SO EnM Office Rajrappa Area
Maintenance of Overhead lines of feeders No.- 6(3.3KV) , 7 (6.6KV), 8(6.6KV), 22(6.66KV) and 24 (3.3KV) originating from 2x12.5 MVA, 33KV/ 6.6KV Main Substation to Mines and Workshop of Rajrappa Project
2022_CCL_246490_1
GM(R)/SO(EnM)/Rjp/22-23/Et/14 dt 14.06.2022
Open Tender
Electrical and Maintenance Works
Item Rate
30 days
Rajrappa Area
Please refer NIT
2 documents required · 2 mandatory
₹3,400
2 Sept 2022
14 Jun 2022
27 Jun 2022
15 Jun 2022
25 Jun 2022
15 Jun 2022
15 Jun 2022 - 19 Jun 2022
Amount
Erection of metallic pole of length Above 10.00 metre and upto 12.00 metre in cement concrete 1:3:6 (1 cement :3 coare sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc.as required.
Supplying and erection of stay set complete (galvanised) with 19/20mm dia* 1.8 metres long stay rod , anchor plate of size 45cm*45cm* 7.5 mm thimble, stay clamps, turn buckle (20mm* 60cm ), 7/ 3.15mm dia G.l stay wire and strain insulator etc in cement concrete 1:3:6 (1cement :3 coarse sand :6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc.as required.
Erection of pole top/ straight two wire /V shape two wire , angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required.
Erection of double pole 3 wire cross arm for 11KV/22KV/33KV over head lines as required.
Supply of Stay clamp (pole Clamp)
Supply of M.S. Nut bolts (5/8" X 7")
Supplying and erection of 11KV disc insulator for 11KV over headlines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps , bolts, nuts, washers etc as required. ( Only Disc insulator departmentally supplied).
Supplying and erection of 11KV pin insulator complete with large steel head G.l pin , nuts, washers etc. as required.
Erection / Tensioning of all aluminium conducter of 7/3.40 mm to 7/4.00 mm diameter and above including binding etc. as required (Route length for erection apporx. 300m).
Supply of 8 SWG G.l wire for Cradling and earth Continuity
Erection of G.l wire No. 8 SWG for erection of earth wire , including binding etc . As required.(15nos. Of spans).
Erection of Cradle Guard 3 Wire.(10 nos of spans).
Dismantling of pole / street light standard/ strut embedded in cement concrete foundation etc . As requied.
Dismantling of overhead lines comprising of copper/aluminium over head conductor, G.I. wire, cross arms, insualtors etc. as required(3 nos. of spans)
Cost for Bush cutting(Lumsum)
Cost for checking & repairing of jumpers.
Add Contractor's Profit
Total impact of GST for the purpose of CTC
Coalfield Construction
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_254644.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .