Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.0 LAccepted-Finance | ₹45.0 L | L1 | Accepted-Finance Being lowest tenderer |
| 2 | L2₹47.5 L+₹2.5 L (5.59%)Accepted-Finance 42 608A PULLOMPARAMBIL HOUSE MANDAKARA ROAD KOCHI 682 018 | ERNAKULAM | KERALA | 682018 | ₹47.5 L+₹2.5 L (5.59%) | L2 | Accepted-Finance Other than lowest tenderer |
| 3 | L3₹48.3 L+₹3.4 L (7.47%)Accepted-Finance DOOR NO 68 2963 E3 MANDAKKARA ROAD AYYAPPANKAVU ERNAKULAM KERALA 682 018 | ERNAKULAM | ERNAKULAM | KERALA | 682018 | ₹48.3 L+₹3.4 L (7.47%) | L3 | Accepted-Finance Other than lowest tenderer |
| Sl No | Description | Qty | Unit | Phejays Agencies L1 | WELTRONENGINEERINGSERVICES L2 | ELAN ENGINEERS L3 |
|---|---|---|---|---|---|---|
| 1.00 | Material and labour for servicing of HT VCB 11 KV alongwith CTs/PTs of current rating upto 800 A of any make and type by drawing out breaker assembly from panel and carry out the following work:-
(i) Cleaning/decarbonizing of all fixed and moving contacts, levers, springs using suitable cleaning agent and tightening of screws, nuts, bolts, spring etc,
(ii) Adjust the trolley in and out mechanism ,
(iii) Lubricating/greasing of all operating mechanism and moving parts, switching & tripping mechanism, automatic shuttering system, necessary brazing, turnig, polishing of main and auxiliary contact, demoisturing of insulators, etc to be done
(iv) Testing of tripping performance of HT VCB by primary & secondary high current injection, testing of CT ratio and polarity,
(v) Checking of tripping relay including interlocking if any.
(vi) Checking of operating mechanism adjustments, measurements of the mechanical clearances of the operating mechanism, internal wiring circuit etc, tightening of all connections, replacement of HRC fuse, fuze carrier base (if any found u/s) including removing moisture deposit inside the VCB. (vii) Checking all end terminals, tightening the nut bolt and washers, replace the unserviceable nut, bolt & washers, draw-in the breaker, put in position, engage the VCB with the supply system and testing for smooth functioning complete all as specified and directed.
NOTE :
(i) The cost of cleaning materials, HT Tape, thinner, cotton waste, monoplast, steel nut, bolt with double washers, HRC fuses, MCB SP upto 6 Amp, fuse carrier base, replacement of complete HT packing/gasket shall deemed to be included in the quoted rate.
(ii) Contractor shall isolate and earth the breaker before start the work.
(iii) Servicing of HT VCBs should be carried out as per the schedule of shutdown prepared by the Engineer-in-charge. No exemption to postpone or cancel the work is permitted unless due to administrative reasons accepted by the Engineer-in-chrge. Failure of doing the work as per schedule shall be levied a penalty of 5000.00 Rs per job. | 157 | Each Job | 4,000 ₹6,28,000 Lowest | 4,500 ₹7,06,500 | 4,500 ₹7,06,500 |
| 2.00 | Supply and fixing Panel spout assembly including front and rear with Plug, Shutters, Adapters for VCB 11 KV HT for R, Y, B (including mail & female contact and taking down old item) for VCBs of make CG as that of existing model and capacity complete all as specified and directed. | 6 | Each Set | 10,000 ₹60,000 Lowest | 10,000 ₹60,000 Lowest | 12,000 ₹72,000 |
| 3.00 | Supply and fixing Panel spout assembly including front and rear with Plug, Shutters, Adapters for VCB 11 KV HT for R, Y, B (including female contact and taking down old item) for VCBs of make ABB as that of existing model and capacity complete all as specified and directed. | 3 | Each Set | 10,000 ₹30,000 Lowest | 10,000 ₹30,000 Lowest | 12,000 ₹36,000 |
| 4.00 | Supply and fixing Panel spout assembly including front and rear with Plug, Shutters, Adapters for VCB 11 KV HT for R, Y, B (including female contact and taking down old item) for VCBs of make SCHNEIDER as that of existing model and capacity complete all as specified and directed. | 3 | Each Set | 10,000 ₹30,000 Lowest | 10,000 ₹30,000 Lowest | 12,000 ₹36,000 |
| 5.00 | Supply and fixing trolley bushing with male and female contact for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Each | 4,000 ₹4,000 Lowest | 4,250 ₹4,250 | 4,500 ₹4,500 |
| 6.00 | Supply and fixing push trip assembly as per existing size, type and suitable for 11 KV HT VCB including taking down old item for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Set | 15,000 ₹15,000 | 14,500 ₹14,500 Lowest | 15,000 ₹15,000 |
| 7.00 | Supply and fixing vacuum interrupter, for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Each | 25,000 ₹25,000 | 25,000 ₹25,000 | 22,500 ₹22,500 Lowest |
| 8.00 | Supply and fixing, Cluster contact for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Set | 3,000 ₹3,000 Lowest | 3,500 ₹3,500 | 3,200 ₹3,200 |
| 9.00 | Supply and fixing ,copper bus bar as per existing size, type and suitable for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity including taking down old item complete all as specified and directed. | 10 | KG | 1,800 ₹18,000 | 1,600 ₹16,000 | 1,450 ₹14,500 Lowest |
| 10.00 | Supply and fixing , aluminium bus bar as per existing size, type and suitable for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity including taking down old item complete all as specified and directed. | 10 | KG | 750 ₹7,500 | 750 ₹7,500 | 700 ₹7,000 Lowest |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
31 Aug 2026, 6:55 pmClosed
SHRI R K SINGH IDSE
HQ CWE (NW) KOCHI
REPAIR MAINT SERVICING OF OCBs VCBs ISOLATORS RMU CERTAIN STABILIZERS HT LT BUS DUCTS AND MISCELLANEOUS E/M WORKS INCLUDING CONNECTED ACCESSORIES AND PAINTING TO HT PANELS AT KATARIBAGH NAY GARUDA AND ALL OTHER AREAS AT NAVAL BASE KOCHI
2026_MES_781619_1
CWE(NW)KOCHI/81669
Open Tender
Civil Works
Item Rate
270 days
GE (NS) KOCHI
As per NIT
7 documents required · 7 mandatory
₹500
GE (NS) KOCHI
₹96,000
Yes
7 Sept 2026
29 Jul 2026
5 Sept 2026
29 Jul 2026
31 Aug 2026
12 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material and labour for servicing of HT VCB 11 KV alongwith CTs/PTs of current rating upto 800 A of any make and type by drawing out breaker assembly from panel and carry out the following work:-
(i) Cleaning/decarbonizing of all fixed and moving contacts, levers, springs using suitable cleaning agent and tightening of screws, nuts, bolts, spring etc,
(ii) Adjust the trolley in and out mechanism ,
(iii) Lubricating/greasing of all operating mechanism and moving parts, switching & tripping mechanism, automatic shuttering system, necessary brazing, turnig, polishing of main and auxiliary contact, demoisturing of insulators, etc to be done
(iv) Testing of tripping performance of HT VCB by primary & secondary high current injection, testing of CT ratio and polarity,
(v) Checking of tripping relay including interlocking if any.
(vi) Checking of operating mechanism adjustments, measurements of the mechanical clearances of the operating mechanism, internal wiring circuit etc, tightening of all connections, replacement of HRC fuse, fuze carrier base (if any found u/s) including removing moisture deposit inside the VCB. (vii) Checking all end terminals, tightening the nut bolt and washers, replace the unserviceable nut, bolt & washers, draw-in the breaker, put in position, engage the VCB with the supply system and testing for smooth functioning complete all as specified and directed.
NOTE :
(i) The cost of cleaning materials, HT Tape, thinner, cotton waste, monoplast, steel nut, bolt with double washers, HRC fuses, MCB SP upto 6 Amp, fuse carrier base, replacement of complete HT packing/gasket shall deemed to be included in the quoted rate.
(ii) Contractor shall isolate and earth the breaker before start the work.
(iii) Servicing of HT VCBs should be carried out as per the schedule of shutdown prepared by the Engineer-in-charge. No exemption to postpone or cancel the work is permitted unless due to administrative reasons accepted by the Engineer-in-chrge. Failure of doing the work as per schedule shall be levied a penalty of 5000.00 Rs per job. | 157 | Each Job | - | - |
| 2 | Supply and fixing Panel spout assembly including front and rear with Plug, Shutters, Adapters for VCB 11 KV HT for R, Y, B (including mail & female contact and taking down old item) for VCBs of make CG as that of existing model and capacity complete all as specified and directed. | 6 | Each Set | - | - |
| 3 | Supply and fixing Panel spout assembly including front and rear with Plug, Shutters, Adapters for VCB 11 KV HT for R, Y, B (including female contact and taking down old item) for VCBs of make ABB as that of existing model and capacity complete all as specified and directed. | 3 | Each Set | - | - |
| 4 | Supply and fixing Panel spout assembly including front and rear with Plug, Shutters, Adapters for VCB 11 KV HT for R, Y, B (including female contact and taking down old item) for VCBs of make SCHNEIDER as that of existing model and capacity complete all as specified and directed. | 3 | Each Set | - | - |
| 5 | Supply and fixing trolley bushing with male and female contact for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Each | - | - |
| 6 | Supply and fixing push trip assembly as per existing size, type and suitable for 11 KV HT VCB including taking down old item for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Set | - | - |
| 7 | Supply and fixing vacuum interrupter, for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Each | - | - |
| 8 | Supply and fixing, Cluster contact for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity complete all as specified and directed. | 1 | Set | - | - |
| 9 | Supply and fixing ,copper bus bar as per existing size, type and suitable for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity including taking down old item complete all as specified and directed. | 10 | KG | - | - |
| 10 | Supply and fixing , aluminium bus bar as per existing size, type and suitable for 11 KV HT VCBs of make CG/ABB/MEGAWIN/STERLING/SCHNEIDER/L&T/SIEMENS as that of existing model and capacity including taking down old item complete all as specified and directed. | 10 | KG | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.62 MB
TENDERDOCUS.pdf
Tender Documents • 1.48 MB
BOQ_875608.xls
BOQ • 0.47 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .