Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.5 LAdmitted-Finance WARD NO 2 KATHUA NEAR RAMLEELA GROUND NEAR RAMLEELA GROUND KATHUA JAMMU KASHMIR 184101 | KATHUA | JAMMU AND KASHMIR | 184101 | ₹9.5 L | L1 | Admitted-Finance |
| 2 | L2₹10.1 L+₹54,020 (5.67%)Admitted-Finance | ₹10.1 L+₹54,020 (5.67%) | L2 | Admitted-Finance |
| 3 | L3₹10.6 L+₹1.1 L (11.1%)Admitted-Finance | ₹10.6 L+₹1.1 L (11.1%) | L3 | Admitted-Finance |
| 4 | L4₹10.8 L+₹1.2 L (13.0%)Admitted-Finance | ₹10.8 L+₹1.2 L (13.0%) | L4 | Admitted-Finance |
| 5 | L5₹10.8 L+₹1.3 L (13.4%)Admitted-Finance | ₹10.8 L+₹1.3 L (13.4%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Patiaya Enterprises L5 | RATHER ELECTRICALS AND CONTRACTOR L7 | M/S DAYAL BUILD TECH L10 | M/s GCS Associates L6 | M/S RAJ ELECTRICAL CONTRACTOR L3 | M/S SIGMA CONSTRUCTION L11 | M/S SALARIA ENTERPRISES L9 | SUMIT SHARMA GOVT CONTRACTOR L1 | M/S SURYA ENTERPRISES L12 | M/S A A ENTERPRISES L4 | HRS ASSOCIATES L2 | M/S KUNDAL ELECTRICAL WORKS AND SUPPLIERS L8 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Auto-Transformers/Power Transformers :- A) Checking of Auto starting of fans, External cleaning of radiators,oil pumps OFAF/ONAF,Cleaning and checking of marshalling boxes of transformer/reactor and OLTC, (ii) Tightening of terminations, Checking of OLTC driving mechanism, Electrical checking/ testing of pressure relief device, Buchholz relay, OLTC surge relay/ checking of alarm/ trip and checking/ replacement of the gaskets of the terminal box, Checking / Tightning of earthing connections, Checking of earth resistance of Neutral, Replacement of Silca Gel of breathers and oil toping of transformers and tightning of bushing clamps on HV/IV/LV sides of 400 MVA,160 MVA,150 MVA Auto transformers and 20MVA to 50MVA Power transformers.Checking of space heater and illumination,etc.Required as per schedule of maintenance. | |||||||||||||||
| 1.01 | 133.33MVA , 220/132 KV | 1 | No. | 21,500 ₹21,500 | 39,000 ₹39,000 | 25,000 ₹25,000 | 29,900 ₹29,900 | 21,000 ₹21,000 Lowest | 26,000 ₹26,000 | 26,000 ₹26,000 | 21,000 ₹21,000 Lowest | 49,000 ₹49,000 | 21,000 ₹21,000 Lowest | 21,000 ₹21,000 Lowest | 26,000 ₹26,000 |
| 1.02 | 160 MVA , 220/132 KV | 1 | No. | 23,500 ₹23,500 | 39,000 ₹39,000 | 25,000 ₹25,000 | 29,900 ₹29,900 | 23,000 ₹23,000 Lowest | 26,000 ₹26,000 | 30,500 ₹30,500 | 23,000 ₹23,000 Lowest | 45,000 ₹45,000 | 23,000 ₹23,000 Lowest | 23,000 ₹23,000 Lowest | 30,000 ₹30,000 |
| 1.03 | 150 MVA , 220/132 KV | 1 | No. | 20,500 ₹20,500 | 35,000 ₹35,000 | 25,000 ₹25,000 | 27,900 ₹27,900 | 20,000 ₹20,000 Lowest | 26,000 ₹26,000 | 27,500 ₹27,500 | 20,000 ₹20,000 Lowest | 41,000 ₹41,000 | 20,000 ₹20,000 Lowest | 20,000 ₹20,000 Lowest | 27,000 ₹27,000 |
| 1.04 | 53.33 MVA , 220/33 KV | 1 | No. | 16,000 ₹16,000 | 30,000 ₹30,000 | 20,000 ₹20,000 | 24,990 ₹24,990 | 15,500 ₹15,500 Lowest | 21,000 ₹21,000 | 18,500 ₹18,500 | 15,500 ₹15,500 Lowest | 36,000 ₹36,000 | 15,500 ₹15,500 Lowest | 17,000 ₹17,000 | 18,000 ₹18,000 |
| 1.05 | 50 MVA , 132/33 KV | 1 | No. | 16,000 ₹16,000 | 25,000 ₹25,000 | 20,000 ₹20,000 | 21,300 ₹21,300 | 15,500 ₹15,500 Lowest | 21,000 ₹21,000 | 20,500 ₹20,500 | 15,500 ₹15,500 Lowest | 31,000 ₹31,000 | 15,500 ₹15,500 Lowest | 15,500 ₹15,500 Lowest | 20,000 ₹20,000 |
| 1.06 | 50 MVA 132/66 KV | 1 | No. | 15,500 ₹15,500 | 25,000 ₹25,000 | 20,000 ₹20,000 | 22,900 ₹22,900 | 15,000 ₹15,000 Lowest | 21,000 ₹21,000 | 18,500 ₹18,500 | 15,000 ₹15,000 Lowest | 26,000 ₹26,000 | 15,550 ₹15,550 | 15,000 ₹15,000 Lowest | 18,000 ₹18,000 |
| 1.07 | 31.5 MVA 132/11 KV | 1 | No. | 17,000 ₹17,000 | 25,000 ₹25,000 | 20,000 ₹20,000 | 20,200 ₹20,200 | 16,000 ₹16,000 Lowest | 21,000 ₹21,000 | 20,500 ₹20,500 | 16,000 ₹16,000 Lowest | 26,000 ₹26,000 | 16,000 ₹16,000 Lowest | 16,000 ₹16,000 Lowest | 20,000 ₹20,000 |
| 2.00Routine Maintenance of Auxilliary Transformers including checking of gaskets,checking and tightening of earthing connections,tightening of bushing clamps,replacement of Silica Gel,etc | |||||||||||||||
| 2.01 | 1MVA, 66/11KV Auxilliary Transformer | 1 | No. | 6,000 ₹6,000 | 18,000 ₹18,000 | 15,000 ₹15,000 | 4,700 ₹4,700 Lowest | 6,000 ₹6,000 | 15,000 ₹15,000 | 10,500 ₹10,500 | 6,000 ₹6,000 | 21,000 ₹21,000 | 6,000 ₹6,000 | 6,000 ₹6,000 | 10,000 ₹10,000 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
27 Mar 2026, 2:00 pmClosed
Executive Engineer Trans Line Maintt Division II
Office of the Executive Engineer Trans Line Maintt Division II JKPTCL Jammu
RATE CONTACT for Preventive Routine Breakdown Maintenance of Equipments for various Grid Stations and Transmission Lines falling under the jurisdiction of TLMD II JKPTCL Jammu for the year 2026 and 27 as specified in the SBD and BOQ
2026_PDD_305154_1
TLMD-II/J/19 of 2025-26 Dated 03-03-2026
Open Tender
Repair and Maintenance Services
Item Wise
365 days
Gladni Jammu, Miransahib, BB-I, Kathua, Chowadhi
As per NIT and SBD
3 documents required · 3 mandatory
₹2,950
Executive Engineer Trans Line Maintt Division II
₹50,000
28 Apr 2026
3 Mar 2026
30 Mar 2026
4 Mar 2026
27 Mar 2026
5 Mar 2026
Auto-Transformers/Power Transformers :- A) Checking of Auto starting of fans, External cleaning of radiators,oil pumps OFAF/ONAF,Cleaning and checking of marshalling boxes of transformer/reactor and OLTC, (ii) Tightening of terminations, Checking of OLTC driving mechanism, Electrical checking/ testing of pressure relief device, Buchholz relay, OLTC surge relay/ checking of alarm/ trip and checking/ replacement of the gaskets of the terminal box, Checking / Tightning of earthing connections, Checking of earth resistance of Neutral, Replacement of Silca Gel of breathers and oil toping of transformers and tightning of bushing clamps on HV/IV/LV sides of 400 MVA,160 MVA,150 MVA Auto transformers and 20MVA to 50MVA Power transformers.Checking of space heater and illumination,etc.Required as per schedule of maintenance.
133.33MVA , 220/132 KV
160 MVA , 220/132 KV
150 MVA , 220/132 KV
53.33 MVA , 220/33 KV
50 MVA , 132/33 KV
50 MVA 132/66 KV
31.5 MVA 132/11 KV
Routine Maintenance of Auxilliary Transformers including checking of gaskets,checking and tightening of earthing connections,tightening of bushing clamps,replacement of Silica Gel,etc
1MVA, 66/11KV Auxilliary Transformer
250KVA, 33/0.440 KV Auxilliary Transformer
250KVA, 11/0.440 KV Auxilliary Transformer
Miscellaneous works related to maintenance of Various Transformers at all voltage levels:
Draining/ De-sludging of transformer oil of transformers
Filling of oil, filtration and dehydration of transformer including installation of vacuum pump to be provided by the Department.
Reparing/replacement of cooling fans of transformers including replacement of damaged winding, bearing etc.
Lifting of top lid of power transformer for complete physical inspection & replacement of gaskets.
Replacement of damaged core bolts/Earthing strip etc.
Making temporary arrangements for carrying out filtration round the clock including setting up of temporary shed.
Carriage of Filtration Plant/Oil Storage Tank along with pipes and accessories with the help of crane/labour from Divisional Stores/Stacking Site to work site.
Maintt. Of Filteration plant by way of replacement of Mobile, Filter pads, MCB's switches etc for effective Filteration.
Testing of Transformer:-
Testing of Transformer:- Tandelta testing of bushing/ winding & BDV testing of transformer oil.other tests on the transformer like ratio test, IR value/ Magnetic balance/ short circuit test etc, kits for testing shall be provided by the department.
DGA and PPM of Transformer from accredited laboratories.
Replacement of damaged/outlived bushing having high tan delta including crane/ mechanical equipment if required.
220 KV Bushing
132 KV Bushing
66 KV Bushing
33 KV Bushing
Overhauling of Circuit Breaker :- VCB/MOCB/SF6 Checking of oil/gas pressure drop during duty cycle operation check, Checking of auto-starting / stopping of oil pump,pressure switch setting,etc, Checking of healthiness of accumulator by checking the pre-charging pressure when building up pressure from zero, Checking of operation of safety valve, Cleaning of breaker units, checking of protection equipments and replacement of defective ones, i.e., complete inspection and testing of SF6/VCB/MOCB type circuit breakers inclusive of operating mechanism.Checking of driving mechanism, trip/closing circuits/ checking of spring charge motor and checking of tripping and closing coils.checking of equipment earthing and strucure earthing. Maintaning gas levels, venting of circuit breakers, replacement of o-rings , gas kits including circuit breaker analysis by Circuit breaker analyser.Checking of space heater and illumination.Required as per schedule of maintenance
220KV SF6 Breaker
132KV SF6 Breaker
66 KV MOCB/SF6
33 KV VCB
Replacement of damaged pole of the circuit Breaker including carriage of the Equipment from divisional store to the site of work and back carriage of the damaged equiupment to the divisional store.
220KV SF6 Breaker
132KV SF6 Breaker
66 KV MOCB/SF6
33 KV VCB
Repairing/Replacement of Single phase Spring Charging motors of Vacuum and SF6 Circuit Breakers.
Replacement of Vacuum circuit Breaker including dismantling of the old/damaged Equipment,carriage from divisional store to the site of work,erection of new breaker and back carriage of the damaged equipment to the divisional store.
CVT's /CT's /PT's :- Visual checking of earthing HF point (in case it is not being used for PLCC,Checking of any breakage or cracks in porclean insulator, Cleaning of CVT capacitor stacks and tightness of terminal connections,Checking and tightness of all connections including earth connections.Checking of healthiness of gaskets, Checking of neutral earthing in CVT, healthiness of all gaskets and oil level and its topping.Measurement of IR value and tightening of all connections and droppers.Primary injection test of CT/PT, Tan delta,knee point value, burden etc.
Plugging of oil leakages including replacement of worn out gaskets,etc
Replacement of damaged CT/PT including carriage of the Equipment from divisional store to the site of work and back carriage of the damaged equiupment to the divisional store.
Surge Arrestors :- Checking of leakage current(third harmonic resistive current), Testing of counters and leakage current meters, Cleaning of insulators, Checking of earth connections between surge arrester,surge monitor and earth, Checking of leakage current after cleaning of porcelain surface, cleaning of LA insulators. Measurement of IR value and tightening of droppers.
Replacement of damaged Surge Arrestor including carriage of the Equipment from divisional store to the site of work and back carriage of the damaged equiupment to the divisional store.
Isolators :- Maintenance of linkages including transmission gears, stopper bolts. Cleaning of auxiliary switch contacts and greasing with silca grease, cleaning of support insulators, termination contacts, checking of electrical / mechanical interlocks with E/S and CB, mounting bolts, alignment, nuts, pins, space heater, illumination, healthiness of gaskets, auxiliary contacts, alignment of earthing blades, operation of earth switch, almunium / copper flexible conductor, earth connections of structures and MB. lubrication of operating mechanism, hinges lock joints, levers, bearings, main contacts, cleaning of post insulators, tightening of clamps.
Replacement of damaged Isolators including carriage of the Equipment from divisional store to the site of work and back carriage of the damaged equipment to the divisional store.
Reparing/Replacement of Three phase motors of isolators including replacement of damaged winding and bearing.
Droppers/Jumpers/Clamps:
Replacement of damaged / burnt droppers or jumpers of isolators/ breakers/transformers /CT/PT etc. in 220/132/66/33 KV Yard.
Replacement of damaged/burnt PG/ PAD/T/CT/Bushing clamp etc. in 220/132/66/33 KV Yard.
Tightening/replacement of nuts and bolts of Clamps/Jumpers/Droppers in 220/132/66/33KV yard
Post Insulators :- Checking of insulators for cracks and cleaning of insulators and its replacement, if required.
Illumination System :-
Checking of healthiness of fittings in street lights,station buildings, outdoor switch yard, Tightening of terminals, etc. and replacing damaged wire and lamp with the help of skylift crane
Replacement of damaged flood light/LED (100W,150W,200 W) with the help of crane/ladder in the outdoor switch yard.
Replacement of LED/CFL along with fitting with the help of ladder in the control room/ division building/office complex
Battery Bank: Checking and cleaning of battery cell terminals, application of petroleum gelly, if required, conduction of battery impendence test and discharge test checking voltage temperature, current, sp. Gravity of individual cells as well as terminals voltage, battery discharge testing etc.Checking of positive/Negative earth fault of dc.Terminal tightening.
Battery Charger :- Checking of control cards, measurement of test point voltage values, testing of DC earthfault and U/V relays, IR measurement of charger transformer, checking of earthing etc. Checking of charger panel / DCDB for electrical connections, cleanliness etc.
Repair of battery charger by way of replacement of PCB Cards, Relay, meters, contractor, coils, Fan etc as per site requirement
Protection System :- Checking of relays and application of CCl4 for cleaning, replacement of worn out / defunct relays, checking and replacement of control wiring, if required, primary & secondary injection testing,software settings etc.
Cleaning of cable trenches/ ducts including of dressing of cables, trays, racks , repair of damaged duct covers etc
sub main
Gantry Columns and Beams :- Tightening of all nuts / bolts and providing of missing nuts / bolts and replacement of damaged members.
L.T. Transformer :- Testing of oil BDV, IR measurement, Testing /checking of OTI,WTI and Buchholz (if provided, Checking of healthiness of Pressure relief diaphragm, Checking healthiness of Buchholz relay.
L.T. Panel: Cleaning of panels,bus bar insulators etc. Relays Testing, Tightning of all electrical connections,Checking of indicating meters ,Check for change-over facility, if provided,Check operation /indications in OFF Load condition of MCCB,
Earthing Mat :- Measurment of earth resistivity, checking of electrical continuity of equipment earthings, tightening of earthing connectors, removal of rust from bolted earth connectors and tightening and additional earthing wherever required. 220/132/66/33 kV
DC Distribution Board :- Checking of connections, wiring, replacement of wiring if needed and checking of healthiness of all D/C and dc circuits of 220/132/66/33 KV yards
AC Distribution Board :- Checking of connections, wiring, replacement of wiring if needed,fuses,MCB,bus bar CT, relays,MFM,LT switchs etc and checking of healthiness of all connections and AC circuits of 220/132/66/33 KV yards
Control cables:- Replacement of damaged/outlived/burnt control cables of different cores including proper ferruling, thimbling and tagging and finally with all appropriate connections including lifting of duct covers before taking up work and placing them back after completion of work.
below 10 core
above 10 core
Marshalling kiosk:- checking of all Terminal blocks, space heaters, light illumination, checking of all connnections and its cleaning. Fixing of cable glands earthing and checking of all other electrical accessories .
Capacitor Banks :- Checking/ tightening of capacitor cells terminals, reactor and checking its wiring connection and its control circuit.etc
Replacement of damaged contactors/MCB in Marshalling Kiosk, Distribution Boards, Transformer MK's etc.
BUS BAR :- Replacement of damaged ACSR Conductor along with its fittings by lowering down the conductor, removing of fittings & clamps, replacing the conductor and re-erecting the string after replacement.
220 KV yard
132 KV yard
66 KV yard
33 KV yard
Automatic voltage regulator:- checking and tightening of connections, auto control unit, oil and its overhaulling
Diesel Generator set: Maintenance and checking of its operation, air filter, oil filter, fan conveyer belt, charging battery, AMF Panel etc.
Removal of wild vegetation/Deweeding of switch yard
Painting of outdoor equipments (Transformers, MK's, CT/PT/CVT, Protection wall, Circuit breaker, isolators,Steel tubular/PCC poles, joist etc.
Painting of 50 MVA Power Transformer
Painting of 133.33/160MVA/150MVA Auto Transformer
Repairing of fire protection wall including painting
AC Units: Checking and Servicing of Installed AC unit inside control room (1- 3 Ton)
White-Washing of Control Room/Residencial Quarters/Office building at Grid Station.
Upkeep of Sanitary installed in the control room/ office building/division building/residential quarters/Toilets and replacement of any damaged item if required.
Upkeep of electrical accessories installed in the control room/ office building/division building/residential quaters/Toilets and replacement of any damaged item if required.
Civil Works:
Providing and laying of cement concrete (1:5:10)
Providing and laying of cement concrete (1:2:4)
Providing and laying of cement concrete (1:3:6)
Providing and laying of cement concrete (1:1.5:3)
Providing and laying of RCC Works (1:2:4)
Providing and laying of RCC Works (1:1.5:3)
Providing and laying of RCC Works (1:3:6)
Plastering works
Applying wall putty
Painting with emulsion
Painting with Aluminium paint
Painting with Synethic enamal paint
Applying priming coat with red oxide
Maintaining of flower beds
Maintaining of lawns
Earth work in excavation
Store handling:
Unloading / Loading of CT/CVT/PT/LA/CB/C&R Panel/ bushing/ Isolators etc in divisional store Gladni including manual Carriage within store yard
Shifting and Stacking of CT/CVT/PT/CB/ C&R Panel/Isolators/LA/bushing etc in divisional store Gladni including manual Carriage within store yard
Shifting and Stacking of empty barrel/battery cell in divisional store Gladni including manual Carriage within store yard
Unloading / Loading/Stacking of Angle iron, Tor steel , Gantry structure material in divisional store Gladni Including manual Carriage within store yard
Unloading / Loading/Stacking of AC Distribution Board/DC Distribution Board in divisional store Gladni
Unloading / Loading/Stacking of PVC Control cables in store Gladni including manual Carriage within store yard
below 10 core
above 10 core
Unloading / Loading/Stacking of Transformer Oil in store Gladni including manual Carriage within store yard
Loading/unloading of Transformer Oil tank of 15000lts /25000lts with the help of crane.
Loading/unloading of Transformer Oil Filteration Plant 6000LPH with the help of crane.
Loading/unloading of Transformer Oil Filteration Plant 5000LPH with the help of crane.
Loading/unloading of Auxilliary transformers with the help of crane:
Providing of skilled/ semi skilled/ un skilled labour for the works which are not covered from S.No. 1 to 63
Skilled labour(Electrician/Fitter)
Semi- skilled labour(Asstt. Electrician/Asstt. Fitter)
Un skilled labour
Carriage of T&P and other allied material from divisional store to the site of work and back carriage of T&P
From Divisional Store to Grid Station Gladni (Average distance 500 Mts)
From Divisional Store to Grid Station Miransahib (Average distance 17 Kms)
From Divisional Store to Grid Station Bari-Brahamna I (Average distance 17 Kms)
Transmission line S/C
Checking and tightening of jumpers
Replacement of damaged /burnt out jumpers
Fixing of damper/vibrator on earthwire/ACSR Conductor
Transmission line D/C :- ( Including carriage of T&P from stores and Shutdown Factor)
Checking and tightening of jumpers
Replacement of damaged /burnt out jumpers
Fixing of damper/vibrator on earthwire/ACSR Conductor
Replacement of damaged disc insulators
Tension string
Suspension string
Repairing of power conductor when lowering of conductor is necessary. Complete job including laying of conductor, making of compression joint, if any, rough sagging tensioning of conductor, fixing dead end assembly etc. upto span of 500 meter tension
Stringing and saging of ACSR conductor including sagging, tensioning, fitting of dead end assamblies etc.(complete job)
Repairing of ground wire when lowering of conductor is necessary. Complete job including laying of conductor, making of compression joint, if any, rough sagging tensioning of conductor, fixing dead end assembly etc. upto span of 500 meter tension
Stringing and saging of ground wire including sagging, tensioning, fitting of dead end assamblies etc.(complete job)
Survey of Transmission Line ( Which includes assessment of damaged foundation, protection wall, route allignment, corridor between tower to tower, components of towers etc.)
Tower S/C and D/C:-( Including carriage of T&P from stores and Shutdown Factor)
Foundation:- Repairing of damaged foundation and protection wall(Revetment) including back filling of earth with RCC concreating.
Provision of providing crate wall (Gabbon wall)
Tightening of nuts and bolts of tower superstructures replacement of missing ones.
a) Tower weight more than 4 tonnes to 7.5 tonnes
b) Tower weight more than 7.5 tonnes
Checking / tightening of tower footing earthing bolts and measuring tower footing resistance.
Branch cutting: under the coridor of 132 KV S/C and D/C transmission line 16 mtr and under tower structure
Replacement of missing tower members.
Reparing damaged conductor by using helical sleeve or Bolted or by shorting method with out lowering the conductor
Fixing of anti-climbing device/Bird Guard over S/C & D/C tower
Fixing of phase plates/No. plates/danger plates over S/C & D/C tower
Fixing of repair sleeves compression type for over ACSR conductor
Store handling:
Loading/Unloading of T&P Material for Transmission Line works including Four Sheaves pulley,Pulleys,Ropes,Compression machine etc in divisional stores Gladni including manual carriage within store yard.
Loading/Unloading of Cement in divisional store Gladni including manual Carriage within store yard
Loading/Unloading of tower material in divisional store Gladni including manual Carriage within store yard
Loading/Unloading of Disc Insulators/Fittings in divisional store Gladni Including manual Carriage within store yard).
Loading/Unloading of ACSR/AAA Conductor etc in divisional store Gladni Including manual Carriage within store yard.
Shifting and re-stacking of tower material within store premisis
Shifting and re-stacking of ACSR/AAA conductor within store premisis
Shifting and re-stacking of Disc Insulators/Fittings within store premisis
Providing of Skilled /Semi-Skilled / UnSkilled labour for the works which are not covered from S.No. 1 to 10
Skilled Labour ( Rigger)
Semi-skilled Labour ( Asstt. Fitter)
UnSkilled Labour
Carriage of T&P and other allied material from divisional store to site of work and back carriage of T&P
Average distance upto 20 Km
Average distance upto 40Km
Average distance upto 60Km
Average distance upto 85Km
Providing and fixing of C.P Brass bib cock confirming to IS 8931
Providing and fixing of PVC connection pipes and waste pipes
Providing and fixing of 10 Ltrs white viterous China flushing Cistern (European type) complete
Providing and laying of water proofing treatment on roof of office building/quarters
Providing and fixing of PVC pipes for drainage of roof water
Repair of existing Electrical wiring and fixtures including wire, switch and holders
Washing/dry cleaning of bed sheets/curtains
Repair and rewinding of ceiling/walls fans
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
SBD.pdf
Tender Documents • 0.91 MB
BOQ_991101.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .