Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.7 LAccepted-AOC D1C 47A JANAK PURI NEW DELHI 110058 | NEW DELHI | DELHI | DELHI | 110058 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹47.0 L+₹7.1 L (17.9%)Rejected-AOC 19 62 1ST FLOOR WEST MOTI BAGH SARAI ROHILLA NEW DELHI 110035 | NEW DELHI | NEW DELHI | DELHI | 110035 | L2 | Rejected-AOC L2 Bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in appropriate cat c(i) |
Tender Value
Refer Docs
EMD Value
₹99,000
Closing Date
6 Mar 2021, 6:00 pmClosed
GE I RND DELHI
MILITARY ENGINEER SERVICES, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REPAIR/MAINTINANCE OF TRANSFORMER, VCB PANEL INCLUDING OF HT CABLES AND CERTAIN ALLIED MISC WORKS AND REPAIR/REPLACEMENT/MAINTINANCE OF CENTRAL AC PLANTS, VRF UNITS AND PACKAGE TYPE AC INCLUDING ALLIED WORKS AT SSPL LAB AND ZONE A AT KWC AREA UNDER G
2021_MES_416783_1
GE/RND-62/DLI/2020-2021
Open Tender
Civil Works
Item Rate
180 days
DELHI
Class D, Category b(ii) and c(i)
2 documents required · 2 mandatory
₹500
GE I RND DELH
₹99,000
Yes
27 Mar 2021
28 Jan 2021
8 Mar 2021
28 Jan 2021
6 Mar 2021
22 Feb 2021
Amount
S&F in repairs cable jointing kit 11 KV (Earthed) indoor termination, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm including thimbling, nut/bolts & washers, HV insulating tape etc. complete all as specified and as directed.
All as per item No 1.00 above but of size 120 to 185 sqmm
All as per item No 1.00 above but of size 240 to 300 sqmm
S&F in repairs cable jointing kit 11 KV (Earthed) straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size upto 70 to 95 Sqmm including thimbling, nut/bolts & washers, HV insulating tape etc. complete all as specified and as directed.
All as per item No 4.00 above but of size 120 to 185 sqmm
All as per item No 4.00 above but of size 240 to 400 sqmm
S&F in repair of unreinforced Precast concrete cable cover , class HVP, Type 1 with peak, size 300mmx180mmx40mm complete all as specified & directed.
S&F in repair of ACB 4 pole ,415 V , with Thermal magnetic release (Manual fixed type) of capacity 630 Amps complete all as specified & directed.
S&F in repair of ACB 4 pole ,415 V , with Thermal magnetic release (Manual fixed type) of capacity 800 Amps complete all as specified & directed.
S&F in repair of ACB 4 pole ,415 V , with Thermal magnetic release (Manual fixed type) of capacity 1000/1250 Amps complete all as specified & directed.
Material and Labour for earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not lesss than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised iron strip of 25x4 mm by means of Copper nuts, bolts and washers. Strip laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point complete all as per plate No 3 of SSR Part-I-2009including testing, taking down old unserviceable cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following:- (a) Earth work in any type of soil. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits). (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 40mm thick reinforced with 8mm dia TMT bars 75mm centre to centre both ways with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover.
M&L for PCC 1:3:6 type C-1 using 20 mm graded stone aggregates) for repairing of LT pole foundation etc including filling in road cuts/ hard standing etc complete all as specified and as directed.
M&L in replacement of old unserviceable for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25x4 mm galvanised iron strip complete all as specified and directed
M&L in replacement of old unserviceable for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 32x6 mm galvanised iron strip complete all as specified and directed
S&F in repair HT XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cable(Heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 120 Sqmm 3 core complete all as specified & directed.
S&F in repair HT XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cable(Heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 185 Sqmm 3 core complete all as specified & directed.
S&F in repair HT XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cable(Heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 240 Sqmm 3 core complete all as specified & directed.
S&F in repair GI pipe light grade of 100mm dia laid in trenches for protection of UG cable complete all as specified & directed.
S&F in repair GI pipe light grade of 80mm dia laid in trenches for protection of UG cable complete all as specified & directed.
M&L for boring of holes under road, pavement, hard standing by trenchless techonology using ultra sound technique/mannually/mechanically and necessary machine including laying of 100mm dia GI pipe complete all as specified and directed
Taking proper shutdown & Isolate the HT electric supply and taking out the trolley of VCB HT 11KV 400 to 630 amps of any make and type and servicing of all minor/major parts of the VCB by cleaning isolating contact moving parts,removing dust particle from the bus bar chamber spout gear mechanism, repair to motor charge spring mechanism,tightening of all nut & bolts of entire trolley component all as directed , inserting the trolley, testing the complete HT electric supply and putting on supply on load complete all as directed. Note:- All cleaning /testing equipment/ safety equipment material shall be provided by the contractor and rate are deemed to be included in quoted rate.
Calibration of relay/load setting/balancing of load of 11KV HT VCBs and 1.1KV ACBs installed at various sub stn at KWC area complete all as specified and directed. Note:- 1. All testing & calibration equipment Certificate issued by OEM shall be submitted as per IE Rules with all accessories shall be brought by the contractor and rate for same is deemed to be included in quoted rates. 2. The complete test report shall be submitted by the contractor to GE (I) R&D Delhi.
S&F in repair HRC fuse link clip type on fuse link 2 to 20 amp operating voltage 415 V complete all as specified and directed
S&F in repair fuse base suitable for cylindrical /DIN type HRC fuse of capacity 2-32 amps complete all as specified and directed.
S&F in repair of closing spring assembly complete all as specified and directed.
S&F in repair of tripping spring assembly complete all as specified and directed.
S&F in repair of charging motor cut off limit switch complete all as specified and directed.
S&F in repair of spring charging handle motorized mechanism of VCB complete all as specified and directed. .
S&F in repair of push button bracket assembly complete all as specified and directed.
S&F in repair of bus bar support insulator 75 mm dia including all fixing accessories complete suitable for VCB/HT Bus bar chamber all as specified and directed.
S&F in repair of bus bar barrier as existing (set of three) with nuts bolts complete all as specified and directed.
S&F in repair of toggle switch for space heater complete with all accessories all as specified and directed.
S&F in repair of Charged/Discharged indication assembly complete all as specified and directed.
S&F in repair control wiring matching with existing size/type including proper laying with the help of locking device as per manufacturer instruction complete all as specified & directed.
Taking down repairable potential transformer of HT VCB 11 KV/ 110 V of any make, opening & dismentling the complete unit and refitting after carry out the following work :- (a) Rewinding of transformer as per existing gauge and pattern. (b) Cleaning and servicing of the PT (c) Replacement of wornout nuts/bolts and other minor parts including HRC Fuse. (d) Soldering / tightening of loose connections. (e) Replacement of potential transformer oil having dielectric strength upto 60 KV. (f) Painting of outer portion of PT with synthetic enameled paint of grey colour of approved make. (g) Testing of the PT's for proper functioning to the entire satisfaction of the engineer in charge.
S&F in repair of unserviceable/not repairable potential transformer of HT VCB 11 KV/110 V of any make complete all as specified and as directed
S&F in repair of 11 pin anti pumping relay 110V DC complete all as specified and directed.
S&F in repair of bottom terminal with jaw contact complete all as specified and directed.
S&F in repair of Top terminal with jaw contact complete all as specified and directed.
S&F in repair of space heater 230V AC 80W complete with all accessories all as specified and directed.
S&F in repair of thermostate complete with all accessories all as specified and directed.
S&F in repair of PT epoxy female bushing suitable for R-Y-B phase complete all as specified and directed.
S&F in repair of PT epoxy male bushing suitable for R-Y-B phase complete all as specified and directed.
S&F in repair of PT fuse 11 KV complete all as specified and directed.
Dehydration and filtration of transformer oil with proper dehydration machine to achieve dielectric strength between 45 to 60 KV including testing/recording of dielectric strength result before and after of dehydration necessary testing report prescribed format shall be submitted to Engr-in-Charge complete all as specified and as directed.
Supply and topping up transformer oil having dielectric strength not less than 45 KV complete all as specified and directed.
Taking shut down from main substation and drain out the transformer oil and to be collected in barrel by opening the transformer cover of capacity 200 to 450 KVA by unscrewing the nuts/bolts and washers and kept in safe custody and reuse the same, and checking the any type of leakage from both HT and LT side including cleaning the sludge etc depositing in the core and tank by using soft brushes and clean with old transformer oil, refilling of transformer oil including refixing of top cover including nut/bolts etc and testing the input & output voltage and adjustment of the voltage through tape changer if required complete to the entire satisfaction of Engineer- in-Charge. Note: Transformer oil required for topup will be measured and paid separately.
All as per ser item No. 47.00 above but of capacity 500 to 1000 KVA.
Taking shut down from main substation and M&L for painting with spray gun with two coats of synthetic enamel grey paint including preparation of old painted surfaces/removing old faded/rust/ cemented material of surface of transformer including base frame, connected LT panels, duct covers including writing MES/SM No of existing size/surface complete all as directed.
S&F in repair HT bushing 11KV suitable for 200 to 650 KVA Transformer including brass rod and complete with gasket as per matching to existing all as specified and as directed.
S&F in repair LT bushing 11 KV suitable for 200 KVA to 650 KVA transformer including brass rod and complete with gasket as per matching to existing all as specified and as directed.
S&F in repair of head gasket sheet 6mm thick suitable for Transformer 200KVA to 450 KVA capacity including replacement of nuts, bolts, washers complete including necessary T&P required at site all as specified and as directed.
S&F in repair of head gasket sheet 6mm thick suitable for Transformer 500KVA to 650 KVA capacity including replacement of nuts, bolts, washers complete including necessary T&P required at site all as specified and as directed.
S&F in repair of Dehydrating breather assembly complete with silica gel grains in the breather assembly suitable for transformers 200 KVA to 1000KVA complete as per matching to existing all as specified and as directed
S&F in repair of temperature gauge analog type complete with all accessories as per matching to existing all as specified and as directed
S&F in repair voltmeter digital type for voltage range of (0-500V) including all accessories and wiring complete all as specified and as directed.
S&F in repair ammeter digital type for current range of (0-1000Amps) as per matching to existing including all accessories and wiring complete all as specified and as directed.
S&F in repair power factor meter digital type for frequency range (45-65 Hz) as per matching to existing one including all accessories and wiring complete all as specified and as directed.
S&F in repair three phase over current earth fault relay MC-61 as per matching to existing one including all accessories and wiring complete all as specified and as directed.
S&F in repair three phase overcurrent earth fault relay MC-61A as per matching to existing one including all accessories and wiring complete all as specified and as directed.
S&F in repair three phase digital KV meter range up to 15 KV as per matching to existing one including all accessories and wiring complete all as specified and as directed.
S&F in repair of A/M Switch . Cat No.61025 of Make: L&T or equivelant make as approved by GE (I)
S&F in repair of LED type Indicating lamp type of voltage AC/DC set of RYB, as per matching to existing.
S&F in repair Battery Charger of capacity 12 volt for amf panel complete all as specified and directed.
S&F in repair Battery Charger of capacity 24 volt for amf panel complete all as specified and directed.
S&F in repair of battery charger 12 volt suitable for charging batterry 12 Volt 180AH complete
S&F in repair of battery charger 24 volt suitable for charging batterry 02 Nos of 12 Volt 180AH complete
S&F in repair of Current Transformer as per matching to exisitng complete all as specified and as directed
S&F in repair of Multifunctional meter complete all as specified and as directed
S&F in repair of VCB Power Pack unit 24 Volt DC 7 AH two Nos with battery bank for backup including panel as per matching to exisitng complete all as specified and as directed
Excavation in trenches in soft/loose soil not exceeding 1.5m depth not exceeding 1.5m in width over energised LT cables for carrying out brick work for preparation of cable duct including for taking out and relaying of LT Cables Complete all as specified & directed
Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25cm thick as in soft/loose soil complete all as specified and as directed.
Removing excavated soil to a distance not exceeding 50 mtr and depositing where directed at a level and not exceeding 1.5 mtr above the starting point complete all as specified and as directed.
Supply & laying dry fine sand for cushioning of underground cable laid in trenches/duct complete all as specified and as directed
Excavation in tranches in hard/dense soil not exceeding 1.5m depth not exceeding 1.5m in width over energised LT cables for carrying out brick work for preparation of cable duct including for taking out and relaying of LT Cables complete all as specified & directed
S&F ACP retro sign board of size 2.2 x 1.2 Mtr using retro reflective high intensity prismatic reflective sheeting. The back ground of board is Blue Colour with white border and writing letter, numbers white colour mentioning the HT Sub Station Details, and Single line Schematic diagram. Retro sign board shall be pasted on 3 mm thick ACP sheet. The board shall be fixed on 50mm dia stainless steel grade 304 of clear height 2M from ground level and 1.00M below ground level including PCC 1:3:6 type C2 of size 0.45 x 0.45 x 1.00M, including fixing clamps, nuts, bolts, washer etc complete all as directed
S&F ACP retro sign board of size 1.5 x 1.1 Mtr using retro reflective high intensity prismatic reflective sheeting. The back ground of board is Blue Colour with white border and writing letter, numbers white colour mentioning the HT/LT subtation Details, and Single line Schematic diagram. Retro sign board shall be pasted on 3 mm thick ACP sheet. The board shall be fixed on 50mm dia stainless steel grade 304 of clear height 2M from ground level and 1.00M below ground level including PCC 1:3:6 type C2 of size 0.45 x 0.45 x 1.00M, including fixing of clamps, nuts, bolts, washer etc complete all as directed
Taking down AMF panel Indoor type of capacity 50 KVAR to 500 KVAR and PCC not less than 0.6mx0.6mx0.6m and coping upto the hight of 0.30m above ground level including disconnecting of all incomming and outgoing electric connection and shifting & fixing in another location complete including incoming and outgoing connection and including necesary earth work PCC & brick work complete all as specified & directed.
M&L for overhauling of compressor of central AC plant of capacity 40 TR of make blue star model JS 43/44 including rewinding of compressor motor, grinding of crank shaft,connecting rod , greasing ,polishing, replacement of any unserviceable spares like connecting rod, piston,liner,piston rings, suction/discharge head, suction/discharge spring, main bush, oil pump assembly, oil filter, gasket, studs,nuts,bolts,thrust washer, oil pump, main bearing and repair of inner guide,wall plate, crank shaft & testing complete all as specified and directed.
M&L for overhauling of compressor of central AC plant of capacity 100 TR of make blue star including rewinding of compressor motor, grinding of crank shaft,connecting rod , greasing ,polishing, replacement of any unserviceable spares like connecting rod, piston,liner,piston rings, suction/discharge head, suction/discharge spring, main bush, oil pump assembly, oil filter, gasket, studs, nuts, bolts, thrust washer, oil pump, main bearing and repair of inner guide, wall plate, crank shaft & testing complete all as specified and directed.
M&L disconnecting, dismantling and strip opening of the existing air handling unit of any description and in any position and of capacity of 40TR/75/100TR for overhauling and servicing, including taking out existing shaft, blower drum, pulley and de-humidifier pump etc of air handling unit, checking thoroughly serviceability of the parts, fixing the serviceable parts in position, replacement of the PCB, electric circut copper conductor, reassembling, commissioning, fixing in position and testing of the air handling unit on full load for its smooth and trouble free operation complete all as specified and directed.
M&L for repairing of cooling tower of central AC plant of capacity 160 TR including replacement of 7.5 HP Motor, FRP side pannels, PVC fills and Jali and jointing , cleaning of cooling tower studs, nuts, bolts and repair of leakage etc if any & testing complete all as per specified and as directed.
All as per ser item No. 83.00 above but 40 TR.
S&F in repair of Aluminium fan with six Nos of blades suitable for 160 TR cooling tower all as specified and as directed.
S&F in repair of Aluminium fan blades with six Nos of blades suitable for 40 TR cooling tower all as specified and as directed.
M&L for repairing of chiller tower of central AC plant of capacity 100 TR of make blue star including PVC fins and cleaning of chiller tower studs, nuts, bolts and repair of leakage etc if any & testing complete all as per specified and as directed.
M&L for overhauling of pump and rewinding of electric mortor with super enameled copper winding wire of existing gauge of capacity 5 to 7.5 HP capacity by opening up and cleaning of all parts such as impeller, rotor, starter, fan cover, greasing and reconnecting back and testing complete all as per specified and as directed.
All as per ser item No. 88.00 above but capacity 10 HP.
All as per ser item No. 88.00 above but capacity 15 to 20 HP.
M&L for descalling and cleaning of 40 TR condenser water cooled by circulating the diluted chemical HCL by forced feed method not less than 6hrs duration by opening of the end covers of the condenser brushing the tubes thoroughly,re-fixing back the end cover of the condesers with 3mm thick rubber gasket and testing complete to maintaining desired discharged pressures for water cooled condenser complete all as specified and as directed.
All as per ser item No. 91.00 above but capacity 75TR.
All as per ser item No. 91.00 above but capacity 100TR Air cooled.
M&L for charging of Refrigerant-134A complete including testing after completion.
M&L for charging of Refrigerant R-22 complete including testing after completion.
M&L for charging of Refrigerant R-410A complete including testing after completion.
Supply & filling in repair of compressor oil (Refrigeration lubricant) including testing for complete all as specified and as directed.
M&L for Finding out leakage in the system, leakage repair including brazing, Nitrogen Testing by holding the pressure for minimum 24 hours and recommissioning of 40 TR water cooled
All as per ser item No. 98.00 above but 75/100 TR.
All as per ser item No. 98.00 above but 22 TR.
All as per ser item No. 98.00 above but 5 TR.
S&F in repair of microprocessor Step Controller including PCB and switch Mode Power Supply System for Hot Water Generator 120 KW suitable for 100 TR AC Plant Model RC120 Make Rapid Cool complete all as specified and directed.
M&L for servicing of air handling units including Blower cleaning, balancing of blower motor pully complete all as specified and directed.
M&L for rewinding of AHU motor 2 HP capacity with super enamelled copper winding wire of existing gauge including tranportation to workshop & back, testing after repair complete all as specified and directed.
S&F in repair of 3 pole contactors 40Amps complete all as specified and directed.
S&F in repair all the accessories including Butterfly Valve 40mm dia including the application of nitrile i.e nuts, bolts, gasket, rubber insulatioin over the valves complete
All as per ser item No. 106.00 above but 100 mm dia.
S&F in repair V belt of size A30 complete all as specified and directed.
S&F in repair V belt of size A42 complete all as specified and directed.
S&F in repair V belt of size A43 complete all as specified and directed.
S&F in repair V belt of size A46 complete all as specified and directed.
S&F in repair V belt of size A48 complete all as specified and directed.
S&F in repair V belt of size A49 complete all as specified and directed.
S&F in repair V belt of size A60 complete all as specified and directed.
S&F in repair V belt of size A65 complete all as specified and directed.
S&F in repair V belt of size A85 complete all as specified and directed.
S&F in repair water pressure gauge along with stop cock and fixing arrangement suitable for water pressure 0-16/20 kg/sq cm complete all as soecified and as directed.
S&F in repair industrial type thermometer of range 0-50 degree centigrade for AC plant complete all as specified and as directed.
S&F in repair suction pressure gauge suitable for suction pressure 0-250 PSI complete all as specified and as directed.
S&F in repair discharge pressure gauge suitable for discharge pressure 0-500 PSI complete all as specified and as directed.
S&F in repair timer electronic type complete all as specified and as directed.
S&F in repair power contractor of MNX-70 complete all as specified and as directed.
S&F in repair power contractor of MNX-25 complete all as specified and as directed.
S&F in repair 3 phase preventer/phase sequence for line complete all as specified and as directed.
S&F in repair of LP switch suitable for central/package type AC plant 40TR/75TR/100TR suitable for as per site requiremet complete all as specified and as directed.
S&F in repair of HP switch suitable for central/package type AC plant 40TR/75TR/100TR suitable for as per site requirement complete all as specified and as directed.
S&F in repair of refrigerant copper pipe 15mm dia, 0.64 mm wall thickness complete all as specified and as directed.
S&F in repair of refrigerant copper pipe 12 mm dia, 0.64 mm wall thickness complete all as specified and as directed.
S&F in repair of refrigerant copper pipe 5/8" (15.88mm) dia thick including foam insulation for copper tube wall complete all as specified and as directed.
S&F in repair of refrigerant copper pipe 3/8" (9.52mm) dia thick including foam insulation for copper tube wall complete all as specified and as directed.
S&F in repair of main PCB suitable for VRF AC 22 TR (Model No. FDC615KXE6 of MITSUBISHI) outdoor complete all as specified and directed.
S&F in repair of inverter PCB suitable for VRF AC 22 TR outdoor (model No. FDC615KXE6 of MITSUBISHI) complete all as specified and directed.
S&F in repair power transitor suitble for VRF AC 22 TR (model No. FDC615KXE6 of MITSUBISHI) complete all as specified and directed.
S&F in repair Compressor hermatically Sealed suitable for VRF AC 22 TR (model No. FDC615KXE6 of MITSUBISHI) complete all as specified and directed.
S&F in repair of PCB suitable for Package type AC plant 5 TR of make Haier complete all as specified and directed.
S&F in repair compressor hermatically Sealed suitable for Package type AC plant 5 TR complete all as specified and directed.
S&F in repair MCCB 125Amps 4 Pole breaking capacity 25KA complete all as specified and as directed.
All as per ser item No. 137.00 above but 100 Amp.
S&F in repair, installation of Microprocessor Magnum Controller alongwith Software, installation and controlling arrangement including thimbles control wire etc complete suitable for 40TR AC Plant of Make Blue Star complete all as specified and directed.
S&F in repair filter of AHU capacity 16000 CMH to 50000CMH complete, all as specified and as directed.
S&F in repair including installation, testing and commissioning of auto air vent valve of 15 mm dia complete all as specified and directed.
S&F in repair MCCB 400 Amps 4 Pole breaking capacity 50KA complete all as specified and as directed.
S&F in repair MCCB 630 Amps 4 Pole breaking capacity 50KA complete all as specified and as directed.
M&L for Soft Chemical servicing of 22 TR VRF AC Plant indoor Units including minor parts complete all as specified and as directed.
M&L for Soft Chemical servicing of 22 TR VRF AC Plant Outdoor Units including minor parts complete all as specified and as directed.
S&F in repair Indoor unit PCB suitable for 22 TR AC Plant complete all as specified and as directed.
S&F in repair diode stack suitable for 22 TR AC Plant complete all as specified and as directed.
S&F in repair communication wire 6 core 2.5 sqmm complete all as specified and as directed.
S&F in repair Interconnecting refrigerant Copper pipe of size 15.9mm with closed cell elastometic nitrile rubber tubular insulation between each set of indoor & outdoor units complete all as specified and as directed.
S&F in repair Interconnecting refrigerant Copper pipe of size 12.7mm with closed cell elastometic nitrile rubber tubular insulation between each set of indoor & outdoor units complete all as specified and as directed.
S&F in repair Interconnecting refrigerant Copper pipe of size 9.5mm with closed cell elastometic nitrile rubber tubular insulation between each set of indoor & outdoor units complete all as specified and as directed.
S&F in repair Interconnecting refrigerant Copper pipe of size 6.4mm with closed cell elastometic nitrile rubber tubular insulation between each set of indoor & outdoor units complete all as specified and as directed.
S&F in repair PVC Drain pipe insulated with 6mm thick nitrile rubber insulation complete all as specified and as directed.
S&F in repair of GI/CI/MS piping work 100/150mm dia inlet/outlet including plumbing work and Welding work as per existing complete all as specified and as directed.
S&F in repair of reactor suitable for VRF AC 22 TR outdoor (Model No. FDC615KXE6 of MITSUBISHI) complete all as specified and directed.
S&F in repair of filter PCB suitable for VRF AC 22 TR outdoor (Model No. FDC615KXE6 of MITSUBISHI) complete all as specified and directed.
SNOWY ENGINEERING INC
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .