GARRISON ENGINEER I R nd D WEST BANGALORE DRDO COMPLEX CV RAMAN NAGAR BANGALORE
OUTSOURCING SERVICES FOR OPERATION AND MAINTENANCE OF HT/LT INSTALLATIONS AND UPKEEPING OF INTERNAL ELECTRIFICATON INCLUDING FITTINGS AND FIXTURES AT NEW CAIR, CEPTAM, DAD QUARTERS AND DCA COMPLEX UNDER GE (I) RndD (WEST) , BANGALORE
2020_MES_349677_1
GE(I) R ND D (WEST)/BAN/15 OF 2020-21 8812E8
Open Tender
Manpower Supply
Item Rate
330 days
Bengaluru
Class and Category as per NIT
8 documents required · 8 mandatory
₹500
GE I R nd D West Bengaluru
₹98,000
Yes
10 Aug 2020
9 Jun 2020
8 Jul 2020
10 Jun 2020
2 Jul 2020
26 Jun 2020
10 Jun 2020 - 25 Jun 2020
Amount
Providing services for operation and maintenance of HT 11 KV Sub Station DG sets and pump sets at New CAIR for round the clock including switching of HT 11 KV, LT 415 Volts, Panel Boards, stand by DG sets, Pump sets, sewage pumps, recording for readings, cleaning of equipments etc, with one number of Electrician per shift in three shifts (1st Shift from - 0600 Hrs to 1400 Hrs, 2nd shift from 1400 Hrs to 2200 Hrs & 3rd shift form 2200 Hrs to 0600 Hrs including Sundays and Holidays) complete all as specified and as directed by Engineer-in-charge.
Providing services for operation and maintenance of HT 11 KV Sub Station DG sets and pump sets at DAD Pump House for round the clock including switching of HT 11 KV, LT 415 Volts, Panel Boards, stand by DG sets, Pump sets, sewage pumps, recording for readings, cleaning of equipments etc, with one number of Electrician cum Pump operator per shift in three shifts (1st Shift from - 0600 Hrs to 1400 Hrs, 2nd shift from 1400 Hrs to 2200 Hrs & 3rd shift form 2200 Hrs to 0600 Hrs including Sundays and Holidays) complete all as specified and as directed by Engineer-in-charge.
Providing services for operation and maintenance of HT 11 KV Sub Station DG sets and pump sets at CEPTUM (Dr RAJA RAMANNA COMPLEX) Pump House for round the clock including switching of HT 11 KV, LT 415 Volts, Panel Boards, stand by DG sets, Pump sets, sewage pumps, recording for readings, cleaning of equipments etc, with one number of Electrician cum Pump Operator per shift in three shifts ((1st Shift from - 0600 Hrs to 1400 Hrs, 2nd shift from 1400 Hrs to 2200 Hrs & 3rd shift form 2200 Hrs to 0600 Hrs including Sundays and Holidays) complete all as specified and as directed by Engineer-in-charge.
Periodical checking and attending all types of complaints connected with internal electrification and maintenance of internal electrification comprising of service connection OH/UG cables from respective feeder pillar boxes, periodical checking of power DB's including tightening of connections, changing of burnt out terminals, MCB's connectors etc., checking to earthing of the LT distribution system, periodical maintenance of earth pits including measurement of earth resistance, attending to day to day complaints including checking and replacement of burnt out and unserviceable items like wirings, connected fittings and fixture, MCB DB's, ceiling fans, exhaust fans, replacement of tube rods of any capacity and watt, choke, starters, point wirings, sub-main wirings, switch socket combination of any capacity, switches, fan regulators, capacitors, replacement of fuses CFL bulbs, lamp holders etc or any other repair works all as specified and as directed in day time by deploying certified/Skilled workers in general shift.(shift of 08 hours from 08.00 AM to 05.00 PM with one hour lunch break in between) with 2 Nos of Electrician and 2 Nos of Helpers, excluding Sunday & Holidays in NEW CAIR, DAD, DCA & CEPTAM Complexes. Notes for Sl Item Nos 1.00 to 4.00 :- (i) Details of equipment/services to be maintained are indicated as appendices in PS. (ii) Various items required for replacement are regulated by the department except those given under relevent items of schedule ‘A’ as supply only. However replacement cost of these items are deemed to be included in this item. (iii) The Items mentioned under relevent items of schedule ‘A’ shall be supplied by the contractor as and when required at site and the same shall be measured and paid under relevant items of Sch 'A',
Notes for Sl Item Nos 1.00 to 4.00 (Contd) :- (iv) Tenderer shall maintain relevant slips of complaints attended and materials used duly signed by users and any other documents as signed by dept and cost of the same is deemed to be included in the rate quoted. (v) T&P, HT fuse wire and safety gear required for attending to the complaints will have to be arranged by the tenderer at no extra cost to the department. (vi) Tenderer shall arrange insurance to his work-men and relevant proofs of the same shall be submitted to the department as and when demanded, the cost for the same is deemed to be included in the rate quoted. Responsibility of compliance of all the labour regulations in force lies with the tenderer.The provision of statutory laws relating to minimum wages, payment of wages through aadhaar linked bank accounts, EPF, ESI payments shall be strictly adhered to by the contractor. (vii) Absent from duty of technician is not permissible as E&M services essential in nature. However, the absence will invite penalty as described in Sch 'A' notes and recovery from bill shall be done through recovery statement.The tenderer will have no claim whatsoever on this account and decision of Accepting officer in this regard will be final and binding. (viii) Attention is drawn to minimum fair wages payable as notified (time to time) by Govt Of India / State Govt / Local body whichever is higher, including taxes as applicable and quote their rates accordingly. Contractor shall not have any claim on account of misunderstanding/under quoting in this regards.
Supply only PVC insulated , PVC un sheathed multi stranded heavy duty copper conductor cable 1.5 sq.mm size FRLS grade complete all as specified
Supply only PVC insulated , PVC un sheathed multi stranded heavy duty copper conductor cable 2.5 sq.mm size FRLS grade complete all as specified
Supply only PVC insulated , PVC un sheathed multi stranded heavy duty copper conductor cable 4 sq.mm size FRLS grade complete all as specified
Supply only PVC insulated , PVC un sheathed multi stranded heavy duty copper conductor cable 6 sq.mm size FRLS grade complete all as specified
Supply only rigid non metallic PVC conduit of size 25 mm dia, medium grade complete all as specified.
Supply only rigid non metallic PVC conduit of size 20 mm dia, medium grade complete all as specified.
Supply only Modular Switch 6 Amps, 240 V, one way single pole and one module complete all as specified
Supply only Modular Switch 16 Amps with indicator, one way single pole and one module complete all as specified
Suply only Modular sockets, 5 pin, 240 v, 50 Hz, 6 Amps two modules complete all as specified
Suply only Modular sockets, 5 pin, 240 v, 50 Hz, 16 Amps two modules complete all as specified
Supply only 3 pin 15 Amps Plug top suitable for Geyser points complete all as specified
Suply only Modular Fan regulator hum free 0-5 steps, 120 W, 240 V, 50 Hz, two module complete all as specified NOTE FOR SL ITEM NO. 12.00 TO 16.00 :- Existing make available at CAIR are Legrand / MK /Anchor-Roma. Contractor shall provide the material as per the make existing at site and as per site requirement only.
Supply only MCB TP 100 Amps, 415 Volts, AC, 50 Hz, 240 V, 10 kA, breaking capacity, complete all as specified.
Supply only MCB TPN 32 to 63 Amps, 'C' curve type, 415 Volts, AC, 50 Hz, 10 kA, breaking capacity, complete all as specified.
Supply only MCB SP 6 to 32 Amps, 'C' curve type, 240 Volts, AC, 50 Hz, 10 kA, breaking capacity, complete all as specified.
Supply only MCB SPN 6 to 32 Amps, 'C' curve Type 240 Volts AC, 50 Hz, 10 kA, breaking capacity, complete all as specified.
Supply only sheet metal enclosure single pole and neutral with a three pin and earth plug and socket complete with one MCB SP 20 Amps, 'C' Curve, 240 Volts AC, 50 Hz, 10 kA, breaking capacity, complete all as specified.
Supply only MCCB, 4 pole, 415 Volts, 63 Amp, 16 KA, 50 Hz, AC fixed in the existing / new LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified.
Supply only MCCB, 3 pole, 415 Volts, 125 Amps, 16 KA, 50 Hz, AC fixed in the existing / new LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified..
Supply only MCCB, 4 pole, 415 Volts, 200 Amps, 35 / 36 kA, 50 Hz, AC fixed in the existing / new LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified..
Supply only fan capacitor of 2.5 Mfd suitable for ceiling fans of any sweep, single phase 230 Volts complete all as specified..
Supply only fan Capacitor of 4.0 MFD suitable for exhaust fan single phase, 230 Volts complete all as specified.
Supply only tube light starter 230 volts single phase for 20/40 watts tube light fitting complete all as specified
Supply only FTL tube rods of 4 feet long 230 volts 36/40 watts capacity complete all as specified.
Supply only FTL tube rods of 2 feet long 230 volts 18/20 watts capacity complete all as specified.
Supply only CFL lamps, 18 watts, 2 pin, diagonal type (retrofit type) complete all as specfieid.
Supply only CFL lamps, 36 watts, 4 pin, complete all as specfieid.
Supply only LED bulbs 9/11 Watt complete all as specified and directed
Supply only angle holder suitable for LED lamp 9/11 W, complete all as specified
Supply only Copper Choke suitable for 1x18/20 Watts FTL fittings, 230 volts complete all as specified.
Supply only Electronic choke suitable for 2x36 Watts FTL fittings, 230 volts complete all as specified.
Supply only Electronic Ballast suitable for 1x36/40 Watts FTL fittings, 230 volts complete all as specified.
Supply only switch piano flush type 5/6 Amps single pole 230 volts one way all as specified
Supply only switch socket combination, 3 & 2 pin, 5 A, 240 V, flush type, multipurpose, controlled by one switch, complete all as specified and directed.
Supply only switch socket combination, 3 & 2 pin, 15 A, 240 V, flush type, multipurpose, controlled by one switch, complete all as specified and directed.
Supply only socket, 3 & 2 pin, 5 A, 240 V, 50 Hz, flush type, complete all as specified and directed.
Supply only ceiling rose three terminal white bakelite type complete all as specified
Supply only calling bell Ding Dong type 230 volts single phase all as specified
Supply only bell push switch single pole flush type 230 volts 5 Amps capacity all as specified
Supply only electronic fan regulator, 230 volts, 120 W, stepped stype complete all as specified
Supply only ceiling fan clamps for fixing of ceiling fans with rubber bushings complete all as directed.
Supply only PVC casing/capping of 20 mm size, ISI marked, complete all as specified..
Supply only PVC casing/capping of 25 mm size, ISI marked, complete all as specified..
Supply only PVC insulated/flexible copper cable 23/0.0052, 3 core 230 volts all as specified and as directed.
Supply only LED tube Rod, 18 Watt, suitable for existing FTL 40 W fittings, with high lumen output, environmental friendly, energy efficient LED, electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, complete as per Cat No CRYSTAL 1213T8DSTL18WLED865SGLASS of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Supply only, wall mounted LED tube light fitting with lamp, 9 Watt, 2 feet, with high lumen output, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, complete with diffuser, polyester louver with 9 watt LED tube & integrated electronic driver 9 W fitting as per cat No LUMILINEBS9WLED865SPCWH of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Supply only, wall mounted LED tube light fitting with lamp, 18 Watt, 4 feet, with high lumen output, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, complete with diffuser, polyester louver with 18 watt LED tube & integrated electronic driver 18 W fitting as per cat No LUMILINEBS18WLED865SPCWH of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Supply only, 42 W, LED, ceiling mounted, high efficient luminaire, 2'x2', Ultra modern designed architectural LED luminaire which provides soft-light and glare free symmetrical illumination suitable for ceiling, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 120 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH , 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, prewired and connecting with 3 Core, 1 sq mm sheathed copper flexible cable, including lamps complete all as specified and directed. MAKE:- Cat No.VENUSNEOHE2X2R18-42WLED840MODUGR<19 of Havells or techno-commercially equivalent model in Philips / CG / Syska complete with all accessories pre-wired, including tubes, connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and as directed.
Supply only, MCB DB TPN 4 way (Horizontal), double door, with Sheet metal enclosure, flush mounted, prewired, 415 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respecitve items.
Supply only, MCB DB SPN 4 way (Horizontal), double door with Sheet metal enclosure, flush mounted, prewired, 240 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respecitve items.
Disconnecting and removing the burnt cable end terminal at incoming of MCCB DB TPN / Cubicals, cutting suitable length of cable of incoming cable and adjusting cable from loop, preparing cable ends of any size, crimpling aluminium lugs of suitable size, connecting back with necessary bolts, nuts, washers, etc.,testing for any loose connections and making good the disturbed surfaces complete all as specified.. Note: The rate shall deemed to include for making hole in masonry / concrete to draw cables from loop and making good the disturbed surface matching with the adjacent surfaces, complete as per directions of Engineer-in-Charge.
Supply only Aluminium cable lugs of 10 to 25 sqmm size all as directed.
Supply only Aluminium cable lugs of 25 to 70 sqmm size all as directed.
Supply only Aluminium cable lugs of 70 to 95 sqmm size all as directed.
Demolishing old earthing pit, and providing new earthing pit with material and labour for earthing complete with Galvanized Iron earth plate electrode 600 mm x 600 mm x 6.3 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to GI earth wire of 4 mm dia by means of bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 15 mm bore (light grade) connected to earthing test point all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 40 mm bore light grade GI pipe for watering funnel wire mesh, PCC chamber in cement concrete (1:3:6), type C1 , manhole cover with RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover and MS frame etc., complete all as specified and as directed NOTES :- (i) The quoted rate deemed to include earth wire and protection pipe up to 7.5 metre from earth plate / earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
Arunachaleswara enterprises
Sai Ram Builders
H S S ENGINEERS AND CONTRACTORS
Solar Electricals and Electronics
Sri Sankar Enterprises
RASI AND COMPANY
M/S Sneha Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .