Pallavpuram
works of Maintenance and Stoppage Leakage of Power T/Fs at installed various 33/11 KV sub-stations under the jurisdiction of EDD-I, Mawana
2021_PVVNL_613185_1
59/EDC-2/MT/2021-22
Open Tender
Repair and Maintenance Services
Item Rate
30 days
Mawana
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE EDC-2
₹2,000
16 Sept 2021
24 Aug 2021
2 Sept 2021
24 Aug 2021
2 Sept 2021
24 Aug 2021
Amount
The Following works Maintenance & Stoppage Leakage of Power T/Fs at installed 33/11 KV sub-stations under Jurisdiction of EDD-I Mawana, with the following works:-
1. Opening of Jumpering Clamps form HV side of Power T/Fs. 2. Closing of Value of Conservative Tank. 3. Drain out of T/F Oil from T/F to Drum. 4. Opening of Section Windows with help of nuts & bolts etc. 5. Opening of HV side bushing with help of nuts, bolts & washers. 6. Opening of LV side Bushing with the help of nuts, bolts & washers etc. 7. Opening & refixing of HV side bushing Rod after remove carbon by amri clothes & filing and damaged rods replacement by New Bushing Rods in connecting rods properly with help of Gas Welding and changing of all Oil Packing of HV side bushing rods properly. 8. Opening & refixing of LV side bushing Rod after remove carbon by amri clothes & filing and damaged rods replacement by New Bushing Rods in connecting rods properly with help of Gas Welding and changing of all Oil Packing of LV side bushing rods properly. 9. Fixing of HV side bushing in flange with help of nuts, bolts & washers after changing all Oil Packing properly. 10. Fixing of LV side bushing in flange with help of nuts, bolts & washers after changing all Oil Packing properly. 11. Closing of Section Windows with help of nuts, bolts & washers after changing of all Oil Packing Properly. 12. Filling of T/F Oil from drum to T/Fs. 13. Opening of Value of Conservative Tank, properly. 14. Tightening of all nuts, bolts & washers of Top Plate of T/F, properly, for smooth & proper working. 15. Tightening of all nuts, bolts & washers of Radiators. 16. Fixing of Jempering Clamps for HV side & LV side of T/Fs.
M/s Shakti Enterprises
M/s Hind Electricals
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .