Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.9 LAccepted-AOC RAM SHIV COLONY GALI NO 2 NAIKA CHATNAG ROAD JHUNSI PRAYAGRAJ UP 211019 | PRAYAGRAJ | UTTAR PRADESH | 211019 | ₹19.9 L Quoted ₹22.8 L | L1 | Accepted-AOC Being lowest |
| 2 | L2₹29.3 LRejected-Finance RAJKOT ROAD AIR FORCE STATION HALWARA 141106 PUNJAB | HALWARA | LUDHIANA | PUNJAB | 141106 | ₹29.3 L | L2 | Rejected-Finance Other than lowest |
| Sl No | Description | Qty | Unit | M/S SANGA SINGH AND CO L2 | TARA ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00 | Material & Labour for 'B' check of DG set Cap 10 KVA to 50 KVA of any make any model as per company norms including the following :-
(a) Complete change of engine Oil
(b) Change Engine oil filters
(c) Check throtle linkage
(d) Clean fuel tank
(e) Supply and replace fuel filters
(f) Supply and replace water filters if any
(g) Check and top Coolant
(h) Supply and replace all air filters
(j) Check leaks
(k) Supply and replace Hose Flexible of any size as per site requirement
(l) Supply and replace Clamp V Band as per site requirement
(m) check tightness of V Belts
(n) Supply and replace Hose clamp as per site requuirement
(o) Supply and replace Clamp T Bolts as per site requirement
(p) Supply and replace gasket as per site requirement and testing, complete to the satsifaction of Engr-in-Charge. | 30 | Each Job | 5,499 ₹1.6 L | 4,000 ₹1.2 L |
| 2.00 | Material & Labour for 'B' check of DG set Cap 62.5 KVA to 160 KVA of any make any model as per company norms including the following :-
(a) Complete change of engine Oil
(b) Change Engine oil filters
(c) Check throtle linkage
(d) Clean fuel tank
(e) Supply and replace fuel filters
(f) Supply and replace water filters if any
(g) Check and top Coolant
(h) Supply and replace all air filters
(j) Check leaks
(k) Supply and replace Hose Flexible of any size as per site requirement
(l) Supply and replace Clamp V Band as per site requirement
(m) check tightness of V Belts
(n) Supply and replace Hose clamp as per site requuirement
(o) Supply and replace Clamp T Bolts as per site requirement
(p) Supply and replace gasket as per site requirement and testing complete to the satsifaction of Engr-in-Charge. | 39 | Each Job | 6,499 ₹2.5 L | 6,000 ₹2.3 L |
| 3.00 | Material & Labour for 'B' check of DG set Cap 200 KVA to 320 KVA of any make any model as per company norms including the following :-
(a) Complete change of engine Oil
(b) Change Engine oil filters
(c) Check throtle linkage
(d) Clean fuel tank
(e) Supply and replace fuel filters
(f) Supply and replace water filters if any
(g) Check and top Coolant
(h) Supply and replace all air filters
(j) Check leaks
(k) Supply and replace Hose Flexible of any size as per site requirement
(l) Supply and replace Clamp V Band as per site requirement (m) check tightness of V Belts
(n) Supply and replace Hose clamp as per site requuirement (o) Supply and replace Clamp T Bolts as per site requirement (p) Supply and replace gasket as per site requirement and testing complete to the satsifaction of Engr-in-Charge. | 5 | Each Job | 8,999 ₹44,995 | 8,500 ₹42,500 |
| 4.00 | Material & Labour for 'B' check of DG set Cap 400 KVA to 750 KVA of any make any model as per company norms including the following :-
(a) Complete change of engine Oil
(b) Change Engine oil filters
(c) Check throtle linkage
(d) Clean fuel tank
(e) Supply and replace fuel filters
(f) Supply and replace water filters if any
(g) Check and top Coolant
(h) Supply and replace all air filters
(j) Check leaks
(k) Supply and replace Hose Flexible of any size as per site requirement
(l) Supply and replace Clamp V Band as per site requirement (m) check tightness of V Belts
(n) Supply and replace Hose clamp as per site requuirement (o) Supply and replace Clamp T Bolts as per site requirement (p) Supply and replace gasket as per site requirement and testing complete to the satsifaction of Engr-in-Charge, complete all as specified and directed.
Note for Sl Item No 01 to 04 :
(i) Make/Model of DG Sets to be confirmed from the Engr-in-Charge before placing the procurement of spare parts.
(ii) Engine oil supplied by the contractor is to be in sealed drum.
(iii). Parts replaced shall be identical to those specified by original manufacturer as existing at site. | 7 | Each Job | 9,999 ₹69,993 | 12,000 ₹84,000 |
| 5.00 | M & L repair/servicing of radiator assembly with intercooler of 10 to 50 KVA DG Set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing, complete all as specified and directed.
Note- Pre-mixed coolent shall be measured and paid separately under relevant item of schedule. | 7 | Each Job | 799 ₹5,593 | 1,000 ₹7,000 |
| 6.00 | M & L Repair/servicing of radiator assembly with intercooler of 62.5 to 160 KVA DG Set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing, complete all as specified and directed.
Note- Pre-mixed coolent shall be measured and paid separately under relevant item of schedule. | 7 | Each Job | 799 ₹5,593 | 1,000 ₹7,000 |
| 7.00 | M & L Repair/servicing of radiator assembly with intercooler of 200 to 320 KVA DG Set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing, complete all as specified and directed..
Note- Pre-mixed coolent shall be measured and paid separately under relevant item of schedule. | 2 | Each Job | 799 ₹1,598 | 1,200 ₹2,400 |
| 8.00 | M & L Repair/servicing of radiator assembly with intercooler of 400 to 750 KVA DG set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing complete all as directed by Enginer-in-Charge.
Note- Pre- mixed coolent shall be measured and paid separately under relevant item of schedule. | 2 | Each Job | 799 ₹1,598 | 1,500 ₹3,000 |
| 9.00 | M & L for dismantling and opening of turbo charger assembly of 10 to 50 KVA DG Set and repair / overhauling and replacement of turbo charger kit and all type of spare parts including refixing and testing, complete all as specified and directed. | 5 | Each Job | 2,999 ₹14,995 | 2,000 ₹10,000 |
| 10.00 | M & L for dismantling and opening of turbo charger assembly of 62.5 to 160 KVA DG Set and repair/overhauling and replacement of turbo charger kit and all type of spare parts including refixing and testing, complete all as specified and directed. | 5 | Each Job | 3,999 ₹19,995 | 2,500 ₹12,500 |
Updated dates
Tender Value
Refer Docs
EMD Value
₹69,460
Closing Date
27 Jan 2026, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
REPAIR / MAINTENANCE OF DG SETS AND ALLIED WORKS AND REPAIR / REPLACEMENT OF EARTHING INFRASTUCTURE ALONGWITH ALLIED WORKS AT AF STN HALWARA
2025_MES_746556_1
GE/HAL-75/2025-26
Open Tender
Electrical and Maintenance Works
365 days
Halwara
MES ENLISTED CONTRACTORS CLASS D CATEGORY b(i)
8 documents required · 8 mandatory
₹500
GE (AF) Halwara
₹69,460
Yes
5 Mar 2026
30 Dec 2025
29 Jan 2026
30 Dec 2025
27 Jan 2026
13 Jan 2026
Material & Labour for 'B' check of DG set Cap 10 KVA to 50 KVA of any make any model as per company norms including the following :- (a) Complete change of engine Oil (b) Change Engine oil filters (c) Check throtle linkage (d) Clean fuel tank (e) Supply and replace fuel filters (f) Supply and replace water filters if any (g) Check and top Coolant (h) Supply and replace all air filters (j) Check leaks (k) Supply and replace Hose Flexible of any size as per site requirement (l) Supply and replace Clamp V Band as per site requirement (m) check tightness of V Belts (n) Supply and replace Hose clamp as per site requuirement (o) Supply and replace Clamp T Bolts as per site requirement (p) Supply and replace gasket as per site requirement and testing, complete to the satsifaction of Engr-in-Charge.
Material & Labour for 'B' check of DG set Cap 62.5 KVA to 160 KVA of any make any model as per company norms including the following :- (a) Complete change of engine Oil (b) Change Engine oil filters (c) Check throtle linkage (d) Clean fuel tank (e) Supply and replace fuel filters (f) Supply and replace water filters if any (g) Check and top Coolant (h) Supply and replace all air filters (j) Check leaks (k) Supply and replace Hose Flexible of any size as per site requirement (l) Supply and replace Clamp V Band as per site requirement (m) check tightness of V Belts (n) Supply and replace Hose clamp as per site requuirement (o) Supply and replace Clamp T Bolts as per site requirement (p) Supply and replace gasket as per site requirement and testing complete to the satsifaction of Engr-in-Charge.
Material & Labour for 'B' check of DG set Cap 200 KVA to 320 KVA of any make any model as per company norms including the following :- (a) Complete change of engine Oil (b) Change Engine oil filters (c) Check throtle linkage (d) Clean fuel tank (e) Supply and replace fuel filters (f) Supply and replace water filters if any (g) Check and top Coolant (h) Supply and replace all air filters (j) Check leaks (k) Supply and replace Hose Flexible of any size as per site requirement (l) Supply and replace Clamp V Band as per site requirement (m) check tightness of V Belts (n) Supply and replace Hose clamp as per site requuirement (o) Supply and replace Clamp T Bolts as per site requirement (p) Supply and replace gasket as per site requirement and testing complete to the satsifaction of Engr-in-Charge.
Material & Labour for 'B' check of DG set Cap 400 KVA to 750 KVA of any make any model as per company norms including the following :- (a) Complete change of engine Oil (b) Change Engine oil filters (c) Check throtle linkage (d) Clean fuel tank (e) Supply and replace fuel filters (f) Supply and replace water filters if any (g) Check and top Coolant (h) Supply and replace all air filters (j) Check leaks (k) Supply and replace Hose Flexible of any size as per site requirement (l) Supply and replace Clamp V Band as per site requirement (m) check tightness of V Belts (n) Supply and replace Hose clamp as per site requuirement (o) Supply and replace Clamp T Bolts as per site requirement (p) Supply and replace gasket as per site requirement and testing complete to the satsifaction of Engr-in-Charge, complete all as specified and directed. Note for Sl Item No 01 to 04 : (i) Make/Model of DG Sets to be confirmed from the Engr-in-Charge before placing the procurement of spare parts. (ii) Engine oil supplied by the contractor is to be in sealed drum. (iii). Parts replaced shall be identical to those specified by original manufacturer as existing at site.
M & L repair/servicing of radiator assembly with intercooler of 10 to 50 KVA DG Set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing, complete all as specified and directed. Note- Pre-mixed coolent shall be measured and paid separately under relevant item of schedule.
M & L Repair/servicing of radiator assembly with intercooler of 62.5 to 160 KVA DG Set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing, complete all as specified and directed. Note- Pre-mixed coolent shall be measured and paid separately under relevant item of schedule.
M & L Repair/servicing of radiator assembly with intercooler of 200 to 320 KVA DG Set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing, complete all as specified and directed.. Note- Pre-mixed coolent shall be measured and paid separately under relevant item of schedule.
M & L Repair/servicing of radiator assembly with intercooler of 400 to 750 KVA DG set as availalbe at site' after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out coolent from radiator and scrapping / removing sludge / scale inside tank with acid including replacement MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing complete all as directed by Enginer-in-Charge. Note- Pre- mixed coolent shall be measured and paid separately under relevant item of schedule.
M & L for dismantling and opening of turbo charger assembly of 10 to 50 KVA DG Set and repair / overhauling and replacement of turbo charger kit and all type of spare parts including refixing and testing, complete all as specified and directed.
M & L for dismantling and opening of turbo charger assembly of 62.5 to 160 KVA DG Set and repair/overhauling and replacement of turbo charger kit and all type of spare parts including refixing and testing, complete all as specified and directed.
M & L for dismantling and opening of turbo charger assembly of 200 to 320 KVA DG Set and repair/overhauling and replacement of turbo charger kit and all type of spare parts including refixing and testing, complete all as specified and directed.
M & L for dismantling and opening of turbo charger assembly of 400 to 750 KVA DG Set and repair/overhauling and replacement of turbo charger kit and all type of spare parts including refixing and testing, complete all as specified and directed.
M & L for dismantling and taking down alternator assembly from existing engine and transporting to workshop and carry out servicing / maintenance of alternator unit of capacity 10 to 50 KVA DG set as per the phase work :- (a) Opening of Alternator and cleaning / remvoing dust from armature and field coil. (b) Cleaning of used / old lubricated substances drive/non drive end bearings. (c) Cleaning end cheeking of AVR unit (d) Cheking and tighting of coupling bolts and replacement of rubber inserts. (e) M&L for carrying out heat varnishing for field and armature coil and kept in heating chamber for 48 hours for drying properly. (f) Replacement of Bearings as per existing size. (g) Reassembling complete unit and carrying out testing at workshop and transportation to installation and coupling with DG Set including necessary alignment, cable connections, complete all as specified and directed.
M & L for dismantling and taking down alternator assembly from existing engine and transporting to workshop and carry out servicing / maintenance of alternator unit of capacity 62.5 to 160 KVA DG set as per the phase work :- (a) Opening of Alternator and cleaning / remvoing dust from armature and field coil. (b) Cleaning of used / old lubricated substances drive/non drive end bearings. (c) Cleaning end cheeking of AVR unit (d) Cheking and tighting of coupling bolts and replacement of rubber inserts. (e) M&L for carrying out heat varnishing for field and armature coil and kept in heating chamber for 48 hours for drying properly. (f) Replacement of Bearings as per existing size. (g) Reassembling complete unit and carrying out testing at workshop and transportation to installation and coupling with DG Set including necessary alignment, cable connections, complete all as specified and directed.
M & L for dismantling and taking down alternator assembly from existing engine and transporting to workshop and carry out servicing / maintenance of alternator unit of capacity 200 to 320 KVA DG set as per the phase work :- (a) Opening of Alternator and cleaning / remvoing dust from armature and field coil. (b) Cleaning of used / old lubricated substances drive/non drive end bearings. (c) Cleaning end cheeking of AVR unit (d) Cheking and tighting of coupling bolts and replacement of rubber inserts. (e) M&L for carrying out heat varnishing for field and armature coil and kept in heating chamber for 48 hours for drying properly. (f) Replacement of Bearings as per existing size. (g) Reassembling complete unit and carrying out testing at workshop and transportation to installation and coupling with DG Set including necessary alignment, cable connections, complete all as specified and directed.
M & L for dismantling and taking down alternator assembly from existing engine and transporting to workshop and carry out servicing / maintenance of alternator unit of capacity 400 to 750 KVA DG set as per the phase work :- (a) Opening of Alternator and cleaning / remvoing dust from armature and field coil. (b) Cleaning of used / old lubricated substances drive/non drive end bearings. (c) Cleaning end cheeking of AVR unit (d) Cheking and tighting of coupling bolts and replacement of rubber inserts. (e) M&L for carrying out heat varnishing for field and armature coil and kept in heating chamber for 48 hours for drying properly. (f) Replacement of Bearings as per existing size. (g) Reassembling complete unit and carrying out testing at workshop and transportation to installation and coupling with DG Set including necessary alignment, cable connections, complete all as specified and directed.
M & L for rewinding of armature with super enamelled copper of required size wire including varnishing, sleeves, cotton tape and heating etc. for DG Set of capacity 10 to 50 KVA, complete all as specified and directed.
M & L for rewinding of armature with super enamelled copper of required size wire including varnishing, sleeves, cotton tape and heating etc. for DG Set of capacity 62.5 to 160 KVA, complete all as specified and directed.
M & L for rewinding of armature with super enamelled copper of required size wire including varnishing, sleeves, cotton tape and heating etc. for DG Set of capacity 200 to 320 KVA complete all as specified and directed.
M & L for disconnecting & taking out of existing control panel of any description and in any position, of 10 to 50 KVA capacity DG set & opening of Panel, checking AC/DC circuits and replacement control wiring with exiting specification , single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the panel on full load after completion of repairs, complete all as specified and directed.
M & L for disconnecting & taking out of existing control panel of any description and in any position, of 62.5 to 160 KVA capacity DG set & opening of Panel, checking AC/DC circuits and replacement control wiring with exiting specification , single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the panel on full load after completion of repairs, complete all as specified and directed.
M & L for disconnecting & taking out of existing control panel of any description and in any position, of 200 to 320 KVA capacity DG set & opening of Panel, checking AC/DC circuits and replacement control wiring with exiting specification , single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the panel on full load after completion of repairs, complete all as specified and directed.
M & L for disconnecting & taking out of existing control panel of any description and in any position, of 400 to 750 KVA capacity DG set & opening of Panel, checking AC/DC circuits and replacement control wiring with exiting specification , single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the panel on full load after completion of repairs, complete all as specified and directed.
M & L for disconnecting and taking out the exhaust system of DG set of any capacity and carrying out cleaning of chocked, carbonized exhaust pipe including exhaust .silencer with de-scaling solution, including soldering / gas welding of leakage of pipe. Cutting the rusted portion of pipes including gas welding of pipes assembling the complete exhaust assembly including replacement of gasket, metallic flexible pipe, nut bolts, and testing for making it leak proof and fixing the same in position and testing the system, complete all as specified and directed.
S&F in repair/ replacment of Self starter 12/24V of existing or As availalbe at site on the 10 to 50 KVA DG Set and taking out u/s self starter from DG set, complete all as specified and directed.
S&F in repair/ replacment of Self starter 12/24V of existing or As availalbe at site on the 62.5 to 160 KVA DG Set and taking out u/s self starter from DG set, complete all as specified and directed.
S&F in repair/ replacment of Self starter 12/24V of existing size ans make at site on the 200 to 320 KVA DG Set, complete all as specified and directed.
S&F in repair/ replacment of Self starter 12/24V of existing or As availalbe at site on the 400 to 750 KVA DG Set and taking out u/s self starter from DG set, complete all as specified and directed.
S&F in repair/ replacment of Alternater for battery charging, 12/24V of existing make for the 10 to 50 KVA DG Set, complete all as specified and directed.
S&F in repair/ replacment of Alternater for battery charging, 12/24 V of existing make for the 62.5 to 160 KVA DG Set, complete all as specified and directed.
S&F in repair/ replacment of Alternater for battery charging, 12/24V of existing make for the 200 to 320 KVA DG Set, complete all as specified and directed.
S&F in repair/ replacment of Alternater for battery charging, 12/24 V of existing make for the 400 to 750 KVA DG Set, complete all as specified and directed.
S&F in repair/replacment of turbo charger assembly of 10 to 50 KVA DG Set of existing make, complete all as specified and directed.
S&F in repair/replacment of turbo charger assembly of 62.5 to 160 KVA DG Set of existing make, complete all as specified and directed.
S&F in repair/replacment of turbo charger assembly of 200 to 320 KVA DG Set of existing make, complete all as specified and directed.
S&F in repair/replacment of turbo charger assembly of 400 to 750 KVA DG Set of existing make, complete all as specified and directed.
S&F in repair / replacment of water pump and replacement of water kit and water seal and connected item of 10 to 50 KVA DG Set, complete all as specified and directed.
S&F in repair / replacment of water pump and replacement of water kit and water seal and connected item of 62.5 to 160 KVA DG Set, complete all as specified and directed.
S&F in repair / replacment of water pump and replacement of water kit and water seal and connected item of 200 to 320 KVA DG Set, complete all as specified and directed.
S&F in repair / replacment of water pump and replacement of water kit and water seal and connected item of 400 to 750 KVA DG Set, complete all as specified and directed.
S&F in repair/replacement AVR unit suitable for DG set upto 10 to 50 KVA capacity available at site, complete all as specified and directed.
S&F in repair/replacement AVR unit suitable for DG set upto 62.5 to 160 KVA capacity available at site, complete all as specified and directed.
S&F in repair/replacement AVR unit suitable for DG set upto 200 to 320 KVA capacity available at site, complete all as specified and directed.
S&F in repair/replacement AVR unit suitable for DG set upto 400 to 750 KVA capacity available at site, complete all as specified and directed.
Supply and topping up only lubrication oil SAE-40 ( 15 W- 40 grade) of Make as approved by GE. should be packed of 40 Ltrs bucket), complete all as specified and directed.
Supply and filling of coolant suitable for radiators of 10 to 750 KVA capacity DG set (should be packed of 20 Ltrs bucket), complete all as specified and directed
Supply only Jute cotton waste (as per sample) for cleaning & day to day maintainance of silencer & DG set installed at different location at this station, complete all as specified and directed.
M & L in repair and refixing to DGs sound proof doors broken hinges and handles of any make and size / Capacity including fixing with suitable size of broken door hinges with nuts, bolts or welding as per site requirements, complete all as specified and directed.
M&L in repair for complete wiring harness of required size with sleeves thimbles, lugs indicator lamp, push button and starting switch etc for DG set of any capacity, complete all as specified and directed.
Supply and Fixing Battery 12 Volt 180 AH with Connecting Copper Lead & Clamp/Terminals with color code, complete all as specified and directed.
S&F in repair/ replacemnt of any type of sensor/relay viz-o-viz triping relay cooling sensor, lubrication sensor or any type required for any DG Sets available at site, complete all as specified and directed.
Repair /maintenance / attending to complaints w.r.t AMF panels of DG Set making it operational in all aspects to the satisfaction of Engr in Charge. The job includes the cost of all the spares requried to make the AMF panel serviveable including contactor, relay, wiring, switch, complete all as specified and directed
S&F in replacement battery charger 12 Volts for DG set of capacity 10 to 63 KVA, complete all as specified and directed.
S&F in replacement battery charger 24 Volts for DG set of capacity 100 KVA to 320 KVA, complete all as specified and directed.
M&L for repair/Attending break down of DG set to make completely functional in all respect to with out repalcing spare parts, complete all as specified and as directed. Note:- The rate quoted shall deemed to be included for any type of breakdown.
Note: The work under subject BoQ (item No. 1 to 59) is meant for maint and repair of DG Set in AF Stn Halwara under GE (AF) Halwara. The work shall be executed on ground on required basis but being remote station and extreme wheather condition contractor must stand by all the material and Engineer to rectify the breakdown of DG Set. Contractor shall deploy sufficient resources to keep smooth working of DG Set in the AF station. In addition any breakdown shall be communicated to contractor or his representative by concerned Engineer-in-charge/JE E/M through phone call, text message, complaint slip and or in writing through site order book or through other means. Non complying of attending breakdown by contractor within 48 hours after notify the complaint, recovery @ Rs 1000/- per day shall be recovered from contractor's payment for each breakdown so notified.
M&L for checking of earth values of each earth pit on monthly basis/on periodcity / on demand / on any anomaly observed of any type of earth pit by deploying skilled and trained personnel with calibrated testing equipments and T&P required for the same and recording the actual earthing test results achieved at site, watering with adequate quantity of water to earth pits from nearest available water point to achieve better results, complete all as specified and directed. Note : Quartely / half yearly / yearly calibration report of the testing equipment shall be submitted by the contractor. Adequate teams should be provided by contractor to carryout the jobs to complete with in desired periodicity.
M&L for replacement of GI earth strip of any size worn out / unserviceable stud insulators and refixing with screws/nuts, bolts and washers, welding/brazing of joints/broken points including replacement of shaddles, making good distorted GI strips by hammering/welding as per site requirement & refixing the same after repair also insulating with HDPE pipe of suitable dia /size, complete all as specified and directed. Note : HDPE Pipe and PVC insulators will be measured and paid seperately under relevant item. The contractor must employ manpower for the said work with in 48 Hrs post receipt of the complaint, failure to this will impose a penality of Rs. 500/- per day.
M&L for replacement of Alluminium strip of any size and wornout / unserviceable stud insulators and refixing with screws / nuts, bolts and washers welding / brazing of joints / broken points including replacement of shaddles, making good distorted Alluminium strips by hammering/welding as per site requirement & refixing the same after repair also insulating with HDPE pipe of suitable dia /size, complete all as specified and directed. Note : HDPE Pipe and PVC insulators will be measured and paid seperately under relevant item. The contractor must employ manpower for the said work with in 48 Hrs post receipt of the complaint, failure to this will impose a penality of Rs. 500/- per day.
M&L for replacement of Copper strip of any size and wornout /unserviceable stud insulators and refixing with screws/nuts, bolts and washers welding/brazing of joints/broken points including replacement of shaddles, making good distorted Copper strips by hammering/welding as per site requirement & refixing the same after repair also insulating with HDPE pipe of suitable dia /size, complete all as specified and directed. Note : HDPE Pipe and PVC insulators will be measured and paid seperately under relevant item. The contractor must employ manpower for the said work with in 48 Hrs post receipt of the complaint, failure to this will impose a penality of Rs. 500/- per day.
S&F in repair of air termination single pointed copper rod of 12mm dia and 300mm long for lighting conductor, complete all as specified and directed.
S&F in repair aluminium strip 25 x 3 mm with PVC shaddles and fixing screws for roof conductors and down conductors and welding/brazing of joints above ground, complete all as specified and directed.
S&F in repair copper strip 20 x 3 mm with PVC shaddles and fixing screws for roof conductors and down conductors and welding/brazing of joints above ground, complete all as specified and directed.
S&F in repair copper strip 32 x 6mm with PVC shaddles and fixing screws for roof conductors and down conductors and welding/brazing of joints above ground, complete all as specified and directed.
S&F in repair test point terminal block made of gun metal or phosphorus bronze of size 75 x 75 x 25 mm drilled and screwed including 3 Nos 8mm dia, 25mm long hex head screws for lighting conductor, complete all as specified and directed.
S&F in repair galvanised iron strip 32 x 6mm with porcealian shaddles and fixing screws for roof conductors and screwed including 3 Nos, 8mm dia, 25mm long hex head scews for lighting conductor, complete all as specified and directed.
M&L in repairs for earthing with galvanised steel earth plate electrode of size 60cmX60cmX6.00mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate no less than 1.5m bellow normal ground level surrounded from all sides by 15cm thick and packed layer of charcol dust and common salt filling in alternatie layers and electrode connected by galvanised iron strip 32mmx6mm by means of bolts, nuts and washers connected to test termination point protected by 40mm bore GI pipe light grade and GI pipe light grade 20mm bore for watering and inlcuding funnel, wire mesh, RCC pit cover and PCC chamber with PCC 1:2:4 type B-1 including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil to a distance not exceeding 50mtr all as specified and shown in Electrical Plate No 3 of SSR Part-I and testing, complete all as specified and directed. Note : - (a) The unit rate shall include for GI water pipe, protection pipe wire mesh, funnel, excavation, RCC pit cover, PCC. Test point, GI strip 32x6mm from top of earth plate upto 7.5 mtr. (b) PCC pit shall be provided at least 1.5m away from the earth pit and extra cost of additional length of water pipes and fixing junction, elbow etc shall be deemed to be included in the unit rate. (c) RCC pit cover shall be precast of RCC 1:2:4 tyupe B-1, 80mm thick reinforced with XPM weighing not less than 4 Kg/sqm.
M&L in repair earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly in ground in vertical position, earth pit not less than 2.25 m deep below ground level with top edge of the plate not less than 1.50m below ground level. The earth plate to be connetced with copper earthing strip of size 20 mmx 3mm thick by means of brazing between copper strip and earth plate min 45 cm in vertical length and copper strip also to be joined by brazing only. The copper earthing strip to be protected by galvanised iron pipe 40 mm bore (light grade) up to ground level and there after with 40mm dia PVC pipe up to test point. Earthing shall include provision of funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand and 2nd layer with 30 cm of Magnesium sulphate powder (compact thickness), 3rd layer with tibba sand up to ground level. Earthing shall also include concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded stone aggregate), 50mm thick precast RCC (1:2:4) cover slab (reinforced with 8mm dia TMT bar @ 15 cm C/C both ways and suitable handle made of 10mm dia) including necessary form work, earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I , complete all as specified and directed.
M& for surface dressing not exc 15cm deep of earth pit surrounding area upto 1.5 Mtr away on all sides and complete earth pit, funnel etc of earth pit chamber including by cutting and cleaning away grass, bushes, small plant, vegetable shrubs, bushes of under roots etc and depositing waste to nearby garbage bin, complete all as specified and directed.
M&L in repair earth pit chamber with 120mm thick walls in PCC 1:3:6 type C-1 of size 300x300mm (internal size)x250mm deep with 150mm thick foundation of size 690x690mm using PCC 1:4:8 type D-2, 15mm thick internal plaster, RCC (1:2:4) type B1 precast cover of size 540x540x40mm thick with 6mm dia 150mm C/C mild steel bars with lifting handles 02 Nos with 8mm dia MS bar complete including marking of earth pit details, complete all as specified and directed.
M&L in repair and renewal of earthing complete including excavation, earth work, taking down of existing earthing plate and earth lead connection. Cleaning the earth plate and refixing with earth lead connection with and including GI nuts bolts and washers, providing layers of charcoal and salt as per plate No 3 of SSR part I, and M&L for precast PCC (1:3:6) type C1 (using 20mm graded stone aggregate) earth pit chamber and RCC (1:2:4) type B1 precast cover 40mm thick with 6mm dia mild steel bars @ 100mm C/C as in cover and testing on completion, complete all as specified and directed. Note : - (i) Test result of of earthing shall be submitted to Engr-in-charge in prescribed format. (ii) Watering pipe, protection pipe and funnel shall be measured and paid separately under respective items of schedule.
M&L in repair galvanised steel tubing 40 mm bore, light grade with all fittings as in protection of earthing lead, complete all as specified and directed.
M&L in repair galvanised steel tubing 20 mm bore light grade with all fitting as in watering pipe for earthing as per plate No 3 of SSR part I, complete all as specified and directed.
S&F in repair funnel made out of GI/mild steel sheet 3 mm thick in conical shape, dia of the funnel at bottom is 15 mm and at top is 75 mm, placed on GI pipe for watering the earth, complete all as specified and directed.
Material and labour chemical Safe Earthing Electrode using M.S Pipes, Outer Dia is 76 mm with a wall thickness of 1.6 mm, Inner Dia is 42 mm with a wall thickness of 2.6 mm, Over all Length is 3000 mm. External Corrosion Protection : Coper Paleted (250+ microns), Internal Corrosion Protection : A ground breaking corrosion resistant Crystalline Conductive Compund filled and compacted in the cavity within the pipes to enhance the electrodes performance. Conforms to IS : 3043 - 1987 i.e., Code of Practice For Earthing. Manufactured using Eco - Friendly minerals, Carbon based, high conductive material, Resistivity : < 0.5 ohm-metre (In dry conditions). Resistivity is not moisture dependant (Ph Value : 6.5 - 8.0) Electronic & Ionic conduction Less susceptible to shrinkage, Maintenance Free, Faster current dissipation while at the same time having hygroscpic & corrosion resistive properties. (Minimum Weight 25 kg) Recommended for harsh conditions incl Poly Plastic Earth pit Chamber Cover Heavy Duty (8 ton Capacity) including laying of copper strip from earth pit to testing point and testing point to equipment alongwith necessary bracing copper rod with copper strip and including the earthing strip to be covered in HDPE pipe of size 50mm fixed on wall using suitable bracket for proper insulation amongst the earthing rods to test point as well as from test point to equipment, complete all as specified and as directed. Note :- Earth test value required below 1ohms, if not found satisfactorily result the contractor will be liable to provide extra required materials for achiveing the earth value less than one ohms. No extra cost will be given to the contractor. In case contractor fails to achieve the desired values no payment will be admissible in this acount.
S&F in repair HDPE pipe 50mm bore with all fittings, complete all as specified and directed.
S&F in repair PVC shaddles/ Insulators and fixing screws for roof conductors, down conductors and on wall conductors above ground, complete all as specified and directed.
M&L for repair/ maint of broken/disconnected strip, hanging/ loose anywhere in station including shaddles, making good distroed strips (Al/GI/Copper) by hammering/welding as per requirement & refixing the same after repair also insulating with HDPE pipe, HDPE pipes shall be used in walls & brackets as per site requirement, complete all as specified and directed. Note : (i) HDPE Pipe shall be measured and paid seperately under relevant item. (ii) The contractor must employ manpower for the said work with in 24 Hrs post receipt of the complaint failure to this will impose a penality of Rs. 500/- per day.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
BOQ_835974.xls
BOQ • 1.07 MB
Tendre75.pdf
Tender Documents • 1.03 MB
Download all tender documents and submit your bid