Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical 31 38 280 4 JAGGARAJU PETA DOCK YARD COLONY BHPV VISAKHAPATNAM ANDHRA PRADESH 530012 | VISAKHAPATANAM | ANDHRA PRADESH | 530012 | Accepted-Technical Technically Qualified |
Tender Value
₹8.3 L
EMD Value
₹16,560
Closing Date
20 Jan 2026, 5:30 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Director, HBCHRC
Homi Bhabha Cancer Hospital and Research Center, Aganampudi, Visakhapatnam, Andhra Pradesh, 530053.
Testing and Calibration of 33KV Substation Electrical equipments for renewal of statutory clearance certificate from Central Electricity Authority (CEA) at Homi Bhabha Cancer Hospital and Research Center, Aganampudi, Visakhapatnam, Andhra Pradesh.
2025_TMC_891787_1
HBCHRC/Elec/2025-26/NIT/03 dated 30/12/2025
Open Tender
Electrical Works
Item Rate
120 days
Homi Bhabha Cancer Hospital Research Centre, Agana
As per NIT
2 documents required · 2 mandatory
₹0
₹16,560
Service Block ENGG Dept
5 Mar 2026
30 Dec 2025
29 Jan 2026
30 Dec 2025
20 Jan 2026
30 Dec 2025
30 Dec 2025 - 13 Jan 2026
9 Jan 2026
Preparation of the testing reports and submission of all hard copies with 2 sets to the CEA including arranging inspection and also necessary approval / safety certificate from authorities etc. The scope also includes obtaining electrical clearance Certificate from the CEA (Central Electricity Authority) for The below Equipment's:- a) 2.5 MVA transformers - 2 Nos b) 8 passenger Lifts - 2 Nos c) 750 KVA DG sets - 6 Nos d) 26 Passenger Bed Lifts - 6 Nos Important Note:- 1. The Total works should be done by 33KV Authorized Licensed Electrical contractor (Govt of Andhra Pradesh/Any state Authorized). 2. The Testing Works should be done by CEIG Approved agency under 33KV Authorized Licensed Electrical contractor. 3. Preparation of the testing reports and submission of all hard copies to the CEA / other statutory bodies , including arranging inspection and also necessary approval / safety certificate from authorities etc. 4. The scope and rates also includes obtaining electrical clearance Certificate from the CEA (Central Electricity Authority) & Annual Electrical Testing For Renewal of statutory clearance from CEA (Central Electrical Authority). 5. The work is including the inspection arranging, obtaining electrical clearance Certificate from the CEA (Central Electricity Authority).
Testing & Calibration of below all types of Protective relays and all other Relays:-
Testing and Recalibration of over current, earth fault, under voltage and other protective relays of numeric relay of M/s Schneider make/DPX-V5/Micom P127 relays installed in HT panels/LT panels/DG sets by secondary injection method to ascertain the healthiness of the relays in confirmation with the designed characteristics as per I.S standard and electricity code of practice, including the recalibration in case any difference in timing & load characteristics beyond the permissible limit to the maximum extend possible and as instructed by E.I.C. Contractor has to submit original calibration certificate of all their testing equipment's .
Testing and calibration APFC Relay Make:BELUK Model: BLR-CXD-14R
Testing and calibration Master trip relay VAJ (VAJH/ VAJC) Make: ALSTOM , Model:VAJH
Testing and calibration Auxiliary Relay VAA33( VAA/VDG) Make: ALSTOM , Model:VAA33
Testing and calibration Multifunction Meter (MFM) Measurement checks for unity PF,0.8 Lead&Lag ,Voltage Current Make: Schneider Conzerv Model EM6400NG
Testing and Calibration of 33KV CT&PT and Cables :-
33KV current transformer
33KV potential transformer
Checking &Testing(IR) of insulation resistance ,Leakage Current of HT cables 3CX300 Sq mm and submission of test Reports
Testing & Preventive Maintenance of Breakers in substation:-
LV ACB's: Yearly Preventive Maintenance and Testing for Air Circuit Breakers, 1250 A/ 4000 A / 6300 A , 440 V, ABB Make The preventive maintenance of LV ACB shall be carried out through authorized service agencies of respective OEM. OEM authorized service agency for LV ACB experienced service agency with certificate of carrying out similar jobs for any other Govt. organizations/PSUs will be allowed to carry-out the maintenance works, Make:ABB, SACE E6H/F 6300A-1Nos, SACE PR121/P- 4000A -2Nos, SACE E2S-1250A- 8Nos.
33KV VCB Panel: BHEL make VCB & Control Panel testing and yearly Preventive Maintenance such as checked/cleaned all loose connection(power&control) checked and tightened as required ,ON-OFF ,TRIP operation checked & necessary rectification as required ,IR value checked by 5KV megger & recorded in the register as per instructed by the Eng -in-charge. Voltage:36KV Type:PVN36 ,Normal Current 1250A
Testing of 2.5 MVA Transformers , Oil Fileration , Supply of Transformer Accessories :-
Testing of 2.5MVA transformer a)Insulation Resistance Test b)Polarization Index Test (PI Test) c) Magnetic Core balance test d) Vector Group Test General Checking :Buch holz Relay ,Bushings , Gasket joints ,Oil levels of MOG( Magnetic Oil Gauge)
DGA test of Transformer oil at any NABL Accredited Lab Including Sample Collection from Site and Submission test Reports
Physical Properties test of Transformer oil at any NABL Accredited lab including sample collection from site and submission of Reports.
Supply & topping up of transformer oil (2 barrels)
Supply of Silicagel Breather (OLTC) 1/2 KG with Required Coupler Model: DTO-2, Gel Qty: 500 Gms, Make: Yogya Enterprises
Supply of Silicagel Breather(Transformer) 1KG with Required Coupler :- Model: DTO-4, Gel Qty: 1.5 Kgs, Make: Yogya Enterpriese
Supply of silica gel for Transformer Breather
Testing & Calibration of OTI
Testing & Calibration of WTI
Black Compound for Sealing
HT 3M tape 38 mm
Calibration of Meters:-
Testing & Calibration of Clamp meter NABL approved laboratory Make: Fluke Model: 305
Testing & Calibration of Clamp meter NABL approved laboratory Make: Fluke Model: 115
LA & ACB trolley :-
Supply of single Piece non Linear Resister type Lightning Arrester suitable for 33KV 4 Pole structure complete with galvanized clamping arrangement ,GI bolts, Nuts, Washers etc.… as required Rating:30KV ,10KA,Class-2,BIL:175KVP,50Hz,Type:STN-DT,MCOV-24KV, Pr. REL CURRENT -40KA
Supply and fixing of First Aid box 18" x 12" x 8"
Supply of ACB Breaker Lifting Trolley
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.54 MB
Tenderdocuments1.pdf
Tender Documents • 2.58 MB
BOQ_937359.xls
BOQ • 0.35 MB
Formofagreement1.pdf
Additional Documents • 0.49 MB
FORMSATOH.xls
Tender Documents • 0.06 MB
Letteroftransmittal1.pdf
Additional Documents • 0.63 MB
Scopeofwork1.pdf
Tender Documents • 0.76 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .