Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAccepted-AOC D NO 10 36 3 2 FLAT NO N 1 DASARATHA ENCLAVE RAM NAGAR VISAKHAPATNAM 530 002 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530002 | ₹1.2 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹1.3 Cr+₹11.0 L (8.93%)Rejected-Finance DOOR NO 43 2 BESIDES VIZAG DEFENCE ACADEMY 104 AREA KAPPARADA VISAKHAPATNAM 530013 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530013 | ₹1.3 Cr+₹11.0 L (8.93%) | L2 | Rejected-Finance Not Being L1 |
| 3 | L3₹1.3 Cr+₹11.7 L (9.50%)Rejected-Finance | ₹1.3 Cr+₹11.7 L (9.50%) | L3 | Rejected-Finance Not Being L1 |
| 4 | L4₹1.5 Cr+₹27.0 L (21.9%)Rejected-Finance | ₹1.5 Cr+₹27.0 L (21.9%) | L4 | Rejected-Finance Not Being L1 |
| 5 | L5₹1.6 Cr+₹32.8 L (26.6%)Rejected-Finance FLAT NO 304 SN TOWERS JAGANNADHAPURAM JUNCTION AKKAYYAPALEM VISAKHAPATNAM 530 016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | ₹1.6 Cr+₹32.8 L (26.6%) | L5 | Rejected-Finance Not Being L1 |
Tender Value
Refer Docs
EMD Value
₹2.2 L
Closing Date
18 Aug 2021, 6:00 pmClosed
GE I DM
GE I DM NAVAL DOCKYARD VISAKHAPATNAM 530014
SPECIAL REPAIR/ REPLACEMENT OF UNSERVICEABLE DAMAGED HT 11 KV UG CABLE FROM MRS TO DS-07 HT VCBs OF VARIOUS CAPACITIES AT E/M INSTALLATIONS OF JETTY AREA AND EXTERNAL ELECTRICAL SUB STATION AT ND (V) UNDER GE (I) DM VISAKHAPATNAM
2021_MES_461549_1
SSGE/8570/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NAVAL DOCKYARD VISAKHAPATNAM
As per tender documents
8 documents required · 8 mandatory
₹1,000
GE I DM
₹2.2 L
Yes
5 Oct 2021
20 Jul 2021
20 Aug 2021
20 Jul 2021
18 Aug 2021
11 Aug 2021
Amount
Supply, install, testing and commissioning of HT 11KV, 3ph, 50Hz, indoor type, totally enclosed metal clad switch gear, floor mounted, complete with Vacuum circuit breaker having rupturing capacity minimum 250MVA, Insulation Level-12KV/28KV/75KVP, SC rating- 31.5 KA for 1 sec, IEC Ref-62271-200 or latest updated, overload and earth fault protection, ampmeter, voltmeter and of current ratting not less than 400 amps including necessary connection with existing cables including following detail specifications : (a) The set of panel shall consist of two (02) incomer, one bus copler with bus riser and ten (10) outgoing feeder = Total 13 VCB (b) Digital numerical relays for earth fault, over current protection, Model- Micom P-127 for normal load and Micom P-225 for motor load or equivelent model of ABB/Siemens (c) High speed trip relays (d) Trip anunciator (e) Closing Coil, Trip coils of 110V, DC (f) VCB will be vertical break and horizontal draw out type
g) Spring charging motor of 230V, AC (h) VCB panel shall be suitable for local/remote control (j) The panel shall be provided with standard LED indicators as specified by OEM. (k) Incoming two panel only shall have 3ph incoming LED indicator, Trip annunciator, Hooter, PT. (l) CT/PT will be cast rasin dry type (m) CT racio- for 02 Nos incoming feeder - 600/300/5-5A, for 06 Nos outgoing feeder - 200/100/5-5A and for 04 Nos outgoing feeder - 100/50/5-5A and SC current rating min 31.5 KA for use of metering and protection, minimum 15 VA barden (n) Auxiliary relay for transformer protection having Buch alarm, Oil Temp alarm & Wdg Temp alarm for transformer feeder only (o) Relay setting after commissioning of VCB according to load/fault condition with secondary injection
Supply, install, testing and commissioning of HT 11KV, 3ph, 50Hz, indoor type, totally enclosed metal clad switch gear, floor mounted, complete with Vacuum circuit breaker having rupturing capacity minimum 250MVA, Insulation Level-12KV/28KV/75KVP, SC rating- 31.5 KA for 1 sec, IEC Ref-62271-200 or latest updated, overload and earth fault protection, ampmeter, voltmeter and of current ratting not less than 400 amps including necessary connection with existing cables including following detail specifications: (a) The set of panel shall consist of two (02) incomer, one bus copler with bus riser and two (02) out going feeder = Total 5 VCB (b) Digital numerical relays for earth fault, over current protection, Model- Micom P-127 for normal load and Micom P-225 for motor load or equivalent model of ABB/Siemens (c) High speed trip relays (d) Trip anunciator (e) Closing Coil, Trip coils of 110V, DC
(f) VCB will be vertical break and horizontal draw out type (g) Spring charging motor of 230V, AC (h) VCB panel shall be suitable for local/remote control (j) The panel will be provided with standard LED indicators as specified by OEM. (k) Incoming two panel only shall have 3ph incoming LED indicator, Trip annunciator, Hooter, PT. (l) CT/PT shall be cast rasin dry type (m) CT racio- for 02 Nos incoming feeder - 600/300/5-5A, for 06 Nos out going feeder - 200/100/5-5A and for 04 Nos outgoing feeder - 100/50/5-5A and SC current rating min 31.5 KA for use of metering and protection, minimum 15 VA barden (n) Auxiliary relay for transformer protection having Buch alarm, Oil Temp alarm & Wdg Temp alarm for transformer feeder only (o) Relay setting after commissioning of VCB according to load/fault condition with secondary injection (p) Lay out VCB is attached in detail tender
Excavating in trenches n. exc. 1.5 m. wide and n. exc. 1.5 m. in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pire holes, etc. n. exc. 10 sqm on plan and not exc. 1.5 m. in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling including spreading levelling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil complete all as specified and as directed.
Removing excavated soil not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point in soil complete all as specified and as directed.
M&L for sand cushioning for protection of cables (below, above and around the cable laid in trenches) complete using clean, dry sand complete all as specified and as directed.
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm complete all as specified and as directed.
M&L PCC 1:3:6 type C2 type (using 40 mm graded broken stone aggregate) as in foundation filling and mass concrete etc complete all as specified and directed.
Supply, laying and connecting up in trenches or in duct or passing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, overall PVC sheathed electric power cables (heavy duty) with aluminium conductor, 11000 volts grade (Earthed) cross sectional area 240 sq. mm 3 core including dismantling / taking down unserviceable one complete all as specified and as directed.
Supply and ifx cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type joint complete with jiointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 240 Sqmm complete all as specified and as directed.
Supply and fix Cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm complete all as specified and as directed.
Supply and lay new GI pipe of size 100 mm bore light grade for cable protection in road crossing complete all as specified and as directed.
M&L for Boring of holes under road, pavement, hard standing by trenchess technology using ultra sounding technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
M/L for cable route indicator, marked as HT 11 KV cable, made with RCC post of size 100mmx100mmx1000 mm long, burried above cable trench upto 500mm depth during refilling work and fixed at interval of 100 mtr
Mavee Syndicate
M/S N.K BUILDERS
Power engineering Associates
MURALI KRISHNA ASSOCIATES
KIRON ENGINEERING CORPORATION
K KUMAR RAJA PROJECTS P LIMITED
UNIVERSAL ENTERPRISES
S.S.TRADERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .