Loading…
Loading…
Tender Value
₹60.9 Cr
EMD Value
₹60.9 L
Closing Date
10 Aug 2026, 2:00 pm
Chief Executive Officer
CONSTRUCTION OF INTERGRATED ADMINISTRATIVE BUILDING FOR AMBAJI AREA DEVELOPMENT AND PILGRIMAGE TOURISM GOVERNANCE AUTHORITY, AMBAJI, GUJARAT
319712
AmdaOfficeBLDG
Open
Civil Works
Banaskantha
8 documents required · 8 mandatory
₹21,240
Chief Executive Officer AADPTGA, Ambaji
₹60.9 L
2 Jul 2026
2 Jul 2026
2 Jul 2026
9 Jul 2026
2 Jul 2026
A Sub-Total Amount (1+2+3+4+5+6+7+8)
1.01 Excavation for foundation upto 1.5 m depth including sorting out and stacking of useful
materials and disposing off the excavated stuff upto 50 Meter lead.(A) Loose or soft
1.02 Excavation for foundation upto 1.5 m depth including sorting out and stacking of useful
materials and disposing off the excavated stuff upto 50 Meter lead.(B) Dense or Hard
1.03 Excavation for foundation for depth from 1.5 m to 3.0 m including sorting out and
stacking of useful materials and disposing off the excavated stuff upto 50 Meter
lead.(A) Loose or soft soil cu. m 134.95 2653.55
1.04 Excavation for foundation for depth from 1.5 m to 3.0 m including sorting out and
stacking of useful materials and disposing off the excavated stuff upto 50 Meter
lead.(B) Dense or Hard soil cu. m 168.81 2575.17
1.05 Excavation for foundation for depth from 3.0 m to 5.0 m including sorting out and
stacking of useful materials and disposing off the excavated stuff upto 50 Meter
lead.(A) Loose or soft soil cu. m 148.17 5453.18
1.06 Excavation for foundation for depth from 3.0 m to 5.0 m including sorting out and
stacking of useful materials and disposing off the excavated stuff upto 50 Meter
lead.(B) Dense or Hard soil cu. m 181.13 5453.18
1.07 Extra for additional depth more than 5.0 m for excavation for foundation including
sorting out and stacking of useful materials and disposing of the excavated stuff upto
50 m lead.(A) Loose or soft soil cu. m 21.96 107.93
1.08 Extra for additional depth more than 5.0 m for excavation for foundation including
sorting out and stacking of useful materials and disposing off the excavated stuff upto
50 m lead.(B) Dense or Hard soil cu. m 21.96 107.93
1.09 Add extra for Disposing off the excavated stuff of above items for lead of (A) 50 m to
1.1 Add extra for Disposing off the excavated stuff of above items for lead of (B) 100 m to
1.11 Add extra for Disposing off the excavated stuff of above items for lead of (C) 200 m to
1.12 Add extra for Disposing off the excavated stuff of above items for lead of (D) 300 m to
1.13 Add extra for Disposing off the excavated stuff of above items for lead of (E) 400 to
1.14 Filling available excavated earth (excluding rock) in trenches. plinth, sides of
foundations etc. in layers not exceeding 20 cm. in depth consolidating each disposited
layer by ramming and watering. cu. m 135.56 14904.88
1.15 Filling in plinth with sand under floors including watering ramming, consolidating and
dressing complete cu. m 440.35 320.40
1.16 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and
saplings of girth up to 30 cm measured at a height of 1 m above ground level and
removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.
1.17 Clearing grass and removal of the rubbish up to a distance of 50 m outside the
periphery of the area cleared. cum 7.51 3419.01
1.18 Supplying chemical emulsion in sealed containers including delivery as specified.
Chlorpyriphos/ Lindane emulsifiable concentrate of 20% litre 196.97 960.00
1.19 Along the external wall below concrete or masonry apron using chemical emulsion @
2.25 litres per linear metre including drilling and plugging holes etc.:
With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration metre 44.85 222.21
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
1.2 Treatment of soil under existing floors using chemical emulsion @ one litre per hole,
300 mm apart including drilling 12 mm diameter holes and plugging with cement
mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With
Chlorpyriphos/Lindane E.C. 20% with 1% concentration Sq m 260.15 2550.99
Treatment of soil under existing floors using chemical emulsion @ one litre per hole,
300 mm apart including drilling 12 mm diameter holes and plugging with cement
mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With
Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Detail of cost each plant Areca Palm having ht. 1.80 m to 2.10 m with 8 to 10 suckers,
1.22 well developed, fresh and healthy with lush green foliage in 30 cm size of Earthen pot / Each 382.50 58.00
Detail of cost each plant Rhapis Palm specimen having ht. 1.50 m to 1.65 m with 40 to
1.23 50 lush green suckers, well developed, fresh & healthy foliage leaves in 40 cm size Pot Each 598.40 30.00
/ Challi / Tray
Detail of cost each plant Schefflera Green plant (three in one), mounted on moss stick
1.24 90 cm, well developed with full of fresh & healthy leaves from bottom to top with rich Each 296.10 26.11
foliage in 25 cm size of Earthen pot / Plastic pot Each 1 240.00 240.00 Total
Detail of cost each plant Spathiphyllum (peace lilly), having 15 cm to 25 cm ht.
1.25 blooming stage with fresh & healthy foliage well developed in 15 cm of Earthen Each 101.05 6.89
pot/plastic pot
Detail of cost each plantCanna dwarf of height 25 to 30 cm., 2 to3 suckers in 20 c.m
1.26 Earthen Pot/Plastic Each 39.50 48.89
Detail of cost each plant Bird of paradise well developed with fresh & healthy 90 cm to
120 cm ht in 30 cm Earthen Pot/ Plastic Pot
Detail of cost each plant Ixora dwarf different colour having 10 cm to 15 cm ht., well
1.28 developed with fresh & healthy foliage with bloom in 15 cm Earthen Pot/Plastic Pot Each 148.05 198.33
Detail of cost each plant Lantana sp. of different colour, well developed with fresh &
healthy foliage with bloom in 20 cm Earthen Pot/Plastic Pot
Detail of cost each plant Lantana sp. of different colour, well developed with fresh &
healthy foliage with bloom in 20 cm Earthen Pot/Plastic Pot
Detail of Cost each plantClerodendrum inerme having ht. 25 cmto 30 cm multi
branched in 25 cm size ofEarthen Pot / Plastic Pot
Detail of Cost each plantClerodendrum inerme having ht. 25 cmto 30 cm multi
branched in 25 cm size ofEarthen Pot / Plastic Pot
Detail of cost each Plant Bigonia gracilis creeper (yellow)of height30 cm to 45 cm,
Healthy, well developedin Poly/Gunny Bag.
Details of cost of each plant. Minia erectra plant of height 45-60 cm. multi branches
well developed in poly bag of size 20 cm.
1.22 Azadirachta indica ( Neem ) height 120-130cm in polybag size 25 cm Each 72.20 30.00
1.23 Detail of cost each plant Ficus retusa well branched height120-135 cm. in poly bag
1.24 Providing and stacking of Michelia champa (Golden Champa) of height 90-105 cm.in
earthen pot of size 25 cm as per direction of the officer-in-charge 81.81 44.00
1.25 Providing and stacking of Plumeria acutifolia of height 150-165 cm. with 3-4 branches
in big size HDPE bag as per direction of the officer-in-charge. 181.78 23.00
Providing and stacking of Plumeria alba of height 165-180 cm. with 3-4 branches and
thick stem in big size HDPE bag as per direction of the officer-in-charge.
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
Providing and stacking of Tabebuia sp. of height 150-165 cm. in poly bag of size
cm as per direction of the officer-in-charge.
Providing and stacking of Plumeria alba of height 165-180 cm. with 3-4 branches and
thick stem in big size HDPE bag as per direction of the officer-in-charge.
Providing and stacking of Largerstroemia indica of height 90-105 cm. multibranched in poly bag
of size 25 cm as per direction of the officer-in-charge.
Total of sub-head
2 CONCRETE WORK
2.01 Providing and laying cement concrete 1:4:8 (1- Cement : 4- coarse sand : 8- hand
broken stone aggregates 40 mm nominal size) and curing complete excluding cost of
formwork in (A) Foundation and Plinth cu. m 2627.15 1075.39
2.02 Providing TMT Bar FE 550D reinforcement for R.C.C. work including bending, binding
and placing in position complete upto floor two level kg 94.05 1487103.91
2.03 Extra for additional lift of concrete for all R.C.C. work above floor two level excluding
cost of reinforcment cu. m 39.53 2699.06
2.04 Extra for additional lift of reinforcing steel for all R.C.C. work above floor two level.
2.05 Providing and laying damp proof course 25mm thick cement concrete 1:2:4 (1-Cement
: 2 coarse sand : 4 stone aggregate 10 mm nominal size) and curing complete
2.06 Providing and laying in position Ready Mixed M-350 grade concrete for reinforced
cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit
mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as per
mix design of specified grade for reinforced cement concrete work including pumping
of R.M.C. from transit mixer to site of laying, excluding the cost of centering shuttering
finishing and reinforcement including cost of admixtures in recommended proportions
as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in - charge. Without
Fly Ash(Min cement level as per latest IS 456 shall be maintained) (Cement level
2.07 Providing and laying in position cast in situ reinforced cement concrete waffle slab,
square or rectangular as per design and shape for floors and roofs in M35 , including
flush or deep ruled pointing at joints in cement mortar 1:2 (1 cement : 2 Fine sand),
including centering shuttering, strutting and propping etc. and removal of the same for
in situ reinforced concrete work in. for all floor levels but excluding the cost of
2.08 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne
capacity after excavating earth to an average of 22.5 cm depth, dressing to camber
and consolidating with road roller including making good the undulations etc. and re-
rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.
2.09 Laying, spreading and compacting stone aggregate of specified sizes to WBM
specifications in uniform thickness, hand picking, rolling with 3 wheeled road/vibratory
roller 8-10 tonne capacity in stages to proper grade and camber, applying and
brooming requisite type of screening / binding material to fill up interstices of coarse
aggregate, watering and compacting to the required density . cum 878.46 904.79
2.10 Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from
batching plant. The ready mixed concrete shall be laid and finished with screed board
vibrator , vacuum dewatering process and finally finished by floating, brooming with
wire brush etc. complete as per specifications and directions of Engineer-in-charge.
(The panel shuttering work shall be paid for separately).
(Note:- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement
used as per design mix is payable/ recoverable separately).
Total of sub-head
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
3.01 Brick work using common burnt clay building bricks having crushing strength not less
than 35 kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:6 (1- Cement : 6 -fine
sand)(B) Conventional cu. m 4172.60 369.55
3.02 Extra for brick work in superstructure above plinth level upto floor two level (B)
Conventional cu. m 278.93 369.55
3.03 Extra for brick work in superstructure above floor two level Item No. 2(6.13) (B)
Conventional per floo r per cu. m 41.70 152.20
3.04 Half brick masonry in common brunt clay building bricks having crushing strength not
less than 35 Kg/Sq.Cm. in Cement mortar 1:3 ( 1-Cement : 3-coarse sand ) with 2 Nos
of 6mm Mild steel round bars after every three course embedded in Cement Mortar in
foundation and plinth (B)Conventional Sq m 689.44 2018.03
3.05 Extra for brick work in superstructure above floor two level Item No. 5 (B) Coventional/
AAC Block Work cu. m 42.01 531.11
3.06 Extra for half brick masonry in superstructure above plinth level upto floor two level. (B)
Conventional/ AAC Block Work Sq m 53.89 714.45
3.07 Extra for half brick masonry in superstructure above floor two level.(B) Conventional/
AAC Block Work Sq m 6.24 908.42
3.08 Masonary work using Aerated light weight concrete block having crushing strength not
less than 35 kg/sqcm for super structure above plinth level upto floor two level in
cement mortar 1:5 ( 1 cement : 5 fine sand ) complete as per Technical Specification
Total of sub-head
4.01 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. Height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (A) Foundations Footings Bases of
Columns etc. and Mass concrete. Sq m 178.61 5130.80
4.02 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. Height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (B) Flat surfaces such as soffits of
supspened floors slabs Landings and the like. (1) Floors etc. upto 200 mm in
4.03 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. Height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (B) Flat surfaces such as soffits of
suspended floor roof slabs Landings and the like. (2) Floors etc. above 200mm in
4.04 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (C) Vertical surface such as walls (any
thickness) partitions and the like including attached buttresses & string course & the
4.05 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (G) Columns PillarsPosts and struts.
(1) Square Rectangular Polygonal in plan. Sq m 315.87 4042.77
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
4.06 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (H) (1) Sides and soffits of Beams
Beam Haunchings cantilevers Girders Bressumers and Lintels not exceeding 1 M. in
4.07 Providing formwork of ordinary timber planking so as to give a rough finish including
centering shuttering strutting and propping etc. height of propping and centering below
supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ
reinforced concrete and plain concrete work in. (M) Staircase with sloping or stepped
soffits including risers and stringers excluding landing. Sq m 256.34 534.29
Total of sub-head
5 WOOD WORK & JOINERY WORK
5.01 Providing wood work in frames of Doors, windows cleare story windows and
othersimilar works wrought, framede and fixed in position. (A) Indian Teak Wood Cu.
5.02 Provoding and fixing flush door shutters, solid core construction with frame of first class
hardwood with cross board and face veneer or plywood face panels, including
anodised alluminium butt hinges with necessary screws. (B) Non-decorative type and
block board core anodised alluminium butt hinges in flush door shutters (2) 35 mm
thick. Sq m 1811.62 406.08
5.03 Provoding and fixing flush door shutters, solid core construction with frame of first class
hardwood with cross board and face veneer or plywood face panels, including
anodised alluminium butt hinges with necessary screws. (B) Non-decorative type and
block board core anodised alluminium butt hinges in flush door shutters (2) 35 mm
thick. Sq m 9018.30 969.08
Providing and fixing extruded aluminum window having extruded aluminum Colour
Powder Coated section frame main outer size 127mm x 38.10mm x 1.35mm ,@
Wt.1.384 Kg/mt,horizontal Four track member size 122.20mm x 31.75mm x 1.10mm @
Wt. 1.205 Kg/mt,vertical member of size 122.20mm x 31.75mm x 1.50mm ,@ Wt.
5.03 1.398 Kg/mt with sliding shutters of horizontal member size 40mm x 18mm x 1.29mm Sq m 2119.14 73.79
@ wt.of 0.456Kg/mt,vertical member of size 40mm x 18mm x 1.29mm @ wt.of
0.456Kg/mt,@ with 5 mm thick transparent bronze colour tinted float glass with
powder coated aluminum fittings and fixtures and transparent silicon sealant glass
fixing to frame as per details etc complete for window.
5.04 Extra for Providing and fixing flush doors with decorative veneering instead of non
decorative ISI marked flush door shutters conforming toIS: 2202 (Part I)
On one side only Sq m 401.07 439.33
5.05 Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on
all edges of flush door shutters (over all area of door shutter to be measured). Sq m 387.94 439.33
5.06 Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws
etc. complete (Copper oxidised as per IS 1378)
5.07 Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with
necessary screws etc. complete (Copper oxidised as per IS 1378)
5.08 Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel
screws etc. complete :
125x64x1.90 mm each
5.09 Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers
and a pair of lever handles of approved quality with necessary screws etc. complete.
5.1 Providing and fixing bright finished brass 100 mm mortice latch with one dead bolt and
a pair of lever handles of approved quality with necessary screws etc. complete.
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
5.11 Providing and fixing aluminium extruded section body tubular type universal hydraulic
door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight
upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed
adjustment with necessary accessories and screws etc. complete.
5.12 Providing and fixing bright finished brass handles with screws etc. complete: each 215.35 4.00
5.13 Providing and fixing bright finished brass hanging type floor door stopper
with necessary screws, etc. complete. each 102.07 217.00
5.14 Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim
Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be
approved by the Engineer- in- charge, all complete. each 7019.76 21.00
5.15 Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side
& 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI
sheet (Zinc coating not less than 120 gm/sqm) suitable for mounting 120 minutes Fire
Rated Glazed Door Shutters. The frame shall be filled with mineral wool Insulation
having density minimum 96Kg/sqm. The frame will have a provision of G.I. anchor
fastners 14 nos (5 each on vertical style & 4 on horizontal style of size M10 x 80)
suitable for fixing in the opening along with factory made template for SS ball bearing
hinges of size 100x89x3 mm for fixing of fire rated glazed shutter. The frame shall be
finished with an approved fire resistant primer or powder coating of not less than
micron in desired shade as per the directions of Engineer - in- Charge. (Cost of SS ball
bearing hinges is excluded).
5.16 Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 minutes Fire
rating conforming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per
laboratory approved by Engineer-in-Charge, with suitable mounting on door frame,
consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of
110 mm x 60 mm made out of 1.6 mm thick G.I. sheet (zinc coating not less than
gm/ sqm) duly filled mineral wool insulation having density minimum 96 kg/ cum and
fixing with necessary stainless steel ball bearing hinges of size 100x89x3 mm of
approved make, including applying a coat of approved fire resistant primer or powder
coating not less than 30 micron etc all complete as per direction of Engineer-in-Charge
(panelling to be paid for seperately).
5.17 Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc.,
with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than
gm/sqm) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm
from the edges and 150 mm c/c , including applying a coat of approved fire resistant
primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic
tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part
3):2016 and as per direction of
Engineer-in-Charge with glass of required thickness having 120 minutes of fire
resistance both integrity & radiation control (EW120) and minimum 20 minutes of
insulation (EI20). The manufacturer have to give test report/certification of fire glass
and the glass should have the stamp showing the value of E, EW & EI. The glass shall
be tested in approved NABL accredited lab or by any other accreditation body which
operates in accordance with ISO/IEC 17011 and accredited labs as per ISO/IEC
for testing and calibration scopes shall be eligible. The maximum glazing size shall not
be more than 1100x2200 mm (w x h) or 2.42 sqm.
5.18 Providing and fixing bright /matt finished Stainless Steel handles of approved quality &
make with necessary screws etc all complete.
Total of sub-head
6 STEEL ALUMINUM & IRON WORK
6.01 Steel work, welded in built up sections framed work including cutting, hoisting, fixing in
position and applying a priming coat of red lead paint. (A)In beams and joists, channels
angles Tees, flats, with connecting plates or angle cleats as in main and cross beams.
Hip and jack rafters, purlins conneted to common rafters and the like
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
6.02 Providing and fixing M.S. round holding down or anchor bolts with nuts and washer
plates complete. Kg 55.05 3000.00
6.03 Supplying and fixing rolling shutters of approved make, made of required size M.S.
laths, interlocked together through their entire length and jointed together at the end by
end locks, mounted on specially designed pipe shaft with brackets, side guides and
arrangements for inside and outside locking with push and pull operation complete,
including the cost of providing and fixing necessary 27.5 cm long wire springs
manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -
part 1 and M.S. top cover of required thickness for rolling shutters.
80x1.25 mm M.S. laths with 1.25 mm thick top cover
6.04 Extra for providing mechanical device chain and crank operation for operating rolling
Exceeding 10.00 sqm and upto 16.80 sqm in the area Sq m 1075.14 54.00
Total of sub-head
7 PAVING & FLOOR FINISHES WORK
7.01 Providing and laying Vitrified tiles 8 to 10 mm thick , 24'' x 24'' in flooring treads of
steps and landing laid on a bed of 12mm thick cement mortar 1:3 (1-cement : 3-coarse
sand ) finishing with flush pointing in white cement. Sq m 1109.27 186.78
7.02 Providing and laying Vitrified tiles 8 to 10 mm thick , in skrting risers of steps and dedo
on 10mm thick cement plaster 1:3 (1-cement : 3-coarse sand) and jointed with white
cement slurry Sq m 1576.63 3.82
7.03 Providing and laying rough chiseled dressed stone flooring over 20mm thick base of
cement mortar 1:5 (1-Cement : 5- coarse sand) or L.M. 1:1.5 including pointing with
cement mortar 1:2 (1-cement : 2-stone dust) etc. complete. (B) 40mm thic Sq m 637.20 5936.45
7.04 Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and
prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias
and similar locations of required size, approved shade, colour and texture laid over
mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white
cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing,
moulding and polishing of edges to give high gloss finish etc. completeat all levels.
Granite stone slab of all colour and texture except black, Cherry/Ruby red Area of slab
Stone work, plain in copings, cornices, string courses and plinth courses, upto 75 mm
thick in Cement mortar 1:6 (1 cement : 6 coarse sand), including pointing with white
cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment
matching the stone shade. Rmt 325.70 14.40
7.05 Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with
grey cement slurry mixed with pigment to match the shade of the slab including rubbing
and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
25 mm thick. Sqm 1634.71 238.41
7.06 Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified
by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in
colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement
Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement
and matching pigment etc., complete. Sqm 920.08 994.35
7.07 Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by
the manufacturer) with water absorption less than 0.08% and conforming to IS:15622,
of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick
cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3
kg/sqm including grouting the joints with white cement and matching pigments etc. The
tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be
done with the notch trowel, plier, wedge, clips of required thickness, leveling system
and rubber mallet for placing the tiles gently and easily.
Double charge vitrified tile polished finish of size
11.41A.1.3 Size of Tile 600 x 1200 mm
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
7.08 Glazed Vitrified tiles Matt/Antiskid finish of size.
11.41A.3.1 Size of Tile 600 x 600 mm Sqm 1229.11 1656.84
7.09 Providing and laying flamed finish Granite stone flooring in required design and
patterns, in linear as well as curvilinear portions of the building all complete as per the
architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of
cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and
pointing with white
cement slurry admixed with pigment of matching shade including rubbing, curing and
polishing etc. all complete as specified and as directed by the Engineer-in-Charge :
11.55.1 Flamed finish granite stone slab Jet Black, Cherry Red, Elite
Brown, Cat Eye or equivalent.
7.10 25 mm wooden planking, tongued and grooved in flooring, including fixing
with iron screws complete with : Sqm 3783.31 1404.88
7.11 Providing and fixing removable raised/false access flooring with system and its
components of approved make for different plenum height with possible height
adjustment upto 50 mm, comprising of modular load bearing floor panels supported on
G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the
architectural drawings, as specified and as directed by Engineer-in-charge consisting
of: (a) Providing at required spacing to form modular framework, pedestals made out of
GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the
G.I. Base plate of size 100 mm x 100 mm x 3 mm at the bottom of the pedestal tube,
G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully threaded stud
mm outer diameter with two GI Check nuts screwed on the stud for level adjustment
upto 50mm, locking and stabilizing the pedestal head in position at the required level.
The pedestals shall be fixed to the subfloor (base) through base plate using epoxy
based adhesive of approved make or the machine screw with rawl plug.
(b) Stringers system in all steel construction hot dipped galvanized of rectangular size
570x20x30x0.80 mm thick having holes at both ends for securing the stringers on to
the pedestal head using fully threaded screws ensuring maximum lateral stability in all
directions, the grid formed by the pedestal and stringer assembly shall receive the floor
panel, this system shall provide adequate solid, rigid support for access floor panel,
the system shall provide a minimum clear uninterrupted clearance between the bottom
of the floor for electrical conduits and wiring etc. all complete as per the architectural
drawings, as specified and as directed by the Engineer-in-charge. (c) Providing and
fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static
high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel
welded construction with an enclosed bottom pan with uniform pattern of
hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and
bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and
welds along each flange).
The panel should be Corroresist epoxy coated for lifetime rust protection and cavity
formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland
cementitious core mixed with light weight foaming compound. The access floor shall
be factory finished with Anti-static High Pressure laminate with Non Warp technology
upto 1 mm thickness for superior adhesion and Surface flatness within 0.75mm. The
panel is to withstand a Concentrated Load of 363 kgs applied on area 25 mm x 25 mm
without collapse in the centre of the panel which is placed on four steel blocks. The
panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and
an impact load of 50kg all complete as per the approved manufacturers specification
and as per the direction of Engineer-in-charge. All specification must be printed on the
side of the panel to ensure the quality of the product.
11.54.2 450 mm Finished Floor Height (FFH).
Total of sub-head
8 ROOF COVERING WORK
8.01 Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 stone
aggregate 10mm and down gauge) including finishing with cement mortar 1:3 (1
cement: 3 fine sand) as per standard design:
a) In 75x75mm deep chase Metre 256.04 483.18
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
8.02 Making khurras 45x45cm with average minimum thickness of 5 cm cement concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20mm nominal size)
over P.V.C. sheet 1mx 1mx400 micron, finished with 12mm cement plaster 1:3 (1
cement : 3 coarse each 250.25 35.00
8.03 Providing and laying broken chine mosaic flooring for terrace using 12 mm to 20 mm
broken pieces of glazed tiles to be laid over cement mortar 1:3 to plain or slope and to
be tempered to bring mortar creme out upto surface using white cement including
rounding off junctions and extending them upto 15 cm along the wall,clearing with
water and oxalic acid etc. as directed. SQM 771.98 2581.08
Total of sub-head
9 CEILING & LINING WORK
9.01 Providing and fixing eco-friendly light weight calcium silicate false ceiling tiles having
Tegular edge & 15 mm Thick Densified edges on the Tile Periphery for Extra Strength
The Light weight calcium silicate ceiling tiles shall have , light reflection 85% non-
combustible as per B.S. 476 part IV, 100% humidity resistance and also having
thermal conductivity0.043° w/m KC.for the best thermal Insulation . The Light weight
calcium Silicate tile shall be of approved texture Fine fissured/ Spintone/Cosmos
having NRC value of 0.5 & Globe having NRC value of 0.75 NRC or equivalent of size
595 X 595 mm to be laid on true horizontal level suspended inter locking metal grid of
hot dipped galvanized steel sections (galvanizing @120 grams per sqm including both
side) consisting of main ‘T’ runner suitably spaced at joints to get required length and
size of 24X38mm made from 0.30 mm thick (minimum) sheet, 1200mm centre to
centre, and cross ‘T’ of size 24X28mm made out of 0.33mm (Minimum) sheet spaced
1200mm along spaced between main ‘T’ at 600mm centre to centre to form agrid of
1200X600mm and secondary cross ’T’ of length 600mm
and size 24x28mm made of 0.30 mm thick (Minimum) sheet to be interlocked at middle
of the 1200X600mm panel to form grid of size 600X600mm resting on periphery
walls/partitions on a perimeter wall angle pre-coated steel of size (24X24X3000mm
made of 0.40mm thick (minimum) sheet with the help of rawl plugs at 450mm centre to
centre with 25mm long dry wall screws @ 230mm interval and laying 15mm thick
Densified edges light weight calcium silicate ceiling tiles of approved texture (Fine
Fissured/Cosmos/Spintone) in the grid including, cutting /making opening for services
like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required,
Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size
25X35X1.6mm fixed to ceiling with 12.5mm dia and 50mm long dash fasteners, 4mm
G.I. adjustable rods with galvanized steel level clips of size 85X30X0.8mm, spaced at
1200mm centre to centre long main ‘T’ bottom exposed with 24mm of all T-sections
shall be pre-painted with polyester baked paint, for all heights, as per specifications,
drawings and as directed by engineerin- charge.Note:-
Only calcium silicate false ceiling area will be measured from wall to wall. No
deduction shall be made for exposed frames/opening (cut outs) having area less than
0.30 sqm. The calcium silicate ceiling tiles shall have NRC. Value of 0.50 (Minimum)
for Fine fissured/Spintone/Cosmos and 0.75 NRC for Globe, light reflection 85%
noncombustible as per B.S. 476 part IV, 100% humidity resistance and also having
thermal conductivity. 0.043° w/m KC.for the best thermal Insulation
9.02 Pro. And fixing single layer water proof gypsum board 12.5 mm thick sections using
water proof board of size 1220 mm x 1830 mm x 8.0 mm suspended by GI suspender
channel of size 25 mm x 3 mm with intermediate channel og size 18 mm x 40 mm x
mm at 1220 mm center to center ceiling section of size 40 mm x 35 mm x 0.55 mm at
457 mm c/c and perimeter channel A of size 20 mm x 27 mm x 30 mm x 0.5 mm at
edges & drops incl.paper tap sand sofit cleat, anchor fastener, scoch bolt connecting
cleat, joining compound top coat on ceiling incl.making necy.opening for light
fitting,diffuser etc. comp. as per detail drawing as directed
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
9.03 Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true
horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel
sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main “T”
runner with suitably spaced joints to get required length and of size 24x38 mm made
from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross
“T” of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced
between main “T” at 600 mm center to center to form a grid of 1200x600 mm and
secondary cross “T” of length 600 mm and size 24x25 mm made of 0.30 mm thick
(minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of
600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of
approved texture in the grid including, required cutting/making, opening for services
like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main “T” runners to be
suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to
ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with
galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to
center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-
painted with polyester paint, all complete for all heights as per specifications, drawings
and as directed by Engineer-in-charge.
9.04 GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size
595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing
of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes
and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester
powder coated of thickness
60 microns (minimum), including factory painted after bending and perforation and
backed with a black Glass fiber acoustical fleece.
Total of sub-head
10 PLASTERING & POINTING WORK
10.01 Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior
plastering upto floor two level and finished even and smooth in (i)Cement mortar 1:3 (1-
cement:3-sand) Sq m 137.27 8798.81
10.02 Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or
half brick walls for interior plastering upto floor two level and finished even and smooth
in (i) Cement mortar 1:3 (1-cement:3-sand) Sq m 181.91 18452.89
10.03 Providing 20mm thick cement plaster in single coat on single or half brick walls for
interior plastering upto floor two level and finished even and smooth in (i) Cement
mortar 1:3 (1-cement:3-sand) Sq m 233.18 4554.97
10.04 Extra over items 58 to 71 for plastering on ceilings and sofits of stairs upto floor two
level instead of plastering on walls. Sq m 25.80 8914.49
10.05 Extra over items 1 to 69, 71 to 87 and 90 for interior plastering above floor two level for
every additional storey height. (1) Single coat plaster Sq m x No. of stor ey 23.66 10026.26
10.06 Extra over items 1 to 69, 71 to 87 and 90 for interior plastering above floor two level for
every additional storey height.(2) Two coat plaster Sq m x No. of stor ey 26.96 3489.92
10.07 Extra over item 91 for plastering on ceiling and soffits of stairs above floor two level for
every additional storey height. Sq m 21.67 1478.88
10.08 Extra for plastering exterior walls of height more than 10m from ground level for every
additional height of 3m or part thereof sqm 73.08 1264.80
10.09 Providing and applying plaster of paris putty of 2 mm thickness over plastered surface
to prepare the surface even and smooth complete sqm 262.70 26025.21
10.1 Painting with synthetic enamel paint of approved brand and manufacture of to give an
a) Two or more coats on new work sqm 130.81 869.15
Total of sub-head
11 WHITE WASHING COLOR WASHING DISTEMPER;ING & OTHER FINISHING
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
11.01 White washing with lime on wall surface (two coats) to give an even shade including
thoroughly booming the surface to remove all dirt, dust; mortar drops and other foreign
matter. Sq m 12.57 1940.00
11.02 Finishing wall with water proofing cement paint of on wall surfaces (Two coats) to give
an approved brand and manufacture and of required shape even shade after
thoroughly brushing the surface to remove all dirt and remains of loose powered
materials. Sq m 64.67 4554.97
11.03 Wall painting (two coats) with plastic emulsion paint of approved brand and
manufacture on undecorated wall surface to give an even shade including throughly
brushing the surface free from mortar droppings and other foreign matter and sand
papered smooth. Sq m 82.36 26781.74
11.04 Extra over item 57 for painting with plastic emulsion paint of approved brand on
ceilings and sloping roofs. Sq m 5.47 830.36
Total of sub-head
12 PAINTING & POLISHING WORK
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
12.01 Applying priming coat over new steel and other metel surface after and including
preparing the surface by throughly cleaning, oil,grease, dirt and other foreign matter
and scoured with brushes fine steel wood, scrapers and sand paper with ready mixed
priming paint brushing red lead. Sq m 36.06 3000.00
12.02 Painting two coats (excluding priming coat) on new steel and other metal surface with
enamel paint, brushing, interior to give an even shade including cleaning the surface
an even shade including cleanicn the surface of all dirt, dust and other foreign matter.
12.03 Painting two coats (excluding priming coat) on new steel and other metal surface with
synthetic enamel paint, brushing to give an even shade including cleaning the surface
of all dirt, dust and other foreign matter. Sq m 67.89 3000.00
12.04 Painting two coats (excluding priming coat) on external surface of new rain water, soil,
waste and vent pipes and fittings with ready mixed bituminous brushing, black,
anticorrosive to give an even shade including cleaning of all dirt, dust and other foreign
matter. (B) 75mm dia. Sq m 22.33 2523.12
12.05 Appliying priming coat over new wood and wood based surface after and including
preparing the surface by throughly cleaning oil, grease, dirt and other foreign matter,
sand papering and knotting. (B) Ready mixed paint brushing wood primier pink.
12.06 Appliying priming coat over new wood and wood based surface after and including
preparing the surface by throughly cleaning oil, grease, dirt and other foreign matter,
sand papering and knotting. (C) Ready mixed paint brushing priming for enamel
12.07 Painting two coats (excluding priming coat) on new wood and wood based surface with
enamel paint, interior to give an even shade including cleaning the surface of all dirt,
dust and other foreign matter sand papering and stopping. Sq m 91.47 20.16
12.08 Finishing wall with weather proof exterior emulsion paint on wall surface (two coats) to
give an required shape even shade after thoroughly brushing the surface to remove all
dirt, and remains of loose powdered materials.etc complete sqm 73.10 25933.68
12.09 Applying two coats of putty & two coats of primer of approved brand and manufacture
on new wall surface to give an even shade including thoroughly brushing the surface
free from mortar dropping and other foreign matter and sand papered smooth.
Providing and fixing to wall ceiling and floor 10.0 Kg. F/Cm2 working pressure
poluthene pipes of the following outside Dia. Low densidy, complete with special
falnge compression type fittings, wall clipsetc. including making good the wall ceiling
and floor.(G)110 mm
Providing and fixing to wall ceiling and floor 10.0 Kg. F/Cm2 working pressure
poluthene pipes of the following outside Dia. Low densidy, complete with special
falnge compression type fittings, wall clipsetc. including making good the wall ceiling
and floor.(G)160 mm
Providing junction for rain water juncton chamber of size 0.60x0.60x0.75m with
excavation of size 1.96x1.96 m & 0.15m thick c.c.1:2:4 bed concrete including brick
masonary wall in CM 1:6 of 0.75m height & 0.23m thick with 15mm thick cement
plaster inside & outside & 1.06x1.06 RCC (1:2:4) slab of thickness 0.15m with CRS
steel and 0.60mx0.45m cast iron manhole cover with frame weight not less than 35 kg
as per directed by Engineer-in-charge
Providing Filter chamber of Brick work in C:M 1:6 of size 2.06mx1.20m x1.20m &
excavation dimension of 2.82mx 1.96x1.35m including C.C 1:2:4 bed concrete of
0.15m thick including brick work in c.m 1:6 for 23cm thick wall including 15mm thick
Drilling in soil with lowering of pipes concrete sealing including gravel packing clay
12.14 breaking and development of bore with air compressor by required capacity vertical Rmt 390.00 90.00
test etc. complete including the cost of benimeter 250mm dia.
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
Supplying slotted PVC pipes of approved quality at site of work confirming to IS.
Total of sub-head
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
13 MISCELLANEOUS BUILDING ITEM WORK
13.01 Providing and supplying aluminium extruded tubular and other aluminium sections as
per the architectural drawings and approved shop drawings , the aluminium quality as
per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-
80 microns conforming to AAMA 2604 of required colour and shade as approved by
the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves,
screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra
shall be paid on this account). The weight of aluminium extruded section shall be taken
for purpose of payment.
13.02 Designing, fabricating, testing, protection, installing and fixing in position semi (grid)
unitized system of structural glazing (with open joints) for linear as well as curvilinear
portions of the building for all heights and all levels, including: (a) Structural analysis &
design and preparation of shop drawings for the specified design loads conforming to
IS 875 part III (the system must passed the proof test at 1.5 times design wind
pressure without any failure), including functional design of the aluminum sections for
fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice
plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather
silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured
EPDM gaskets for water tightness, pressure equalisation & drainage and protection
against fire hazard including: (b) Providing, fabricating and supplying and fixing panels
of aluminium composite panel
cladding in pan shape in metalic colour of approved shades made out of 4mm thick
aluminium composite panel material consisting of 3mm thick FR grade mineral core
sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium
composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF /
Lumiflon based fluoropolymer resin coating of approved colour and shade on face #
and polymer (Service) coating on face # 2 as specified using stainless steel screws,
nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. “ (c) The
fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with
serrations and serrated washers to arrest the wind load movement, fasteners, SS
Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-
metallic contacts all complete required to perform as per specification and drawing The
item includes cost of all material & labour component, the cost of all mock ups at site,
cost of all samples of the individual components for testing
in an approved laboratory, field tests on the assembled working curtain wall with
aluminium composite panel cladding, cleaning and protection of the curtain wall with
aluminium composite panel cladding till the handing over of the building for occupation.
The Contractor shall provide curtain wall with aluminium composite panel cladding,
having all the performance characteristics all complete, as per the Architectural
drawings, as per item description, as specified, as per the approved shop drawings
and as directed by the Engineer-in-Charge. “However, for the purpose of payment, only
the actual area on the external face of the curtain wall with Aluminum Composite Panel
Cladding (including width of groove) shall be measured in sqm. up to two decimal
"Note : The following performance test are to be conducted on ACP system if area of
ACP system exceeds 4500 Sqm from the certified laboratories accreditated by NABL
(National Accreditation Board for Testing and Calibration Laboratories), Department of
Science & Technologies, India.
The NIT approving authority will decide the necessity of testing on the basis of cost of
the work, cost of the test and importance of the work. Performance Testing of ACP
system Tests to be conducted in the NABL certified laboratories 1. Performance
Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per
ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr“ 2. Static
Water Penetration Test. (50pato 1500pa) as per ASTME- 331-09 testing method for a
range upto 2000 ml.“ 3. Dynamic Water Penetration (50pato 1500pa) as per AAMA
501.01-05 testing method for a range upto 2000 ml“ 4. Structural Performance
Deflection and deformation by static air pressure test ( 1.5 times design ind pressure
without any failure) as per ASTME-330-10 testing method for a range upto 50 mm“
Seismic Movement Test (Upto 30 mm) as per AAMA 501.4-09 testing method for
Qualitative test. Tests to be conducted on site 6. Onsite Test for Water Leakage for a
pressure range 50 kpa to 240 kpa (35 psi) upto 2000 ml"
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
13.03 Providing, assembling and supplying vision glass panels (IGUs) comprising of
hermetically-sealed 6-12-6 mm insulated glass (double glazed) vision panel units of
size and shape as required and specified, comprising of an outer high performance
heat strengthened float glass 6mm thick, of approved colour and shade with reflective
coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear
float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and
secondary seal (structural silicone sealant) etc. all complete for the required
performances, as per the Architectural drawings, as per the approved shop drawings,
as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled
in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in
the curtain glazing is included in cost of item No.1)
For payment, only the actual area of glass on face # 1 of the glass panels (excluding
the areas of the grooves and weather silicone sealant) provided and fixed in position,
shall be measured in sqm. (i) Coloured tinted float glass 6mm thick substrate with
reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear
Glass of approved make having properties as visible Light transmittance (VLT) of 25 to
35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading
coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of
performance glass shall be decided by technical sanctioning authority as per the site
13.04 Extra for openable side / top hung vision glass panels (IGUs) including providing and
supplying at site all accessories and hardwares for the openable panels as specified
and of the approved make such as heavy duty stainless steel friction hinges, min 4 -
point cremone locking sets with stainless steel plates, handles, buffers etc. including
necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as
per the Architectural drawings, as per the approved shop drawings, as specified and as
directed by the Engineer- in-Charge.
13.05 Designing, fabricating, testing, installing and fixing in position Curtain Wall with
Aluminium Composite Panel Cladding, with open grooves for linear as well as
curvilinear portions of the building , for all heights and all levels etc. including:
(a) Structural analysis & design and preparation of shop drawings for pressure
equalisation or rain screen principle as required, proper drainage of water to make it
watertight including checking of all the structural and functional design.
(b) Providing, fabricating and supplying and fixing panels of aluminiumcomposite panel
cladding in pan shape in metalic colour of approvedshades made out of 4 mm thick
aluminium composite panel material consisting of 3 mm thick FR grade mineral core
sandwiched between two Aluminium sheets (each 0.5 mm thick). The aluminium
panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon
based fluoropolymer resin coating of approved colour and shade on face # 1 and
polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts,
washers, cleats, weather silicone sealant, backer rods etc.
(c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised
with serrations and serrated washers to arrest the wind load movement, fasteners, SS
316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-
metallic contacts all complete required to perform as per specification and drawing The
item includes cost of all material & labour component, the cost of all mock ups at site,
cost of all samples of the individual components for testing in an approved laboratory,
field tests on the assembled working curtain wall with aluminium composite panel
cladding, cleaning and protection of the curtain wall with aluminium composite panel
cladding till the handing over of the building for occupation. Base frame work for ACP
cladding is payable under the relevant aluminium items.
The Contractor shall provide curtain wall with aluminium composite panel cladding,
having all the performance characteristics all complete , as per the Architectural
drawings, as per item description, as specified, as per the approved shop drawings
and as directed by the Engineer-in-Charge. However, for the purpose of payment, only
the actual area on the external face of the curtain wall with Aluminum Composite Panel
Cladding (including width of groove) shall be measured in sqm. up to two decimal
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
13.06 Providing and fixing structural steel frame (for dry cladding with 30 mm thick gang saw
cut with machine cut edges sand stone) on walls at all heights using M.S. square/
rectangular tube in the required pattern as per architectural drawing, including cost of
cutting, bending, welding etc. The frame work shall be fixed to the wall with the help of
M.S. brackets/ lugs of angle iron/ flats etc. which shall be welded to the frame and
embedded in brick wall with cement concrete block 1:2:4 (1 cement :2 coarse sand :4
graded stone aggregate 20 mm nominal size) of size 300x230x300 mm, including cost
of necessary centring and shuttering and with approved expansion hold fasteners on
CC/RCC surface, including drilling
necessary holes. Approved cramps/ pins etc. shall be welded to the frame work to
support stone cladding, the steel work will be given a priming coat of Zinc primer as
approved by Engineer-in-charge and painted with two or more coats of epoxy paint
(Shop drawings shall be submitted by the contractor to the Engineer-in-charge for
approval before execution). The frame work shall be fixed in true horizontal & vertical
lines/planes. (Only structural steel frame work shall be measured for the purpose of
payment, stainless steel cramps shall be paid for separately and nothing extra shall be
13.07 Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and
prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias
and similar locations of required size, approved shade, colour and texture laid over
mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white
cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing,
moulding and polishing of edges to give high gloss finish etc. complete at all levels.
Granite stone slab of colour black, Cherry/Ruby red
Area of slab over 0.50 sqm
13.08 Providing and fixing anodised aluminium grill (anodised transparent or dyed to required
shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved
design/pattern, with approved standard section and fixed to the existing window frame
with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting
the grill to proper opening size for fixing and operation of handles and fixing approved
anodised aluminium standard section around the opening, all complete as per
requirement and direction of Engineer-in-charge. (Only weight of grill to be measured
13.09 Providing and fixing of façade at all heights with extruded hollow Clay / Terracotta
ventilated rainscreen tiles of height 250/ 300/ 400 mm and length of 595 mm of
approved texture,design and pattern having Flexural Strength/ Modulus of Rupture of ≥
14 N/m² and maximum water absorption of 10% tested as per ISO 10545-4:2004(E)
and ISO 10545-3:1995 respectively in true level fixed to a supporting aluminium
framework(Alloy 6063 T5/T6) consisting of vertical ‘T’ (for intermediates)/ ‘L’(for ends/
termination)/ Tubular sections (at corners)of size 80x60x2 mm/ 40x60x2 mm / 40x40x2
mm respectively, spaced at maximum spacing of 600 mm c/c matching to the tile
vertical grid, and horizontal aluminium ‘C’-clamps of size 56x25x2 mm thickness of
length 150 mm at junction of tiles and of length 75 mm at wall ends/ corners fixed on
top of the vertical sections at spacing of 250/ 300/ 400 mm c/c matching to the tile
horizontal grid with two numbers of self-drilling / self-tapping SS screws of size 5.5x25
mm with EPDM washers. The vertical ‘T’/’L/ Tubular’ sections shall be fixed to the wall
(hot-dip-galvanized) steel L-brackets (galvanizing thickness of minimum 80 microns)of
size 110x80x6 mm at intermediate vertical aluminium profiles and of size 220x110x12
mm at outer corners and stainless steel grade 304,M10 full threaded anchor fasteners
with nylon sleeve 100 mm long (for brick work) and M8 expansion anchor fasteners
mm long for concrete surface, spacing of brackets to be based on a structural/ static
calculation. The brackets shall be of length 175 mm at junction of two vertical
aluminium profiles and of length 100 mm at intermediate points of vertical profiles and
shall be fixed to the vertical aluminium T / L / Tubular profiles using two numbers self-
drilling/ self-tapping SS screws of size 5.5x25 mm with EPDM washers. EPDM gaskets
to be fixed in between brackets and vertical profiles. The tiles shall be mounted on the
‘C’ clamps such that the tiles are supported at top and bottom at both ends.
SUBHEAD-1 CIVIL WORK INCLUDING LANDSCAPE
S. No. DESCRIPTION UNIT RATE Quantity Amount
The tiles shall be additionally secured to the horizontal ‘C’ clamps using special SS
clips of required size which shall be inserted and pressed into position on the ‘C’
clamps holding the tiles and the cut-tiles shall be glued at points to the horizontal ‘C’
clamps by using MS Polymer sealant adhesive. The vertical joint open groove between
two adjacent tiles shall be 5 mm. The tiles and system shall be designed to resist wind
load as per IS 875 (Part 3) according to different zones. The tiles shall be installed
using the ventilated rain screen principle with provision for natural ventilation of the
space between the façade tiles and the structural wall. The work shall be carried out as
per specification,
drawing and as per direction of the Engineer-in-Charge. Note : Scaffolding wherever
required to be paid separately
With 16 mm thickness (+/- 10%) terracotta tiles of other than grey colors
Total of sub-head
WOOD WORK & JOINERY WORK
STEEL ALUMINUM & IRON WORK
PAVING & FLOOR FINISHES WORK
ROOF COVERING WORK
CEILING & LINING WORK
PLASTERING & POINTING WORK
WHITE WASHING COLOR WASHING DISTEMPER;ING & OTHER FINISHING
PAINTING & POLISHING WORK
MISCELLANEOUS BUILDING ITEM WORK
Subhead-2 Plumbing Works
Sl. No Subhead AMOUNT
Grand Total (Without GST)
Grand Total (Without GST)
BILL OF QUANTITIES OF PLUMBING
S.No. Item Description
Unit Total Quantity Rate Amount
Providing and fixing wsh down water closet (European type,
W.C. Pan) with integral P or S trap including jointing the
1 trap with soil pipe in Cement Mortar 1:1 (1-Cement : 1-fine Nos 72 1343.38
sand) (Seal and cover to be measured and paid for
separately)(A) vitreous China Pattern :(i) in white colour
Providing and fixing plastic seat and cover for wash down
2 water closer with C.P. brass hinges and rubber buffers. (B) Nos 72 288.45
Black plastic seal and cover.
3 Providing and fixing toilet paper holder.(A) C.P. Brass Nos 72 372.1
Providing and fixing 12.5 Litres low level flushing cistern
with a pair, of C.I. or Mild brackets, complete with fittings
such as lead valve less syphon, 15mm nom.nal size brass
ball valve with polythene float, C.P brass handle unions and
couplings for connections, with inlet, outlet and overflow
pipes, 40mm dia. porcelain enamelled flush bend including
cutting holes in walls and making good the same
connecting the flush bend with cistern and closet (overflow
pipe to be measured and paid for separately)(A) Vitreous
China (I) In white colour
Providing and fixing washbasin with single hole for pillar
tap with C.I. or M.S. brackets painted white including
5 sutting holes and making good the same but excluding Nos 72 1511.53
fittings.(A) Vitreous China:(ii) Flat Back washbasin 550 mm
x v 400mm size. (i) In white colour.
Providing and fixing chromium plated, bottle trap with
necessary couplings of approved quality for wash basin.
7 Providing and fixing Rubber plug for sink or wash basin. Nos 77 16.98
Providing and fixing Kitchen sink with C.I. or M.S. brackets,
painted white including cutting holes in walls and making
good the same but excluding fittings. (C) Vitreous China
Sink.(i) 600mm x 450mm x 150mm size (H/C mixer)
Providing and fixing C.P. brass waste for washbasin or sink.
Providing and fixing M.I. fisher union for washbasin or sink.
Providing and fixing screw down bib taps of following
11 size.(B) Brass chromium plated screws down Bib Tap. (i) Nos 72 184.98
Providing and fixing Urinal or approved quality including
conecting the Urinal with waste pipe , tap etc. complete.(A)
White earthenware flat back or corner type size 430mm x
13 Providing & fixing CP Brass shower rose with 15 mm or 20 mm inlet Nos 6 279.37
INTERNAL WATER SUPPLY
Providing and fixing concealed center point to wall ceiling
& floor CPVC (SDR 13.5) PIPE having National Sanitation
14 Foundation (NSF) seal for potable water of following dia. Rmt 509.9 168.67
nominal bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete.[A] 15 mm.(Inside the
BILL OF QUANTITIES OF PLUMBING
S.No. Item Description
Unit Total Quantity Rate Amount
Providing and fixing concealed center point to wall ceiling
& floor CPVC (SDR 13.5) PIPE having National Sanitation
Foundation (NSF) seal for potable water of following dia.
nominal bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete. [B] 20 mm..(Inside the
toilet & Vertical in shaft)
Providing and fixing concealed center point to wall ceiling
& floor CPVC (SDR 13.5) PIPE having National Sanitation
Foundation (NSF) seal for potable water of following dia.
nominal bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete. [C] 25 mm..(Inside
the toilet & Vertical in shaft)
Providing and fixing concealed center point to wall ceiling
& floor CPVC (SDR 13.5) PIPE having National Sanitation
Foundation (NSF) seal for potable water of following dia.
nominal bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete. [D] 32mm.(Inside the
toilet & Vertical in shaft)
Providing and fixing concealed center point to wall ceiling
& floor CPVC (SDR 13.5) PIPE having National Sanitation
Foundation (NSF) seal for potable water of following dia.
nominal bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete. [E] 40mm.(Vertical in
Providing and fixing concealed center point to wall ceiling
& floor CPVC (SDR 13.5) PIPE having National Sanitation
19 Foundation (NSF) seal for potable water of following dia. Rmt 28 654.04
nominal bore tube fittings and clamps including making
good the wall, ceiling and floor etc. complete. [F] 50mm..(Vertical in
25mm Air release valve as per IS:14845 ISI
Marked (Domestic loop gravity,Hydropnumatic,Flushing) Nos
Supplying, fixing, testing and commissioning of
butterfly valve of PN 1.6 rating with bronze/gunmetal
21 seat duly ISI marked complete with nuts, bolts,
washers, gaskets conforming to IS 13095 of
following sizes as required :
INTERNAL DRAINAGE & EXTERNAL DRAINAGE
BILL OF QUANTITIES OF PLUMBING
S.No. Item Description
Unit Total Quantity Rate Amount
Providing, laying and jointing in true line and level
diametre U.P.V.C (Type B) conforming to IS 13592-1992
with one end plain and other end socketed with rubber
ring, & fittings conforming to ISI 14735-1999 of approved
make for drainage system pipe line, pipe shall be jointed
with each other with rubber lubricant, pipe shall be fixed on
22 wall using of PVC clamp of the size 160 mm diametre x 210 Rmt 274.8 826.12
mm length x 196 mm heigh at every 2000 mm center to
center or shall be concealed in walls as directed including
necessary fittings such as bends, shoes etc. including
testing of pipes and joints and jointed with adhesive solvent
cement including cost of all materials.(Soil & Waste ,RWP Pipe
diversion at 1st basement ceiling level)
Providing, laying and jointing in true line and level
diametre U.P.V.C (Type B) conforming to IS 13592-1992
with one end plain and other end socketed with rubber
ring, & fittings conforming to ISI 14735-1999 of approved
make for drainage system pipe line, pipe shall be jointed
with each other with rubber lubricant, pipe shall be fixed on
wall using of PVC clamp of the size 110 mm diametre x
mm length x 145 mm heigh at every 2000 mm center to
center or shall be concealed in walls as directed including
necessary fittings such as bends, shoes etc. including
testing of pipes and joints and jointed with adhesive solvent
cement including cost of all materials.
110 mm (Inside the toilet-Soil+Basement header connection) Rmt 198.903 1043
110 mm (Vertical in shaft-Soil) Rmt 286 1043
110 mm (Vertical in shaft Waste+Basement header connection-Soil Rmt 369 1043
Providing and fixing PVC SWR Nahni trap IS 14735 for Nos
drain - 100 mm diameter with jali of the following nominal
24 diameter of self cleansing design with C.I scread down or 114 726
hinged grating including the cost of cutting and making
good the walls.
Providing and fixing S.W. gully trap with C.I. grating brick Nos
masonry chamber and water tight C.I. cover with frame of
300mm x 300mm size (inside) with standard weight.(i)
Square mouth traps. (A) 100mm x 100mm size P type.
BILL OF QUANTITIES OF PLUMBING
S.No. Item Description
Unit Total Quantity Rate Amount
Providing laying (to level or slopes) and jointing reinforced
concrete Light duty non-pressure pipes I.S. class NP2 of the
following internal diameter with collars and butt ends
prepared for collar joints including testing of joints
complete.(B) 150mm (Basement +Ground Storm water exit & entry
& sewer manhole to manhole connection & 2nd floor RWP pipe
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1-
cement :2-coarse sand : 4-graded stone aggregate 20mm
nominal size) foundation concrete 1:3:6 mix (1-cement : 3-
coarse sand :6-Brick bats 40 + 50mm size) inside plastering
15mm thick with Cement Mortar 1:5 (1-Cement : 5-coarse
sand) finished with a floating coat of neat cement and
making channels in cement concrete 1:2:4 mix (1-Cement :2-
Coarse sand :4-stone aggregate 20mm nominal size) finished
smooth complete including curing and festing (i) Inside size
900mm x 1200mm and 1.5M. deep including C.I. cover with
frame size 560mm diameter total weight of cover and frame
to be not less than 128 kgs. (Wt. of cover 64 Kg. and Wt. of
frame 64 Kg.)(A) With 230mm thick walls of brick msonry
using brick having crushing strength not less than 35Kg. /
Sq.cm. in Cement Mortar 1:5 (1- Cement: 5-Coarse sand) (3)
C type depth 2.25 Metre for 150mm diameter sewer.
Supplying, installation, testing and commissioning of STP/ETP of
appropriate technology including civil works (except plant room),
Plant size upto 50KLD set 1 3146501
Total Amount 3671.603 3189544.3
Total Amount 3671.603 3189544.3
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
Providing, fixing, testing and commissioning of ABS Chrome plated Brass
Hand Shower (Health Faucet) of approved make and quality and as
approved by Engineer - In - Charge, including 8 mm dia, 1 to 1.5 Meter long
Flexible tube & wall hook including cutting and making good the walls
wherever required complete with necessary accessories as per directions of
the Engineer In charge.
Providing, fixing, testing and commissioning of C.P brass pillar cock with
single lever hot and cold mixer (Flowrate as 5.0 Lit per min AT 3.0 bar) for
2 Kitchen Sink of approved make and quality, and as approved and directed by Each 7.00 8500.0
the Engineer In charge, including CP wall flanges and all necessary materials
required for fixing and making good as required.
Providing and fixing of 15mm Eachminal bore CP Brass Angle valve with CP
wall flanges and confirming to IS: 8931, for wash basins, water coolers,
geyser points, etc of approved quality and as approved by and directed by
the Engineer In charge.
15mm Eachminal bore (WC+Wash Basin+Sink) Each 149.00 1350.0
Providing, fixing, testing and commissioning of S.S. Double coat hook of
4 approved make, fixed to PVC cleats with C.P. brass screws etc.all Each 59.00 850.0
necessary accessories complete as per directions of the Engineer In charge.
Providing, fixing, testing and commissioning of Chrome plated brass battery
operated automatic Liquid Soap Dispenser with 1 litre capacity of approved
5 make and quality, and as approved by the Engineer, including all necessary Each 24.00 4300.0
materials required for fixing. All complete as per directions of the Engineer
Providing, fixing, jointing, testing and commissioning of CPVC (Chlorinated
Poly Vinyl Chloride) water supply pipes with pipe as per CTS SDR
(operating pressure - 7 Bar @ 82 Deg C and 28 Bar @ 23 Deg C) for pipes
from 1/2 Inch to 2 Inch. Schedule 40 Pipe to be used from 2-1/2 Inch to
Inch. Pipes shall be joined using solvent welded CPVC Sch-80 fittings as per
ASTM F 439 i.e. Tees, Elbows, Couplers, Unions, Reducers, brushings etc.
including transition fittings (connection between CPVC & metal pipe/GI) i.e.
6 Brass Adaptors (both Male & Female threaded) conforming to ASTM D- - - -
2846. ASTM F441 with only CPVC solvent cement conforming to ASTM F-
493. All termination points for installation of faucets shall have brass
termination fittings. Installation shall be to as per Technical Manual of
manufacturer of pipes & fittings.(includes chasing, hyradullic testing and
making good/finish in all respect the demolished portion).Endcaps/plugs
required to be put at all open ends post completion of work till the final
commisioing to avoid debris entering into pipes.
65 mm dia Rmt 21.00 1650.0
Providing, fixing, Testing and commissioning of Ball valve of forged Brass
7 body, Chrome plated Brass ball, Full bore construction, BSPT Female - - -
threaded connection (In shaft, after loop)
15 mm dia Each 2.00 589.8
20 mm dia Each 25.00 775.4
25 mm dia Each 15.00 1150.0
32 mm dia Each 4.00 1529.7
40 mm dia Each 13.00 1939.8
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
50 mm dia Each 8.00 2600.0
Providing, fixing, jointing and testing in position the following U-PVC pressure
threadedsolvent cement joint Pipes as per ASTM D 1785 Schedule 40 and
threaded conforming to IS:554. Cut to required lengths including all necessary
fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc.
The pipes & fittings shall be tested to a pressure of 15 Kg/Sq.cm. Fixing at wall/
8 ceiling level supported by clamps, fastener, hangers etc. as per specification. - - -
Cutting hole in wall / floor slab and making good the same with cement concrete
1:2:4 complete as required. GI heavy class pipe sleeve of larger diameter shall be
provided wherever the pipes crossing the walls/floor slab and sealing the sleeves
as per consultants requirement. Threading, jointing & making proper
40 mm dia (Admin bldg to Fire bldg Hydropnumatic domestic line) Rmt 265.00 752.40
50 mm dia (UGT to OHT Pump Room to vertical shaft-Domestic &
Flushing)+STP flushing tank to fire bldg
65 mm dia (Terrace & Fourth floor Loop Domestic -Gravity) Rmt 352.00 1,038.40
100mm dia (Terrace & fourth floor loop Flushing -Gravity) Rmt 176.00 2,466.20
80 mm dia ( External Water Supply to UGT) Rmt 80.00 1,687.40
Providing, fixing, testing and commissionig of Thermal insulation (Nitrile
Rubber of density 40 kg/m³) and propritery polyshileld outer mechanical
protection on Nitrile rubber insulation comprising of wrapping with poly glass
9 tape helically wound and subsequently applying two coats of polyshield - - -
material (Rasing and hardner) as per manufactureres specifications and
approved by Project manager/Consultant. (Inside the toilet-for shower,
condensate drainage pipes).
15 mm dia (9 mm thickness) Rmt 17.00 479.60
32 mm dia ((13 mm thickness) Rmt 35.00 585.20
50 mm dia (13 mm thickness) Rmt 120.00 688.60
Providing, fixing, jointing, testing and commissioning of Water Meter with
direct reading dial in KL for cold water line with all necessary fittings such as
threaded pieces, unions, 1 Each. pressure gauge with ball valve, 1 Each.
NRV, 2 Each. isolation valve at inlet and outlet, flanges piece for future
removal, flanges/ unions complete with all necessary testing charges and
obtaining test certificates from municipal authorities, on following size pipe
10 lines. The water meter shall have RS-485/Modbus/BACnet over IP/ BACnet - - -
over MSTP port to integrate with Building Management System without any
external hardware/converter requirement. Technical integration details shall
be provided by Plumbing contractor to BMS contractor and ensure proper
integration is done, it shall also comply to ISO 4064 standard, feasible for
class B or Class A installation with all necessary accessories, as per
specification/drawings and as directed by Engineer In Charge.
32 mm dia Each - - -
40 mm dia Each - - -
50 mm dia Each 5.00 61600.0
80 mm dia Each 1.00 97900.0
Providing, fixing, jointing, testing and commissioning of 600 mm dia ductile
iron (Medium Duty) water tank circular cover with frame (as per EN-124)
11 with lockable arrangement complete in all regards with all necessary Each 15.00 7800.0
accessories, as per specification/drawings and as directed by Engineer In
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
Providing, Fixing, Jointing, testing and commissioning of uPVC Type-B SWR
push fit pipes as per IS 13592, solvent joint for sunken or push fit type for
suspended with moulded fittings as per IS-14735, concealed in wet or dry
walls including all fittings such as bends in proper alignment, Y, Tee,
junction, vent cowls, offset, access pieces (Plain or door), etc. As per
12 approved shop drawing. Cost shall includes fixing at wall / ceiling level - - -
making holes complete with necessary hydraulic test. All pipe supports shall
be of MS hot dip galvanised with 85 micron galvanisation with rubber
insert(sizes indicated are Eachminal outside diameter).Endcaps/plugs
required to be put at all open ends post completion of work till the final
commisioing to avoid debris entering into pipes.
200 mm dia (Diversion at 1st basement ceiling level+Rainwater bypass line
connected to the ground floor storm water & Pipe diversion at 2nd floor Rmt 215.00 2400.0
Providing, Fixing, Jointing, testing and commissioning of uPVC Type-B SWR
push fit pipes as per IS 13592, solvent joint for sunken or push fit type for
suspended with moulded fittings as per IS-14735, concealed in wet or dry
walls including all fittings such as bends in proper alignment, Y, Tee,
junction, vent cowls, offset, access pieces (Plain or door), etc. As per
13 approved shop drawing. Cost shall includes fixing at wall / ceiling level - - -
making holes complete with necessary hydraulic test. All pipe supports shall
be of MS hot dip galvanised with 85 micron galvanisation with rubber
insert(sizes indicated are Eachminal outside diameter).Endcaps/plugs
required to be put at all open ends post completion of work till the final
commisioing to avoid debris entering into pipes.
75 mm (In Toilet-Waste Pipe) Rmt 293.31 489.8
Providing, Fixing, Jointing, testing and commissioning of uPVC Type-A SWR
Push fit pipes confirming to IS 13592 on exposed wall faces including all
fittings confirming to IS 14735 such as bends, tees, clamps, cowls etc. as
per approved shop drawing. The cost shall inclusive of cutting holes and
14 making good the walls satisfactory. All pipe supports shall be of MS hot dip - - -
galvanised with 85 micron galvanisation with rubber insert (sizes indicated
are Eachminal outside diameter).Endcaps/plugs required to be put at all
open ends post completion of work till the final commisioing to avoid debris
entering into pipes. (For Vent in Shaft area)
80 mm dia (Vent Pipe) Rmt 284.00 434.7
Providing, fixing, jointing, testing and commissioning of UPVC pipe
(connecting waste pipe from Wash basin, Urinal waste pipe and for Planter /
landscape drain) conforming to IS : 4985 (Pipe Class III - 6 kg / sq.cm) cut to
required lengths including all necessary fittings as per IS 7834 and specials
such as bends, junctions offsets, access pieces (plain or door). Fixing at
wall / ceiling level supported by G.I. clamps, hangers etc. duly epoxy coated.
32 mm dia Rmt 35.00 144.9
40 mm dia Rmt 88.00 175.4
50 mm dia Rmt 228.00 198.3
Sump Pump Discharge- Surface - - -
110 mm dia (Dewatering Pump & Domestic & Flushing Pump Room sump
Providing, fixing, jointing, testing and commissioning of PVC clean out plug
16 with all necessary accessories as per specification/ drawings and directed - - -
by Engineer In charge.
100 mm dia (Soil Pipe in the toilet) Each 17.00 400.0
75 mm dia (Waste Pipe In the Toilet) Each 14.00 300.0
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
Providing & fixing rain water parapet outlets size as given in the drawings
suitable for the outlet sizes as mentioned below. Required depth with lead
17 flashing around the pipe with one piece lead sheet of 3 mm thick set on a - - -
layer of cold bitumen along with CI grating, threaded adaptor for spigot
connection etc. as per drawing complete as required.
100 mm dia outlet Each 2.00 2700.0
150 mm dia outlet (Fourth floor & Roof ) Each 14.00 4300.0
Providing, fixing, testing and commissioning of pre-fabricated grease
18 intercepter suitable for underground / floor mounted application, - - -
conforming to EN 1825 / DIN 4040-100.
Flow rate: 1.0……….. l/s Each 1.00 75000.0
Flow rate: 1.5……….. l/s Each 1.00 95000.0
Supply & Installation of Ductile Iron Heavy Duty Manhole Cover (Heavy
19 duty) internal dimensions, with lifting hooks , Frame with cover (For - - -
Basement & Ground storm water)
450 X 450 mm ( Basement Storm + Ground Planter) Each 12.00 8000.0
600x600 mm (Ground Floor -Flow Transition) Each 5.00 10300.0
Providing and fixing over straight or curved drain MS Hot dipped
Galvanized grating bolted with fixed frame of angle 40mm x 40mm x 5mm
size fixed to concrete with 25mm x 3 mm hold fasts approx. 100 mm long
welded at interval of 600 mm and welded cross braced at 1200 mm
20 interval by 40 mm x 5 mm thick MS flats. The removable grating shall be - - -
made of with outer frame of size 600 mm long with M.S. flats of 32mm x
5mm having welded cross members on one direction with M.S. flats of
size 32mm x 5mm at a spacing of 30 mm c/c. Including hot dip galvanising
upto 85 micron.(Basement & Ground)
300mm wide (At Basement) Rmt 165.00 1650.0
450 mm wide (At Ground) Rmt 495.00 2250.0
Construction, testing and commissioning of conical manholes meeting the
intents of the specifications and drgs. complete with:
i) 1:4:8 cement concrete foundation.
ii) brick masonry wall in 1:5 cement mortar.
iii) 20mm plaster, inside & outside in 1:3 cement mortar with water proof
iv) 1:3:4 cement concrete benching and channelling.
v) PVC rungs @ 300mm c/c.
vi) DI Heavy Duty Frame & Cover confirming to BSEN–124 standard and
600 t.d, 900 b.d & 375mm wall and depth not exceeding 1650mm with
600mm dia Frame & Cover
WATER TANK ACCESSORIES - - -
Providing and fixing 600 mm long MS hot dip galvanized PUDDLE FLANGES
fabricated out of 6 mm thick MS plates of suitable size and IS:1239 heavy class
pipes properly fixed in walls & top slab of tanks. The entire fittings shall be hot
dipped galvanized after fabrication. Length shall be minimum 600 mm or wall
thickness plus 200 mm on either side (which ever is more) as per specification/
drawings and as directed by Engineer In charge.
50 mm dia (flanged ends) Each 14.00 2200.0
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
65 mm dia (flanged ends) Each - 2600.0 -
80 mm dia (flanged ends) Each 2.00 2800.0
100 mm dia (flanged ends) Each 59.00 2900.0
150 mm dia (flanged ends) Each 16.00 3800.0
200 mm dia (flanged ends) Each 2.00 4400.0
250 mm dia (flanged ends) Each 2.00 5400.0
Rate (In Words) : Rupees - - -
300 mm dia (flanged ends) Each - - -
Rate (In Words) : Rupees - - -
Providing and fixing blank flanges, making flanged joints with bolts, nuts, washers
and rubber insertion 3 mm thick, testing the flange and joints etc. complete for pipes
of following diameter as per specification/ drawings and as directed by Engineer In
50 mm dia Each 1.00 239.8
Rate (In Words) : Rupees - - -
65 mm dia Each 1.00 275.4
Rate (In Words) : Rupees - - -
80 mm dia Each 1.00 329.7
Rate (In Words) : Rupees - - -
100 mm dia Each 1.00 450.0
Rate (In Words) : Rupees - - -
150 mm dia Each 1.00 650.0
Rate (In Words) : Rupees - - -
Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS:
1786, having minimum cross section as 23 mmx25 mm and over all
minimum length 263 mm and width as 165 mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by ribbing
or chequering besides necessary and adequate anchoring projections on tail
24 Lumpsum 200.00 450.0
length on 138 mm as
per standard drawing and suitable to with stand the bend test and chemical
resistance test as per specifications and having manufacture's permanent
identification mark to be visible even after fixing, including fixing in manholes
with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand :
6 graded stone aggregate 20 mm Eachminal size) complete as per design
Providing and fixing in position G.I. vent with brass mosquito proof coupling and
air filter including return bend, complete as required. The entire fitting shall be hot
dip galvanised with all necessary accessories, as per specification/drawings and as
directed by Engineer In Charge.
100 mm dia (UGT +OHT) Each 9.00 2100.0
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
Supply & Installation of UG tank double door Access Cover for 600 mm x
600 mm door to open outside of tank, manhole cover frame made of
guage Jindal make aluminium section of 50mm X 25mm with 5mm good
quality aluminium sheet inserted between the frame for avoiding unwanted
foriegn particles entering into the tanks, heavy duty SS hinges with stopper
for lock and key arrangement complete in all respect the whole aluminium
frame and sheet will be factory anodised before fixing on the place for Fire,
Domestic, Flush water tank (Top Manhole) UGT+OHT
PUMPS AND ACCESSORIES - - -
Supplying, installing, testing and commissioning of Water Transfer Pump
for Tank Filling SS horizontal multistage centrifugal pump. Each pump shall
have TEFC1450 RPM three phase electric motor. The pump shall have cast
Iron head, SS base, SS Shaft/ Impeller/ Intermediate chamber. Pump shall
be provided with mechanical seal. The pump shall be suitable for auto/
manual operation.
Flow rate : 3.0 LPS (1 Working +1 Stand By) Set 1.00 130000.0
Head : 45 Mts - - -
Purpose : Domestic water transfer pump - - -
Flow rate : 3.0 LPS (1 Working +1 Stand By) Set 1.00 130000.0
Head : 45 Mts - - -
Purpose : Flushing water transfer pump - - -
Flow rate : 5.0 LPS (1 Working +1 Stand By) Set 1.00 90000.0
Head : 30 Mts - - -
Purpose : Rain Water water transfer pump - - -
Complete (Skid mounted , wall mounted / floor mounted) electrical control
panel comprising of all accessories such as Cyclic Timer, Contactors, Single
Phasing Preventers, Overload Relays, Push Buttons, Voltmeter, Ammeter,
with Selector Switches, A/M Swich, Main Incomer Switch, Dry Pun Each 3.00 55000.0
Preventers with float switches, Overflow control with Float Switches,
control wiring upto tank and any other necessary imports etc. (list to be
provided by the vendor)
Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and
delivery header, pressure gauge, MS base frame (Synthetic enamel painted Set 3.00 52000.0
over a coat of primer) has to be provided.
Terrace Booster Pump system - - -
Supply, Installation, Testing And Commissioning Of Compact Self
28 Contained Skid Mounted factory fitted & factory tested Hydropneumatic - - -
Booster Pump System As Follows:
In-Line, Multisage, centrifugal pumps with SS-304 casing and impeller and
SS-316 shaft, CI base & head TEFC motor (with mechanical seal)
(Vendor to submit performance curves and technical catalog of the
proposed model for review & information)
The pump shall be selected for performance at best efficiency point.
However, the pump selection shall be suitable for performance with set - - -
point @ + 20% of the rated head.
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
Flow rate :3.0 LPS (1Working + 1 Standby) - - -
Head : 35 meter (H) - - -
Purpose : Domestic Terrace Booster for 4th & 3rd Floor Set 1.00 95000.0
Flow rate : 2.0 LPS (1Working + 1 Standby) - - -
Head : 35 meter (H) - - -
Purpose : Domestic Hydrpnumatic pumps for Fire Bldg Set 1.00 85000.0
Flow rate :1.5 LPS (1Working + 1 Standby) - - -
Head : 35 meter (H) - - -
Purpose : Flushing Hydrpnumatic pumps for Fire Bldg Set 1.00 68000.0
External Pump mounted or wall mounted microprocessor PID controller and
frequency inverter integrated in a single body or as separate components
with pressure sensor transmitter minimum two lined LCD display, diodes to
indicate pump ready, pump running and fault and capable to communicate
with other controllers following MODBUS-RTU or BACNET Class-2 protocall - - -
through RS485 port (Variable Frequency Drive ). System should be
capable to compensate for frictional losses at lower flows. All alarms
should be displayed in the controller. System should be equiped with dry
running protection.
Complete (Skid mounted wall mounted / floor mounted) electrical control
panel comprising of all accessories such as PLCs, pressure switches,
pressure transducers, control wiring and any other necessary imports etc. Each 3.00 35000.0
(list to be provided by the vendor). Panel Should be with IP 54 Class of
Precharged diaphram pressure vessel with food grade membrane, charging
connection, connected to outlet header with necessary flanges, gaskets, Each 3.00 30000.0
isolating valves, nuts/bolts etc complete.
Set of accessories such as pressure switches, pressure transducers, inter
connecting power and control cabling etc. complete
Accessories like NRVs, isolating valves, SS-304 (non-Magnetic) suction and
delivery header, pressure gauge, MS base frame (Synthetic enamel painted Set 3.00 24000.0
over a coat of primer)
Booster Pump System as described above - - -
Submersible Centrifugal Non-clog Drainage Pumps - - -
Supply, installation, testing and commissioning of submersible pumps As
Supply, installation, testing and commissioning of continuous duty
Submersible Centrifugal Eachn-clogging or vortex type drainage pumps
complete with 3 phase motor with all necessary protection and mechanical
seal as per manufacturer standard etc. Pumps set shall have auto coupling
assembly. The installation shall be complete with all necessary
indigeEachus accessories as required to complete the installation with
pressure gauge in the discharge line as per specification/drawings and as
directed by Engineer In Charge
Contractor shall provide pump lifting arrangement shall comprise of MS
galvanized guide bar & MS assembly with SS 304 chain with shakle suitable
for 2 Each. submersible drainage pumps in a sump of overall depth Eacht
more than 2.0 m,
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
1 Set : (1 Duty + 1 Assist) - - -
Total flow rate of system: 10.0 LPS - - -
Flow rate : 5.0 LPS each - - -
Head : 30 Mts - - -
Solid Handling : 25 MM - - -
Location : Plantrooms - - -
Purpose : Plant Room Drainage (Fire ,Domestic +STP Flushing Pump
MOC : CI -Body, C.I impeller & SS shaft - (420 or 431) - - -
Rate (In Words) : Rupees - - -
1 Set : (1 Duty + 1 Assist) - - -
Total flow rate of system: 10.0 LPS - - -
Flow rate : 5.0 LPS each - - -
Head : 30 Mts - - -
Solid Handling : 25 MM - - -
Location : Basement and trench - - -
Purpose : Basement Drainage for Fire Zone ( 2 Nos of dewatering
MOC : CI -Body, C.I impeller & SS shaft - (420 or 431) Set 2.00 178000.0
Rate (In Words) : Rupees - - -
Supply, installation, testing and commissioning of Automatic Level Control
system including level indicator with BMS compatibility consisting of
following items 1.1) Water Level Float Switch single sensor (low /high) with
NO/NC contacts 1.2) Control Box 24V,1.3) Necessary cabling ie (From float
switches (UGT & OHT) to control panel, control panel to valves and control
panel to pump & main power supply to control panel) 1.4) On-Off Type
Motorized Butterfly Valve (100 MM dia), Solenoid valve (50 mm dia and
below) and other neccessary accessories to make system complete as per
specification/drawings and as directed by Engineer In Charge. (For UGT -
Potable, Non-potable , For OHT - Potable & Non Water)
Providing, fixing, jointing, testing and commissioning of Automatic Level
Control system including level indicator with BMS compatibility consisting
of following items 1.1) Water Level Float Switch single sensor (low /high)
with NO/NC contacts. 1.2) Control Box 24V ,1.3) Necessary cabling i.e
31 (From float switch to control panel, panel to valves & main power supply to Each 1.00 17000.0
control panel) 1.4) On-Off Type Motorized Butterfly Valve (200MM dia-2 nos
), CI.Body with PTFE Seat and other neccessary accessories to make
system complete as per specification/drawings and as directed by Engineer
In Charge. Purpose :For Terrace Rain Water bypass system
Supplying, installing, testing and commissioning of Filter, Frontal piping,
32 valves and necessary accessories suitable for a flowrate of __ LPS at 4.5 - - -
Kg/Sq cm pressure. The material of construction shall be composite MSEP.
Multi-Grade Pressure Sand Filter (Filteration Velocity 15000 lts / hr / sq.m) Set 1.00 125000.0
Flow rate: 2.0 LPS - - -
For Activated Carbon Filter (Filteration Velocity 12000 lts / hrs / sq.m) Set 1.00 85000.0
Flow rate: 2.0 LPS - - -
BILL OF QUANTITIES OF PLUMBING
S.No Item Description Unit
QUANTITY Rate Amount
Supplying, installing, testing and commissioning of Sodium Hypochlorite
dosing system consisting of one HDPE tank of 100 litres capacity with a positive
displacement diphragm dosing pump having variable flowrate of 0-6 lph. The
33 motor shall be suitable for operation at 240 V / single phase /50 Hz. Supply. The Set 1.00 32000.0
pump shall be supplied complete with necessary polypropylene piping, valves,
strainers, low level switch and injection fittings. The pump shall be speed & stroke
control Asia LMI / equivalent make.
Supplying, installing, testing and commissioning of pH correction dosing
system consisting of one HDPE tank of 100 litres capacity with a positive
displacement diaphragm dosing pump having variable flowrate of 0-6 lph. The
34 motor shall be suitable for operation at 240 V / single phase / 50 Hz.supply. The Set 1.00 24000.0
pump shall be supplied complete with necessary polypropylene piping, valves,
strainers, low level switch and injection fittings. The pump shall be speed and stoke
control Asia LMI / equivalent.
Supplying, installing, testing and commissioning of Water Transfer Pump,
Self-primimg, Negative Suction, SS Vertical multistage centrifugal pump.
Each pump shall have TEFC2900 RPM three phase IE2 electric motor. The
35 pump shall have cast Iron head & base, SS Shaft/ Impeller/ Intermediate - - -
chamber. Pump shall be provided with mechanical seal. The pump shall be
suitable for auto/ manual operation including transportation to Site in
Factory fitted condition.
Complete (wall mounted) electrical control panel comprising of all
accessories such as Cyclic Timer, Contactors, Single Phasing Preventers,
Overload Relays, Push Buttons, Voltmeter, Ammeter, with Selector
Switches, A/M Swich, Main Incomer Switch, Dry Run Preventers with float
switches, Overflow control with Float Switches, control wiring upto tank
and any other necessary imports etc. (list to be provided by the vendor)
Accessories like Foot Valve, Priming POT, NRVs, isolating valves, SS-304
(Eachn-Magnetic) suction and delivery header, pressure gauge, MS base - - -
frame (Synthetic enamel painted over a coat of primer) has to be provided.
Flow rate :2 LPS (Set=1 working + 1 stand by) - - -
Head : 20 Mts - - -
Purpose : Filter Feed Pump Set 1.00 90000.0
Supply and installing Rain Water Percolation pits - 1500 mm in diameter up
to 3200 mm deep, bottom 500 mm filled with boulders 150 - 230 mm size,
over which one Each. UPVC 160 mm dia (4.0 kg/cm2) perforated pipe with
mm dia perforations protected by a cowl on upper end 2100 mm long,
surrounding filled with broken bricks up to 1000 mm, pebbles 40 to 50 mm
up to 400 mm, Gravel 15 to 25 mm up to 400 mm and upper most layer of
300 mm with coarse sand of 3 to 5 mm. The top 600 mm shall be left open,
with RCC grated cover on top.
Total Amount - 2187638.1
Total Amount - 2187638.1
Subhead-3 Fire Fighting Works
Sl. No Subhead Amount
Total Cost of Fire Fighting Works Excluding GST
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
(a) Supplying, installation, testing and
commissioning of Electric driven Main Fire Pump
conforming to IS 12469: 2019 suitable for automatic
operation and consisting of following, complete in all
respects, as required :
(b) Horizontal type, multistage, centrifugal, split
casing pump of cast iron body & bronze impeller
with stainless steel shaft, mechanical seal as
1 (c) Suitable HP Squirrel cage induction motor,
TEFC, synchronous speed 1500 RPM, suitable for
operation on 415 volts, 3 phase 50 Hz, AC supply
with IP 55 protection for enclosure, horizontal foot
mounted type with Class-'F' insulation, conforming to
(d) M.S. fabricated Common base plate, coupling,
coupling guard, foundation bolts etc. as required.
(e)Suitable cement concrete foundation duly
plastered with anti vibration pads.
2280 lpm at 70 m Head Each 2.00 3,25,710.00
1620 lpm at 56 m Head Each 1.00 2,51,374.00
Note: *The head of the pump is selected in a
manner so as to give a minimum 3.5kgf/cm2 -
pressure at the highest/farthest point.
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
(a) Supplying, installation, testing and
commissioning of diesel engine driven main fire
pump conforming to IS 12469: 2019 suitable for
automatic operation and consisting of following,
complete in all respects, as required : (Diesel Driven
(b) Horizontal type, multistage, centrifugal pump of
cast of iron body and bronze impeller with stainless
steel shaft, mechanical seal as required. (c) Suitable HP,
RPM water cooled with
radiator, diesel engine conforming to relevant IS
standard complete with auto starting mechanism,
2 /24 volts electric starting equipment, diesel tank, -
exhaust pipe extended upto 10 m outside pump
house duly insulated with 50 mm thick glass wool
with 1.0 mm thick aluminium sheet cladding,
residential silencer, instruments and protection as
per standard specification, stop solenoid for auto
stop in the event of fault with audio indications,
painted with post office red colour etc. as required.
(d) M.S fabricated, common base plate, coupling,
coupling guard, foundation bolts etc. as required.
(e) Suitable cement concrete foundation duly
plastered and with anti vibration pads.
2280 lpm at 70 m Head Each 1.00 5,38,775.00
Note: * The head of the pump is selected in a
manner so as to give a minimum 3.5kgf/cm2 -
pressure at the highest/farthest point.
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
(a) Supplying, installation, testing and
commissioning of electric driven pressurisation
pump conforming to IS 12469: 2019 suitable for
automatic operation and consisting of following,
complete in all respects, as required : (Jockey
(b) Horizontal type, multistage, centrifugal pump of
cast iron body and bronze impeller with stainless
steel shaft, mechanical seal as required.
(c) Suitable HP squirell cage induction motor TEFC
type suitable for operation on 415 volts, 3 phase
50 Hz AC supply with IP 55 class of protection for
enclosure, horizontal foot mounted type with Class-
'F' insulation, conforming to IS-12615:
(d) M.S. fabricated Common base plate, coupling,
coupling guard, foundation bolts etc. as required.
(e) Suitable cement concrete foundation duly
plastered and with anti vibration pads.
180 lpm at 70 m Head Each 2.00 91,671.00
180 lpm at 56 m Head Each 1.00 73,087.00
Fabrication, supplying, Installation testing &
commissioning of Electrical control panel of cubical
construction, floor mounted type, fabricated out of
2mm thick CRCA sheet, compartmentalised with
hinged lockable doors, dust and vermin proof,
powder coated of approved shade after 7 tank
treatment process, cable alley, inter-connection with
suitable size copper conductor cable/solid copper
strip, having switchgears and accessories,
mountings and internal wiring, earth terminals,
numbering etc. complete in all respect, suitable for
250A, 50kA 4 Pole MCCB, Ics=100% Icu rating
Digital Voltmeter 0-500V with selector switch
Digital Ammeter (0-250 A) with selector swtich &
LED type RYB phase indicating lamps, ON, OFF,
trip indicating lamps
Set of Copper Bus Bar 300A
( Note : All outgoing feeders for pumps should have
digital Ammeter with selector switches, and LED
type ON, OFF, trip indicating lamps)
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
125 A, 50kA TPN MCCB, Ics=100% Icu, with fully
automatic Star/Delta starter suitable for 60 HP pump
with overload protection, current sensing type single
phase preventor complete with all acceessories and
internal wiring required for automatic operation,
selector switch for local/remote, auto/manual/OFF
63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable
HP fully automatic Star/Delta starter with overload
protection, current sensing type single phase
preventor complete with all acceessories and
internal wiring required for automatic operation,
selector switch for local/remote, auto/manual/OFF
Diesel Engine Control
Control for diesel engine comprising -
Automatic/Manual selctor switch & 3 attempts
starting device, timers and relays as required, push
buttons, start/stop in manual mode
Indicating lamp for high/ Low Lub. Oil pressure, High
Water Temp and Engine on indication
Battery charger suitbale for 12V/24 V DC with boost
and trickle selector switch, 0-30 V DC volt meter,
and 0-20 A DC Ammeter
PIPES & ACCESSORIES
Providing laying, testing & commissioning of 'C'
class heavy duty MS Pipe conforming to IS
1239/Class -II of IS: 3589 i/c fittings like elbows,
tees, flanges, tapers, nuts bolts, gaskets etc. in
ground including welding, excavation & providing
cement concrete blocks as supports, anticorrosive
treatment with coaltar/asphalt tape as per IS
refilling the trench etc. of following sizes complete as
150 mm. Dia Meter 605.00 4,283.00
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Providing, laying, testing & commissioning of 'C'
class heavy duty MS pipe conforming to IS
1239/Class -II of IS: 3589 including Welding, fittings
like elbows, tees, flanges, tapers, nuts bolts, gaskets
etc. and fixing the pipe on the wall/ceiling with
suitable clamp/support frame and painting with two
or more coats of synthetic enamel paint of required
shade complete as required :
25 mm dia Meter 1,919.00 772.00
32 mm dia Meter 61.00 872.00
40 mm dia Meter 613.00 1,056.00
50 mm dia Meter 406.00 1,306.00
65 mm dia Meter 319.00 1,640.00
80 mm dia Meter 356.00 1,911.00
100 mm dia Meter 336.00 2,582.00
150 mm dia Meter 572.00 3,607.00
200 mm dia (wall thickness 6.3 mm) Meter 13.00 5,555.00
250 mm dia (wall thickness 6.3 mm) Meter 5.00 6,732.00
300 mm dia (wall thickness 7 mm) Meter 19.00 - -
Supplying and fixing single headed internal hydrant
valve with instantaneous Gunmetal/Stainless Steel
8 coupling of 63 mm dia with cast iron wheel ISI -
marked conforming to IS 5290 (Type -A) with blank
Gunmetal/Stainless Steel cap and chain as required
Single headed Stainless steel Each 14.00 5,565.00
Supplying and fixing Single headed external yard
hydrant valve with 1 No. 63 mm dia instantaneous
FM Gunmetal/Stainless Steel coupling and cast iron
wheel, ISI marked, conforming to IS 5290 (type A)
with blank Gunmetal/Stainless Steel cap and chain
Single headed Stainless steel Each 7.00 5,565.00
Supplying, fixing, testing and commissioning of -
butterfly valve with Tamper Switch of PN 1.6 rating with
bronze/gunmetal seat duly ISI marked complete with nuts,
bolts, washers, gaskets conforming to IS 13095 of
following sizes as required :
50 mm dia Each 1.00 - -
100 mm dia Each 4.00 - -
150 mm dia Each 7.00 - -
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Supplying, fixing, testing and commissioning of GST
butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly
ISI marked complete with nuts, bolts, washers, gaskets
conforming to IS 13095 of
following sizes as required :
40 mm dia Each 1.00 3,247.00
50 mm dia Each 10.00 3,452.00
65 mm dia Each 1.00 3,954.00
80 mm dia Each 16.00 4,536.00
100 mm dia Each 8.00 6,101.00
150 mm dia Each 26.00 8,170.00
200 mm dia Each 4.00 13,633.00
Providing, fixing, Testing and commissioning of Ball valve of
forged Brass body, Chrome plated Brass ball, Full bore
20mm dia Each 3.00 - -
25mm dia. Each 1.00 - -
Supplying, fixing, testing & commissioning of double
flanged sluice valve of rating PN 1.6 with non rising
11 spindle, bronze/gun metal seat, ISI marked -
complete with nuts, bolts, washers, gaskets and
conforming to IS 780 of following sizes as required :
200 mm dia Each 4.00 34,726.00
Supplying and fixing orifice plate made out of 6 mm
thick stainless steel (Grade 304) with orifice of
required size to be fitted between flange & landing
valve of external and internal hydrants to reduce
pressure at the outlet to the level of 3.5 kg/cm2
complete as required. Each
Providing, installation, testing and commissioning of
non-return valve of following sizes confirming to IS:
5312 complete with rubber gasket, GI bolts, nuts,
washers etc.as required :
65mm dia Each 1.00 5,800.00
80mm dia Each 3.00 6,926.00
100mm dia Each 1.00 9,945.00
150mm dia Each 5.00 15,845.00
200mm dia Each 1.00 25,924.00
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Providing, installation, testing and commissioning of
stainless steel Y-strainer fabricated out of 1.6 mm
thick stainless steel, Grade 304, sheet with 3 mm
dia holes with stainless steel flange.
80 mm dia Each 1.00 4,294.00
100mm dia Each 4.00 6,100.00
150mm dia Each 1.00 9,802.00
200mm dia Each 3.00 19,778.00
Supply, lnstallation, testing and Commissioning of Brass Body
Air Release Valve for risers, suitable for pressure not less than
175 PSI as per specification, inclusive of all accessories -
required for satisfactory installation as per
specification/drawings and as directed by Engineer In Charge.
25 mm dia Each 12.00 - -
Supplying and fixing 63 mm dia, 15 m long RRL
hose pipe with 63 mm dia male and female
couplings duly bound with GI wire, rivets etc.
conforming to IS 636 (type-A) as required :
Stainless Steel (Grade 304) Each 42.00 3,916.00
Supplying and fixing first-aid Hose Reel with MS
construction spray painted in post office red,
conforming to IS 884 complete with the following as
(a) 20 mm nominal internal dia water hose
thermoplastic (Textile reinforced) type -2 as per IS:
(b) 20 mm nominal internal dia gun metal globe
valve & nozzle.
(c) Drum and brackets for fixing the equipmets on
(d) Connections from riser with 25 mm dia stop gun
metal valve & M.S. Pipe and socket.
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Providing and fixing 4 mm thick glass door of size 1.5 m x
m along with anodised aluminium frame with centre opening
for fire hose cabinet. Suitably marked on the outside with the Each 14.00 - -
letters FIRE HOSE including locking arrangement. Complete
door & frame work to be in Red P.O. color over a coat of primer.
Providing & fixing lockable indoor type fire hose cabinet
frames fabricated from 40 x 40 x 5 angle iron sections and
gauge MS sheet with full front glass door and locking
arrangement, suitable to accommodate landing valves, 2 nos.
15 m long hoses, first-aid hose reel and branch pipe nozzle &
fire mans’ axe. The cabinet frame shall be painted with one
coat of primer and two or more coats of synthetic enamel paint
of approved make and shade of as required (Approx 1.5 m
(high) x 0.9 m (wide) x 0.6 m (deep) ). The item shall be
complete of MS housing with front door.
(Cost shall be inclusive of providing break glass box containing -
Supplying & fixing 63 mm dia gun metal short
branch pipe with 20 mm nominal internal diameter
17 size nozzle conforming to IS 903 suitable for -
instantaneous connection to interconnect hose pipe
coupling as required:
Stainless Steel (Grade 304) Each 21.00 2,855.00
Supplying and fixing standard Fireman's Axe with heavy duty
insulated rubber handle as per IS: 926 with clamps as per
Supplying and fixing of fire brigade connection of
cast iron body with gun metal male instantaneous
18 inlet couplings complete with cap and chain as reqd. -
for suitable dia MS pipe connection conforming to IS
904 as required:
2 way-100 mm dia M.S. Pipe Each 1.00 6,093.00
4 way - 150 mm dia M.S. Pipe Each 1.00 12,435.00
3 way - 150 mm dia M.S. Pipe Each 1.00 8,472.00
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Supplying and fixing air vessel made of 250 mm dia,
8 mm thick MS sheet, 1200 mm in height with air
release valve on top and flanged connection to riser,
19 drain arrangement with 25 mm dia gun metal wheel 16,280.00
valve with required accessories, pressure gauge
and painting with synthetic enamel paint of approved
shade as required. Each
Providing, Fixing, testing and Commissioning of UL Listed/FM
Approved 15 NB, 79 deg. K 5.6 (80), Pendant type, Quick
Response, Quartzoid bulb sprinkler, teflon tape, lock tite
solution with required accessories etc. complete as per
specification/drawings and as directed by Architect & Engineer
Pendent Sprinkler Each 12.00 - -
Providing, Fixing, testing and Commissioning of UL
Listed/FM Approved 15 NB, 68 deg. K 5.6 (80), Pendant type,
Quick Response, Quartzoid bulb sprinkler, teflon tape, lock
tite solution with required accessories etc. complete as per -
specification/drawings and as directed by Architect &
Engineer in charge.
Pendent Sprinkler Each 786.00 - -
Upright Sprinkler Each 741.00 - -
Horizontal side wall sprinkler Each 5.00 - -
Concealed sprinkler Each 10.00 - -
Providing, Fixing, testing and Commissioning of UL
Listed/FM Approved 15 NB, 68 deg. K 5.6 (80), Pendant type,
Standard Response, Quartzoid bulb sprinkler, teflon tape, -
lock tite solution with required accessories etc. complete as
per specification/drawings and as directed by Architect &
Engineer in charge.
Upright Sprinkler Each 237.00 - -
Horizontal side wall sprinkler Each 8.00 - -
Providing & fixing of adjustable rosette plate for 15mm dia UL -
Listed or FM approved complete as required. Note :
Finish/ colour shall be as per specification/drawings and as - -
directed by Architect & Engineer in charge . Each
20 Providing & fixing of pressure switch in M.S. pipe 1,401.00
line including connection etc. as required. Each
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Providing & fixing flow switch in following sizes M.S.
pipe including connection etc as required.
100mm dia Each 4.00 6,770.00
150mm dia Each 7.00 8,092.00
Providing and fixing in position industrial type pressure
22 gauges with gun metal / brass valves complete etc. as 1,251.00
Supply, lnstallation, testing and Commissioning of FM
approved Venturi Type Flow Test Meter on Test Line to
measure 150% of pump flow and suitable for mounting on 150 - -
mm dia pipe as per specification/drawings and as directed by
Engineer In Charge. Each
Providing, fixing, testing & commissioning of
installation control valve of cast iron body,
brass/bronze working parts comprising of water
motor alarm, bronze seat clapper, clapper arm and
hydraulically driven mechanical gong bell to sound
23 continuous alarm when the wet riser/sprinkler -
system activates, pressure gauges, emergency
releases, strainer, pressure switch, cock valve
complete with drain valve and bypass, test control
box, ball valves, MS pipe of required size, flanges,
orifice plate, gasket etc of follwing sizes as required:
150mm dia Each 1.00 42,629.00
Supplying, installation, testing & commissioning of
sprinkler flexible pipe (UL Listed) of stainless steel
complete with 15 NPT on reducer thread with
maximum working pressure of 175 PSI test pressure
24 of 875 PSI (Burst) with branch line (Inlet) 25mm -
NPT male thread to sprinkler head (Outlet) 15mm
NPT female thread with reducer, nipple, 2 side
brackets, center bracket, stockbar of following sizes
complete as required.
Subhead-3 Fire Fighting Works
Sl. No Item Description
Unit Qty Amount
Supplying, installation, testing & commissioning of
deluge valve (to be used for water curtains) UL
25 listed with wet pilot basic trim assembly for DVA with -
test and alarm, drip and drain valve with water motor
gong complete as required.
Providing, installation, testing & commissioning of
water curtain nozzle 15mm dia nickel chrome plated
brass, BSPT, K-factor as per design consideration
complete as required. Each
Providing, installation, testing & commissioning of
electric release trim assembly for deluge wall with
two way solelnoid valve, weather proof operation on
24 volts DC supply complete as required. Each
on, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL ListedEach
- complete as required. -
Subhead-3 Fire Fighting Works
S.No Item Description
Unit Qty Rate Amount
FIRE FIGHTING SYSTEM
Supplying, fixing, testing and commissioning of
butterfly valve with Tamper Switch of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts,
bolts, washers, gaskets conforming to IS 13095 of
following sizes as required :
50 mm dia Each 1 13,983.00
100 mm dia Each 4 29,831.00
150 mm dia Each 7 32,627.00
Providing, fixing, Testing and commissioning of Ball valve of forged Brass body, Chrome plated Brass ball, Full bore
construction, BSPT Female threaded connection.
20mm dia Each 3 1,324.00
25mm dia. Each 1 1,946.00
Supply, lnstallation, testing and Commissioning of Brass Body Air Release Valve for risers, suitable for pressure not less
3 than 175 PSI as per specification, inclusive of all accessories required for satisfactory installation as per -
specification/drawings and as directed by Engineer In Charge.
25 mm dia Each 12 3,200.00
Providing and fixing 4 mm thick glass door of size 1.5 m x 0.9 m along with anodised aluminium frame with centre
4 opening for fire hose cabinet. Suitably marked on the outside with the letters FIRE HOSE including locking arrangement. Each 14 17,250.00
Complete door & frame work to be in Red P.O. color over a coat of primer.
Providing & fixing lockable indoor type fire hose cabinet frames fabricated from 40 x 40 x 5 angle iron sections and
gauge MS sheet with full front glass door and locking arrangement, suitable to accommodate landing valves, 2 nos. 15 m
5 long hoses, first-aid hose reel and branch pipe nozzle & fire mans’ axe. The cabinet frame shall be painted with one coat Each 7 12,000.00
of primer and two or more coats of synthetic enamel paint of approved make and shade of as required (Approx 1.5 m
(high) x 0.9 m (wide) x 0.6 m (deep) ). The item shall be complete of MS housing with front door.
(Cost shall be inclusive of providing break glass box containing key for the cabinet along with hammer). -
Supplying and fixing standard Fireman's Axe with heavy duty insulated rubber handle as per IS: 926 with clamps as per
Providing, Fixing, testing and Commissioning of UL Listed/FM Approved 15 NB, 79 deg. K 5.6 (80), Pendant type, Quick
7 Response, Quartzoid bulb sprinkler, teflon tape, lock tite solution with required accessories etc. complete as per -
specification/drawings and as directed by Architect & Engineer in charge.
Pendent Sprinkler Each 12 550.00
Providing, Fixing, testing and Commissioning of UL Listed/FM Approved 15 NB, 68 deg. K 5.6 (80), Pendant type,
8 Quick Response, Quartzoid bulb sprinkler, teflon tape, lock tite solution with required accessories etc. complete as -
per specification/drawings and as directed by Architect & Engineer in charge.
Pendent Sprinkler Each 786 450.00
Upright Sprinkler Each 741 375.00
Horizontal side wall sprinkler Each 5 550.00
Concealed sprinkler Each 10 1,550.00
Providing, Fixing, testing and Commissioning of UL Listed/FM Approved 15 NB, 68 deg. K 5.6 (80), Pendant type,
9 Standard Response, Quartzoid bulb sprinkler, teflon tape, lock tite solution with required accessories etc. complete -
as per specification/drawings and as directed by Architect & Engineer in charge.
Upright Sprinkler Each 237 450.00
Horizontal side wall sprinkler Each 8 650.00
Providing & fixing of adjustable rosette plate for 15mm dia UL Listed or FM approved complete as required. Note :
Finish/ colour shall be as per specification/drawings and as directed by Architect & Engineer in charge .
Supply, lnstallation, testing and Commissioning of FM approved Venturi Type Flow Test Meter on Test Line to measure
11 150% of pump flow and suitable for mounting on 150 mm dia pipe as per specification/drawings and as directed by Each 2 1,40,800.00
Engineer In Charge.
Providing and fixing inspectors test assembly complete with inspector's test valve, sight glass, auxiliary drain valve,
union; necessary piping, threading, jointing & with corrosion resistant orifice all complete strictly as per drawing.
Supply, lnstallation, testing and Commissioning of Carbon Dioxide (CO2) type Fire Extinguisher conforming to
13 IS:15683, with ISI marked approved fitted with required accessories including wall suspension brackets as per -
specification/drawings and as directed by Architect & Engineer in charge .
Subhead-3 Fire Fighting Works
S.No Item Description
Unit Qty Rate Amount
Supply, lnstallation, testing and Commissioning of ABC Dry Chemical powder Mono-Ammonium Phosphate (MAP)-
14 90% (stored pressure) type - 6 kg Fire Extinguisher conforming to IS:15683, with ISI marked approved fitted with Each 29 2,500.00
required accessories including wall suspension brackets as per specification/drawings and as directed by Architect &
Engineer in charge .
Supply, lnstallation, testing and Commissioning of ABC Dry Chemical powder Mono-Ammonium Phosphate (MAP)-
15 90% (stored pressure) type - 9 kg Fire Extinguisher with all required accessories, conforming to IS:15683, with ISI Each 1 3,900.00
marked approved fitted with required accessories including flool mounting stand and all accessories required as per
specification/drawings and as directed by Architect & Engineer in charge .
Supply, lnstallation, testing and Commissioning of Mechanical Foam type (AFFF media) 9 Liter. cylindrical shape fire
16 extinguisher with gas cartridge, hose and all required accessories, complete as per IS:15683 - trolley mounted type for Each 2 2,200.00
portable use as per technical specifications with all the necessary accessories as required for complete installation
shall also be included as per specification/drawings and as directed by Architect & Engineer in charge .
Supply, Installation of Floor mounted bucket stand with GI buckets to hand 4 nos. of 9 ltrs buckets sand filled (as
17 per IS: 2546). The stand shall be 5'(L) x 3'(H) x 2"(W) made out of 30 x 300 x4mm MS angle frame duly coated with 2 Each 2 5,400.00
coats of red oxide primer & 2 coats of red finish paint as per specification/drawings and as directed by Engineer In
Sand Bucket with Fine Sand 10 Kgs capacity with Stand
Bucket shall be of Galvanized mild steel confirming to IS 2346-1974. In addition to galvanizing, be painted with two coats
18 of white paint on the inside and two coats of red paint on the handles and the. Ears shall be painted with two coats of Each 8 7,000.00
The word ‘FIRE’ shall be painted in black. Centrally on the outside; its letters shall be 75mm high, and approximately
Construction of valve chamber of 1500 x 750 x 1000mm Deep valve chamber with 230mm brick masonry wall on
100mm thick PCC 1:4:8 bed, finished plastered internally smooth steel trowel and externally rough with sponge trowel
complete with DI recessed top cover of 600 x 600 mm size in leaves Suitable for Fire tender Load (48 metric ton,
10kgs/sqcm point load) with necessary hinges and locking arrangement including water proofing and curing
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
VARIABLE REFRIGERANT VOLUME SYSTEM
VRF OUTDOOR UNIT
1 Supply Installation, Testing & Commissioning of modular type
Variable Refrigerant Volume air cooled Outdoor units suitable
for cooling and heating, having all hermetically sealed inverter
type Scroll Compressor(s), microprocessor based Controller, top
discharge type condensing unit(s), with R410 A Refrigerant (Or
Eco Friendly Green Gas if any), vibration isolators, with suitable
foundation, MS Stand for Unit with necessary paint etc.
complete as required. The unit shall deliver the rated capacity at
AHRI Conditions and work even at 50°C ambient temperature Per Hp 618.0 24,214.0
without tripping. The unit shall be suitable to work on 400V +/-
10%, 3 Phase, 50Hz AC power supply. The unit shall be filled
with first charge of the refrigerant and ready for use as required.
The COP at AHRI conditions shall not be less than 3.1 and
IEER not less than 6.5. (Design should be got approval before
execution from engineer in charge)
VRF INDOOR UNITS -
2 Supply, installation, testing and commissioning of following
minimum capacity 4-way/2 way/radial flow as per approval
VRV Cassette Type Indoor ceiling mounted unit equipped with
synthetic washable media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section
with DX Copper coil, electronic expansion valve, outer cabinet,
drain pump, grill, necessary supports, vibration isolation, cord
less remote control etc., suitable for operation on single phase
230 V ± 10%, 50Hz AC supply, max noise level 60dB @ 400 -
cfm per TR(minimum) complete, as required. The unit shall
have automatic force shut down provision in case of fire on
receiving signal from BMS System. The cooling capacity of
indoor unit will be at air inlet conditions of 27 Degree C DB and
19 Degree C WB temperature fresh air provision compatible for
Remote Operation System
3 Supply, installation, testing and commissioning of following
minimum capacity VRV High wall type Indoor unit equipped with
washable synthetic media pre-filter, fan section with noise level
maximum 60 dB @min 400 cfm /dynamically balanced blower,
multispeed motor, coil section with DX copper coil, electronic
expansion valve, outer cabinet, cord less remote control, drain
pan, necessary accessories etc., suitable for operation on 230 V
± 10%, 50 Hz, single phase AC supply, complete as required.
The unit shall have automatic force shut down provision in case
of fire on receiving signal from BMS System. The cooling
capacity of indoor unit will be at air inlet conditions of 27 Degree
C DB and 19 Degree C WB temperature.
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
4 Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRV ceiling
mounted ductable type Indoor unit equipped with washable
synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section
with DX copper coil, electronic expansion valve, corded remote
control, outer cabinet, vibration isolators, drain pan, other
necessary supports etc., suitable for operation on single phase - -
AC supply 230 V ± 10%, 50 Hz complete as required. The unit
shall have automatic force shut down provision in case of fire on
receiving signal from BMS System. The cooling capacity of
indoor unit will be at air inlet conditions of 27 Degree C DB and
19 Degree C WB temperature.
Mid Static Ductable units (minimum 45 pascal external
static pressure)
High Static Ductable units (minimum 110 pascal external
static pressure)
AIR HANDLING UNITS - -
Supply, Installation, Testing and commissioning of factory built floor
mounted DX-type double skin type horizontal/vertical air handling
units made of 25mm thick panels consisting of pre plasticized G.I.
casing of thickness 0.8mm outside layer and 0.8 mm inside layer with
polyurethane foam (PUF) insulation factory injected between them by
injection moulding machine, complete with blower section with
blower suitable for static pressure as required, minimum 2 bend
GSS/PVC eliminators, cooling coil section with aluminium finned
copper tubes (tubes thickness not less than 0.5mm) cooling coil of
row deep, filter section with 50mm thick metal viscous/ washable
synthetic type air prefilters, belt drive package with TEFC drive motor
of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase
AC supply with suitable variable frequency drive control panel,
drain connections,
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
stainless steel (18G) drain pan with PUF insulation, , necessary
vibration isolation arrangement etc. complete as per specification and
of following capacities.
AHU shall be connected to VRF Outdoor Units.
AHU shall have necessary provisions for VRF kit installation along
with required accessories to complete the system
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
VRF EEV Kit - -
Include for the Supply, complete installation, Testing & Commissioning of Air
handling unit / Treated Fresh air unit Kit which will interface with the VRV/VRF
outdoor unit with the necessary instrumentation and field devices for efficient
It shall be as detailed in the specifications and on the Drawings and to the
complete satisfaction and approval of the Engineer and all concerned Statutory
Authorities and under the following sections. To be read in conjuction with the
standard installation detail drawing. Refer to the specifications for design intent
AHU-L00-01 (FOR ENTRANCE FOYER) (11000 CFM/15 TR/ 30 mm wg ESP) Nos 2.0 84,000.0
AHU-L01-01 (8000 CFM/18 TR/ 30 mm wg External Static) Nos 1.0 1,00,800.0
CSU-L01-01 (MULTIMEDIA ROOM) (2800 CFM/5.8 TR/ 30 mm wg External
CSU-L02-01 (RECORD ROOM) (2800 CFM/5.0 TR/ 30 mm wg External Static) Nos 2.0 28,000.0
AHU-L03-01 (FOR RECREATIONAL AREA-01) (9000 CFM/20 TR/ 30 mm wg ESP) Nos 1.0 1,12,000.0
AHU-L03-02 (FOR RECREATIONAL AREA-02) (6500 CFM/15 TR/ 30 mm wg ESP) Nos 1.0 1,00,800.0
CSU-L03-01 (RECEPTION) (2600 CFM/4.7 TR/ 30 mm wg External Static) Nos 1.0 28,000.0
CSU-L02-01 (WORKSTATION/BREAKOUT) (2800 CFM/5.0 TR/ 30 mm wg
External Static)
TFA-L04-01 (7000 CFM/46 TR/ 30 mm wg ESP) Nos 1.0 2,57,600.0
TFA-L04-02 (5600 CFM/37 TR/ 30 mm wg ESP) Nos 1.0 2,24,000.0
TFA-L00-01 (KITCHEN TFA) (1500 CFM/6.6 TR/ 30 mm wg ESP) Nos 1.0 56,000.0
COPPER REFRIGERANT PIPING - -
8 Supply, Installation, testing and commissioning including
vaccumiazation and Nitrogen testing of following nominal sizes
of soft/hard drawn copper refrigerant piping for VRV system,
complete with fittings, with suitable adjustable ring type hanger
supports, jointing/brazing including accessories, insulated with
XPLE Class-0 tubular insulation/with Class-0 closed cell - -
elastometric nitrile rubber tubular sleeves sections of specified
thickness as given below for Suction and Liquid lines, all
accessories as per specifications etc with necessary refrigerant
joint as required :
(A) 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
(B) 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
(C.) 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
(D) 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
(E) 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
(F) 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
(G) 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm Mtr.
with 19 mm thick insulation
(H) 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 Mtr.
mm with 19 mm thick insulation
(I) 31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm Mtr.
with 19 mm thick insulation
(J) 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm Mtr.
with 19 mm thick insulation
(K) 38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 Mtr.
mm with 19 mm thick insulation
(L) 41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 Mtr.
mm with 19 mm thick insulation
REFRIGERANT GAS - -
9 Supplying colourless non inflammable refrigerant Gas R-410 Kg.
CONDENSATE DRAIN PIPING - -
10 Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm
thick.nitrile rubber insulation.
(A) 50 mm dia. RMT 200.0 153.0
(B) 40 mm dia. RMT 185.0 129.0
(C.) 32mm dia. RMT 70.0 104.0
(D) 25 mm dia. RMT 185.0 104.0
(E) 19 mm dia. RMT 100.0 80.0
CONTROL CABLES & WIRES - -
11 Supply installation testing commissioning Shielded Shielded
Control Cables for VRV System with necessary ISI mark
Medium class rigid PVC pipes with necessary accessories with
termination in machine and control equipments..
(A) 2C X 1.5 Sq mm Shielded Armoured Mtr. 2,492.0 142.0
(B) 3C X 1.5 Sq mm Shielded Armoured Mtr. 110.0 152.0
(C) 4C X 1.5 Sq mm Shielded Armoured Mtr. 105.0 201.0
12 Central Control System - -
(A) Cord type remote control with thermostat, LED Display and
internal wiring for Cassette, FCU & CSU
(B) Central wired Remote Control System Per HP 559.0 1,654.0
DUCTING, GRILLS, DIFFUSER AND INSULATION - -
13 Supply, installation, balancing and commissioning of factory
fabricated GSS sheet metal rectangular/round ducting complete
with neoprene rubber gaskets, elbows, splitter dampers, vanes,
hangers, supports etc. as per approved drawings and - -
specifications of following sheet thickness complete as required.
(A) Thickness 0.63 mm sheet (22 Gauge) Sq.Mtr. 2,755.0 1,296.0
(B) Thickness 0.80 mm sheet (20 Gauge) Sq.Mtr. 3,025.0 1,504.0
(C.) Thickness 1.00 mm sheet (18 Gauge) Sq.Mtr. 50.0 1,663.0
(D) Thickness 1.25 mm sheet ( 16 Gauge) Sq.Mtr. 10.0 2,162.0
14 Supply, installation, balancing and commissioning of fabricated
at site GSS sheet metal rectangular/round ducting complete
with neoprene rubber gaskets, elbows, splitter dampers, vanes,
hangers, supports etc. as per approved drawings and - -
specifications of following sheet thickness complete as required.
(A) Thickness 0.63 mm sheet (22 Gauge) Sq.Mtr. 65.0 1,245.0
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
(B) Thickness 0.80 mm sheet (20 Gauge) Sq.Mtr. 80.0 1,453.0
(C.) Thickness 1.00 mm sheet (18 Gauge) Sq.Mtr. 10.0 1,867.0
(D) Thickness 1.25 mm sheet ( 16 Gauge) Sq.Mtr. 5.0 2,091.0
15 Kitchen Exhaust air system
Supply, fabrication and erection of factory fabricated 16G thick mild
steel Rectangular ducting with all accessories as per specifications.
(with clean outs as per NFPA at base of vertical riser and change in
direction and maximum at every 6.1 M in horizontal & every third floor of
vertical riser and at sprinkler heads)
16 Supply, installation, testing and commissioning of Fire wraping
complete in all respects, on kitchen exhaust ducts, smoke extraction
ducts with “Fire duct wrap (3M) / Fire paint (Flame bar BW11) or cladding
(Promat) to provide 1 Hr fire rating.
17 Supply, installation, testing and commissioning of GI
volume control duct damper complete with neoprene rubber
gaskets, nuts, bolts, screws linkages, flanges etc, as per SQMTR 21.5 8,298.0
specifications.
18 Supply, installation, testing and commissioning of Motorized
(ON-OFF Type) duct mounted GI volume control damper with
enthalpy sensor and necessary control wire (minimum 1.5 sq-
mm) for integration within AHU room
Damper SQMTR 5.0 9,739.0
Actuator Ea. 6.0 9,749.0
19 Supplying & fixing of powder coated extruded aluminium Supply
Air Grills with aluminium volume control dampers complete as
per specifications and size & shape as per site requirement and SQMTR 66.5 10,328.0
approved design.
20 Supplying & fixing of powder coated extruded aluminium Return
Air Grills with louvers but without volume control dampers
complete as per specifications and size & shape as per site SQMTR 80.5 7,003.0
requirement and approved design.
21 Supplying, fixing testing commissioning of supply air diffuser of
powder coated aluminium with aluminium volume control
dampers with anti smudge ring & removable core and size & SQMTR 27.0 13,553.0
shape as per site requirement and approved design.
Supplying, fixing testing commissioning of Return air diffuser of powder
coated aluminium without volume control dampers with anti smudge ring & SQMTR 13.8 9,301.0
removable core and size & shape as per site requirement and approved design
25 Supply, installation, testing & commissioning of thermal
insulated flexible duct of following sizes duly supported at
regular interval as per site requirement etc. complete - -
as required as per specifications.(A) 200 mm dia.
200mm dia RMT 20.0 696.0
26 Supply, installation, testing and commissioning of constant airflow regulator
with flexible silicon bulb as specified and suitable for
Air qty : 50CFM
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
27 Supply, installation, testing and balancing of inlet air louvers with bird screen
for fresh air as per specifications and approved shop drawings.
Powder coated/Anodised extruded aluminium construction. SQMTR 6.5 11,000.0
28 Supply, installation, testing and balancing of outlet air louvers with bird
screen and volume damper for exhaust air as per specifications and approved - - -
Powder coated/Anodised extruded aluminium construction. SQMTR 12.1 7,200.0
30 Supply Installation testing and commissioning of CO2 sensor (in AHU return
Air duct) as per specification specification
31 Supplying, installation, testing and commissioning of duct mounted
Combined Temperature & RH sensor (Airside) on AHU/TFA/FCU outlet where
ever required and as show in drawing, schematic with necessary arrangement
as per specification
32 Supplying, Fixing, testing and commissioning of fire dampers
in supply air duct/main branch and return air path as and where
required of required sizes i/c control wiring,the damper shall be
motorized and spring return so as to close the damper in the
event of power failure automatically and open the same in case
of power being restored. The spring return action shall be - -
inbuilt mechanism and not externally mounted. The damper
shall also be closed in the event of fire signal complete
as required and as per specifications.
Fire Damper SQMTR 12.0 11,905.0
Actuator Ea 55.0 11,153.0
33 Supplying and fixing of following thickness duly
laminated aluminum foil of mat finish closed cell Nitrile rubber
(Class "O") insulation on existing duct after applying suitable
adhesive for Nitrile rubber. The joints shall be sealed with
mm wide and 3 mm thick self adhesive nitrile rubber tape - -
insulation complete as per specifications and as required.
25mm thick SQMTR 4,170.0 1,092.0
34 Supply,installation,testing and commissioning of acoustic insulation
with 15 thick open cell Class "O" Nitrile rubber insulation having thermal
conductivity less than or equal to 0.037W/m°K along with necessary
supports,nuts,bolts,gaskets, clips and in accordance with specification
15 mm thick (for TFA, AHU, SA/ R.A ducts initial 6mtr)
Supply Installation testing and commissioning of acoustic insulation
for AHU room (walls and ceiling) with 50 thick open cell Class "O" Nitrile
rubber insulation having thermal conductivity less than or equal to SQMTR 220.0 1,199.0
0.037W/m°K along with necessary supports,nuts,bolts,gaskets, clips
and in accordance with specification and drawings.
SPLIT AIR CONDITIONERS - -
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
36 Providing and erecting Inverter based approved make split air-
conditioning unit consisting of condensing unit with variable
speed fan motor, inverter type hermetically sealed rotary
compressor with accessories etc. duly connected separately
erected evaporating unit and blower motor with its accessories - -
by means of extra supplied proper insulated copper tubing,drain
PVC pipes suitable for ( cost includes Eco Friendly green gas
charging and 15A plug top & Remote Control & MS Stand) with
necessary core cutting.
(2)For ISEER Range (KWH/KWH)(4.0 to 4.49) - -
(B) for 1.5 ton capacity- Premium Cat. Nos 2.0 52,558.0
38 Supplying and erecting insulated pair of soft copper tubing open
or concealed including power and control cable,necessary PVC
drain pipes for Split AC machine up to 4 TR capacity
VENTILATION - -
SUPPLY AIR AXIAL FLOW FANS (FOR PRESSURISATION) & General
Ventilation & Basement Ventilation
Supplying, installation, testing and commissioning of AMCA Certified (For Air
and Sound Performance) floor mounted supply air vane/tube axialflow fans of
following capacity with GSS casing construction and aluminium alloy impellers
with high efficiency aero‐foil sections, blades, the impeller directly driven by
TEFC induction motor should be of high efficiency class IE3 (as per IS 12615) - -
suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'F' insulation, fire rated
flexible connection,hot dipped galvanised MS rings at inlet and outlet for
connecting flexible connection,anti-vibration Isolators etc. including all
accessories complete as required and as per specifications. Fan total efficiency
should not be less than 70 %, noise level should not be more than 85 dB(A) @
3 m distance when measured in hemispherical reverberant room conditions.
All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating
and complete with bird screen at inlet. The fan shall be provided with suitable
rating TP isolator within MS enclosure complete as required confirming to
specification. Gravity louvers will be provided at the discharge of the fan so as
to avoid reverse flow.
Static pressure shall be checked/verified by contractor prior to order. Entire fan
model & AMCA Seal shall appear in technical submittal of fan. Air moving
capacity shall be as follows:
STAIRCASE PRESS FAN (23000CFM / 20MM WG ESP) Nos 2.0 1,85,169.0
LIFTWELL PRESS FAN (9000CFM / 20MM WG ESP) Nos 3.0 72,458.0
LIFT LOBBY PRESS FAN/TRANSFORMER ROOM FRESH AIR /KITCHEN FRESH
AIR (9500CFM / 20MM WG ESP)
TRANSFORMER ROOM EXHAUTS (10000CFM / 20MM WG ESP) Nos 1.0 70,339.0
PUMP ROOM ROOM EXHAUTS+FRESH AIR (8000CFM / 20MM WG ESP) Nos 2.0 56,271.0
STP EXHAUST (10000CFM / 20MM WG ESP) Nos 1.0 70,339.0
STP FRESH AIR (8000CFM / 20MM WG ESP) Nos 1.0 56,271.0
FRESH AIR FAN FOR ZONE-01 : (12000CFM / 20MM WG ESP) Nos 2.0 1,22,034.0
Toilet Extract Air Fan (800CFM / 15MM WG ESP) Nos 1.0 15,678.0
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
Supplying, installing, testing and commissioning of Cabinet Fans with single
skin construction as per specifications, each complete with squirrel cage
induction motor (mounted internally), DIDW centrifugal fan, belt drive and
vibrations isolators.Motors shall have IE-3 efficiency rating shall be suitable for
415 +- 10% volts, 50 cycles , 3 phase AC supply. Fan static pressure shall be as
indicated . Fan-motor assembly (as whole) shall be statically & dynamically - -
balanced to grade G6.3 as per ISO-1940/AMCA 204-3. The motor shall have
IE3 class efficiency rating. Fan shall be with flexible fire proof connection at
inlet and outlet
The fan shall be suspended or floor mounted through spring isolators as per
the standard installation details and as mentioned in specifications
PANTRY EXHAUST FAN (2000 CFM/20 ESP) Nos 1.0 55,000.0
PANTRY FRESH AIR FAN (1800 CFM/20 ESP) Nos 1.0 55,000.0
TOILET EXHAUST FAN (6000 CFM/20 ESP) Nos 1.0 73,000.0
TOILET FRESH AIR FAN (1800 CFM/20 ESP) Nos 1.0 55,000.0
PANEL ROOM EXHAUST FAN (5500 CFM/20 ESP) Nos 1.0 65,000.0
PANEL ROOM FRESH AIR FAN (5000 CFM/20 ESP) Nos 1.0 65,000.0
TOILET EXHAUST FAN (600 CFM/15 ESP) Nos 2.0 45,000.0
Kitchen exhaust air fan with Scrubber unit
Supply, installation, testing and commissioning of exhaust air fan with
Scrubber Unit (MERV-8 and MERV-13 filter, Electro static precipitator &
Activated carbon filter bank units or Electro static precipitator unit only)
for the treatment of the exhaust from the kitchen as per specifications and
equipment schedule.
Fans shall be of SISW Centrifugal type with single skin construction as per
specifications, each complete with squirrel cage induction motor (mounted
internally), SISW centrifugal fan, belt drive and vibrations isolators.Motors shall
have IE-3 efficiency rating. - -
Fan shall be with flexible fire proof connection at inlet and outlet
Motors shall be suitable for 415 +- 01% volts, 50 cycles , 3 phase AC supply an
static pressure shall be as indicated.
Fan-motor assembly (as whole) shall be statically & dynamically balanced to
grade G6.3 as per ISO-1940/AMCA 204-3.
All Fan sections shall be suitable for outdoor duty and complete with flexible
fire proof connection at inlet and outlet and volume control damper .The
Scrubber shall be with all necessary supports, nuts bolts and accessories
required to complete the fixing.
KITCHEN EX FAN WITH SCRUBBER (10000CFM) Nos 1.0 4,86,000.0
44 Supplying, installation, testing and commissioning of duct mounted
OZONE GENERATION UNIT with VOC sensor and controller, carbon di-
oxide sensor and controller. Ozone monitor cum high Ozone cut out
switch complete with wiring and control wiring. The Ozone generation
system shall be provided for the following areas based on design data
provided in technical specification.
BASEMENT VENTILATION - -
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
SMOKE EXHAUST AIR AXIAL FLOW FANS (SMOKE EVACUATION) :
Supplying, installation, testing and commissioning of AMCA Certified (For Air
and Sound Performance) ceiling hung exhaust air vane/tube axial flow fans of
following capacity with GSS casing construction and aluminium alloy impellers
with high efficiency aero‐foil sections, blades, the impeller directly driven by
TEFC induction motor should be of high efficiency class IE3 (as per IS 12615)
suitable for 3 Phase 50 Hz 415V ± 10 %, of class 'H' insulation, fire rated
flexible connection,hot dipped galvanised MS rings at inlet and outlet for
connecting flexible connection,anti-vibration Isoaltors, etc. including all
accessories complete as required and as per specifications. Motor shall be of
high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. Fan total
efficiency should not be less than 70%, noise level should not be more than
db @ 3 m distance when measured in hemispherical reverberant room
All the fans shall be hot dip galvanized with minimum 220 GSM Zinc Coating
and complete with bird screen at inlet. Suitable TP isolator within MS
enclosure should be provided complete as required confirming to
specification. Gravity louvers will be provided at the discharge of the fan so as -
to avoid reverse flow. Static pressure shall be checked/verified by contractor
prior to order. Entire fan model & AMCA Seal shall appear in technical
submittal of fan. Air moving capacity shall be as follows:
EXHAUST AIR FAN FOR ZONE-01 : (12000CFM / 20MM WG ESP) Nos 2.0 1,22,034.0
EXHAUST AIR FAN FOR ZONE-02 : (12000CFM / 20MM WG ESP) Nos 2.0 1,22,034.0
AMCA rated JET THRUST / IMPULSE FAN with 100% thrust facility in forward
and reverse direction. Complete Fan including and each components shall be
fire rated as per IEC standards and designed to with stand 300° C
temperatures for 2 hour in the event of fire. Fan motor shall be two speed
4P/6P , high efficiency and low noise design to meet NR 55.Sound levels @
1m from fan shall not exceed levels of 72/57 dba. Each fan shall be of
octogonal/circular design with impeller not more than 350 mm in dia and with
a thrust not less than 50 NM to cover an area of apprx 300 sqm. Fan casings
and outside sheet for fan housing and silencers manufactured from pre-
galvanised sheet.Fan and its standard isolator to fully meet the F300 time/
temperature classifications of EN 12101-3 (300°C for 120 minutes). Test
Certificates to be produced prior to delivery of the units. The fan shall
incorporate factory mounted silencers at the inlet and the outlet alongwith all
accessories like mounting brackets etc.,.
Silencers to be with integrated inlet cones and guide vanes to straighten air
flow. Sound attenuating material to be non-flammable in accordance with
NFPA/DIN 4102 and as per EU guide line.Steel (powder coated) Protection
guards to be provided at inlet and outlet for each fan.
Each fan to have a pre-wired terminal box with starters, contactors, relays and
autochangeover from low speed to high speed with Dahlander connection (
tapped winding). It shall be manufactured to resist high tempertures in the - -
event of emergency.Box to have easy access for service. The fan module to be
removable for easy maintenance.
Jet fans with dual speed motor Nos 12.0 92,000.0
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
Supplying, installing, testing and commissioning of direct driven PROPELLER
FANS as shown in drawings. Each fan shall be complete with permanent split
capacitor or shaded pole motor, with wiring from fan to the small power outlet
mounting plate, accessories like wire guard, bird screen and fixed louvers for - -
weather protection as required.
The motor selected shall be energy efficient having IE3 efficiency class rating.
Air moving capacity shall be as follows:
Electrical Room Extract Air Fan (500CFM) Nos 2.0 7,627.0
Electrical Room Supply Air Fan (500CFM) Nos 2.0 7,627.0
48 Computational Fluid Dynamics CFD Analysis and simulation to ensure proper
placement of fans to comply with the air movement, ACPH, exposure
levels/time of CO to persons and applicable building regulations. CFD analysis
to include complete preparation and simulation study of 3D modellling, intake
and extract openings available for ventilation. The scope shall cover complete
basement and the contractor shall submit a complete CFD report with data Lot 1.0 75,000.0
sheets, graphs for review and approval of Client and Consultant. The Agency
scope is to work on the coordination drawings and produce the results, any
comments to be incorporated and revisions made to getthe final CFD approved
by Client / Consultant. Minimum 3 runs shall be included. CD containing visual
output shall be submitted.
Supply, installation, testing and commissioning of Carbon monoxide sensors
comprising of a carbon monoxide meter and a 0‐10 VDC transmitter an all
electronic system that utilizes a microprocessor to measure carbon monoxide
(CO), calculate various calibration factors and analogue output. The sensor
shall average samples over a time period and update the output every 2 ½
minutes. The sensor is intended to be used in enclosed basement, where it Nos 6.0 9,624.0
shall provide CO data to building automation computers or controllers. A box
shall house the sensor and provide an easy‐to‐mount, sturdy housing for the
system. Sensors shall be mounted on walls or columns about 1600 mm above
the floor. Sensors shall be evenly spaced and not put in corners, or directly in
front of air inlets. Each sensor must have a cable directly to the control panel.
50 Supply, installation, testing and commissioning of standalone intelligent
PLC control system for both CO monitoring and smoke control. The
basement shall have an individual PLC Control Panel. The PLC control
system shall control all jet, exhaust & supply air fans located in
basement. The broad logic shall be as follows:
PLC based Logic panel shall be provided to receive signals from the
Carbon Monoxide Detector panel and the Fire Control Panel which will
contain DDC (Direct Digital Controller) to give command to Jet, Supply
and Exhaust fans for their operation on the basis of the logic provided to
the PLC panel as detailed in the specification.
51 Supply, laying, testing and commissioning of 600/1000V Copper Conductor
FRLS insulated PVC Sheathed Armoured - IEC 60502, with max short circuit - -
temperature 300⁰C.
3 Core x 2.5 sqmm Copper cable armoured RMT 20.0 270.0
CONTROL PANELS FOR AHUs/FANS (OPERATED THROUGH VFD) - -
52 Design, manufacture, supply, installation, testing and commissioning of
the following cubicle type, dead front, sheet steel, wall mounted control
panels, including anchoring into the wall, incoming cable wiring - -
terminating into MCCB and copper earthing, in each panel shall be
provided by the electrical contractor.
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
All outgoing shall be provided with Stop /Manual /Auto selector switch to
facilitate operation through BAS. All starters shall be provided with - -
potential free Contact for Connections to Building Automation System.
All internal wiring, power cabling and copper earthing of motors from
the panel to VFD & to the motor shall be included.
The panel shall include the following components & accessories. - -
MCCB as per the ratings given below, suitable for motor duty and able to
withstand fault level of 20 KA.
Terminal block for power distribution as required. - -
Contactor, over load relay with built in single phasing protection. - -
Phase indicating lights and indicating light for `ON’ status. - -
96 mm x 96 mm voltmeter and digital ammeter with selector switches. - -
Time delay relay for delayed automatic restart of motor. - -
Wiring for microswitch for stopping the fan when fire damper closes (in
case of Fan only).
For on/off/remote and local operation, 3 pole single throw switch shall
be provided in each panel to facilitate override of the automatic - -
3 Nos of Single Pole MCB's Shall be provided at the incoming section of
the starter panel for DDC Panel , fire damper actuator & as a spare.
220 / 24 V Transformer & control wiring - -
The number of control panels shall be as follows. - -
125 amps MCCB, 60 HP VFD Nos 1.0 3,81,356.0
100 amps MCCB, 35 HP VFD Nos 1.0 2,96,610.0
60 amps MCCB, 25-30 HP VFD Nos 1.0 2,11,864.0
40 amps MCCB, 15-20 HP VFD Nos 1.0 1,48,305.0
40 amps MCCB, 10/12.5 HP VFD Nos 7.0 1,27,119.0
30 amps MCCB, upto 7.5 HP VFD Nos 6.0 84,746.0
SECTION 3-10 / MINIATURE CIRCUIT BREAKERS. - -
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C Curve)
having 10KA breaking capacity & confirms to IS :8828 in existing box having - -
following capacity
(A) 6 to 32 Amp. - -
Cat.III Ea 35.0 649.0
SECTION 3-4 MOULDED CASE CIRCUIT BREAKERS - -
Note:-1 Add Rs. 10% extra for housing/Encloser of MCCB for Item No 3-4-1 to 3-
4-12 (The Enclosures should be used of same company of MCCBs to be used)
*Add 35% additional for microprocessor type of mccb in place of conventional
for item no.3-4-1 to 3-4-12
Providing and erecting Approved make Three pole moulded case circuit breaker
having breaking capacity ICU of 25 K.A. at 415 V having normal current rating
up to 25 A to 100A. with Fixed thermal & magnetic release suitable to work on - -
A.C. supply 50 c/s. with all internal connections, spreader tinned copper &
complete erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III Ea. 10.0 5,832.0
Providing and erecting Approved make Three pole moulded case circuit
breaker having breaking capacity/strength ICU of 35 K.A. at 415 V. having
normal current rating 125A.with Fixed thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all internal connections,
spreader tinned copper & complete erected in existing 16 G.M.S.
ICS=100% of ICU only Cat III Ea. 1.0 7,161.0
SUBHEAD-4 HVAC WORKS
Description Unit Quantity Rate (Rs.) Amount (Rs.)
59 Providing and fixing approved make Perforated C type cable
tray. Made from pre- galvanized sheet steel. The cable tray
should be bended as per IS 2062/1079 . with max 17.5%
perforation with coupler plate / Fish plate and GI hardware like - -
nut - bolt and washers etc. erected on existing support as per
Specification and as per instruction of engineer in charge..
60 Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured
copper cable 1.1 KV grade to be erected as directed of following - -
(A) 2 core 2.5 Sq. mm Mtr. 2.0 125.0
(K) 4 core 4 Sq. mm Mtr. 130.0 298.0
(L) 4 core 6 Sq. mm Mtr. 1.0 451.0
(N) 4 core 16 Sq. mm Mtr 30.0 902.0
61 Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench / pipe of following
(A) 3 1/2 core 25 Sq. mm ( 16 Sq. mm 1/2 core) RMT 935.0 218.0
(B) 3 1/2 core 35 Sq. mm ( 16 Sq. mm 1/2 core) RMT 264.0 262.0
64 Providing and erecting Annealed bare Copper wire 4.064mm to
65 Providing and erecting HOT deep Galvanised iron strip/wire
Subhead-5: Electrical Works
Sl. No Subhead Amount
1 Electrical Works
2 Electrical Panels
Total Amount (excluding GST)
Total Amount (excluding GST)
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
Point wiring for Tissino / Modular secondary light point with 2-1.5 sq.mm &
earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 kV grade FRLS
PVC insulated multi strand copper wires, in below type of pipe to be
erected complete with earth continuity and necessary connection with
1 primary light with accessories erected on Metal / PVC / wooden box
covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet for open /
concealed wiring. with necessary Lamp holder / ceiling rose /
H.D.Connector as directed.
Note:- Maximum up to 6 mtrs length, excess will be considered as Mains
for Secondary Point.
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm
(Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi
strand copper wires up to 10 mtr length , in below type of pipe erected with
6A Modular type switch / bell push & accessories and earth continuity of
2 following type, erected on PVC / Metallic/Wooden box, single mounting
base frame covered with textured/metallic/white front plate modules
erected on / in wall / ceiling as per pipe erected, with necessary Lamp
holder/ceiling rose / H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Cat. III Pt 300.00 577.00
Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both
are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper
wires up to 10 mtr length, in below type of pipe erected complete with
3 Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box - -
covered with appropriate front plate modules erected on / in wall / ceiling as
per pipe erected with following type of accessories.
[I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby
switchboard/mcb db board
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Cat. III Pt 581.00 606.00
[II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Cat. III Pt 302.00 886.00
[III] For 16A Plug and 16 amp switch with 2-4 sq.mm Cu. Wire with
sq.mm ( green) earthing wire from mcb d b board.
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Cat. III Pt 92.00 1,036.00
Point wiring for on board Looped Plug with 6A Modular type switch & 5 pin
socket erected on PVC / Metallic/Wooden box, single mounting base frame
4 covered with textured / metallic/white front plate modules erected on / in - -
wall / ceiling with following type accessories
Cat. III Pt 115.00 306.00
Providing following type of Modular Type Accessories mounted with PVC /
metallic/Wooden box, single mounting base frame covered with textured /
5 metallic/white front plate , modules erected with necessary connections as
per site situation directed by Engineer In charge.
(4) TV Co-axial Socket outlet
Cat. III Pt 12.00 159.00
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
(23) USB Charger with output of 5 V DC,2.1 A with
inbuilt surge protection. Cat-III
Section - 1-3 Conduits & Pipes -
Providing and erecting ISI mark Medium class RIGID PVC PIPES of
following size complete to be erected on/in wall or ceiling erected with
6 necessary PVC fittings & Junction boxes fixed with adhesive solution & -
Clamps with following dia of pipes, in approved manner as directed
Providing & erecting PVC Corrugated Flexible Conduit with required nos. of
coupling, PVC bushes, Check-nuts etc. complete of following sizes.
METAL TRUNKING SYSTEM - -
Supplying under floor pregalvanised corrosion proof rectangular sheet
steel cable trunking of 1.6 mm thick having with stand point load up to
Ton & free from seepage of concrete of screed water with all
8 accessories,Junction Box,Joints as required and demanded by engineer- - -
incharge and laying/erecting as per OEM guidelines and as per instruction
of engineer incharge having following size of dimensions and No of
compartments (W x D x T) Cat-III
[1] 50mm x 25mm x 1.6 mm with One Compartment Mtr 1.00 295.0
[2] 75mm x 25mm x 1.6 mm with One Compartment Mtr 1.00 374.0
[3] 100mm x 25mm x 1.6 mm with one compartment Mtr 55.00 454.0
[4] 225mm x 25mm x 1.6 mm with Three Compartment Mtr 1.00 965.0
[5] 250mm x 25mm x 1.6 mm with Three Compartments Mtr 55.00 1035.0
[7] 50mm x 38mm x 1.6 mm with One Compartments Mtr 25.00 374.00
[8] 75mm x 38mm x 1.6 mm with one compartments Mtr 25.00 454.00
[9] 100mm x 38mm x 1.6 mm with One Compartments Mtr 649.00 543.00
[10] 150mm x 38mm x 1.6mm with Three Compartments Mtr 25.00 758.00
[11] 225mm x 38mm x 1.6mm with Three Compartments Mtr 177.10 1,084.00
[12] 250mm x 38mm x 1.6mm with Three Compartments Mtr 25.00 1,183.00
[13] 300mm x 38mm x 1.6 mm with Three Compartments Mtr 203.50 1,329.00
Section - 1-4 Mains & Wires -
Providing and erecting Mains with 1.1 kV grade FRLS PVC insulated ISI
marked stranded Copper conductor wire in following type of pipe to be
9 erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper -
conductor FRLS PVC insulated stranded wire of green colour for earth
continuity of following size
(A) With medium class Rigid PVC pipe and accessories
providing and erecting Mains with 1.1 kV grade FRLS PVC insulated ISI
marked stranded Copper conductor wire in following type of pipe to be
10 erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC
insulated stranded wire of green colour for earth continuity of following size
(A) with medium class Rigid PVC pipe and accessories
(a) 2 wire 4 sq. mm Mtr. 200.00 139.00
(g) 4 wire 4 sq. mm Mtr. 6,875.00 224.00
Providing & Erecting approved make following size of TV Co-axial flexible
cable comprising inner conductor of solid bare copper insulated with Foam
11 PE & Secondary conductor made of poly - Aluminium film bonded Al. -
Braids @ suitable coverage overall sheathed with black PVC insulation.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
Section 1-6 Wiring Accessories -
Providing & erecting Switch board for Computer or electric apparatus
consisting of following modular type accessories mounted with PVC /
Metallic concealed/open box with single mounting base frame covered with
textured/metallic /white front plate,modules erected with necessary
12 connections as directed -
1 no. 6A/16A universal plug-switch combined.
3 nos. 6A Switch
3 nos. 6A 5 pin Plug
For Modular Type Accessories -
SECTION 4-2 UNARMOURED COPPER CABLES -
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper
cable 1.1 KV grade to be erected as directed of following size.
(J) 4 core 2.5 Sq. mm Mtr. 314.00 209.00
(E) 3 core 2.5 Sq. mm Mtr. 170.00 170
(F) 3 core 4 Sq. mm Mtr. 50.00 234
SECTION 4-3 ARMOURED ALUMINIUM CABLES -
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe of following size of
(A) 3 1/2 core 25 Sq. mm ( 16 Sq. mm 1/2 core) Mtr. 950.00 218.00
(B) 3 1/2 core 35 Sq. mm ( 16 Sq. mm 1/2 core) Mtr. 300.00 262.00
(C) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm core) Mtr. 175.00 338.00
(D) 3 1/2 core 70 Sq. mm ( 35 Sq. mm 1/2 core) Mtr. 25.00 450.00
(E) 3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2 core) Mtr. 50.00 584.00
(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core) Mtr. 335.00 642.00
(G) 3 1/2 core 150 Sq. mm ( 70 Sq. mm 1/2 core) Mtr. 50.00 868.00
SECTION 4-4 ARMOURED COPPER CABLES -
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable
multistrand Copper conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe at road crossing or
floor of following size of cables.
(A) 4 core 2.5 sq.mm Mtr. 50.00 336.00
(B) 4 core 4 Sq. mm Mtr. 1,760.00 451.00
(C) 4 core 6 Sq. mm Mtr. 430.00 631.00
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable
multistrand Copper conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe at road crossing or
floor of following size of cables.
(A) 4 core 10 Sq. mm Mtr. 895.00 838.00
Supplying & laying of following 1100 volt grade XLPE insulated zero halogen & low
smoke compound inner sheathed and zero halogen & low smoke compound outer
17 sheathed aluminium conductor armoured Fire survival cables as per specification in -
existing trenches, cable trays, ducts, clamped to wall with suitable clamps including,
saddles fixing bolts, connecting testing and commissioning.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
4Cx2.5 mm FS XLPE Cu Mtr. 100.00 260.17
4Cx4 mm FS XLPE Cu Mtr. 1,580.00 506.78
4Cx10 mm FS XLPE Cu Mtr. 380.00 1,133.05
4Cx16 mm FS XLPE Cu Mtr. 100.00 1,414.41
3.5Cx25 mm FS XLPE Alu Mtr. 60.00 693.22
3.5Cx35 mm FS XLPE Alu Mtr. 50.00 847.46
3.5Cx50 mm FS XLPE Alu Mtr. 75.00 986.44
3.5Cx70 mm FS XLPE Alu Mtr. 30.00 1,233.05
3.5Cx240 mm FS XLPE Alu Mtr. 100.00 3,158.47
SECTION 4-6 CABLE GLANDS -
Providing and, fixing heavy duty flange type brass cable gland with
rubber ring for PVC insulated armoured cable complete with out
going tails, insulating tape etc for following size of cables.
(B) 2 to 4 core 6 Sq. mm Ea. 38.00 38.00
(C) 2 to 4 core 10 Sq. mm Ea. 24.00 38.00
(D) 2 to 4 core 16 Sq. mm Ea. 2.00 47.00
(E) 2 to 4 core 25 Sq. mm Ea. 4.00 51.00
Providing and, fixing heavy duty flange type brass double
compression type cable gland with rubber ring for PVC insulated
armoured cable complete with out going tails, insulating tape etc for
following size of cables.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
SECTION 4-7 CABLE LUGS. -
Solder less crimping type Aluminium lugs conforming to IS suitable for cable
of following size evenly crimped with high pressure tool & connected to
switchgear terminals with brass/cadmium plated nut bolts in an approved
Solder less crimping type Copper lugs conforming to IS suitable for cable of
following size evenly crimped with high pressure tool & connected to
switchgear terminals with brass/cadmium plated nut bolts in an approved
SECTION 4-5 MISCELLANEOUS. -
Providing & laying approved make ISI marked HDPE 6Kg / cm2 (Class-3)
as per IS:4984:1995 PE-80 to be erected at road crossing on or floor as
22 directed for laying of cable. The pipes as following size of dia & weight per -
(F) 110 mm inner Dia. Mtr. 110.00 725.00
SECTION 2-15 LED LUMINARIES -
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt
assembled on single MCPCB, with housing used as a heat sink shall be made of
thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated
and high U.V. & corrosion resistance with diffuser with company mark/name 160V
to 270V, Power Factor more than 0.95, THD < 15%,
Luminaire efficacy> 85 lumens/watt ,LED
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown
ranges of Wattage capacity of LED fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.)
(A) Tube Light with integral driver -
(iii) 18-20 Watts, Surge - 2KV,IP-20, conventional 4 feet -
Cat.III Ea. 205.80 293.00
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt
assembled on single MCPCB, with housing used as a heat sink shall be made of
thick sheet Steel conforming to IS: 513/CRCA/aluminium pressure die cast powder
coated and high U.V. & corrosion resistance with diffuser housed in aluminium
casted body with company mark/name
160V to 270V,Power Factor more than 0.95, THD < 15 %,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown
ranges of Wattage capacity of LED fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.)
(A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for
spring loaded mounting clips complete.IP20
(i) 5-9 watts,Surge-2 KV -
Cat.III Ea. 219.20 218.00
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
(ii) 11-15 watts, Surge-2 KV - -
Cat.III Ea. 566.80 423.00
(B) LED Panel Light with provision for Plane
front frame with translucent cover fixed to - -
housing complete.IP20
(vi) 36 watts, 24" x 24", Surge- 2KV - -
Cat.III Ea. 2.00 1,777.00
(vii) from 45 to 48 watts, 24" x 24", Surge-2 KV - -
(D) LED Strip Light -
(i) Minimum 4.8W-120 LED per meter (2 wire,
IP-65) with non integral suitable Driver -
Cat.III Ea. 36.20 134.00
(H) Mirror Light 9 Watts, wall mounted
minimum 1 feet long
(I) Adjustable spot light with COB led having
aluminium reflector of following wattage
(i) 8 Watts - -
Cat.III Ea. 11.00 851.00
(ii) 12 Watts - -
Cat.III Ea. 14.00 957.00
SECTION 2-16 LED OUTDOOR FITTINGS -
Supplying and erecting LED street light / Flood light fittings with High power White
LEDs wattage of 3 Watt and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast aluminum housing with
smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened glass with company mark/name
engraved or embossed 160 to 270 V,Power Factor more than 0.95, THD < 10 %, CCT
3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED
driver efficiency > 85 %.( fittings required LM-79 & LM-80 certificates)(NOTE: Below
description have shown ranges of Wattage capacity of LED fittings.The Engineer
incharge may select any wattage capacity between the ranges shown.)
(A) Street Light (IP-65), Surge protection -4KV integral and ,Light must have 440VAC
line supply with over-voltage protection.
(iii) Above 60 to 90 watts -
Cat.III Ea. 25.00 5,030.00
(C) Post Top Lantern LED fitting comprises of finish cast aluminum spigot and spun
aluminum canopy fixed with opal polycarbonate, pipe arrangement for vertical - -
mounting driver and accessories wired upto terminal block.IP
Cat.III Ea. 28.00 3,444.00
Supplying & erecting Steel tubular pole (Swaged) confirming to IS - 2713 (Part-II)
1980. Manufacturing process of steel tubular pole should be as per IS specification.
26 Basic steel tube should be ISI Marked. Pole should be painted by one coat of Zinc - -
comet Primer and two coat of Aluminium /approved paint to be erected on / in
existing Foundation. The length of poles are as below.
(A) 7.5 mtr. Long Swaged Steel tubular pole - -
(i) pole as per IS code 410-SP-4 with 300 X 300 X 4 mm base plate with necessary
G.I. J Bolts (Approximate Pole weight 67 Kg) For burial erection
(ii) Add Extra for M.S. Base plate 300 X 300 X 16 mm for pole, Suitable for mounting
on surface of foundation with GI foundation bolts, with required stiffeners welded Ea. 25.00 973.00
(iii) Add Extra for PU base primer and PU Paint on pole. Ea. 25.00 383.00
SECTION 6-4 POLE BOXES -
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
Supplying & erecting approved make SMC press moulded composite FRP.
loop-in, loop-out approx. 2mm thick box complete with Bakelite connector
strip 5way(3P+N+E),DIN rail for mounting mob & hinged doors as per
requirement having locking arrangements with mounting clamp with nuts,
bolts & washers suitable for erection on pole with cable clamps& earth bolt of
following size of box.
(B) 250mm x 200mm x 100mm [deep] Ea 20.00 510
SECTION 6-7 TIME SWITCHES -
Supplying & erecting approved make Digital time switch having lithium cell 6 years
operative and operate battery backup 1 channel day clock with 14 memory
programme, suitable to operate on 240V + 5%, 16A with, floating contacts Minimum
28 switching setup time 1 minimum & LCD display. Also comprised permanent ON/OFF Ea. 3.00 3,137.00
switching. Programming switches & housed in fire proof thermoplastic enclosure &
transparent cover erected as required with necessary connection erected as
Supplying & erecting power contactor ,AC3 duty for time switch complete erected as
per direction Cat III
SECTION 3-11 MCB DISTRIBUTION BOARDS -
Providing and erecting Sheet Steel powder coated MCB distribution board - flush /
surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to
IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The
DBs should be used of same company of MCB to be used) suitable for
(A) single phase incoming and horizontal single
(b) sheet steel double door (IP-43) -
(B) three phase incoming and single phase
horizontal type outgoing Per phase isolation - -
(b) sheet steel double door - -
SECTION 3-13 / DANGER NOTICE BOARDS. -
Providing and erecting metallic vitrified danger notice board as per language
31 suggested by engineer incharge for MEDIUM VOLTAGE installation to be erected as Ea. 16.00 69.00
Providing and erecting metallic vitrified danger notice board as per language
32 suggested by engineer incharge for HIGH VOLTAGE installation to be erected as per Ea. 6.00 81.00
SECTION 3-14 EARTHING -
Providing and erecting required size HOT deep Galvanised iron strip for earthing of
H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using proper clamp.
Providing and erecting required size Copper strip for earthing of H.T. OCB / ACB/
Transformer, LT panel board, Motors etc. using copper clamp.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
35 Providing and erecting Annealed bare Copper wire 4.064mm to 1.626mm. Kg. 30.00 787.00
36 Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG. Kg. 30.00 77.00
Supplying & erecting funnel type earthing having earth plate of following size burred
in specifically prepared earth pit 3 mtr. below ground with 40 kg. charcoal and salt
with alternate layers of charcoal & salt, 20mm.dia. G.I. pipe with Funnel with a wire
mesh for watering & bricks masonry block, C.I. Cover complete as per para 7.3 of IS
37 3043 with necessary length of double Galvanised Iron / copper earth wire No 6 SWG -
bolted with lug to the plate and covered in 12 mm dia. G.I. pipe 2.5 mtr long
complete connected to the nearest switch gear with end socket as per direction &
duly tested by earth tester confirming to IS (As per drawing) with following
(A) With 30 x 30 x 0.35 cms: C.I. earth plate Ea. 2.00 2,289.00
(B) With 45 x 45 x 0.35 cms. C.I. earth plate Ea. 21.00 2,543.00
(C) with 60 x 60x 0.315 cms. Copper earth Plate Ea. 4.00 7,797.00
SECTION 4-11 METAL PERFORATED CABLE TRAYS -
Providing and fixing approved make Perforated C type cable tray. Made from pre-
galvanized sheet steel. The cable tray should be bended as per IS 2062/1079 . with
38 max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut - bolt -
and washers etc. erected on existing support as per Specification and as per
instruction of engineer in charge..
Providing and fixing approved make Ladder type cable tray. Made from M.S sheet.
The cable tray should be bended as per IS 2062/1079 shall be fabricated of double
bended channel section longitudinal members with single bended Channel section.
Rungs of members welded to the base of the longitudinal members at 250 mm c/c
spacing . as per IS and shall be coated with hot dip galvanizing as per IS 2629/4759.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc.
erected on existing support as per Specification and as per instruction of engineer in
SECTION 8-15 / POWER CAPACITORS & UPS -
Supplying & erecting bank of all polypropylene condenser (APP type) with standard
capacity of 2,3,5,7, 10,12.5 & 15 KVAR units of P.F. correction for operation on
phase 50 c/s, 400 /440V (+ / - 10%) with externally discharging resistance, earthing
terminal & built on angle iron of channel iron frame work and provided with terminal
cover box. Complete erected on provided iron bracket or on floor duly tested by
Supplying and erecting approved make online Un-interruptible Power Supply system
comprising flat cum-boost charger with IGBT base rectifier & Inverter & sealed
maintenance free SMF batteries. The charger having operating capacity for input 160-
270V AC & inverter having output 230V,50 Hz Ac with 0.8 load power factor with
battery, over/under voltage output with over load & short circuit protection
equipment. The system housed in CRC sheet duly powder coated paint with
following power backup.with MS painted batteries stand, 10% Overload capacity for
momentary load.
(I) 10 KVA 3 - phase with 1Hr Backup Ea. 1.00 268306.0
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
(J) 20 KVA 3 - phase with 1Hr Backup Ea. 3.00 3,93,391.00
SECTION 10-1 SUBSTATION EQUIPMENT -
Providing, erecting, testing commissioning & getting Plan Approval as well as NOC
from Electrical Inspector for extensible H.T panel comprising of one
630A/800A/1250A. H.T. VCB incoming & Two outgoing 630/800/1250 A Drawout
type VCB confirming as per I.S. for use on 11 KV, 3 phase, 50 c/s. unearthed A.C.
supply system having breaking rupturing capacity of 350 MVA or Above complete
with spring operated mechanism, mechanically & automatic ON-OFF and spring
mechanism charged, discharged indicators, ON-OFF mechanical push button,
operation counter necessary auxiliary switches, closing shunt trip, air insulated
busbar chamber having heat shrinkable PVC sleeves, mechanical interlocks safety
shutters, isolating plugs and a VCB trolley with three vacuum interrupters with epoxy
support insulators and self aligning finger type isolating contacts. The breaker shall
be Manual cum motorised mechanism & auto spring charge with TNC switch closing
with following accessories. The Standared Companies Switchgear shall be Used and
Only Manufacutres as per IEC 61439 for beneficial use.
1.flush mounting type digital multifunctional meter with communication facility -
2. Power Factor Meter One No -
3. Double core current transformer cast resin type having ratio 200 to 50/1 core for
metering & second core for protection having required class of accuracy. - Three Sets
4. Instantaneous under voltage relay,Over Voltage relay & Temperature rise Tripping
5. Electrical closing coil & short trip coil operating on 110V. D.C.- Three Sets -
6. Auxiliary relay for anti pumping device -
7. Three phase Three limb Drawout type feeder connected & output of 200 VA cast
resin insulated potential transformer having ratio 12000V./110V. and 200 VA Burdon -
with 0.5 accuracy. - One No.
8. Common Alarm bell operating on 110V A.C.- One No. -
9. Digital KWH Meter - One No. -
10. Cable boxes suitable up to 11 KV 3core 150 sq.mm XLPE cable. - Three Nos. -
11. 230V. A.C. to 110V. D.C. power pack for closing & tripping circuit common. -
12.Breaker ON-OFF, Auto trip and spring charged indicators. - Three Sets. -
13.Phase indicating & panel illumination lamps with plug socket - Three Sets. -
14.Numerical Communicable type non directional O/C & E/F Relay with
a setting of 5-250% both in O/C & E/F. -Three Set
complete with necessary interconnection with air insulated high grade copper
busbar {Breaker Testing scope include Closing Time, Opening Time, VCB Hi-Pot test
at Site}{ Relay Testing Scope Include testing of all protection by three phase testing
kit at site }(VCB Trolley is to be provided)
Supplying, installing, testing approved make Resin Vacuum Impregnated Dry Type,
AN Naturally Cooled Double wound core type, suitable for Indoor / Outdoor
Installation, Copper Wound 11/ 0.433 kV Step Down Transformer of following
capacities operating on 3 phase,50Hz, 4wire and neutral earthed system. H.V. shall
be connected Delta and Secondary with star connection having vector group Dyn-
11.Continuously rated for a Temperature Rise in winding not exceeding 90 degree at
maximum ambient temperature of 50 degree with F Class Insulation and 115 degree
with H Class insulation respectively whichever is required. Following standard fitting
as per applicable BIS 11171 & BIS 2026 with Off Circuit Links in steps of + /- 5%,+ /-
2.5%’on H.V. side for H.V. variation should be provided. The Transformer should have
Cable end Boxes on H.T. side Suitable for 3 Core, 150Sq.mm. XLPE cable on L.T. side
suitable for Busduct or Cable Box as per requirement.
Enclosure shall be painted with enamel paint shade 632 as per
I.S.(Crompton/Kirloskar / Alsthom / Voltamp make) -
1. 1No. Winding Temperature Indicator with Alarm and Trip Contacts.
2. Rating and Diagram Plate -
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
3. Off Circuit Tapping Links for + /-5%H.V. variation in steps, in steps of 2.5% -
4. 2 Nos, Earthing Terminals . -
5. Base Channel with Hauling Holes. -
6. Lifting lugs for Transformer -
7. Enclosure with suitable arrangement to accept H.V. L.V. Cables / Busduct -
8. Ventilation grid. -
9. Warning Plate -
10.Junction Box for Winding Temperature Indicator. -
11. Ventilation Louvers -
12. Flat Rollers -
13. Lifting lugs as applicable -
14.Primary and Secondary Un-drilled Gland Plates./15. H.V. & L.V. and Neutral
Providing and fixing printed instruction chart both in English and Gujarati and duly
44 framed with front glasses, for treatment of person suffering from Electric shock with Ea. 1.00 129.00
minimum 50" diagonally size.
45 Providing pair of rubber hand gloves suitable for working on 11 KV/22 KV supply. Ea. 1.00 212.00
46 Supplying rubber matting of following thickness as per IS:15652/IEC 61111 -
Supplying stand first AID box with antiseptic cream, medicine for use on wounds due
burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-aid)
adhesive tape for medicinal user, Scissors, anti-septic solution (Savlon or similar)
etc. (All above contents shall be of standard makes)
Supplying FIRE bucket round bottom of 9 litres capacity made out of 24 gauge G.I.
sheet with extra handle at bottom duly painted white inside and Red out side with
FIRE mark, filled with dry-sand and kept on existing stand provided or hung on wall
Supplying and erecting floor mounting stand for keeping four nos. of FIRE buckets
comprising 1500 mm in length, 900 mm height frame made out of 30mm X30 mm X
4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted
with one coat of red lead and two coats of approved enamelled silver paint.
Providing and erecting ISI Marked 3core 240 Sq.mm XLPE insulated 11 KV armoured
50 cable Aluminium conductor IS-7098 to be laid on wall with clamps or in provided Mtr 50.00 2,196.00
cable trench / pipe approved manner as directed.
Providing and erecting cable end termination kit, heat shrinkable Push on type
51 Densons’/ ‘Raychem’/ Elastimold make suitable for 11 KV XLPE cable 3 core 50 & 70 - -
(B) Indoor type Ea. 4.00 6,628.00
Providing and erecting cable end termination kit, heat shrinkable Push on type
52 Densons/ Raychem/ Elastimold make suitable for 11 KV XLPE cable 3core 95 & 120 -
(B) Indoor type Ea. 1.00 7,925.00
Supplying and erecting high tension cable end box outdoor type suitable. for 11 KV
240Sq.mm 3core H.T. cable complete with gland bushing and jointing material.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
Supplying & erecting D.C.P. type fire extinguisher for following capacity cartridge type
with gun metal cap 150 gram CO2 gas cartridge, powder and brackets confirming to
IS 2171 1985 and complete erected with necessary clamps made from 50 x 6 mm M
S Flat with nuts and bolts grouted in wall complete.
[A] For 5 Kg Capacity Ea. 2.00 1,696.00
Supplying & erecting carbon dioxide (CO2) fire extinguisher user of following capacity
55 with necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in - -
[A] For 4.5 Kg Capacity Ea. 1.00 6,526.00
[B] For 5.5 / 6.5 KG Capacity Ea. 1.00 8,586.00
Supplying & erecting ABC powder type 'Ceasefire' type Fire extinguisher as per IS
13849 or 1 Kg capacity with necessary clamp for erection on wall
Supplying and erecting Right angle / straight boot made from Synthetic rubber and
57 suitable for covering of cable up to 400 sq mm & should be installed directly on DIN Ea. 1.00 1,527.00
Bushing on HT VCB or Transformer without bending of boot.
10-4 Generating Sets -
Supply, Installation, Testing and Commissioning (SITC) of Silent Type Diesel
Generating (DG) Set(s) of prime power rating (kVA) as specified, complete as a
packaged system, conforming to CPCB IV+ (or better) emission norms, and
complying with all applicable statutory requirements, codes and standards including
(but not limited to) IS 4722:1968, IS 13364 (Part 2) and BS 5514 (latest
editions/amendments). The DG set shall be suitable for 415 V ±10%, 50 Hz ±5%, 3-
phase, 4-wire operation at 0.8 lagging power factor, 1500 RPM, for tropical
conditions, and shall be capable of delivering 10% overload for one (1) hour after
twelve (12) hours of continuous operation (ISO 8528), unless otherwise stated by the
OEM. The scope shall include complete accessories, interconnections,
58 foundations/anti-vibration arrangements, exhaust system, acoustic enclosure,
earthing (as required), consumables for first commissioning, and all works necessary
to render the installation fully functional and compliant, as directed by the Engineer-
in-Charge (EIC). Factory testing shall be carried out with fuel and load bank at
power factor and the DG set shall be offered for inspection prior to dispatch. The DG
set shall be provided with a durable QR code/label fixed on the enclosure/control
panel, linking to a document repository containing (as a minimum) approved GA
drawings, wiring diagrams, foundation and installation details, OEM catalogues,
operating & maintenance manuals, factory test reports, type test certificates (where
applicable), warranty certificate, geo-tag of manufacturing location, and rating plate
data as per relevant IS/BS/ISO requirements.
The OEM/Contractor shall provide a Remote Monitoring System (RMS) with minimum
one (1) year connectivity (SIM/data plan/server access as applicable), including
dashboard access, user ID/password, and data download facility. RMS shall, at
minimum, capture and report: DG status (Auto/Manual/Off), start/stop events,
kW/kVA/kVAR, V/I/Hz, PF, run hours, fuel level, battery voltage, alarms/trips with time
stamp, and GPS/location (where supported). All licences/subscriptions required for
the stated period shall be included in the quoted price.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
(A) Diesel Engine:
Turbocharged, 4-stroke, water-cooled, multi-cylinder diesel engine, suitably rated for
the specified DG set prime rating at site conditions, complete with dynamically
balanced flywheel, heavy-duty engine mounting, and electric starting arrangement.
The engine governing shall be electronic (isochronous/droop as per OEM standard)
and shall comply with ISO 8528/BS 5514 requirements for steady-state speed
regulation. Engine shall be complete with dry type air cleaner with restriction
indicator, lube oil cooler (if required), radiator/cooling package (as applicable), and
all sensors/switches required for protections and annunciation. The engine shall be
capable of 10% overload for one (1) hour after twelve (12) hours continuous
operation and shall be suitable for continuous duty under tropical ambient
conditions. The offered engine model shall be CPCB IV+ compliant and shall be
supplied with complete emission control/after-treatment system (including
DEF/urea dosing where applicable) along with all accessories, tanks, pumps, heaters
and controls required for compliant operation. The supply shall include first fill of
lubricating oil, coolant and consumables required for initial commissioning and
testing. All fasteners, couplings, guards, hoses and standard/recommended
accessories required for safe and reliable operation shall be included and shall be
subject to inspection/approval by the EIC.
(B) Engine-Mounted Instrumentation/Control Panel:
Engine-mounted instrument/control panel shall be microprocessor based, with
LCD/LED display, event log and alarm/trip annunciation, complete with all wiring,
harnesses and terminations. Indications/protections shall include (minimum) the
following and any additional protections recommended by the OEM: (i) Start/Stop
key switch and/or push buttons with emergency stop; (ii) Output breaker: suitably
rated 4-pole ACB/MCCB/MCB as applicable, with minimum 25 kA rupturing capacity
(or as per fault level at site, whichever is higher), with shunt trip where required; (iii)
Jacket water/coolant temperature – indication and high temperature alarm/trip; (iv)
Lube oil pressure – indication and low pressure alarm/trip; (v) Lube oil temperature
(where provided) – indication/alarm; (vi) Battery charging indication, battery voltage
indication and charging failure alarm; (vii) Engine speed (RPM) indication and
overspeed trip; (viii) Engine running hours meter (non-resettable); (ix) Fuel level
indication and low fuel alarm; (x) Fail-to-start / crank fail alarm; (xi) Under/over
frequency and under/over voltage protection (alternator side) as applicable; (xii)
Common alarm and common trip indication with potential-free contacts for
BMS/remote annunciation. All meters/indications shall be of proven industrial
quality and the panel shall be wired, ferruled and labelled. The contractor shall
submit wiring diagrams, protection settings and datasheets for approval prior to
dispatch/installation.
(C) Alternator:
Synchronous, brushless alternator of appropriate kVA rating, 415 V, 3-phase, 50 Hz,
1500 RPM, 0.8 lagging PF, continuous duty, dynamically balanced rotor, self-cooled,
self-excited and AVR regulated. Enclosure shall be SPDP, minimum IP23. Insulation
shall be Class H with suitable tropicalization; temperature rise shall be within limits
of the applicable standard. The alternator shall comply with IS 13364 (Part 2), IS
4722 and/or BS 2613 (latest), as applicable. Voltage regulation with AVR shall be
within ±1.0% (steady state) or OEM standard whichever is better. The alternator shall
be capable of 10% overload for one (1) hour after twelve (12) hours of continuous
operation. Harmonic distortion shall be suitable for non-linear loads; alternator shall
be equipped with appropriate AVR features (e.g., soft start, UFRO) and shall be
suitable for motor starting duties typical to the installation. Terminals shall be
brought out to a terminal box with adequate space for termination and shall include
earthing terminals. All routine/type test certificates (as applicable) shall be
submitted for acceptance.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
(D) Base Frame & Foundation: Engine and alternator shall be mounted on a suitably
designed, fabricated MS channel base frame with stiffeners, lifting arrangement and
coupling guard, duly painted/treated for corrosion protection. The set shall be
installed on an adequately designed cement concrete foundation/pedestal with
anchor bolts, pockets, grouting and anti-vibration mounts (AVMs) / spring isolators
as per OEM recommendations and site conditions. Vibration levels shall be within
OEM permissible limits. The contractor shall be responsible for alignment, levelling,
tightening torque and re-check after load trial, complete in all respects.
(E) Fuel Tank: In-built/base fuel tank fabricated from minimum 3 mm thick MS sheet,
duly leak-tested, complete with filling arrangement, vent, drain, cleaning opening,
level indication and isolation valve(s). The capacity shall be adequate for minimum
eight (8) hours continuous operation at full load. Fuel piping between tank and
engine shall be MS ‘C’ class pipes of suitable diameter with compatible flexible
connections (where required), complete with all valves, clamps, supports, unions
and fittings. Any additional safety provisions required by local fire
authority/UGVCL/competent authority (such as double wall/bunding, flame arrestor,
etc.) shall be provided within the quoted scope.
(F) Exhaust System: Heavy-duty residential type exhaust silencer suitable for CPCB
IV+ installation (with DEF/after-treatment system wherever applicable) along with
exhaust piping of required length, bends, supports and flexible bellow, complete with
rain cap, drain arrangement and all accessories. Exhaust piping shall be thermally
insulated/lagged and cladded where required to ensure personnel safety and to limit
heat radiation inside the DG room/enclosure. The complete exhaust arrangement
shall be designed such that engine exhaust back pressure remains within OEM
permissible limits and shall comply with applicable statutory and safety
(G) Starting System:
12 V / 24 V DC electric starting system (as per OEM design) comprising starter
motor(s), battery charger/alternator charging arrangement, relays, cabling and
terminals, complete with maintenance-free batteries of suitable Ah capacity to
ensure minimum three (3) consecutive cranking attempts. System shall include
battery isolator and indication of charging healthy/failure. All battery
interconnections shall be with crimped lugs, insulated sleeves and proper supports,
complete in all respects.
(H) Acoustic and Weatherproof Enclosure: Acoustic enclosure shall be factory-
fabricated, weatherproof and corrosion protected, suitable for outdoor installation,
with minimum IP65 protection (or better) for the enclosure body. Enclosure design
shall provide adequate fresh air intake and hot air discharge for engine radiator and
alternator cooling such that the internal temperature rise remains within OEM limits
at full load. Provision shall be made for safe access/maintenance including lockable
doors, viewing window (where provided), emergency stop access, and cable entry
glands. Noise level of the complete DG set with enclosure shall not exceed 75 dB(A)
measured at 1.0 m distance in free field conditions, in accordance with applicable
CPCB requirements. The enclosure shall comply with CPCB IV+ (or better)
requirements and other applicable local rules/regulations. All louvers, acoustic
infill/insulation, fasteners and sealing arrangements shall be of fire-
retardant/industrial grade as per OEM standard. Any deviation from the specified
noise/IP requirements shall be treated as non-compliance unless explicitly approved
by the EIC in writing.
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
Erection, testing, commissioning and satisfactory performance demonstration shall
be carried out as per site requirements and as directed by the Engineer-in-Charge.
The scope shall include pre-commissioning checks, insulation resistance tests, no-
load and load trials, safety/protection checks, and performance test on load bank
(where directed) with submission of test records. The contractor shall provide initial
consumables including first fill of diesel fuel (minimum up to 80% of fuel tank
capacity), lubricating oil, coolant, etc. required for commissioning and the specified
tests. The bidder/OEM shall provide comprehensive warranty/guarantee for the
complete DG system (engine, alternator, control panels, RMS, enclosure and all
accessories) for a minimum period of two (2) years from the date of
commissioning/handing over, whichever is later, covering defects in materials and
workmanship. During warranty, all spares/repairs/replacements and visits required
to maintain the DG set in serviceable condition shall be carried out at no additional
cost. All necessary statutory approvals, inspections, testing and certification from
the Electrical Inspector/competent authority (including provision, testing and sealing
of energy meter(s) wherever applicable) shall be arranged and obtained by the
contractor within the quoted scope and time, at no extra cost. Required O&M
manuals, as-built drawings, warranty certificates and training to operating staff shall
be provided prior to handing over.
Note: The DG set specifications shall comply with the latest CPCB
guidelines/notifications and all applicable local rules/regulations prevailing as on the
last date of tender submission applicable local rules/regulations prevailing as on the
last date of tender submission
(V) Continuous rating of 500 KVA ,BHP not less than 600 BHP Each 1.00 5022726.00
Free standing floor mounted IP 42 automatic mains failure control panel
including auto by-pass, suitable for KVA as below for silent type DG set complete
with relays, timers, set of CTs for metering & protection and energy analyser to
indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo
Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW (MFM) & provision for
overload, short circuit, restricted earth fault, under frequency, all complete and
inter locking and communication/ Ethernet /RS485/SNMP port open protocol
for BMS integration including suitable software, the panel shall be of DG Set. as
per approved by Engineering in charge and including the following:
1. Suitable numbers and appropriate capacity 4 ACB/ MCCB with electronic
release for O/C & E/F and shunt trip. (Icu=100%Ics) (Not below 25KA Breaking
Capacity at 415Volts), (Total Three Breakers)
2. Auto/Manual/Test/Off selector switch
3. Protection for under and over voltage phase reversal (2 nos Over voltage
relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).
4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I
5. Energy analyser unit to indicate current, Voltage( L- N & L_L), kW, kVA (Phase &
Total), Frequency, KWH, PF.
6. LED Indicating lamps for load on mains and load on set
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
7. Fuse/ MCB for instruments
8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and
ammeter, selector switch for trickle, off and boost and current adjustment.
9. Control/Signal/Multi core/Communication Cables between DG Set and AMF Panel
10. Main supply failure monitor
11. Supply failure timer
12. Restoration timer
13. Control unit with three impulse automatic engine start/stop and failure to
14. Impulse counter with locking and reset facility.
15. ON/OFF/Control circuit switch with indicator
16. Audio/Video annunciation for
(i) High water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start
(v) Full load/maximum load warning
16. Protection for over/under Frequency, Loss of AC sensing, Over Current,
Unbalancing load with suitable number of relays and accessories
17. Maintenance notification based on Engine Run Hour & due date.
18. Load Management through PLC to achieve auto opening and closing of
incomer breakers, bus coupler switching of essential panel , interlocking
providing signal to AMF Panel for load status and AMF shall give command to
DG Set to auto start / auto stop depending upon load status and requirement
etc. and necessary hardware and software required to perform the operation
shall be provided by the contractor including all control wiring.
(G) AMF Control Panel for 500 kVA 3 phase DG Set Ea. 1.00 438931.00
Acoustic enclosure (canopy) -
Supplying and erecting Acoustic enclosure
(canopy) made out of 18 SWG, CRCA Sheet,
sound absorbing material Rockwool of
density & 100 mm thick conforming to IS:8183
The resin bonded Rockwool / PU FOAM
covered from inside level not more than 75 dB
at a distance of 1 mtr, as PVCT norms , on
provided foundation suitable for following size of
DG Set. The enclosures for following capacity
(H) For 500 kVA Each 1.00 394916.00
10-5 LIGHTNING ARRESTER -
SITC of Vertical Air Termination Solid aluminium with Base- 10 mm Each
dia and 1000 mm long. Air Termination Base tested for conditioning,
Ageing Test & Lightning impulse current withstand test: 100 kA of
61 10/350µs waveform in an accredited Third party laboratory as per 6.3 34.00
& 6.4 of IEC 62561-1 2017 protocol with MAST 34mm dia 3000 mm
long- Cold Galvanized
Bill of Quantities for Electrical Works (Admin Building & External Development)
SUBHEAD 6A ELECTRICAL WORKS
SECTION - 1-2 Point wiring in Copper (MODULAR)
Sl.No Description Unit Total Quantity Rate Amount
SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid Mtr
and tested as per IEC 62561- 2 conducted in the Govt. accredited
thirty party laboratory to meet the requirement of IS/IEC 62305 with
Required Accessories - Aluminium Holding clamp at every 1 mtr
distance, Aluminium/SS cross splicer at every crossing of Alu.
conductor, Expansion piece with connectors at every 20 mtr distance,
Aluminium straight Splicer to connect conductors. All Accessories
should be tested as per IEC 62561-1 2018 Cl. 6.3 for conditioning &
Ageing Test & 6.4 for Lightning impulse current withstand test:
kA of 10/350µs waveform(Ageing & Electrical test ) conducted in a
sequence manner & tested in the Govt. accredited Third party
laboratory to meet the requirements of IS/IEC
SITC of 10 mm MS Round Solid Conductor having smooth surface Mtr
Should be tested and use exclusively for lightning protection (Vertical
Riser/Down Conductor which shall be concealed in Column OR
Flushed on) to meet the requirement of IS IEC 62305 With
Accessories - Earthing stud of dimension SS-75mm OD plate with
10mm dia tail connector used in structural steel ring earthing system
to meet the requirements of IS/IEC 62305. (For Interconnecting the
Column and the Terrace AL Conductor / Strip/Flat), SS Cross
Connector to connect Earth fixing point to vertical raiser/Down
63 conductor, SS Straight Splicer at every 4 Mtr to connect MS 1,350.00
conductor in column, Bonding /Rebar Clamp at every 3 mtr suitable
for interconnecting round conductor with reinforcement inside the
concrete for structural earthing system, SS connector -To connect
external conductor 8- 10 mm with earth fixing point. All Accessories
should be tested as per IEC 62561-1 2018 Cl. 6.3 for conditioning &
Ageing Test & 6.4 for Lightning impulse current withstand test:
kA of 10/350µs waveform(Ageing & Electrical test )
conducted in a sequence manner & tested in the Govt. accredited
Third party laboratory to meet the requirements of IS/IEC
SITC of Galvanized Steel Flat 25x6 mm thickness from earth Mtr
electrode directly in ground as required. Zinc coating: 500 g/m
64 square (Approx:70 micron coating) tested and used exclusively for 170.00
lightning protection earthing system and ring equipotential bonding.
SITC of 14.2 mm dia 3 mtr long Earth electrode of High tensile steel Per Set
electrode with 250 micron copper bonding & 1 bag of Carbon fill
Based environment friendly backfill tested as per IEC 62561-7 in
NABL accredited Laboratory and suitable stainless Steel double
65 sided clamp. Eco Friendly rust proof heavy duty weather proof 34.00
Polyethylene Earth Pit Chamber with following dimensions :254 mm
dia (top), 330 mm dia (bottom) & 260 mm (height).
Sl. No. Description Unit QTY Rate Amount
1 Cable Terminal ( ‘Plain" Type)Set of Four for
2 Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 25 KA. at 415 V,having
normal current rating up to 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C. supply 50 c/s. with all -
internal connections, spreader tinned copper & complete erected in
existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III Ea. 12.00 6,723.00
3 Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. at 415 V. having
normal current rating 125A. with Fixed thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all internal connections, -
spreader tinned copper & complete erected in existing 16 G.M.S.
ICS=100% of ICU only Cat III Ea. 3.00 8,774.00
4 Providing and erecting Approved make Four pole moulded case
circuit breaker having breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with variable Thermal & magnetic
release suitable to work on A.C.supply 50 c/s. with all internal -
connections, spreader tinned copper & complete erected in existing
ICS=100% of ICU only Cat III Ea. 1.00 17,667.00
5 Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. and above at 415 V .
having normal current rating 250A. with variable thermal & magnetic
release suitable to work on A.C.supply 50 c/s. with all internal -
connections, spreader tinned copper & complete erected in existing
G.M.S. housing.
ICS=100% of ICU only Cat III Ea. - 22,813.00 -
6 Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 KA and above at 415 V
having Normal current rating 400A. with variable Thermal & magnetic
release suitable to work on A.C.supply 50 c/s. With all internal -
connections, spreader tinned copper & complete erected in existing
G.M.S. housing.
ICS=100% of ICU only Cat III Ea. 2.00 27,477.00
7 Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 K.A. and above at 415 V
having normal current rating up to 630A. with variable thermal &
magnetic release suitable to work on A.C.supply 50 c/s. with all -
internal connections, spreader tinned copper & complete erected in
existing 16 G.M.S. housing
ICS=100% of ICU only Cat III Ea. 3.00 30,685.00
8 Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 K.A. and above at 415 V
having normal current rating 800A.with variable thermal & magnetic
release suitable to work on A.C.supply 50 c/s. with all internal -
connections, spreader tinned copper & complete erected in existing
ICS=100% of ICU only Cat III Ea. - 33,472.00 -
Sl. No. Description Unit QTY Rate Amount
9 Providing and erecting Approved make Three pole moulded case
circuit breaker having breaking capacity ICU of 25 K.A. at 415 V
having normal current rating up to 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C. supply 50 c/s. with all -
internal connections, spreader tinned copper & complete erected in
existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III Ea. 30.00 5,832.00
Sl. No. Description Unit QTY Rate Amount
10 Providing and erecting Approved make Three pole moulded case
circuit breaker having breaking capacity/strength ICU of 35 K.A. at
V. having normal current rating 125A.with Fixed thermal & magnetic
release suitable to work on A.C.supply 50 c/s. with all internal -
connections, spreader tinned copper & complete erected in existing
G.M.S. housing.
ICS=100% of ICU only Cat III Ea. 4.00 7,161.00
11 Providing and erecting Approved make Three pole moulded case
circuit breaker having breaking capacity/strength ICU of 35 K.A. and
above at 415 V. having Normal current rating 200A.with variable
Thermal & magnetic release suitable to work on A.C.supply 50 c/s. -
with all internal connections, spreader tinned copper & complete
erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III Ea. - 16,963.00 -
12 Providing and erecting Approved make Three pole moulded case
circuit breaker having breaking capacity/strength ICU of 50 K.A. and
above at 415V. having normal current rating 250A. with variable
thermal & magnetic release suitable to work on A.C.supply 50 c/s. with -
all internal connections, spreader tinned copper & complete erected in
existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III Ea. 1.00 24,272.00
13 Providing and erecting Approved make Three pole moulded case
circuit breaker having breaking capacity/strength ICU of 50 K.A. and
above at 415 V having Normal current rating 400A.with variable
Thermal & magnetic release suitable to work on A.C.supply 50 c/s. -
With all internal connections, spreader tinned copper & complete
erected in existing 16 G.M.S. housing.
Sl. No. Description Unit QTY Rate Amount
ICS=100% of ICU only Cat III Ea. 1.00 27,477.00
14 Providing and erecting Approved make Earth fault Relay suitable to
mount with inter connection suitable to following size of moulded case
circuit breaker having CT ratio & MCCB rating as following along with -
shunt trip 220V AC. with all internal connections & complete erected in
existing M.S.housing..
15 Providing and erecting following additional parts for panel mounting
(A)Extended operating rotary handle with pad lock with three position
trip,off,on suitable for 25A to 250 A panel mounting cat-III
(B)Extended operating rotary handle with pad lock with three position
trip,off,on suitable for 400A to 630 A panel mounting cat-III Ea. 6.00
16 Approved make standard Draw out type 4 Pole Air circuit breaker.
Having 50 kA breaking capacity with ICU=ICS=ICW (1 sec)Vsr=690 v,
Ui=1kv ,impulse voltage=12 kv with following type of relay and -
(1) Manual Draw out type (MDO) with following type of relay system
(B) with microprocessor Release with over load, short circuit, earth
fault protection and metering display in modular design with LED
display and Test Trip button facility, CTs and auxiliary contacts, of -
following current ratings.
(i) 800Amp 50 kA Cat III Ea. 2.00 1,32,891.00
(iv) 1600Amp 50 kA Cat III Ea. 1.00 1,72,789.00
17 Providing & erecting Accessories For Air Circuit Breakers as follows:
(A) Six way Isolating Contact block Ea. 3.00 1,433.00
(B) Lockable Trip Push Button Type A,B,C,D Ea. 3.00 2,094.00
(C) Lockable Trip Push Button Kit L, M, LM, MN Ea. 3.00 9,476.00
(D) Locking of ACB in Isolated Position Ea. 3.00 2,145.00
(E) Locking of ACB in Any Position Ea. 3.00 2,145.00
(F) Racking Inter Lock Ea. 3.00 3,967.00
(G) Door Inter Lock Ea. 3.00 2,145.00
18 Providing & erecting additional parts for Air Circuit Breakers as
(A) Auxiliary Contact Block for CN-CS 800 to 2500 & 2 NO + 2 NC
(E) Shutter Accessories for 800 / 1000 / 1250/ 1600 A ACBs Ea. 3.00 882.00
(H) Shunt Release Type EA1 : 240V AC Ea. 3.00 2,035.00
(M) CTs for 800 C / 1000 C with 400A / 640A and 800A taps for Fixed
& Drawout Type ACBs
(N) CTs for 1250 C / 1600 C for Fixed & Drawout Type ACBs Ea. 1.00 2,924.00
(P) Fixed Type Arcing Contacts Kit for 3 Pole ACB of 800A to 1600A
19 Supplying and erecting triple pole & neutral 440V / 500V panel
mounting Copper Busbars with four equal Nos. of electrolyte bus
having current density not more than 1.6 Amp. / sq.mm (Rated current
/ cross section area) duly wrapped with colour insulating tape for
phase sequence of following current carrying capacity, erected with -
necessary bus bar supports /insulators, main cable socket to each bar,
erected in existing cubical panel with necessary connections.
(A) Suitable for 100 Amp. Capacity Rn.Mtr 80.00 1,942.00
Sl. No. Description Unit QTY Rate Amount
(B) Suitable for 200 Amp. Capacity Rn.Mtr 61.00 3,171.00
(C) Suitable for 300 Amp. Capacity Rn.Mtr 25.00 4,861.00
(D) Suitable for 400 Amp. Capacity Rn.Mtr 45.00 7,247.00
(E) Suitable for 630 Amp. capacity Rn.Mtr 10.00 10,455.00
(F) Suitable for 800 Amp. capacity Rn.Mtr 10.00 13,069.00
Suitable for 1600 Amo. Capacity
20 providing and erecting Miniature circuit breaker single pole 6A to 25A
suitable to operate on 240 V A.C. system and having breaking
capacity 10 KA to be erected in existing box. confirming to IS -
8828/1996 with ISI Mark
Cat.III Ea. 615.00 122.00
21 Providing & erecting 415V MCB Four Pole Switch for Lighting Load (B
curve) having 10KA breaking capacity & confirms to IS :8828 in -
existing box having following capacity
Cat.III Ea. 10.00 696.00
22 Providing & erecting 415 V MCB Four Pole for Motor & Inductive
Load (C Curve) having 10KA breaking capacity & confirms to IS :8828 -
in existing box having following capacity
Cat.III Ea. 4.00 729.00
Cat.III Ea. 10.00 803.00
23 Providing & erecting 415 V MCB three Pole for Motor & Inductive
Load (C Curve) having 10KA breaking capacity & confirms to IS :8828 -
in existing box having following capacity
(a) 6 to 32 Amp. -
Cat.III Ea. 59.00 641.00
Cat.III Ea. 21.00 706.00
Cat.III Ea. 1.00 780.00
24 providing and erecting Approved make RCCBs conforming to IS:
12640 and having sensitivity of 30 mA and Short Circuit withstand
capacity of 10 KA and suitable for operation on single phase
V,50Hz. having characteristic of quick action & tripping with all -
advance feature & do not incorporate any electronic component. for
following Max. rating erected as directed
(i) 25 Amps.DP -
Cat. III Ea. 1.00 2,145.00
(ii) 40Amps. DP -
(iii) 63 Amps. DP -
25 Providing and erecting metallic vitrified danger notice board as per
language suggested by engineer incharge for MEDIUM VOLTAGE Ea. 20.00
installation to be erected as per IS-2551.
26 Providing and erecting metallic vitrified danger notice board as per
language suggested by engineer incharge for HIGH VOLTAGE Ea. 2.00
installation to be erected as per IS.-2551.
Sl. No. Description Unit QTY Rate Amount
27 Providing & erecting weather proof, dust & vermin proof, floor mounted
front operated indoor type cubical panel board necessary IP-42 and
above protection as per approval from engineer incharge made from
14 SWG thick CRC M.S. sheet for outer body & doors, 16 SWG thick
CRC M.S.sheet for internal partitions with necessary accesories , -
supporting angles/ flats channel including cutting, bending, drilling,
welding, riveting with internal partitions & cable alley as per
requirements & instruction of engineer-in-charge with erection of
Sl. No. Description Unit QTY Rate Amount
supplied switch gears, BUSBARS, suitable size of inter connecting
PVC copper wire / copper-aluminium strips, rubber grommets, rib,
bakelite control fuses/MCB for measuring instruments, earth bus &
earth bolts, foundation flange - bolts-base Plates, sufficient nos. of
hinged doors, handles with locking arrangement and rubber -
gasket,heavy duty end terminal connection,danger notice
board,necessary ventilation,earthing strip complete. The Panel shall
be painted with epoxy powder coating.
(The rates excludes the cost of switchgears, bus bars, inter connecting
mains & Copper Aluminium strips, meters, Fuses etc. The dimension
shall be measured excluding base beams) The panel shall be supplied -
with following approved manufacturers with following size.
(C) The standard companies switch gear shall be used and only
manufacturers as per IEC 61439 for beneficial use.
(i) with 350mm depth Sq.Mtr 26.00 16,230.00
(ii) with 550 mm. Depth Sq.Mtr 37.00 21,116.00
(iii)with 750 mm. Depth Sq.Mtr 1.00 36,556.00
(iv) with 1000 mm. depth Sq.Mtr 36.00 44,654.00
28 Providing , erecting , fabricating the M.S. structure as per requirement
on site incorporating proper size of M.S. angles,square,round, flats,
bars, channels, sections complete with cutting, welding, grinding &
finishing duly painted with one coat of red oxide with erection on site Kg. 15.00 77.00
as per direction of engineer in charge with necessary grouting,
cementing, plastering & finishing complete.
SCHEDULE OF QUANTITIES
Subhead-6 ELV WORKS
GENERAL NOTES :
All items of work under this Contract shall be executed strictly to fulfil the requirements laid down under “Basis of Design” in the specifications. Type of
equipment, material specification, methods of installation and testing and type of control shall be in accordance with the specifications, approved shop
drawings and the relevant Indian Standards, however capacity of each component and their quantities shall be such as to fulfil the above mentioned
2 The unit rate for all equipment or materials shall include cost in RUPEES for equipment and materials including all taxes and duties and also including
forwarding, freight, insurance and transport into Contractor’s store at site, storage, installation, testing, balancing, commissioning and other works required.
3 The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated otherwise, include cost of :
All materials, fixing materials / supports , flanges , accessories, appliances tools, equipment, transport, labour and incidentals including all civil works required
in preparation for and in the full and entire execution, testing, balancing, commissioning and completion of work called for in the item and as per Specifications
b. Wastage on materials and labour.
Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing in position, protecting, disposal of debris and all
c. other labour necessary in and for the full and entire execution and for the job in accordance with the contract documents, good practice and recognise
d. Liabilities, obligations and risks arising out of Conditions of Contract.
All requirements of Specifications, whether such requirements are mentioned in the item or not. The Specifications and Drawings where available, are to be
read as complimentary to and part of the Schedule of Quantities and any work called for in one shall be taken as required for all.
In the event of conflict between Schedule of Quantities and other documents including the Specifications, the most stringent shall apply. The interpretation of
the Consultant/Project Manager shall be final and binding.
All equipment, quantities and technical data indicated in this Schedule are for the Contractor’s guidance only, these are based on the documents prepared by
4 the Consultant. This schedule must be read in conjunction with other documents. The Contractor shall be paid for the actual quantity of work executed by him
in accordance with the approved Shop Drawings at the contract rates.
5 This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all items shall be filled in INK including NIL items.
No alteration whatsoever is to be made to the text or quantities of this Schedule unless such alteration is authorised in writing by Consultant. Any such
alterations, notes or additions shall, unless authorised in writing, be disregarded when tender documents are considered.
In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of the unit rate and quantity, the unit rate quoted by the
tenderer shall be regarded as firm and the extensions shall be amended on the basis of rates.
Any error in totalling in the amount column and in carrying forward total shall be corrected. Any error, in description or in quantity, omission of items from this
Schedule shall not vitiate this Contract but shall be corrected and deemed to be variation required by the Consultant/Project Manager.
Rates have been called for a number of items of works, as alternatives which, for the present do not form part of the total value of tender. However the rates for
9 these items shall be quoted, with due care so that in the event of choice of an alternative item of work, said rate shall form part of the contract and shall not
violate the contract any way.
The Contractor shall procure and bring Materials/Equipment to the site only on the basis of drawings approved for construction and shop drawings and not on
the basis of Schedule of Quantities which are provisional only
The required provisons for physical secuirty equipments such as Civil foundations , underground HDPE pipes etc will be in Civil vendor scope. ELV vendor to
coordinate with respective vendor.
Client - AMBAJI AREA DEVELOPMENT AUTHORITY
Project: ADMINISTRATIVE & FIRE SERVICES BUILDING
GRAND SUMMARY FOR FIRE ALARM, DIGITAL PUBLIC ADDRESS SYSTEM,SECURITY, CBS &
Sr. No DESCRIPTION AMOUNT
A FIRE ALARM & DIGITAL PUBLIC ALARM SYSTEM
B CCTV (IP BASED) SYSTEM
C ACCESS CONTROL SYSTEM -IP BASED
D BUILDING AUTOMATION SYSTEM (BAS)
E IT NETWORK FOR SECURITY & BAS SYSTEM
F OFFICE IT NETWORK(Passive)
G CENTRAL BATTERY SYSTEM (CBS) FOR
EMERGENCY & EXIT LIGHTING SYSTEM
TOTAL AMOUNT (Ecluding GST)
TOTAL AMOUNT (Ecluding GST)
Bill for Quantities for Fire Alarm & Digital Public Address System
SCHEDULE OF QUANTITIES FOR FAS & PA SYSTEM
SR NO. DESCRIPTION OF ITEM UNIT RATE AMOUNT
I FIRE ALARM & DIGITAL PUBLIC ALARM SYSTEM
A INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
Supply, Instllation, Testing & Commissioning of the following equipment for
Supplying, Installing, Testing & Commissioning of Fire Alarm Panel (FACP) same
shall be Multi Loop (as mentioned below point a & b) Networked Microprocessor
based for the loop per panel as mentione below (each loop shall be able to connect
minimum 125 detectors and 125 modules or 250 Detector & Devices any
combination) intelligent, one loop mshall not exceed 85% of total loop capacity
,analogue addressable type fire alarm control panel, LCD display minimum
Characters, four access levels, 400 event historical logging, flash EPROM sufficient
numbers of programmable relay controls, Fiber Optic Module for Networking,240
volts AC power supply, automatic battery charger, 24 volts sealed lead acid
1 batteries sufficient for 24 hours normal working and then be capable of
operating the system + 1 hr backup with 25% Loop under fire condition
including all necessary , Floor mounted Battery Stand , Accessiories & software for
remote programming of fire alarm system through central control station and shall
have provision for 20% spare capacity including all necessary software for remote
programming of fire alarm system through central control station. All the panel
should be networkable on decicated fire alarm network through Optical Fiber
connectivity cable & Shall provide BACnet MSTP communication protocol form
integration with BMS sytem, UL & FM approved (Location: At Ground floor Fire &
Secuirty Control Room )
Supplying, installation, testing and commissioning of micro processor based
Intelligent addressable main Fire Alarm Panel, central processing unit with the
following loop modules and capable of supporting not less than 240 devices
(including detectors) and minimum 120 detectors per loop and loop length up to
km, network communication card, minimum 320 character graphics/ LCD display
with touch screen or other keypad and minimum 4000 events history log in the non
volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up
with 24 volt sealed maintenance free batteries with automatic charger.
The panel shall have facility to connect printer to printout log and facility to have
seamless integration with analog/digital voice evacuation system (which is part of
the schedule of work under SH: PA System) and shall be complete with all
accessories . The panel shall be compatible for IBMS system
with open protocol BACnet/ Modbus over IP complete as per specifications.
(Location: At Ground floor Fire & Secuirty Control Room )
a 10 Loop Panel 1.00 Each 4,01,655.48
b 2 Loop Panel 1.00 Each 2,10,119.15
Note : 1) All the Fire Alarm Panels,Detector & Devices shall be UL/ EN Certified
approved & shall meet 10th Edition compliance of Fire Panel & 7th Edition for -
Detectors & Device
2) While Selecting the Fire Panel & no of Loop in each panel ,Vendor to Make Sure
Loop Shall Not Exceed 85% Of Total Its Capacity.
UL/EN Listed Auxillary Power Supply 24 DC for Hooter cum Strobe , gas
detetcors, UVIR Detectors, The power supply shall be with efficiency greater then
85% and have indicators for power Monitoring.Note: Max 5-6 Hooters shall be
clubbed in one power supply.
Supplying, installation, testing & commissioning of Repeater panel with
4 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence 2.00 Each 95,430.44
switches complete as required
Note : 1 No Network Repeater at Admin Building Reception area -
1 No Network Repeater at FS Building Reception area -
Supplying, installation, testing & commissioning of central graphical fire alarm
management system to centrally monitor and operate the fire alarm system
complete as required.
(Location: At Admin Building Ground floor Fire & Secuirty Control Room )
SR NO. DESCRIPTION OF ITEM UNIT RATE AMOUNT
B DETECTORS AND DEVICES -
All Detectors & Devices shall be Supplied and Installed with Complete with
2mm thick MS Powder coated RED Colour Junction Box & Back Box with
Cover for mounting on Surface, Cable lugs at Ends, cable Double
compression glands, cable tags and Ferruling etc.
Supplying, installation, testing & commissioning of Intelligent analog addressable
photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal
6 detector with rate of rise cum fixed temperature thermistor complete with base as 105.00 Each 2,404.77
Supplying, Installing, Testing & Commissioning Intelligent addressable type Multi
7.0 Sensor detectors with mounting base, LED, address switch/Automatic address 325.00 Each 3,000.00
completeas per specifications .(AFC/BFF/BFC) Detectors shall be UL/EN Approved
Supplying, installation, testing & commissioning of response indicator on
8.0 surface/recessed MS Box having two LED, metallic cover complete with all 271.00 Each 256.75
connections etc as required.
Supplying, installation, testing & commissioning of fault isolator complete with
base as required.
Supplying, Installing, Testing & Commissioning of Addressable Monitor modules
with OEM with LED face plate to monitor status like flow Switch,Tamper Switch in
Fire fighting, PNG gas detector and other applications etc.as per specifications
Supplying, installation, testing & commissioning of addressable fire control
module complete as required.
Supplying, installation, testing & commissioning of addressable manual call point
complete as required.
Supplying, Installing, Testing & Commissioning of Universable Stopper Dome for
Manual Pull Station , Polycarbonate Transparent Covers for the Manual Pull Stations
Flush mount with Red Colour Strip & Leble Configuration UL listed LPCB (To
prevent accidental operation of the manual Pull point)
Supplying, installation, testing & commissioning of addressable horn cum strobe
complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset
complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack
complete as required.
Supplying, installation, testing & commissioning of intelligent interface unit
18.00 BACnet/ Modbus protocol i.e. supplying communication links between building 2.00 Each 1,64,630.81
management system and fire alarm control panel complete as required.
Supplying, installation, testing & commissioning of Auto Dialer unit as per
Supplying, installation, testing & commissioning of Heavy guage Magnetic Door
Contact for Fire Exit Doors as per Specification shall be UL approved
II DIGITAL PUBLIC ADDRESS SYSTEM
Supplying, Installing, Testing & Commissioning of the Public Address system
consisting of the following:
SR NO. DESCRIPTION OF ITEM UNIT RATE AMOUNT
NETWORK CONTROLLER / DIGITAL VOICE CONTROLLER (DVC) With ACCESSIORIES
Supplying, Installing, Testing & Commissioning of Control Equipment OF Digital
Sound Management System with Emergency Sound System , certified to
International standards of Emergency Sound System (IEC 60849) with following
features:The qouted rate shall inclussive of all required for the satisfactory of the
- SITC of EN54 Certified Digital Controllers & Amplifiers for All floors
- The system shall work as a standalone voice alarm system as well as be
integrated with each other over dedicated fiber optics ring network for paging
- Audio Matrix Stackable Voice Alarm system, 8+2In x8 Out, Master module incl.
21 local network.
- All systems should work seamlessly over dedicated fiber optics ring network
without any middle level converter with the ability of making zone wise paging
announcmenents from any of the call stations in from any of the buidings
- The paging stations should work as an intercom between other paging stations in
case of an emergency.
Amplifier fault logging upto 2048 incidents, Amplifier monitoring, Integration with
FACP, 100 priority levels, 7 band parametric equaliser per zone
Distribution/Location of controllers & amplifiers will be as per floor darwings
(Contractor shall furnish quantity and unit rate for each type of amplifier & 2.00 Sets
Controllers considered by him.)
- Completely digital (DSP signal) audio transmission.
- Optical Fiber Based redundant ring Cabling for communication
- In-built digital message recording and broadcast.
- Each level shall have N+1 redundancy for amplifiers.(Every 4 Amplifier there shall
be stand by 1 amplifer
- Shall be Expandable to 256 zones
- Total PC based programmable
- Min 20 simultaneous audio channels for messaging
- Power Saver Mode
- Integration with Fire alarm system
- Integration with BAS system in Conrtoller Modbus RS 485 communication card
shall be provided
Equipment Rack / PA RACK: Floor mountable Equipment Rack for housing PA
Network Controller , Amplifiers and Music Source at required location with required
slots as per the equpement requirement (Contractor to select the the Rack as per
requirements) The cost of the Rack shall be included in each floor DVC line item
Supplying, installing, testing & commissioning of Music Source of Rack Mounted
DVD/CD/MP3 and AM/FM Music Source At engineering block Main IBMS room.
NOTE : All The Digital Audio Amplifiers, Digital Voice Controllers shall be EN
54 Approved & Speakers shall be EN 54 Complied
DIGITAL AUDIO AMPLIFIERS
SITC of Power amplifier, 2x500W 2 ✕ 500 W class-D power amplifier (70/100 V
Low power consumption in standby mode
Excellent sound quality, high signal-to-noise ratio
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Power amplifier, 250W X 2 class-D
power amplifier (70/100 V output)
Low power consumption in standby mode Excellent sound quality, high signal-to-
EN 54-16 and ISO 7240-16 system certification
23 [Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]- 3.00 Each 35,000.00
All Equipment should be Rack Wall or Surface mountable Equipment Rack for
(Contractor shall furnish quantity and unit rate for each type of amplifier
considered by him saperate saperate for Each fllor as per zone full tapping
load wattage calculation keeping 20% spare wattage capacity in each zone &
SR NO. DESCRIPTION OF ITEM UNIT RATE AMOUNT
SITC of Power amplifier, 124W X 4 class-D
power amplifier (70/100 V output)
Low power consumption in standby mode Excellent sound quality, high signal-to-
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]-
All Equipment should be Rack Wall or Surface mountable Equipment Rack for
(Contractor shall furnish quantity and unit rate for each type of amplifier
considered by him saperate saperate for Each fllor as per zone full tapping
load wattage calculation keeping 20% spare wattage capacity in each zone &
Note: Refer PAS Schematic & General notes for no of Zone configuration -
SITC of Ceiling loudspeaker 6W metal clamp mount Suitable for speech and music
Easy to install
Optional certified fire dome
EN 54‑24 certified [Approved
by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Metal fire dome
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Cabinet loudspeaker, metal, rectangular Suitable for speech and music
Robust metal enclosure
Surface and/or recessed mounting
Provision for internal mounting of the optional line/loudspeaker supervision boards
EN 54-24 certified
BS 5839‑8 and EN 60849 compliant
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
Supplying, Installing, Testing & Commissioning of 20 W Wall Mounted weather
28 proof Metal Projector Speaker with Multi Tapping & all fixing accessories Feature 20.00 Each 3,600.00
as per Specifcation. EN 54 Complied
SR NO. DESCRIPTION OF ITEM UNIT RATE AMOUNT
Supplying, Installing, Testing & Commissioning of Touch Screen 5" display IP
based Announcement console complete with microphone and Zone selection
Vendor to slect the console as per no of zones in the block with spare 20% Zone
quantity (Location : Fire & Secuirty Command center )
III CABLES & ACCESSORIES for FAS & PA -
FAS Cable: Supplying, installing, testing and commissioning of 2 core 1.5 Sqmm
Fire Survival Armored ATC cable for fire detection and alarm system with Cross
linkable Low smoke zero halogen insulation and LSZH inner and outer sheath
with insullation with Glass Mica (Fire barrier) tape ,cable shall retain circuit
30 integrity upto min 3 Hours @ 950 Deg C as per latest IS 17505 Code approved as 28,000.00 Mtrs. 160.17
per any Indian Govt. approval agency viz., ERDA Armored cables as per standards.
cable should be RED in color, The quoted rate shall be inclusive of suitable saddles
spacers, hardware, Double compression glands, heavy guage 2mm thick junction
boxes / concealed back boxeswith all necessary accessories required for system
PAS Cable: Supplying, installing, testing and commissioning of 2 core 1.5 Sqmm
Fire Survival Armored ATC conductor ,Shielded, Twin Twisted cable for PA
system with Cross linkable Low smoke zero halogen insulation and LSZH inner
and outer sheath with insullation with Glass Mica (Fire barrier) tape ,cable shall
31 retain circuit integrity upto min 3 Hours @ 950 Deg C as per latest IS 17505 Code 5,500.00 Mtrs. 160.17
approved as per any Indian Govt. approval agency viz., ERDA Armored cables as
per standards. The quoted rate shall be inclusive of suitable saddles spacers,
hardware, Double compression glands, heavy guage MS Powder coated 2mm thick
junction / concealed back boxes with all necessary accessories required for system
FAS Communication Cable: Supplying, installing, testing and commissioning of
2Pair X 1.5 Sqmm Fire Survival Armored ATC conductor ,Shielded, Twin
Twisted cable for PA system with Cross linkable Low smoke zero halogen
insulation and LSZH inner and outer sheath with insullation with Glass Mica
32 (Fire barrier) tape ,cable shall retain circuit integrity upto min 3 Hours @ 950 Deg C 1,000.00 Mtrs. 127.12
as per latest IS 17505 Code approved as per any Indian Govt. approval agency
viz., ERDA Armored cables as per standards. The quoted rate shall be inclusive of
suitable saddles spacers, hardware, Double compression glands, heavy guage MS
Powder coated 2mm thick junction / concealed back boxes with all necessary
Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted
black surface/concealed of following size complete to be erected on/in wall
or ceiling with erected with necessary saddles, screws, bends, junction
boxes etc. with following (Nominal Bore) dia of pipes, in approved manner
Note: Metal Conduit shall be provided for concealing the cable within the wall -
Supplying, installing, testing and commissioning of 2 mm thick GI trunking with
34 cover of the following sizes complete with angle iron supports/hanging arrangement -
and all other necessary accessories etc
The rate of each item of work for Fire Detection and Alarm System & PA shall also include the following :
1. All materials, fixing materials, accessories, appliances, tools and equipment.
2. Approved cover plates for inspection, junction and outlet boxes.
3. 2 mm thick MS Powder coated outlet boxes and junction boxes with Double compression Glands .
4. All fixing accessories such as clips, nails, screws etc.
5. Providing and fixing approved saddles, hooks and grouting the same as required, in the case of all exposed cable work.
6. Embedding cables and accessories in wall, floors etc. during construction and / or cutting chases and making good as in the case of all concealed cables work.
7. Testing and commissioning of each device, circuit as per the requirements of NFPA 72, TAC, local authorities and to be witnessed by the PMC / Client / Consultant.
Bill for Quantities for CCTV (IP BASED) SYSTEM
SCHEDULE OF QUANTITIES FOR CCTV SYSTEM
DESCRIPTION OF ITEM
QUANTITY UNIT AMOUNT
II CCTV (IP BASED) SYSTEM
Supply,Installation Testing of the following equipment for IP based CCTV System
5MP @20 fps or better) IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized
1 lens Dome Camera. 103.00 Each 15,732.51
2MP (@ 25/30fps@1080P (1920×1080)) IP IR Dome Camera with 2.8/ 3.6mm fixed lens
2 For Lift 4.00 Each 4,690.38
Note : The installation and routing of the data cable inside the lift car shall be carried out
by the Lift OEM and shall be connected to nearest Network Rack
5MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens outdoor
3 Bullet Camera. 32.00 Each 15,732.51
5MP IP IR motorized PTZ @25/30fps or better camera, Triple streaming , configurable
on resolution:- Main stream: 5MP@25/30 fps Sub streams:1080p@25/30 fps, varifocal
lens 3.95mm (±5mm) ~ 177.75mm (±5mm) or better with Automatic & manual Focus
Adjustment provisions, 45x Optical zoom and 16x Digital zoom with angle of view H:
65.7°–1.9°V: 39.4°–1.1°D: 73.1°–2.1, PAN Travel: Pan: 0° ~ 360° endless,Manual Pan: -
Supply, installation, testing and commissioning of MS poles for outdoor cameras, made
out of 5mm thick, 80mm dia pipe with zinc chromite primer & powder coating of suitable
shade along with Outdoor IP 65/66 rated Pole mounted Box for termination approx size
(300mmx 200mmx100mm) for housing Din ril mounted Power supply &
module/converters (OFC to Copper). Total Pole height including pedestal =5Mts. -
6 Network Video Recorder (NVR) -
Supplying Installation Testing and Commissioning of following Channel Network Video
Recorder (NVR) with camera licenses to record for all channels having specifications
and features etc as mentioned below :
1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses
to record per NVR and to provide a live view, storage and simultaneously Multi-channel
7 playback of all IP camera or more and must be ONVIF with minimum support of 384 -
Mbps incoming Bandwidth.
2) NVR should support video compressions : H.265 or better, H.264, MJPEG.
3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with
G.711U/A, G.711u, PCM, G726 audio compressions.
4) Intelligent auto power on when power resumes after power outage.
8) Video Output Ports: 2x HDMI and 2 VGA
9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external
sensors and output devices like hooter/ Siren etc.
10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated
mobile number for power failure, HDD failure, vandalism, tempring, network -
disconnection and panic
11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for
alerts and viewing.
12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter,
15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing)
16) The VMS application shall support all the features & functionalities of the offered
17) VMS should consist Licenses for all channels to record Cameras with General,
motion detection, intelligent, alarm and POS recording modes. VMS should be
provided with Camera Licenses , with no dependency of VMS licenses by binding with
the MAC address of the cameras to achieve the functionality. -
18) The NVR OEM shall be responsible for providing a mobile application compatible
with both Android and iOS devices, enabling remote monitoring and playback of
cameras/NVR footage.
19) The OEM must provide its own DDNS server hosted in India, eliminating the need
for a public IP address for remote monitoring over the Internet.
20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode
DESCRIPTION OF ITEM
QUANTITY UNIT AMOUNT
23) The Network Video Recorder (NVR) shall be configured to send email whenever a
system message is created or an alarm event occurs. The email server shall be a valid
SMTP server. Each recipient email address shall be configured to receive any
combination of critical, warning, or informational messages or alarm notifications. When
an alarm occurs, the email message includes the NVR name, time of alarm and a list of
camera that is configured to record upon alarm
24) It should have Web and GUI interface.25) Built-In Artificial Intelligence: NVR should
have built-in AI :-- 2 Channel face detection and recognition, - Minimum 4 Channel
perimeter protection, - Minimum 8 Channel Smart Motion Detection 26) Face Recognition
Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum
20,000 Faces or more with Face Detection speed of 12 face images/sec and facility to
add Name, gender, birthday, address, credential type, credential No., countries & regions
and state to each face image.
27) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group,
29) Alarm Notifications based on: Motion detection, video tampering, video loss, scene
changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter
protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd
distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan,
cybersecurity exception30) Alarm Notification should be linked with Recording, snapshots, -
Camera external alarm output, buzzer, logs, presets and email.
31) General AI Based Search: Search Pictures by channel, time, event type, target
classification (Fall Detection, People Approach Detection, People No. Exception
Detection, People Staying Detection,Violence Detection.
32) Smart playback function: Should support smart search for the selected area in the
32 Channel Network Video Recorder (NVR) having display split :- Main screen:
screen: 1/4/8/9/16
HDD to be slected/Calculated for 16 FPS @ 1080p resolution for 45 days on Motion -
The camera shall be viewed on 25 FPS ie live viewing -
Hard Disk Drive
Supplying, Installation, Testing and Commissioning following capacity Serveillance
grade Hard Disk with -
upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor,
SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, -
4TB (Terabytes)
6TB (Terabytes)
8TB (Terabytes)
Supply, installation, testing & commissioning of CCTV Remote Viewing station as
per Specification with the following Minimum Configurations :-
- Processor : Intel i7 processor Latest Generation or Intel® Xeon® D latest series
Processor Technology
- High Speed 32 GB DDR4 Expandable to 64 GB
Graphic Accelerator Multi graphics Technology N-vidia Quadra with 4GB Memory with
Dual/Quad monitor capable graphics card – Maximum display can be connected.
Hard DiskFor OS500GB SSD Network Interface CardON Board - 1/10Gig -
Minimum 2 Ports
Network Interface CardPCI Slot based 1/10Gig - Dual with Dual SFP prots for fiber
Power Supply Energy Start /PA compliant
Keyboard & Mouse Wireless/Cordless 104 keys window 98 keyboard & Mouse,
OS Software ConfigurationWindows 10 Pro with Lifetime Licensed Along with
Enterprise version MacAfee or equivalent Reputed pre-loaded Lifetime Licensed
InterfacesHDMI & DVI -Yes, VGA – Yes, shall have USB* 3.1 and Thunderbolt™
technology , 8 USB 2.0, 1 serial, 2 Ultra ATA/100,2 optional IEEE1394, 1 PS/2 Keyboard,
1 PS/2 Mouse, 1 video, 1 Microphone jack, 1 Line-in jack, 1 RJ-45, 1 Headphone jack &
line-out jack (analog/SPDIF digital),
CD DVD WriterDVD/CD-RW Combo Drive with speakers
Note : The viewing Station Quantity is for Viewing 224 Nos cameras at one time any -
combination (Operator to select) out of Total - 400 Nos camera -
Supply, installation, testing and commissioning of 24" LED colour UHD resolution ,Flat
10 Screen type 24x7 operated Professional CCTV Surveillance HD monitor for above client 6.00 Each 25,000.00
workstation along with 1 no for 2 no monitors , Heavy duty Desk Stand, Height Adjustable,
Swivel & Tilt Support, Articulating Stand (Dual Monitor ARM) for for above client -
DESCRIPTION OF ITEM
QUANTITY UNIT AMOUNT
Supplying, Installation, Testing and Commissioning of following size LED display (LED
monitor) industrial
11 grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast -
connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video
wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V):
170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and
55 inch or larger
TOTAL II CARRIED TO SUMMARY
Client - AMBAJI AREA DEVELOPMENT AUTHORITY
Project: ADMINISTRATIVE & FIRE SERVICES BUILDING
Bill for Quantities for ACCESS CONTROL SYSTEM (IP BASED)
SCHEDULE OF QUANTITIES FOR ACCESS CONTROL SYSTEM (IP BASED)
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
III ACCESS CONTROL SYSTEM -IP BASED
Supply, installation, testing & commissioning of following Access
control system equipments
ACCESS CONTROL MANANAGEMENT SERVER & SOFTWARE
Software for Web based Access Control System 1.00 Each 81,537.17
Supplying, Installation, Testing and Commissioning of Web based
Access Control Enrolment and Device Configuration Software,
Should be independent of OS (Windows), Unified Management of
Biometric, Card, and Controllers, Import Functionality for bulk user details,
Biometric Template Retrieval for Data Recovery, User Management, Logs
and Terminal Management, Support for IP-based and USB Biometric
Devices, User-specific Access Policies, Different User Policies on the
Same Terminal, Assignment of Specific Access Schedules, Pushing
Users to Terminals or Groups, Admin Authority Management to define
rights of each user to perform, Blacklist User Management, Access
Schedule Creation, Real-Time Log Retrieval, Real- Time User
Identification, Secure Storage of Biometric/Users Data, Capable to
integrate with 3rd party applications over Web API's, MQTT protocol
Supply, installation, testing & commissioning of Management , Data
base & Domain server with Redundancy (N:N) Specification with the
following configuration :
All software components are pre-installed at the factory with proper
hardening including :
Operating System (OS) ,Software Patches ,Firmware updates ,Factory
Configured Raid , throught Benchmarked and Finely tuned and optimized
Form Factor : 2U Rackmount
Rack Support: Sliding Rack Rail with Cable Management Arm
Processor(s) : Intel® Xeon® Silver 2nd Gen Scalable Processoror 1.00 Set 6,05,932.00
Latest as per OEM (Server Graded) (16 Cores, 32 Threads, Turbo
GHz per processor using Intel®)
HDDFor OS500GB SSD , For Application and DatabaseMin 3*2 TB
7200RPM - SCSI with RAID support
Operating System : Windows Server 2019 Standard
Database SoftwareMSSQL 2008 and above or Oracle 8i or IBM DB2.
or latest with Lifetime Licensed
Memory : 64 GB DDR4 with memory expandable 128GB through four
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
RAID Controller PERC H740P (8GB NV Cache, Supports RAID 0, 1, 5,
Networking : Single Processor: (2) 1GbE RJ45 Ports, (2) 10GbE SFP+
Ports upto 2033 Mbit/s,10Gb NIC
Redundant Power Supply Yes Power ManagementEPA compliant
Keyboard & Mouse Wireless/Cordless 104 keys window 98 keyboard &
Mouse with Lifetime Licensed Along with Enterprise version MacAfee or
equivalent Reputed pre-loaded Lifetime Licensed
Graphic AcceleratorNVIDIA GeFore - 2GB RAM (Dedicated)
Remote Management : iDRAC with plug-in integrates with VMS and
provides hardware events, notifications and alarms to be presented within
LCD Display & KVM Switching : 19" LCD/LED Rack Mounted Display for
accessing Servers , Software with
KVM Switches (Keyboard, Video, Mouse) – Centralized control for multiple
servers if required.
Redundancy Management , Data base & Domain server shall be N : N
Configuration. Cost shall be along with Redundancy set.
(Refer Technical specifications documents etc.) (This is only Minimum
requirement. Vendor to consider as per OEM recommendations in case of
higher configurations required as per System requirements to fulfil the
complete functionality of the system and quote accordingly and submit the
Configuration to Client/Consultant) :
Supply, installation, testing & commissioning of ACS Remote station
as per Specification with the following Minimum Configurations :-
- Processor : Intel i7 processor Latest Generation or Intel® Xeon® D
latest series Processor Technology
- High Speed 16 GB DDR4 Expandable to 64 GB
Graphic Accelerator Multi graphics Technology N-vidia Quadra with 4GB
Memory with Dual/Quad monitor capable graphics card – Maximum
display can be connected.
Hard DiskFor OS500GB SSD Network Interface CardON Board -
1/10Gig - Minimum 2 Ports
Network Interface CardPCI Slot based 1/10Gig - Dual with Dual SFP
prots for fiber termination
Power Supply Energy Start /PA compliant
Keyboard & Mouse Wireless/Cordless 104 keys window 98 keyboard &
OS Software ConfigurationWindows 10 Pro with Lifetime Licensed
Along with Enterprise version MacAfee or equivalent Reputed pre-loaded
Lifetime Licensed
InterfacesHDMI & DVI -Yes, VGA – Yes, shall have USB* 3.1 and
Thunderbolt™ technology , 8 USB 2.0, 1 serial, 2 Ultra ATA/100,2
optional IEEE1394, 1 PS/2 Keyboard, 1 PS/2 Mouse, 1 video,
Microphone jack, 1 Line-in jack, 1 RJ-45, 1 Headphone jack & 1 line-out
jack (analog/SPDIF digital),
CD DVD WriterDVD/CD-RW Combo Drive with speakers
Workstation shall be with all fixing accessories & stand.
(This is only Minimum requirement. Vendor to consider as per OEM
recommendations in case of higher configurations required as per System
requirements to fulfil the complete functionality of the system and quote
accordingly and submit the Configuration to Client/Consultant)
4.00 Supply, installation, testing and commissioning of 24" LED colour UHD
resolution ,Flat Screen type 24x7 operated Professional CCTV
Surveillance HD monitor for above client workstation along with 1 no for
no monitors , Heavy duty Desk Stand, Height Adjustable, Swivel & Tilt
Support, Articulating Stand (Dual Monitor ARM) for for above client
IP Based ACCESS CONTROL PANEL -
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
6.00 Supply, installation, testing and commissioning of Wall Mounted IP
Network based 4 Reader Control panel housed in MS Powder Coated
Cabinet with Tamper Switch, complete with On-board IP / LAN port, and
Built-in Web Server for Remote Log in to every controller. Each Controller
shall have min 24 Inputs and 16 outputs. Also the Controller should have
spare potential free contact to add/trip any third party system, if required. 25.00 Each 55,085.00
It shall be Complete with power supply unit for Controllers & Magnetic
Locks. All Controllers shall have necessary integration device to connect
Fire alarm system to operate automaticlly during emergency or shall be
integrated based on client requirements.
(Refer Technical specifications documents, DBR etc.)
Access Control System with Face recognition -
Supplying, Installation, Testing and Commissioning of Access Control
System comprising of Face and
fingerprint Recognition, Smart Card, QR Code, NFC & PIN Code based
Reader, following sizes of 5” IPS TFT Touch Screens, 1GB RAM, 8 GB
ROM, Live Face Detection with anti-spoofing against 2D photograph,
mobile selfie & video, Fake Fingerprint and face Detection Technology,
30,000 Face storage (1:N) /, 3,000 fingerprint (1:N), QR code
30,000 card storage (1:N), 2 lakh transaction storage, 20,000 image logs,
onboard dual camera (colour & IR) Primary camera min 2MP, Support
authentication & verification from up to 1 meters, Communication potocols
WiFi, TCP/IP, Wiegand Out,
Wiegand IN, USB, MQTT protocol, Blacklist Employee Management, User
wise authentication modes; Built in Lock Control, Mask Detection & Alert
(configurable), 40 to 30,000 lux illumination, IP65 for Ingress Protection,
Certification: CE, FCC, BIS, ROHS, etc. Metal Enclosure with battery
backup, suitable for mounting on metal surface/metal frames/ wooden
frames/wall/flap barriers including all mounting bracket & accessories
complete etc. as required.
5" IPS TFT Touch Screen 4.00 Each 48,922.64
Note : Face recognition Is used for Attendence located near Employee
Electromagnetic locks -
Supplying, Installation, Testing and Commissioning of Electromagnetic
locks (fail safe type) for following type of Doors suitable for operation on
12 V DC having holding force 600 lbs for Single Leaf Door and 1200lbs for -
Double leaf door with suitable feedback i/c connection complete etc. as
Single Leaf Door 26.00 Each 4,053.53
Double leaf door (Each leaf 600lbs & Total 1200 lbs) 17.00 Each 6,371.04
Supply, installation, testing and commissioning of Smart card reader
with working Frequency of 13.56 Mhz and read range upto 5 cm.Read
Distance- 5Cm, Memory Type: 1Kbyte / 4Kbyte, Internal LED and Buzzer, 86.00 Each 12,712.00
Operating Temperature range 0-60 Deg C, Humidity- 10 - 90%, IP54.
(Refer Technical specifications documents etc.)
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
12.0 Supply, installation, testing and commissioning of Emergency door
release Exit Glass break unit (Green) With Test Switch (Glass
Type)green double pole. Will all accessories such as Back box , Glands, 43.00 Each 636.00
Key etc for making the system fully functional
(Refer Technical specifications documents)
13.00 Supply, installation, testing and commissioning of DOTL (Door Open to
Long ) with inbuilt Buzzer for alarm with heavy guage Magnetic Contact
for Fire exit doors .
VISITOR MANAGEMENT SYSTEM -
Supply, installation, testing and commissioning of Client Visitor
Management software , Software should be seamlessly integrated with
Access Control System Server Software, same should be configurable
visitor fields to be customized by the system administrator as per owner 2.00 Lot 4,00,000.00
requirement,system should support min 10,000 visitor cards along with
manual or automated email/SMS notifications facility.All these along with
high end security features consist in single package as per specification
Supply, installation, testing and commissioning for Visitor Management
Station shall be min Intel i7 (latest genration) +Processor(Latest
Tecnology) Min 16GB DDR4 Expandable to 64GB , Non-ECC, HDD -
500GB for OS & Min 1 TB 7200RPM - SCSI, Nvidia Quadra with 2GB
Memory dedicated graphic Card with 24 "monitor card output, DVD
Combo, 1/10Gig - Dual Ethernet NIC (Dual Giga Bite Ethernet Ports) &
SMF Fiber port , Inbuilt compatiable Speaker for alarm sound & all other
ports as mentioned in specs. cost shall be along with 5Mp or Better HD
high resoultion USB portable digital camera with mini tripod stand , Visitor 2.00 Set 1,50,000.00
Digital Signing pad, Cordless 104 keys window 98 keyboard & Mouse,
DVD Combo Drive etc., Power supply , latest configuration PCI slots
,USB* 3.1 and Thunderbolt™ technology Port , Cost should be with Life
time Licensed software as follows OS 64 bit Windows 10Pro License or
any latest version compatiable with software, MacAfee Enterprise version
or equivalent Reputed pre-loaded, MS office latest version etc Cost shall
be along with 24" LED UHD Screen & all other accessiories as per
Visitor management module with badge printer (Paper), import tool
(import cardholder & credential data)
CABLES, CONDUITS WITH ACCESSORIES -
Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted
black surface/concealed of following size complete to be erected on/in
wall or ceiling with erected with necessary saddles, screws, bends,
junction boxes etc. with following (Nominal Bore) dia of pipes, in approved
Note: Metal Conduit shall be provided for concealing the cable within the
Supplying, installing, testing and commissioning of 2 mm thick GI
19.00 trunking with cover of the following sizes complete with angle iron -
supports/hanging arrangement and all other necessary accessories etc
TOTAL III CARRIED TO SUMMARY
Bill for Quantities for BAS SYSTEM
SCHEDULE OF QUANTITIES FOR BAS SYSTEM
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
V BUILDING AUTOMATION SYSTEM (BAS)
Supply, Installation, Testing & Commissioning of BMS system devices
A CENTRAL SUPERVISORY STATIONS FOR BMS SYSTEM
1 BMS DATBASE SERVER
Supply, installation, testing & commissioning of Management , Data
base & Domain server with Redundancy (N:N) Specification with the
following configuration :
All software components are pre-installed at the factory with proper
hardening including :
Operating System (OS) ,Software Patches ,Firmware updates ,Factory
Configured Raid , throught Benchmarked and Finely tuned and optimized for
Form Factor : 2U Rackmount
Rack Support: Sliding Rack Rail with Cable Management Arm
Processor(s) : Intel® Xeon® Silver 2nd Gen Scalable Processoror Latest
as per OEM (Server Graded) (10 Cores, 20 Threads, Turbo 3.20 GHz per
processor using Intel®)
HDDFor OS500GB SSD , For Application and DatabaseMin 3*2 TB
7200RPM - SCSI with RAID support
Operating System : Windows Server 2019 Standard
a Database SoftwareMSSQL 2008 and above or Oracle 8i or IBM DB2. or 1.00 Set 6,05,932.00
latest with Lifetime Licensed
Memory : 64 GB DDR4 with memory expandable 128GB through four
RAID Controller PERC H740P (8GB NV Cache, Supports RAID 0, 1, 5,
Networking : Single Processor: (2) 1GbE RJ45 Ports, (2) 10GbE SFP+
Ports upto 2033 Mbit/s,10Gb NIC
Redundant Power Supply Yes Power ManagementEPA compliant
Keyboard & Mouse Wireless/Cordless 104 keys window 98 keyboard &
Mouse with Lifetime Licensed Along with Enterprise version MacAfee or
equivalent Reputed pre-loaded Lifetime Licensed
Graphic AcceleratorNVIDIA GeFore - 2GB RAM (Dedicated)
Remote Management : iDRAC with plug-in integrates with VMS and
provides hardware events, notifications and alarms to be presented within
LCD Display & KVM Switching : 19" LCD/LED Rack Mounted Display for
REMOTE WORKSTATION FOR BAS REMOTE GRAPHIC
Supply, installation, testing & commissioning of BAS Remote Graphic
station as per Specification with the following Minimum
Configurations :-
- Processor : Intel i7 processor Latest Generation or Intel® Xeon® D latest
series Processor Technology
- High Speed 16GB DDR4 Expandable to 64 GB
Graphic Accelerator Multi graphics Technology N-vidia Quadra with 4GB
Memory with Dual/Quad monitor capable graphics card – Maximum display
can be connected.
Hard DiskFor OS500GB SSD Network Interface CardON Board -
1/10Gig - Minimum 2 Ports
Network Interface CardPCI Slot based 1/10Gig - Dual with Dual SFP
prots for fiber termination
a Power Supply Energy Start /PA compliant 2.00 Set 3,26,271.00
Keyboard & Mouse Wireless/Cordless 104 keys window 98 keyboard &
OS Software ConfigurationWindows 10 Pro with Lifetime Licensed Along
with Enterprise version MacAfee or equivalent Reputed pre-loaded Lifetime
InterfacesHDMI & DVI -Yes, VGA – Yes, shall have USB* 3.1 and
Thunderbolt™ technology , 8 USB 2.0, 1 serial, 2 Ultra ATA/100,2 optional
IEEE1394, 1 PS/2 Keyboard, 1 PS/2 Mouse, 1 video, 1 Microphone jack,
Line-in jack, 1 RJ-45, 1 Headphone jack & 1 line-out jack (analog/SPDIF
CD DVD WriterDVD/CD-RW Combo Drive with speakers
Workstation shall be with all fixing accessories & stand.
(This is only Minimum requirement. Vendor to consider as per OEM
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
Main Viewing Screens with wall mount facility having 24" LED screens, with
HDMI/VGA outputs, PC inputs.LED screens should be Full High Definition
(Minimum 1920 x 1080) or Better should have 5 ms or better response
b time,Thin Bezel max 5-8 mm, Energy Star compliant & capable to operate 2.00 Nos 27,500.00
for 24x7 operation .It shall come with remote control and shall have various
picture mode options for data representation with all necessary wall fixing
accessiories for viewing.
Supplying, Installation, Testing and Commissioning of following size LED
display (LED monitor) industrial
grade with 3840x2160 resolution or better, USB playback, bluetooth and
3 miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500- -
nits or better, Video wall mode should be available, contrast ratio: 1200:1,
OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms,
Display control shall be on monitor screen and programmable with remote
(remote shall be supplied with system), Key Board, Optical Mouse, etc. as
55 inch or larger 1.00 Each 68,851.00
4.0 LaserJet printer -
Supplying Installation Testing Commissioning of LaserJet printer having
printing resolution 1200 x 1200 dpi, (dot/inch) or better, 21 to 30 ppm printing 1.00 Each 19,025.00
speed (LaserJet) complete etc. as required
B Software for Building Management System : -
Supplying Installation Testing Commissioning of Necessary Software (UL
listed) Packages containing Building Management with Capability of
Collection, Storage, Processing and Controlling all the Data. Software shall
support Open Standard Protocols like
XML, BACnet, Modbus, Lon works etc. and without the use of Proprietary
Protocols, with Enterprise Level Database Like MS SQL complete Lifetime
Licenced & capable to collect, store & access all points from Fire Alarm
Systems, IT Systems, Automation Systems, HVAC System, Lift, Energy
management, Water Management System, etc. to create & monitor
historical & event data, event management data, alarm management data &
reporting data, Email Alerts for Critical alarms for all the systems. The scope
5 includes additional software required by BMS software (to enable a standard -
Web browser) to be resident on the DDC/client machine (manufacture-
specific browsers shall not be acceptable). User log-on identification and
password shall be required & a minimum three-layered security system(User
interface Level, Application Level and Data Base Level) to be deployed for
safety. The supplied computer software shall employ object-oriented
technology (OOT) for representation of all data and control devices within
the system. This data shall reside on a server for all database access
(Systems requiring proprietary database and user
interface programs shall not be acceptable). All components and controllers
supplied under this contract shall be true “peer-to-peer” communicating
devices (Components or controllers requiring “polling” by a Master / Global /
a For Upto 500 point included 1.00 Each 81,706.00
b For Upto 2500 point included 1.00 Each 1,40,873.00
c For Upto 5000 point included 2.00 Each 2,07,165.00
C MIDDLEWARE & INTEGRATORS FOR SOFT POINTS -
Supply, installation, testing, commissioning of Following BAS
DESCRIPTION OF ITEM QUANTITY UNIT RATE AMOUNT
6 Integration Unit -
Supplying Installation Testing Commissioning following type 3rd party
Integration unit to provide the interface between Ethernet LAN and the 3rd
party field control devices or any other devices which need to be integrated.
These shall also provide supervisory capability of functions over the devices
connected to it. The purpose of using these units should be limited to
integrate the devices only. The Unit must have two onboard Ethernet port,
minimum 2/3 on board RS485 ports. The Integration unit should have inbuilt -
memory for program storage. The Unit must communicate over TCP/IP with
communication speed of 10/100MBPS. The Integration unit should be
capable of handling multiple protocol simultaneously such as Bacnet,
Modbus, SNMP restricted to single protocol. All integrators should be
mandatorily BTL listed. The integration unit shall be housed in suitable size
Integrator for 500 Points 1.00 Each 1,22,608.00
Integrator for 1250 Points 1.00 Each 1,47,975.00
Integrator for 5000 Points 2.00 Each 1,90,253.00
Soft IO Points Breackup as follows: -
VFD System - BACnet MSTP (VFD- 10 Nos) (Connected Respective DDC)
Total -110 Nos Soft IO Points
Outdoor Air Quality Transmitter - AQT-1 No Modbus RS 485 (AQT-
1Nos) Total - 8 Nos Soft IO Points
Indoor Air Quality Transmitter - IAQ-36Nos Modbus RS 485 (IAQ- 1Nos)
Total -252 Nos Soft IO Points
Basment Jet Ventilation Fan PLC - Bacnet IP/Modbus IP (Jet Fans with
EA & FA- 16 Nos) Total - 480 Nos Soft IO Points
VRF Integration (ODU-14 & IDU-79) =93 Nos BACNET OVER IP Total -
2325 Nos Soft IO Points
UPS Integration- BACnet MSTP/ BACNET OVER IP (Qty- 4NOS) Total -
116 Nos Soft IO Points
Battery Monitoring System Integration- Modbus RS 485 (Battery -
Nos) Total - 80 Nos Soft IO Points
Energy Meter & Multifuntion Meter Integration - Modbus RS
(EM=224 Nos & MF- 15 Nos)) Total - 4338 Nos Soft IO Points
DG Integration- BACnet MSTP/IP (DG sets - 1 NOS) Total - 22 Nos Soft
IO Points Integration- Modbus RS485/IP (Elevators- 4 NOS) Total -
Nos Soft IO Points
FAS Integration :BACnet MSTP Total - 2000 Nos Soft IO Points -
STP Integration - Bacnet IP/Modbus IP Total - 150 Nos Soft IO Points -
WTP Integration - Bacnet IP/Modbus IP Total - 150 Nos Soft IO Points -
Hrdropneumatic System (Domestic & Flushing) PLC Integration -
Modbus RS 485 Total - 200 Nos Soft IO Points
Digital RR System Integration : Modbus RS485 (RR- 7 NOS) Total -
Water IO Points
Meter Integration : Modbus RS485 (WM- 7 NOS) Total - 28 Nos
Note : 1) Refer the IO summary BAS IO SUMMARY for Soft IO point
D IP BASED DDC CONTROLLER AND HARDWARE: -
Supply, installation, testing, commissioning of Following -
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
TECHNICAL BID FOR INTEGRATED ADMINISTRATIVE BUILDING OF AADPTGA.pdf
BOQ_AADA_1.7.26 R3.pdf
AADA_TENDER DRAWINGS Part-1.pdf
AADA_TENDER DRAWINGS Part-2.pdf
AADA_TENDER DRAWINGS Part-3.pdf
AADA_TENDER DRAWINGS Part-4.pdf
AADA_TENDER DRAWINGS Part-5.pdf
AADA_TENDER DRAWINGS Part-6.pdf
AADA_TENDER DRAWINGS Part-7.pdf
AADA_TENDER DRAWINGS Part-8.pdf
AADA_TENDER DRAWINGS Part-9.pdf
AADA_TENDER DRAWINGS Part-10.pdf
Download all tender documents and submit your bid