Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.0 LAccepted-AOC | ₹40.0 L Quoted ₹40.7 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹42.2 LRejected-Finance 81 82 GHER SAIKH MITHOO KUBRHI PAKHAR ZAKHERA BAREILLY UP | BAREILLY | BAREILLY | UTTAR PRADESH | ₹42.2 L | L2 | Rejected-Finance Being higher bidder |
| Sl No | Description | Qty | Unit | kumaon and hills strument engnering services L1 | shahji contractors L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, laying, jointing and testing of HT underground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts earthed, with stranded compact aluminium conductor 11000 volts grade 95 sq mm 3 core confirming to IS:7098 (Part-II) with latest amendements, suitable for earthed system laid in duct/trench/along pole etc. including making connection complete all as specified and directed. | 485 | RM | 1,200 ₹5.8 L | 1,199 ₹5.8 L |
| 2.00 | Excavation in trenches n. exc. 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of underground cable and getting out in hard / dense soil complete all as specified and directed. | 128 | Cum | 350 ₹44,800 | 350 ₹44,800 |
| 3.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed. | 87 | Cum | 120 ₹10,440 | 90 ₹7,830 |
| 4.00 | Removing excavated soil n exc. 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. | 40 | Cum | 300 ₹12,000 | 90 ₹3,600 |
| 5.00 | Supply and laying of brick, common burnt clay,building bricks, sub class 'B' designation 75, best quality locally available laid flat, dry in trenches for cable protection complete all as specified and as directed by the Engineer-in-change. | 2,522 | Each | 2 ₹5,044 | 12 ₹30,264 |
| 6.00 | M&L for sand cushioning with layer of sand 8 cm thick before laying of cable and 15 cm after lying of cable in trenches complete all as specified & directed.
Note- Punned thickness of sand will be measured (18 cm) and paid | 26 | Cum | 1,800 ₹46,800 | 1,400 ₹36,400 |
| 7.00 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm, 11000 Volts grade complete all as specified and directed. | 11 | Each | 5,000 ₹55,000 | 5,000 ₹55,000 |
| 8.00 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm, 11000 Volts grade complete all as specified and directed. | 6 | Each | 6,000 ₹36,000 | 6,000 ₹36,000 |
| 9.00 | S & F GI pipe light grade 80mm bore for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. | 30 | RM | 450 ₹13,500 | 600 ₹18,000 |
| 10.00 | M & L for cutting the road/hard standing to a size not exceedind 75 cm in depth and 45 cm in width for protection of XLPE cable including making good so as to match with existing finishing with PCC (1:4:8) type D2 (using 40 mm graded stone aggregrate) for 100 mm thick on top including fair finishing complete all as specified & directed. | 20 | RM | 200 ₹4,000 | 800 ₹16,000 |
Updated dates
Tender Value
₹60.8 L
EMD Value
₹1.2 L
Closing Date
19 Dec 2025, 6:00 pmClosed
CWE (HILLS) PITHORAGARH
HQ CWE (HILLS) PITHORAGARH POST OFFICE - BHARKATIA DISTRICT - PITHORAGARH STATE - UTTARAKHAND PIN 262520
CA NO. CWE/HILLS/PGH/110 OF 2025-2026 SPECIAL REPAIR FOR REPLACEMENT AND RE-ROUTING OF HT UG CABLE AND ALLIED WORKS FOR 7 E MAP ACCN AREA AND ARO STP AT MIL STN PITHORAGARH UNDER GE PITHORAGARH
2025_MES_739958_1
89298/25-26/E8
Open Tender
Electrical and Maintenance Works
240 days
PITHORAGARH
Class - C
10 documents required · 10 mandatory
₹1,000
Yes
GE (MES) PITHORAGARH
₹1.2 L
Yes
29 Jan 2026
14 Nov 2025
26 Dec 2025
14 Nov 2025
19 Dec 2025
5 Dec 2025
Amount
Supply, laying, jointing and testing of HT underground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts earthed, with stranded compact aluminium conductor 11000 volts grade 95 sq mm 3 core confirming to IS:7098 (Part-II) with latest amendements, suitable for earthed system laid in duct/trench/along pole etc. including making connection complete all as specified and directed.
Excavation in trenches n. exc. 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of underground cable and getting out in hard / dense soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing excavated soil n exc. 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Supply and laying of brick, common burnt clay,building bricks, sub class 'B' designation 75, best quality locally available laid flat, dry in trenches for cable protection complete all as specified and as directed by the Engineer-in-change.
M&L for sand cushioning with layer of sand 8 cm thick before laying of cable and 15 cm after lying of cable in trenches complete all as specified & directed. Note- Punned thickness of sand will be measured (18 cm) and paid
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm, 11000 Volts grade complete all as specified and directed.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm, 11000 Volts grade complete all as specified and directed.
S & F GI pipe light grade 80mm bore for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed.
M & L for cutting the road/hard standing to a size not exceedind 75 cm in depth and 45 cm in width for protection of XLPE cable including making good so as to match with existing finishing with PCC (1:4:8) type D2 (using 40 mm graded stone aggregrate) for 100 mm thick on top including fair finishing complete all as specified & directed.
Dismantling of old unserviceable HT steel tubular Pole four pole structure with connected HT insulators accessories and fuse assembly of any description /size for installation of HT RMU Panel complete all as specified and directed.
Supply, Installation, testing, and commissioning of 11 KV Outdoor duty (IP54 enclosure) SF6 gas insulated 3-way motor operated Ring Main Unit comprising of 2 Nos. 630Amps Load Break Switches and 1 No 630Amps Vacuum Circuit Breaker, cable termination from the front, breaking capacity 21KA/3sec (Internal Arc Classification ALF-R 21kA-1sec both for tank and cable box as per IEC IEC 62271-200), enclosed in robotically welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. The switchgear shall accommodate all the 3 modules in one tank. Protection CTs should be ring core type. Cable bushings should be replacable at site complete all as specified and directed. NOTE:- Others details:- System Particulars: for 3 Way RMU (1)Nominal System Voltage : 11KV. (2) Voltage variation on supply side : +10 % (3) Corresponding Highest System Voltage: 12KV. (4) Frequency : 50 Hz with +- 3 % tolerance (5) Transient condition : -20 % or + 10 % combined variation of Voltage and frequency. (6 )Number of Phase : 3 Phases. (7) Neutral earthling : Solidly earthed. (8) Fault level (minimum) kA /Sec : 21/3). 9) Lightning Impulse Withstand Voltage (kVp) : 75 (10) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV (11) Rated Dynamic Withstand Current for 1 second duration (kAp) : 52.5KA
Applicable Standards: a) The design, manufacture and performance of the Ring Main Units shall comply with all currently applicable statutes, regulations and safety codes. Nothing in this specification shall be construed to relieve the bidder off his responsibilities. b) Unless otherwise specified, the Ring Main Units offered shall conform to the latest applicable, IEC 62271-100, IEC 62271-200. All live parts, bus bars, shall preferably be enclosed in one tank to avoid multiple inter connections & sealed for life robotically welded non magnetic and non ferrite grade stainless steel tank Grade SS304 of minimum 2.5 mm thickness.The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR as per IEC62271-200. The outer enclosure shall cover the full length of the switch gear, to ensure IP54 protection for full door covering of complete switchgear. The protection relay shall be for 3 OC + 1EF (IDMT Type) , MODBUS communication along with RS 485 Port .
RMU and Vaccum Interruptor shall be of same make. All the mechanical bushings should be replacable at site, to avoid dismantling RMU from site and carrying to OEM factory for rectification for the minor gas leakages from mechanical bushing, this is operational & maintenane point, cannot be deviated. No additional plate/ accessories to be add to achieve Internal Arc of the Cable of 21kA-1sec, in the able box camber. RMUs should be manufactured, inspected and invoiced from the OEM factory only; no licensee partner manufactered RMU is exceptable. SERVICE CONDITIONS (a) The SF6 gas filled 11 kV, 630 Amps, extensible type, Outdoor, SCADA compatible Motorized Ring Main Unit with Vacuum Circuit Breaker to be supplied against this specification shall be suitable for satisfactory continuous operation under the following tropical conditions, design ambient temperature (Degree C) 40 as per IEC.
The unit shall include the following with all necessary standard fitting as required at site: a) Vacuum Circuit Breaker 12kV 630Amps 21kA-3sec and fault making type Earthing Switch with micro-processor based selfpowered 3 O/C + 1E/F relay fitted with fixed type voltage indicator device as per IEC 61958. Protection CTs suitable ratio 2.5VA burden (CT ratio shall be confirmed at time of drawing approval).-1 No. b) Load Break Switch 12kV 630Amps 21kA-3sec with copper bus Bar and earth switch fitted with fixed type voltage indicator device as per IEC -2 Nos. for 3 way. Note: Standard mano meter -01 for each tank, Operating handle - 01, cable clamping provision (standard)-01 / for every cable entry suitable for 1RX3C cable upto 300Sqmm, Operation and maintenance manual - 01, RMU Foundation (Earth Work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted. Height of plinth should not be less than 0.5 mtrs from ground level.
Supply, Installation, testing, and commissioning of 11 KV Outdoor duty (IP54 enclosure) SF6 gas insulated 4-way motor operated Ring Main Unit comprising of 3 Nos. 630 Amps Load Break Switches and 1 No 630Amps Vacuum Circuit Breaker, cable termination from the front, breaking capacity 21KA/3sec (Internal Arc Classification ALF-R 21kA-1sec both for tank and cable box as per IEC IEC 62271-200), enclosed in robotically welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. The switchgear shall accommodate all the 3 modules in one tank. Protection CTs should be ring core type. Cable bushings should be replacable at site complete all as specified and directed.
NOTE:- Others details:- System Particulars: for 3 Way RMU (1)Nominal System Voltage : 11kV. (2) Voltage variation on supply side : +-10 % (3) Corresponding Highest System Voltage: 12kV. (4) Frequency : 50 Hz with +- 3 % tolerance (5) Transient condition : -20 % or + 10 % combined variation of Voltage and frequency. (6 )Number of Phase : 3 Phases. (7) Neutral earthling : Solidly earthed. (8) Fault level (minimum) kA /Sec : 21/3). 9) Lightning Impulse Withstand Voltage (kVp) : 75 (10) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV (11) Rated Dynamic Withstand Current for 1 second duration (kAp) : 52.5KA Applicable Standards: a) The design, manufacture and performance of the Ring Main Units shall comply with all currently applicable statutes, regulations and safety codes.Nothing in this specification shall be construed to relieve the bidder off his responsibilities. b) Unless otherwise specified, the Ring Main Units offered shall conform to the latest applicable, IEC 62271-100, IEC 62271-200. All live parts, bus bars, shall preferably be enclosed in one tank to avoid multiple inter connections & sealed for life robotically welded non magnetic and non ferrite grade stainless steel tank Grade SS304 of minimum 2.5 mm thickness.The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR as per IEC62271-200. The outer enclosure shall cover the full length of the switch gear, to ensure IP54 protection for full door covering of complete switchgear. The protection relay shall be for 3 OC + 1EF (IDMT Type) , MODBUS communication along with RS 485 Port .
RMU and Vaccum Interruptor shall be of same make. All the mechanical bushings should be replacable at site, to avoid dismantling RMU from site and carrying to OEM factory for rectification for the minor gas leakages from mechanical bushing, this is operational & maintenane point, cannot be deviated. No additional plate/ accessories to be add to achieve Internal Arc of the Cable of 21kA-1sec, in the able box camber. RMUs should be manufactured, inspected and invoiced from the OEM factory only; no licensee partner manufactered RMU is exceptable. SERVICE CONDITIONS (a) The SF6 gas filled 11 kV, 630 Amps, extensible type, Outdoor, SCADA compatible Motorized Ring Main Unit with Vacuum Circuit Breaker to be supplied against this specification shall be suitable for satisfactory continuous operation under the following tropical conditions, design ambient temperature (Degree C) 40 as per IEC.
The unit shall include the following with all necessary standard fitting as required at site:
a) Vacuum Circuit Breaker 12kV 630Amps 21kA-3sec and fault making type Earthing Switch with micro-processor based selfpowered 3 O/C + 1E/F relay fitted with fixed type voltage indicator device as per IEC 61958. Protection CTs suitable ratio 2.5VA burden (CT ratio shall be confirmed at time of drawing approval).-1 No.
b) Load Break Switch 12kV 630Amps 21kA-3sec with copper bus Bar and earth switch fitted with fixed type voltage indicator device as per IEC -3 Nos. for 4 way
Note: Standard mano meter -01 for each tank, Operating handle - 01, cable clamping provision (standard)-01 / for every cable entry suitable for 1RX3C cable upto 300Sqmm, Operation and maintenance manual - 01, RMU Foundation (Earth Work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted. Height of plinth should not be less than 0.5 mtrs from ground level.
M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mmx 600 mmx 6.0 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone agg) complete all specified and directed.
shahji contractors (BID ID -3493970)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
PS110.pdf
Tender Documents • 2.00 MB
BOQ_828552.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid