Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance TEHSIL TRINTHA DISTRICT REASI 182311 JAMMU AND KASHMIR | REASI | JAMMU AND KASHMIR | 182311 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹16.1 L
EMD Value
₹32,200
Closing Date
13 Mar 2023, 4:00 pmClosed
Executive Engineer
Office of the Executive Engineer Electric Division Vijaypur JPDCL Jammu
Creation of 630 KVA Sub Station on Turnkey basis for providing of Electric Load to 47th BN ITBP, Rai Tapyal, Samba within the Jurisdiction of Electric Division Vijaypur JPDCL , Jammu
2023_PDD_207227_1
EDV/ 42 of 2022-23 Dt 06-03-2023
Open Tender
Electrical Works
Turn-key
30 days
Samba District
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
Executive Engineer Electric Division Vijaypur
₹32,200
3 Apr 2023
6 Mar 2023
14 Mar 2023
7 Mar 2023
13 Mar 2023
7 Mar 2023
7 Mar 2023 - 13 Mar 2023
Amount
Scope of works for Creation,Testing & Commissioning of 630 KVA Distribution Transformer Sub Station
Supply, Installation & commissioning of 11/0.433 KV, 630 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Copper Wound) along with LV Cable Box having detachable Aluminum Gland plate including Transportation
Supply, Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of GI channel Angle / flat of sizes including Clamps for LA Set/G.O Set /Horn Gap
Supply, Installation, Testing & Commissioning of 11 KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 KV Horn Gap Fuse Set 3 Phase 200 A .
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Providing & Fixing of 630 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
Providing & Fixing of Distribution Box for 630 kVA DTR with MCCB for incomer & SFU's for Outgoing Circuits
Providing of Earthing of substation --Excavation of earth pit of dia. 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GIStrip for neutral earthing of size 25 mm x 3 mm for connection of transformer body ,G.O Set &lightening arrestor as per IS 2629/85, GI nuts &bolts ,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Stone Pad 300mmx300mmx75mm
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Galvanized Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia. GI stranded wire complete
Providing and fixing of P G Clamps
M/S RATHER CONSTRUCTIONS AND TRADERS
M/S APR CONSTRUCTIONS
NEW ALLIED TRADERS
M/S SURAJ PARTAP SINGH
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .