Loading…
Loading…
| # | Company | Offered Item | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹3.0 CrQualified Make: SAFETY FIRST
Model: SFPFP275LPM C 210 BHAICHAND TEXTILE MILL LBS MARG BHANDUP WEST MUMBAI MAHARASHTRA 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | Make: SAFETY FIRST
Model: SFPFP275LPM | ₹3.0 Cr | L1 | Qualified MSE |
| 2 | L2₹3.0 Cr+₹2.0 L (0.69%)Qualified Make: Integral
Model: Integral 1ST FLOOR SANJAY BLDG NO 7 MITTAL INDL ESTATE ANDHERIKURLA RD ANDHERI E MUMBAI MAHARASHTRA 400059 | MUMBAI SUBURBAN | MAHARASHTRA | 400059 | Make: Integral
Model: Integral | ₹3.0 Cr+₹2.0 L (0.69%) | L2 | Qualified MSE |
| 3 | Disqualified Make: SAFETY FIRE
Model: PFPSF275LP PLOT NO 32 KAMALA NIWAS D LANE SECTOR 8 VASHI NAVI MUMBAI THANE MAHARASHTRA 400703 | THANE | MAHARASHTRA | 400703 | Make: SAFETY FIRE
Model: PFPSF275LP | - | - | Disqualified MSE, Category: General |
Tender Value
Refer Docs
EMD Value
Exempted
Closing Date
25 Sept 2018, 10:00 amClosed
Average Turn Over of Last 3 Years 1199 Lakh (s) Experience with Gov. Required 5 Year (s) Portable Pump Set For Fire Fighting ( 100 ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Allowed Values GENRIC Conformity to Indian Standard for portable pump set for fire fighting IS 942/1982 reaffirmed 2015 * General Requirements The unit shall consist of the pump having an output of not less than 275 LPM at a pressure of 4 kgf/cm²
fitted on a tubular steel frame and with anti-vibration coils/pads. The complete unit shall be of lightweight construction
so that it can be easily carried by two men. * Minimum discharge output 275 LPM at a pressure of 4 kgf/cm ² * 1/5 CONSTRUCTIONAL Material for Pump comprising volute
body ( casing ) impeller and one delivery outlet light aluminium alloy conforming to IS : 617-1975(Latest) * Pump Type Single stage centrifugal type
directly mounted on the extension of the crankshaft of the engine and complete as per clause 4.1.2 of IS:942 * Tubular Frame Material Mild Steel Tubes used for the fabrication of tubular frame shall conform to IS : 3601- 1966 (latest) * Delivery valve Type Screw down type and fitted with 63 mm female instantaneous coupling and blank cap. conforming to IS : 4928-1968( latest) * Spindle of the Delivery Valve made of stainless steel conforming to 07CR l8Ni 9 Grade of IS : 6603- (latest) * Engine Fuel Type Diesel * Engine Type Single cylinder
four stroke
air cooled engine as per clause 4.1 of IS:942 * Starting Mechanism Battery operated self start as well as Recoil Type starting * Fuel Gauge for Engine Tank YES * Cradle Fitments Fitted with 4 folding handles of spring loaded type. The handles shall be capable of being used for tying the ropes for slingling the pump down in the well. * Frame work Cradle design made of tubular steel and provided with anti- vibration coils/pads. * Cradle colour Painted in Fire Red
Shade No. 536 of IS : 5-1978 . The paint shall conform to IS * 2/5 :2932-1974 Suction Hose Diameter 75 * Suction Hose conforming to IS : 2410-1963 fitted with 75 mm suction hose coupling conforming to IS : 902-19747 Four Nos lengths of 2.5 meter each * Marked with photo luminescent tape for visibility in darkness YES * A tool kit comprising all essential tools required for normal maintenance
shall be provided with each pump along with a fully illustrated booklet and item wise spare parts list YES * Maximum Weight of complete unit 120 * PERFORMANCE Water Discharge Performance The pump shall be tested with suction stainer fitted continuously for 4 hours with a lift of 3 m for output 275 LPM at 4.0 kg/cm²
365 LPM at 3.5 kg/cm² and 545 LPM at 2.5 kg/cm² * Lift performance conditions 30 cm every 300 m elevation above mean sea level and One percent for every 2.5⁰C rise in water temperature * Horse Power of Engine(HP)(on the basis of minimum discharge
maximum delivery Head
efficiency of pump and coupling (HP) 15 * Fuel Tank Capacity for continuous run of minimum two hour 10 * Primer The primer shall be capable of lifting water at least through 7 m in not more than 45 * 3/5 seconds and shall be preferably fully automatic. CERTIFICATION Engine shall meet applicable environmental protection norms and emission standards YES * Availability of Type Test Report to prove conformity of parameters to the specification from any ILAC/NABL accredited/Central Govt Lab NEW BHARAT FIRE * Test certificate Number - * Test Report Date - * Name of the Lab where test Conducted - * Product Warranty ( in years) 10 * Availability of service and spares parts through supplier/OEM from date of installation (in years) 10 * * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Madhusudan Reddy 788001
OC OMC NO 2 MGAR DISTT CACHAR SILCHAR 20 90 2 Ajay Rawat 785005
OC OMC
No-3 MGAR Near Civil Airport Jorhat-785005 40 90 3 Deepak V Sharma 797112
OMC No-1 MGAR Walford Area Rajbari Complex Near Circuit House Dimapur Nagaland-797112 20 90 4 Vishal Chopra 795015
OC OMC NO 4 MGAR
MARAM 20 90 4/5
594728
GEM/2018/B/84455
Portable Pump Set for Fire Fighting
90 days
Assam; Cachar, Assam; Dimapur, Nagaland; Senapati
PRODUCT
| Item | Delivery Location | Qty | Delivery |
|---|---|---|---|
| Average Turn Over of Last 3 Years 1199 Lakh (s) Experience with Gov. Required 5 Year (s) Portable Pump Set For Fire Fighting ( 100 ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Allowed Values GENRIC Conformity to Indian Standard for portable pump set for fire fighting IS 942/1982 reaffirmed 2015 * General Requirements The unit shall consist of the pump having an output of not less than 275 LPM at a pressure of 4 kgf/cm² | - | - | - |
| fitted on a tubular steel frame and with anti-vibration coils/pads. The complete unit shall be of lightweight construction | - | - | - |
| so that it can be easily carried by two men. * Minimum discharge output 275 LPM at a pressure of 4 kgf/cm ² * 1/5 CONSTRUCTIONAL Material for Pump comprising volute | - | - | - |
| body ( casing ) impeller and one delivery outlet light aluminium alloy conforming to IS : 617-1975(Latest) * Pump Type Single stage centrifugal type | - | - | - |
| directly mounted on the extension of the crankshaft of the engine and complete as per clause 4.1.2 of IS:942 * Tubular Frame Material Mild Steel Tubes used for the fabrication of tubular frame shall conform to IS : 3601- 1966 (latest) * Delivery valve Type Screw down type and fitted with 63 mm female instantaneous coupling and blank cap. conforming to IS : 4928-1968( latest) * Spindle of the Delivery Valve made of stainless steel conforming to 07CR l8Ni 9 Grade of IS : 6603- (latest) * Engine Fuel Type Diesel * Engine Type Single cylinder | - | - | - |
| four stroke | - | - | - |
| air cooled engine as per clause 4.1 of IS:942 * Starting Mechanism Battery operated self start as well as Recoil Type starting * Fuel Gauge for Engine Tank YES * Cradle Fitments Fitted with 4 folding handles of spring loaded type. The handles shall be capable of being used for tying the ropes for slingling the pump down in the well. * Frame work Cradle design made of tubular steel and provided with anti- vibration coils/pads. * Cradle colour Painted in Fire Red | - | - | - |
| Shade No. 536 of IS : 5-1978 . The paint shall conform to IS * 2/5 :2932-1974 Suction Hose Diameter 75 * Suction Hose conforming to IS : 2410-1963 fitted with 75 mm suction hose coupling conforming to IS : 902-19747 Four Nos lengths of 2.5 meter each * Marked with photo luminescent tape for visibility in darkness YES * A tool kit comprising all essential tools required for normal maintenance | - | - | - |
| shall be provided with each pump along with a fully illustrated booklet and item wise spare parts list YES * Maximum Weight of complete unit 120 * PERFORMANCE Water Discharge Performance The pump shall be tested with suction stainer fitted continuously for 4 hours with a lift of 3 m for output 275 LPM at 4.0 kg/cm² | - | - | - |
| 365 LPM at 3.5 kg/cm² and 545 LPM at 2.5 kg/cm² * Lift performance conditions 30 cm every 300 m elevation above mean sea level and One percent for every 2.5⁰C rise in water temperature * Horse Power of Engine(HP)(on the basis of minimum discharge | - | - | - |
| maximum delivery Head | - | - | - |
| efficiency of pump and coupling (HP) 15 * Fuel Tank Capacity for continuous run of minimum two hour 10 * Primer The primer shall be capable of lifting water at least through 7 m in not more than 45 * 3/5 seconds and shall be preferably fully automatic. CERTIFICATION Engine shall meet applicable environmental protection norms and emission standards YES * Availability of Type Test Report to prove conformity of parameters to the specification from any ILAC/NABL accredited/Central Govt Lab NEW BHARAT FIRE * Test certificate Number - * Test Report Date - * Name of the Lab where test Conducted - * Product Warranty ( in years) 10 * Availability of service and spares parts through supplier/OEM from date of installation (in years) 10 * * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Madhusudan Reddy 788001 | - | - | - |
| OC OMC NO 2 MGAR DISTT CACHAR SILCHAR 20 90 2 Ajay Rawat 785005 | - | - | - |
| OC OMC | - | - | - |
| No-3 MGAR Near Civil Airport Jorhat-785005 40 90 3 Deepak V Sharma 797112 | - | - | - |
| OMC No-1 MGAR Walford Area Rajbari Complex Near Circuit House Dimapur Nagaland-797112 20 90 4 Vishal Chopra 795015 | - | - | - |
| OC OMC NO 4 MGAR | - | - | - |
| MARAM 20 90 4/5 | - | - | - |
Exempted
25 Sept 2018
25 Sept 2018
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
bid_594728.pdf
GEM_BID
termsCondition.pdf
OTHER
2657c7ca70287299b5181580fdb5a7ab.pdf
OTHER
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .