HQ CWE No 02 Meerut
Headquarters Commander Works Engineer No 2 Military Engineer Services Boundary Road, Near Supply Depot Meerut Cantt-250001
REPAIR / MAINT VCBS, RMUS, GODS, LIGHTNING ARRESTER HT UG CABLE, TRANSFORMER INCULDING ALLIED HT WORK AND CONNECTED WORK FOR HT 11 KV AT ROORKEE MILITARY STATION AND, PURKAZI UNDER GE(MES) ROORKEE
2026_MES_798415_1
95558/RKE/E8
Open Tender
Civil Works
Item Rate
180 days
Roorkee
Please refer tender pages
9 documents required · 9 mandatory
₹500
GE Roorkee
₹80,000
12 Nov 2026
12 Nov 2026
5 Dec 2026
12 Nov 2026
3 Dec 2026
26 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L and labour for preventive maintenance/servicing of outdoor type 5 MVA 33/11 kV power transformer, including disconnection of incoming and outgoing connections, ensuring complete safety isolation and discharge; opening of transformer top cover wherever required; cleaning and servicing of accessible internal and external parts; checking, cleaning and tightening of all electrical and mechanical connections; carrying out insulation resistance (IR) tests using megger for 33 kV HV winding and 11 kV LV winding, HV winding-to-earth, LV winding-to-earth and between HV and LV windings, recording all test values and parameters; checking transformer oil level and condition by visual inspection and carrying out BDV test; inspection of gaskets, bushings, terminals and connections for any defects/leakage; removal of carbon deposits, dust and oxidation from connections and joints; checking and functional testing of protective and monitoring devices including Buchholz relay, Pressure Relief Device (PRD), temperature indicators/gauges and associated alarm/trip circuits; checking condition and continuity of transformer tank and earthing connections; carrying out minor repairs and replacement of defective/damaged minor internal/external components as required; complete in all respects as specified and directed by Engineer-in-Charge. For the following capaity of Transformer :-
NOTE :-(i) The cost of dismantling and assembly is deemed to be including.
(ii) work to be carried out by qualified personael to ensure safe and reliable operation (Testing will be done by qualified protection Engr & having valid EHT electrical license fro state/ central chief electrical inspector with requsite protection / calibration Experience). Preventing maint/servicing of transformer will be carried out by any equipment manufacture/certified firm and work to be carried out as per
standrded and recommendations complete in all respect. All test perameter service and report shall be submitted by contractor.
(iii) If the transformer winding as per testing is burnt the probable reason for the same should be mentioned in the report and report to be counter sign by GE. | 1 | Each Job | 100 | ₹100 |
| 2 | All as per item No 01 here-in-before but 3 MVA, 33/11 kV Power Transformer | 1 | Each Job | 100 | ₹100 |
| 3 | All as per item No 01 here-in-before but 2 MVA, 33/11 kV Power Transformer | 1 | Each Job | 10 | ₹10 |
| 4 | Material and labour for disconnecting of distribution transformer indoor/outdoor type for testing/servicing / cleaning / repairing of transformer, checking and tightening of all electrical/mechanical connections, checking of gasket, repairing of leakage e.i replacement of gland, change of brass nut/bolt, removing of carban from connection, gasket and joint, minor repair etc, ensuring safety isolation and testing (IR values for HV/LV windings & winding-to-earth) oil level & condition checking (visual and BDV test), checking of bushings, including external inspection , checking of earthing connection and re-connecting after carrying out required repair/testing servicing in the transformers.
NOTE :-(i) The cost of dismantling and assembly is deemed to be including.
(ii) work to be carried out by qualified personael to ensure safe and reliable operation (Testing will be done by qualified protection Engr & having valid EHT electrical license fro state/ central chief electrical inspector with requsite protection / calibration Experience). Preventing maint/servicing of transformer will be carried out by any equipment manufacture/certified firm and work to be carried out as per
standrded and recommendations complete in all respect. All test perameter service and report shall be submitted by contractor.
(iii) If the transformer winding as per testing is burnt the probable reason for the same should be mentioned in the report and report to be counter sign by GE.Upto 250 KVA transformer | 9 | Each Job | 10 | ₹90 |
| 5 | All as per item No 04 here-in-before but above 250 to 500 KVA transformer | 20 | Each Job | 10 | ₹200 |
| 6 | All as per item No 04 here-in-before but above 500 to 750 KVA transformer | 4 | Each Job | 10 | ₹40 |
| 7 | M&L for transportation of defective transformer declared defective after testing and recommendation as per Item No. 2 above, from 2/4 pole structure, platform mounted substation or AGE E/M store yard to a workshop approved by GE and included in the approved list of State Electricity Board/Electrical Inspectorate, having suitable test bench/facilities for testing of transformers and capable of issuing test certificate after repair. The item shall include taking down and transportation of the defective transformer to the approved workshop; opening of transformer top cover by carefully unscrewing and removing nuts, bolts and associated fittings; Dismantling of old damaged conservator tank and radiator carefully and fixing new conservator tank and radiator, transformer oil and keeping the same safely for reuse after filtration; dismantling/removing HT/LT coils/windings, gaskets, bushings, core, tap changer and other associated components as required, carefully removing burnt/damaged insulating materials such as tape, paper, insulating strings etc. and keeping reusable components safely; cleaning/washing of transformer tank, core, cooling tubes/radiators and all other parts to remove dust, rust, dirt, sludge and carbon deposits using suitable caustic soda/detergent/cleaning agent as required; taking out and cleaning cooling tubes/radiators; carrying out minor welding/fabrication and rectification of tank, joints and other defective portions as required; cleaning and preparing the inner surface of transformer tank and applying suitable zinc chromate protective coating/paint to the inner side of tank; cleaning and preparing all components for reassembly; reassembling the transformer after carrying out the required repairs, including refitting of core, HT/LT coils/windings, bushings, tap changer, gaskets, cooling tubes/radiators and other fittings; refilling/reusing filtered transformer oil as required; transporting the repaired transformer back to site/MES store yard and installing the same on existing 2/4 pole structure/platform with necessary fixing arrangements; reconnecting HT/LT electrical connections and earthing; carrying out necessary testing, commissioning and complete in all respects as specified and directed by Engineer-in-Charge. For the following capaity of Transformer :-Upto 250 KVA transformer.
NOTE :- (i) Reusing of transformer oil and filling of new transformer oil shall be paid separately.
ii) To accertain the fault of transformer at installed location, the transformer will be tested with HT 10KV magger, multimeter in the presence of AGE E/M/JE E/M. All T&P required like HT magger 10KV, multimeter and cables will be arrenged by contractor.
(iii) All the transformer shall be opened in presence of Engr- in- Charge/ his rep veryfy the various repairs/replacement involved and the transformer shall be assembled in the presence of Engr- in- Charge/his rep after necessary repairs/replacement.
(iv) All the transformer shall be tested in the factory in the presence of Engr- in- Charge/ his rep, as per ser note No (i) above and also in addition the transformer where specified to be installed and commissioned on the 2/4 pole structure, platform and also shall be tested by the contractor in the presence of Engr- in- Charge/his rep.
(v) All the testing arrangement shall be provided by the contractor without any extra payment. | 3 | Each Job | 10 | ₹30 |
| 8 | All as per item No 07 here-in-before but above 250 to 500 KVA transformer | 3 | Each Job | 10 | ₹30 |
| 9 | All as per item No 07 here-in-before but above 500 to 750 KVA transformer | 2 | Each Job | 10 | ₹20 |
| 10 | Taking down of transformers of capacity from 2/4pole structure or from PCC plateform with due care after disconnecting all HT/LT connections on pole mounted structures, Transportation of transformer from PCC/ 2 or 4 pole structure to any other required location in Roorkee cantt / Purkazi lowering and remounting it on 2/4pole structure or PCC plateform with due care by through crane and reconnection in new location including earthing connection and as directed and specified by engineer in charge for the following capaity of Transformer :-Upto 250 KVA transformer | 5 | Each Job | 10 | ₹50 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
BOQ_895666.xls
BOQ • 0.36 MB
Tender95558.pdf
Tender Documents • 1.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .