Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹1.2 CrAccepted-AOC | ₹1.2 Cr | 1 | Accepted-AOC L1 |
| 2 | 2₹1.2 Cr+₹2.8 L (2.42%)Rejected-AOC | ₹1.2 Cr+₹2.8 L (2.42%) | 2 | Rejected-AOC L2 |
| 3 | 3₹1.2 Cr+₹3.7 L (3.14%)Rejected-Finance | ₹1.2 Cr+₹3.7 L (3.14%) | 3 | Rejected-Finance L3 |
Tender Value
₹1.2 Cr
EMD Value
₹50,000
Closing Date
16 Dec 2024, 6:55 pmClosed
Chief Electrical Engineer
Office of the CEE PWD Electrical Wing, Public office, Thiruvananthapuram
G E N E R A L G o v e r n m e n t S e c r e t a r i a t Thiruvananthapuram Disaster Management Department Construction of Alternate State Emergency Operation Centre ASEOC in the North Block of Govt Secretariat Eelctrical installation Genera
2024_PWD_713450_1
PWD/BLDG/TR/18984/2024_6_1_1/1
Open Tender
Electrical Works
Item Rate
120 days
Thiruvananthapuram
Please refer Tender documents.
7 documents required · 7 mandatory
₹6,508
₹50,000
Yes
1 Mar 2025
6 Dec 2024
19 Dec 2024
6 Dec 2024
16 Dec 2024
6 Dec 2024
6 Dec 2024 - 16 Dec 2024
Amount
Electrification
OD155965/2024-2025:Supply and providing of Recces mounted LED Tunable downlighter with 3000K to 6500 K CCT and dimming option via DALI having system output of 1200 lumens and maximum power consumption 17w. Luminous , CRI > 80, power factor > 0.9, UGR <19, 60 degree beam angle, and >50,000 burning hours as per L70. The luminaires is made of Diecast Aluminium body, Aluminium Reflector and PMMA diffuser to reduce glare of Philips DN590B M LED12S/TWH PSD WH WB or techno commercial equivalent.
OD155966/2024-2025:Supply and providing of Recces mounted LED Dimmable downlighter with 4000 K CCT and dimming option via DALI having system output of 2100 lumens and maximum power consumption 18w. Luminous , CRI > 80, power factor > 0.9, UGR <19, 60 degree beam angle, and >50,000 burning hours as per L70. The luminaires is made of Diecast Aluminium body, Aluminium Reflector and PMMA diffuser to reduce glare of Philips DN590B M LED20S 4000 PSD WH WB or techno commercial Equivalent.
OD155967/2024-2025:Supply and providing of 30w(+/-3w) LED Decorative Dimmable 2x2 fitting with 4000 lumens system output and 125 Lumens per watt system efficiency. UGR value shall be less than 16, 50,000 burning hours as per L70, Fitting shall be made with with dimming option via DALI, 4000K CCT, CRCA Body of Philips RC600B LED40S 840 PSD W60L60 WH or techno commercial Equivalent .
OD155968/2024-2025:Supply and providing of 30w (+/-3w) LED Recess mounting 2x2 fixture with 3000 Lumens light output, UGR value less than 19 by using Prismatic diffuser and single piece CRCA sheet aluminium housing. <19, 50,000 burning hours as per L70, Fitting shall be made with with dimming option via DALI,of Philips RC380B LED30S-4000 G6 W60L60 PSD OC WH /techno commercial Equivalent .
OD155969/2024-2025:Supply and providing of 190(+/-5w) LED Onespace luminous ceiling Prefab fitting with dimming option via DALI, Diamention 3000mm W x 1800mm L without e-box and weight 55KG, the dimming profile of the fitting shall be 0% - 100%, 50,000 burning hours as per L70 and CRI >85. The luminaire shall have Acoustic Properties 0.85 class B EN 11654 and Noice Reduction Coefficient NRC 0.85 ASTM C423 -99. The CCT of the fitting shall be 4000k and the diffuser of the fitting shall be made of Special fabric Polyster of Philips LP717P OSP W1800L2700 840 BK CE D or techno commercial equivalent.
OD155970/2024-2025:Supply and providing of 26w(+/-2w) LED Linear Tunable continous mountable fitting with 3000K to 6500K CCT and dimming option via DALI having 2600 lumens system output, >110 Lumens per watt system efficiency, 50,000 burning hours as per L70, width 60mm, Diecast aluminium body, PMMA Diffuser including end caps and suspension kit of Philips SP780X LED26S-TW PSD W6L12 OD SI /techno commercial Equivalent.
OD155971/2024-2025:Supply and providing of Philips recess mountable 360 degree multifunction sensor that combines motion detection (PIR), Infrared remote control reception (IR) and ambient light level detection (PE) into one device. The Maximum detection range: 5 m Detection area: 7.4 m x 5.6 m rectangular (at a height of 2.4 m) and Detection speed: 1.0 m/s, LED activation indicator Sensor of Quad element pyroelectric of Philips DUS360CR or techno commercial Equivalent.
OD155972/2024-2025:Supply and providing of 6 Button Antumbra Display Keypad User interphase - 16 Pages support up to 96 Functions, Automatic wall wash lighting effect triggered by user presence, Multiple language and icons to understand button functions easily of Philips PADPE-AM or techno commercial Equivalent.
OD155973/2024-2025:Supply and providing of Backbone communication module to user interphases with onboard Processor, Can store and recall up to 21 configurations using the DIP switch, powered through Dynet and no additional power required of Philips DACM -V2 or techno commercial equivalent
OD155974/2024-2025:Supply and providing Philips DALI Controller for Programming & Scene setting of light fixtures DALI Outputs including CCT Tuning suitable for DALI HF Ballasts, electronic low voltage transformers and LED fixtures Upto 64nos x 3 loops/ Circuits :192 Nos – each rated at 20A Built In DALI Bus Power Supply, automatically isolate the power circuit when all associated channels are at 0%. Control Options - Control of this device can be via a combination of methods, eg. serial control port, relay contacts, push button wall stations, infrared receivers and time clocks. DIN Rail mount installation. All connection terminals are accessible without disassembly of Philips DDBC320-DALI or techno commercial equivalent
OD155975/2024-2025:Supply and providing of Relay controller 12 channel 20A or above Actuator designed to control any type of switched load. The power circuit is of a “feed-through” design and is electrically equivalent to a four-pole contactor, with the additional advantage of each pole being separately controllable via the BUS Protocol network. The Actuator is DIN-rail mountable, designed to be installed in a switchboard next to the circuit breakers, feeding the circuits to be controlled. Each channel is fitted with a hardware override switch which is accessible from the front panel. of Philips DDRC1220FR/GLV2 or techno commercial equivalent
OD155976/2024-2025:Supply and providing of Philips Network Power Supply 15 V DC 1.5 A regulated power supply to supplement the DyNet network DC supply, DIN Rail mount installation of Philips DDNP1501 or techno commercial equivalent
OD155977/2024-2025:Supply and providing of Philips Dynalite Envision Network Gateway for multipurpose Ethernet connection to lighting control system and supports access to the lighting system via app as well as providing a web interface delivering access of Philips PDDEG or techno commercial equivalent
OD155978/2024-2025:Supply and providing of Philips Dynalite RS232 Gateway for serial port integration between a DyNet network and third-party systems like Audio, vedio, Blinds etc DIN Rail mount installation of Philips DDNG232 or techno commercial equivalent
OD155979/2024-2025:Supply and providing of Philips Dynalite flexible network communications bridge designed for RS-485 networks. The two opto-isolated RS-485 ports enable the DDNG485 to implement a trunk and spur topology with the bridge providing a high-speed backbone opto-coupled to many lower speed spurs of Philips DDNG485 or techno commercial equivalent
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
OD155980/2024-2025:Supply and fixing Surface mounting type Low deep Aluminium Profile for fixing LED strip 8mm X 17mm including fixing ,making good the damages etc as required. (1piece/meter)
OD155981/2024-2025:Supply and installation testing and commissioning flexible LED strip high brightness SMD LED as the light source for indoor application. It is highly suitable for cove-lighting , decorative lighting etc : warm/white :- 45 W LED (Pro Glow) or techno commercial equivalent, 900 lm/meter having a length of 5 mtr warm/white including drive connection etc
OD155982/2024-2025:Supply, Conveyance, Installation, Testing and Commissioning of surface mounted 10W integrated LED bath room mirror lamp fitting including fixing ,making good the damages etc as required (Philips or techno commercial equivalent
OD155983/2024-2025:Supply and fixing 1800 lumen round/ square(1X1) recessed fitting made of diecast aluminium, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, (Chip make: Cree/Osram/lumilled/Nichea) fixed in fall ceiling including cutting holes and giving connection etc if required.
OD155984/2024-2025:Supply, conveyance, installation, testing and commissioning of pre-wired 3600 lumen square (2ft X 2ft) recessed fitting made of CRCA sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, (Chip make Cree/Osram/lumilled/Nichea (UGR less than 19) suspended from ceiling properly hooked to steel hooks anchored to the ceiling and giving connections etc. as required.
OD155985/2024-2025:Supply and fixing 1500 lumen round/ square(1X1) recessed fitting made of diecast aluminium, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, (Chip make: Cree/Osram/lumilled/Nichea) fixed in fall ceiling including cutting holes and giving connection etc if required.
90.3.24.4:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 2X20W LED Lamp with box type fixture
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD155986/2024-2025:Supply and providing 4 Tyre Flexi DB for Lighting Power 2 x 14 way
OD155987/2024-2025:Supply and providing 4 Tyre Flexi DB 14 X 4 Way
1.53.1:Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
OD155988/2024-2025:a) Pre installation site level support through site visits (4 to 5 times as required by site condition) to guide the contractor on wiring part. b) Post wiring visit to check the wiring has done as per requirement. Assisting contractor in testing the lighting circuits. c) Commissioning, Installation and programming for above list of components. d) Testing and handover of the Lighting control system.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD155989/2024-2025:Supply and providing floor mounted free standing metal body pedestal fan having thermal overload protection with cord wires supplied along with the fan and giving connection etc. as required..- 400 mm sweep,1360 RPM metal body floor Mounting pedestal fan
OD155990/2024-2025:Supply, Installation , testing and commissioning of 225 mm sweep, light duty Exhaust fan in metal frame working on 230 V A/C exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.:-225 mm sweep, light duty Exhaust fan in metal frame working on 230 V A/C
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD155991/2024-2025:Supply, Installation , testing and commissioning of 305 mm sweep, 1400 rpm Heavy Duty Exhaust fan working on 230 V A/C exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.:-305 mm sweep, 1400 rpm Heavy Duty Exhaust fan working on 230 V A/C
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.21.4:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.40 mm
OD155992/2024-2025:Supply and fixing 20 mm dia PVC flexible conduit with accessories on surface of wall making good the damages etc as required.
90.6.4.1:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 1 Run
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
1.17.33:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 6 sq. mm
90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.2:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable devider
90.9.2.4:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 degree
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.11:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable retainer
90.9.2.12:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.1 to 3 module mounting box
90.9.2.13:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.4 to 5 module mounting box
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
90.10.1.4:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )4 module moulded plastic box on surface
90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.3:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.4 Module
1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
OD155993/2024-2025:Supply and fixing flush mounting POP-UP boxes with installation kits for fixing in furniture -6 (2x3) Module Matt Steel Finish
OD155994/2024-2025:Supply and fixing flush mounting POP-UP boxes with installation kits for fixing in furniture -8 (2x4) Module Matt Steel Finish-
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
OD155995/2024-2025:Supply and providing Sub Main Distribution Board with IP42 protection complying to IEC 61439-2 with copper bus bar neutral link earth bus etc suitable for providing 4/3 pole MCCBs as incoming and 3pole MCCBs outgoing fixed on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc. as required.
OD155996/2024-2025:Supply and providing Metering Extension box for the existing(250A bus, 8way/12way) Sub Main Distribution Board with IP42 protection complying to IEC 61439-2,Fixing on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc.
OD155997/2024-2025:Supply and providing Bottom cabling box for the existing(250A bus,-8way/12way) Sub Main Distribution Board with IP42 protection complying to IEC 61439-2,Fixing on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc.
OD155998/2024-2025:Supply and providing Corner box for the existing(250A bus,8way/12 way) Sub Main Disribution Board with IP42 protection complying to IEC 61439-2,Fixing on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc.
OD155999/2024-2025:Supply and providing Right side cabling box for the existing(250A bus,-8way) Sub Main Distribution Board with IP42 protection complying to IEC 61439-2, fixing on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc.
OD156000/2024-2025:Supply and providing Left side cabling box for the existing(250A bus,-8way) Sub Main Distribution Board with IP42 protection complying to IEC 61439-2, fixing on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc.
OD156001/2024-2025:Supply and fixing Spreader Terminals to the Sub Main Distribution Board (250A MCCB as Incomer) for connecting the cables.
OD156002/2024-2025:Supply and providing 100/5 A, 5 VA, accuracy class 0.5, Resin Cast Metering CT
OD156003/2024-2025:Supply and fixing Three Phase Digital type Voltmeter accuracy class 1
OD156005/2024-2025:Supply and fixing Single Phase Digital type Ammeter accuracy class 1
OD156006/2024-2025:Supply and fixing Red, Green, blue, Yellow, Orange colours LED indicator, AC/DC, as required
OD156007/2024-2025:Supply and fixing 16 A, 415 V, HRC type Kit kat fuse unit with 2 A-16A clip-on offset tag fuse link of size f1
OD156008/2024-2025:Painting letters or figures with enamel paint as identification mark to SB, DB, panel board etc as required
90.14.10.2:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD156009/2024-2025:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.3:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
90.12.5.33:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 150 sq mm
90.12.5.35:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 240 sq mm
90.12.6.33:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 150 sq mm
90.12.6.35:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 240 sq mm
90.12.7.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
90.12.7.35:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 240 sq mm
90.12.7.44:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 50 sq mm
9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
9.1.36:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 50 sq. mm (35mm)
14.13.3:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm dia
14.13.4:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required150 mm dia
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
OD156010/2024-2025:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 100amps 240 volts "C" curve DP Isolator complete with connections, testing and commissioning etc. as required.
2.20:Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
OD156011/2024-2025:Supply and providing Manual Changeover In Sheet Steel Enclosure including operating accessories etc asr equired.
OD156013/2024-2025:Supply and providing following sizes of C class 150mm dia MS pipe conforming to IS 3589/IS 1239 with flanged coupling in each full length of pipe, an additional exhaust piping,fixing the same firmly in the building / structure using necessary supports such as angle iron MS clamps etc. Painting the pipe and accessories with synthetic enamel paint over a coat of Zinc chromate primer etc as required.
OD156014/2024-2025:Exhaust pipe/muffler cladding: Supply and fixing 65mm thick resin bonded fiber glass wool having density of 48kg/m3 for thermal insulation and totally covered with a layer of chicken mesh and finally applying 0.63mm aliminium sheet cladding complete as required on the existing C class MS pipe of 150mm dia/muffler of DG exhaust .
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.10:Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
OD156015/2024-2025:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB (for preparing scheme & records for scrutiny & completion) first A3 Sheet
OD156016/2024-2025:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB (for preparing scheme & records for scrutiny & completion) Additional Sheet
OD156017/2024-2025:Class B / Type 1 tested Surge Protection Devices for Main Panel: Three Phase Application: Pluggable type surge arrester in suitable enclosure Class B / Type 1 as per IEC 61643 -11 for lightning current equipotential bonding to VDE 0185-305 (IEC 62305). The device with visual status LED indication and inbuilt common remote indication for defective arresters 3 nos of encapsulated, non-extinguishing spark gap to connect between Line and Neutral and one number arrester encapsulated, non-extinguishing spark gap type to connect between Neutral and Earth of following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, Total Lightning Impulse Current - 150 kA (10/350μ sec) for Line to Neutral & 125 kA(10/350μ sec) for Neutral to Earth, Total Nominal discharge current- 150 kA (8/20μ sec) for Line to Neutral & 125 kA(8/20μ sec) for Neutral to Earth, Voltage protection level 1700V (L to N) & 1500V (N to E). Operating temp -40o to +85oC. Response time < 100 nano sec with Short-circuit resistance should be 10 kA. • Line following current quenching 25 kA Ipeak, arrester backup fuse to 500 A gL/gG. The product shall be tested and approved by any one of the following external testing institute(UL, KEMA, OVE, VDE,IEC)
OD156018/2024-2025:Class C/ Type 2 Surge Protection Devices For VDB/Sub Distribution Board (SDB): Three Phase Application: This panel should include pluggable type surge arrester in suitable enclosure Class C/ Type 2 as per IEC 61643 -11 for surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4- 44). Modular connectable arrestor with dynamic cut-off unit and visual status display for each cartridge. It should be included Locking mechanismwith vibration protection and voltage keying for safe operation of the device. And the remote signalling can be acheived by inbuilt potential-free changeover contact in FS version. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E) . Total Nominal discharge current- 60 kA (8/20μ sec) for Line to Neutral & 40 kA(8/20μ sec) for Neutral to Earth, Total Max discharge current - 160 kA (8/20μ sec). Voltage protection level 1400V (L to N) & (N to E). Operating temp -40o to +80oC. Response time <25 nano sec (L to N), < 100 nano sec (N to E). DIN rail mounting type etc complete with back up fuse as required and as directed. The product should be tested and aproved by any one of the following external testing institute(UL, KEMA, OVE, VDE)
OD156019/2024-2025:Supply and providing IP66 5 division Junction box with dimension 190x150x125 mm for enclosing (Surge Protection Device) SPD , IK RATED
SITC of 30KVA UPS
OD155964/2024-2025:Supply, installation, and commissioning of 30KVA/30KW power cabinet pure sine wave UPS with min 6 modules Three phase in and out with vortical & horizontal paralleling compatibility with indoor (IP21) with surge protection system, bypass arrangement and with 30 min backup battery @ 30kw and battery over charge and under charge cut off (SMF battery of reputed approved make Exide/quanta/Panasonic), having battery bank with Min VAH 48000 with dual battery bank per ups, Input pf >0.99, output powerfactor: unity. input THDi <3 % without use of any external filters, double conversion technology with input voltage range 305- 485 with cut off. Ambient Temperature: 0-40 degree. 50Hz Three Phase, output 230V, 50Hz Single phase, SNMP card for network monitoring compatibility etc. It shall be 100% generator compatible, with Efficiency > 94% and output power factor unity ( 30kVA= 30kW), Eco mode Efficiency 98% and including all accessories etc as required. The system shall comply to a) EN/IEC 620401 for General Safety compatibility b) EN/IEC 620402 for Electromagnetic Compatibility. c) EN/IEC 620403 for Performance, d) EN/IEC 620404 for Environmental Compatibility. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic bypass built-in. The system shall have IGBT rectifier and inverter. warranty 3 years for UPS and batteries.. ( Make; Numeric-Legrand ). Indications : Digital indications of Input V & A, output V & A, Battery charge, Temperature
Building Management system
OD155954/2024-2025:Workstation with INTEL CORE I7 processor latest Generation with minimum 16 GB DDR RAM; Minumum 2GB graphics card , minimum 2 x 512 GB SSD drive, DVD R/W, Optical Mouse, 104 Keys Keyboard, latest windows 11 Pro version, 32" LCD Monitor and A4 laser jet colour printer
OD155955/2024-2025:Supply, Install, Testing & Commissioning of Building Management software. (Model Siemens Desigo CC/Techno commercial Equivalent) The software should be capable of generating reports as per client requirement mentioned in technical specification. In addition , The contractor/client to suggest the different reports which are not specifically mentioned in the specification but inline with OEM capabilities. The Software shall support a BACnet protocol which is an ASHRAE, ANSI and ISO standard protocol operating in three modes. It should be able to communicate & integrate with other protocols.
OD155956/2024-2025:Supply, Install, Testing & Commissioning of Third Party Integration: The Protocol Integrator/ Convertor shall be Capable to Integrate Open protocol systems on BAC net /Modbus/LONWORKS/M-Bus/J-Bus Protocol or on serial RS 485 / 232 interface. Make Siemens Desigo /techno commercial equivalent
OD155957/2024-2025:Supply, Install, Testing & Commissioning of Network Switch with rack to connect all the DDC
OD155958/2024-2025:Supply, Install, Testing & Commissioning of Microprocessor based BACnet/IP DDC controller/panel with 1. Support BACnet/IP communication protocol. 2. All panels shall be provided with a power failure/auto restart capability. 3. 10% spare capacity should be allowed inside each DDC controller/panel rack for future expansion. Client to refer the I/O summary list provided for DDC panel configuration.
OD155959/2024-2025:Supplying, Installing, Testing & Commissioning of Room type Temperature and RH Sensor
OD155960/2024-2025:Supplying, Installing, Testing & Commissioning of Room Co2 Monitoring
OD155961/2024-2025:Supply and surface laying of 4C x 1 sq.mm unscreened cu armoured cable
OD155962/2024-2025:Supply and surface laying of 2C x 1.5 sq.mm unscreened cu armoured cable
OD155963/2024-2025:Supply and surface laying of 2C x 1 sq.mm unscreened cu armoured cable
1.53.1:Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
S K Electrics and Infrastructures (BID ID -2019904)
D SURESH (BID ID -2020547)
Bidder Name
D SURESH
S K Electrics and Infrastructures
K.Reghunathan
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1123562.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .