media Tube Settler Media-03 m3 Cbm 3.00 ₹ 10,738.00 ₹ 32,214.00
Providing & fixing all piping (as described below) with isolation control valves for
making system complete.
UPVC : Submerged Air Piping
MS : Air piping
PVC Piping : Pumped effluent & tank overflow pipe line
UPVC : Interconnecting pipe line after delivery header of pump/filter LS 1.00 ₹ 43,660.00 ₹ 43,660.00
Supply, installation, testing & commissioning of Lime/Alum/Polyelectrolyte type
46 dosing system comprising of 100 ltrs HDPE/FRP tank with 0-06 lph electronic Nos 1.00 ₹ 27,730.00 ₹ 27,730.00
metering pump with 1/2 hp Agitator System
100 ltrs HDPE/FRP Tank
0-06 lph electronic Dosing Pump
1/2 hp Agitator System For Mixing
Supply, installation, testing & commissioning of horizontal/ vertical centrifugal Filter
Feed Water Pumps CI casing & Bronze impeller along with motor for the pump.
Pressure guage with isolation cock, Isolation valve, NRV on delivery line. Isolation
47 valve, strainer (with by pass) at suction. Mechanical seal, suitable vibration
elimination pad of approved designed, drain pipe with valve (25mm dia). The pump
shall be suitable for 415+10% volts, 3 phase AC Supply.
Capacity : 08-10 m3/Hr
Head : 14- 16 Mtr
Supplying, installing, testing and commissioning of FRP Vessel Filter. Filter shall be
suitable for working pressure of 4.0 kg / cm2 and shall include media, standard
fittings like pressure gauges, sampling cock, rinse drain, vacuum breaker, 1no water
flow meter at outlet complete (flow meter shall be of approved by department of
weights & measures). Including frontal piping and multi port valves.
49 Dual Mulitgrade Ressure Sand Filter 24 72
Dia : 600 mm x 1800 mm height
Filtration PSI 150 Bar: 10.3 Capacity Liter: 3407 Ltr
50 Activated Carbon Filter 24 72
Dia : 600 mm x 1800 mm height
Filtration PSI 150 Bar: 10.3 Capacity Liter: 3407 Ltr
Sludge Loading/Disposal Pump: Screw Type Sludge loading / Disposal pump,
51 complete in all respects and as per specifications. (Sludge Holding Tank To Filter No. 2.00 ₹ 38,055.00 ₹ 76,110.00
Press & Sludge Drying Bed)
52 Filter Press- 12 inch * 12 inch 12 Plates With Hydrolic System- 1 Hp Nos 1.00 ₹ 90,860.00 ₹ 90,860.00
Cake Thikess: 35
Filteration: 39.40
Wet Volume Cake: 315 Ltr
Online Electronically Reading Meters
Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of motor control centre shall be fabricated out of 14 gauge CRCA
sheet steel in form in 3 formation with reinforcement of suitable size angle iron,
channel ‘T’ sections irons and/or flats wherever necessary. Cable gland plates shall
be provided on top as well as at the bottom of the panels. Panels shall be treated
53 with all anticorrosive process before painting as per specifications with 2 coats of red
oxide primer and final approved shade of powder coated paint. 2 Nos. earthing
terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks
shall also be provided in case of large panels. Approval shall be taken for each panel
before fabrication. Galvanised hardware with zinc passivation shall be used in
fabrication of panels.
MCC-1 (STP Motor Control Centre)
100 amps TPN MCCB with the following accessories:
a. 0-500 volts 96 x 96 mm square digital electronic voltmeter with selector switch
shall be protected by 2 amps TP MCB. 1 Set
b. 0-100 amps 96 x 96 mm square digital electronic ammeter with selector switch
and 100/5 amps 15 VA CL: 1 CTs. 1 Set
c. Phase indicating lamps shall be protected by 2 amp SP MCB 3 Sets
100 amps TPN (25 KA) copper bus bar with heat shrinkable insulation sleeves.
As per the STP equipment rating
MCC for all STP equipments/pumps as described in sub head -A. JOB 1.00 ₹ 1,78,180.00 ₹ 1,78,180.00
Total Amount Including Taxes ₹ 17,20,215.80
Total Amount Including Taxes ₹ 17,20,215.80
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
detail.html
html • 0.06 MB
NIT.pdf
Tender Document
Scope of work.pdf
Tender Document
Technical Specification.pdf
Tender Document
Tender Drawings.pdf
Tender Document
GCC for Construction Works 2026.pdf
Tender Document
SCC.pdf
Tender Document
Physical Milestone.pdf
Tender Document
Standard Make.pdf
Tender Document
Soil Test Report.pdf
Tender Document
Integrity Pact.pdf
Tender Document
BOQ.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .