ASSISTANT EXECUTIVE ENGINEER
O/o AEE PWD ELECTRICAL SUB DIVISION KOLLAM
DEPOSIT General Education annual Plan 2022 General Civil Work 2023 Renovation of Laboratories for Govt Higher Secondary School Anchal West Kollam General Electrical Work
2024_PWD_674448_2
PWD/BLDG/EST/7670/2024
Open Tender
Electrical Works
Item Rate
30 days
Anchal west
Please refer tender document
9 documents required · 9 mandatory
₹2,760
₹29,607
9 Sept 2024
3 Jul 2024
15 Jul 2024
3 Jul 2024
10 Jul 2024
3 Jul 2024
Amount
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
90.3.20.3:Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
OD25008/2024-2025:Dismantling the existing 1200mm sweep ceiling fan, scrapping, cleaning, overhauling, greasing the bearing, reassembling and painting the same using suitable colour enamel paint, refitting the same in position and giving connection etc. as required.
OD25184/2024-2025:Supply and renewing fan condenser of ceiling fan in place of faulty ones and giving connection.
90.4.9:Charges for cutting holes suitable for accommodating exhaust fans above 305mm sweep and up to 450mm sweep including plastering colour washing etc. as required.
OD25009/2024-2025:Supply conveyance, installation , testing and commissioning of exhaust fans of size up to 450mm in the existing opening, fixing necessary anchor bolts / bolt and nuts etc. as required including giving connections with the supplied wire along with the exhaust fan. 380mm Heavy Duty Exhaust Fan working on 230 V A/C
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
1.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
OD25024/2024-2025:Supply and providing Sub Main Disribution Board with IP42 protection complying to IEC 61439-2 with copper bus bar neutral link earth bus etc suitable for providing 3 pole MCCBs as incoming and outgoing fixed on wall using necessary anchor bolts including cutting hole on the wall , making good the damages, colour washing etc. as required. (Model No.SMDB-TN250D,O/G- 250A 8 Way of M/s L&T Enersys or equivalent - 8 way
OD25030/2024-2025:Supply & Fixing Single Phase Voltmeter accuracy Class 1Digital LED Type 96x96mm
OD25031/2024-2025:Supply & Fixing Single Phase Ammeter accuracy Class 1
OD25026/2024-2025:Supply and fixing 20 A, HRC Fuse Base with 2A HRC Fuse link
OD25027/2024-2025:Supply & fixing 2 A, 415 V, 2 way neutral link mounted on DMC/ SMC base.
OD25028/2024-2025:Providing and fixing Blue colour LED indicator, AC/DC, 22.5 mm cut out dia in existing panel and giving connection complete
OD25029/2024-2025:Providing and fixing Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia in existing panel and giving connection complete
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.1:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD25040/2024-2025:Supplying and fixing following way, sheet steel, MCB enclosure suitable for 4 pole MCB, 240 volts, on surface/ recess, complete with powder painted including earthing etc. as required. (But without MCB/RCCB/ isolator) 4 way, Single door
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
OD25038/2024-2025:Supplying and clamping the following sizes of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required. 20 mm dia
OD25039/2024-2025:Supplying and clamping the following sizes of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required. 25 mm dia
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
90.12.7.31:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
OD25111/2024-2025:Supply and providing test joint for the earthing system using 2 NOs of the following sizes of strips including cutting and bending to shape ,drilling necessary holes and fixed to the watering pipe etc as required 2x25x3 mm tinned copper strip
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
OD25109/2024-2025:Supply and providing 25x6 mm brass bolt and nut with washer including drilling holes as required
OD25110/2024-2025:Supply and providing 25x3 mm brass bolt and nut with washer including drilling holes as required
OD25175/2024-2025:Supply,Installation,Testing and commissioning of 3 kva 2 hour backup Minimum VAH 8640 per UPS SMF battery of reputed approved make exide/quanta), 12v 120ah x 6 nos or above with rack and interconnecting cables
OD25176/2024-2025:Supply, installation, and commissioning of 3kva UPS stand-alone Configuration.builtin isolation transformer Single phase in and out. with indoor (IP20) Input pf 0.99, it shall be 100% generator compatible, with Efficiency > 83 % and output power factor unity (3kVA =3kW), including all accessories etc as required. The acoustic noise at 1m of the system should be<55dB.The system shall comply to IEC /EN 62040-1,2,3 and relevant IS standard along. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic & manual bypass switch. The system shall have IGBT rectifier and inverter. With quick charge and programable output socket. Including conformal quoting for all PCB’s Camparable/Approved brands Numeric-legrand/APC/GE
OD25146/2024-2025:Supply,Installation,Testing and commissioning of 5 KVA 2 hour backup Minimum VAH 15600 per UPS SMF battery 12v 65ah x 20 nos with rack and interconnecting cables.Make-Exide or Equivalent
OD25108/2024-2025:Supply, Installation,Testing and Commissioning of 5KVA UPS stand-alone Configuration builtin isolation transformer. Three phase input and single phase out. with indoor (IP20) Input pf 0.99, it shall be 100% generator compatible, with Efficiency > 83 % and output power factor unity (5kVA =5kW), including all accessories etc as required. The acoustic noise at 1m of the system should be<55dB.The system shall comply to IEC /EN 62040-1,2,3 and relevant IS standard along. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic & manual bypass switch. The system shall have IGBT rectifier and inverter. With quick charge and programable output socket. Including conformal quoting for all PCB’s Make-Numeric-legrand or Equivalent
OD29525/2024-2025:Supplying , Installation, Testing and Commissioning of Three Phase Surge Protection Device as per EN 61643-11/ IEC 61643-11 suitable for protecting Class 1+Class II Modular combined lightninig current and surge arrester as TT and TN-S systems (3+1 configuration). Lightning Impulse current upto 50kA with a response time (tA) less than 100 ns. The Lightning impulse current shall be min 25/50kA suitable for mounting on Din rails. Easily replicable protection module having indication green to red
Jose S
Bidder Name
N.SIVA PRASAD
Jose S
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1055790.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .