Loading…
Loading…
Tender ID
Tender Value
₹14.8 L
EMD Value
₹15,000
Closing Date
31 Jan 2026, 6:00 pmClosed
Executive Engineer, Irri. Mech. Dn. No.1, Vadodara
Providing & Erecting Indoor E.I. & Outdoor Lighting at Diesel Section under IMSD 2/1, Ukai.
265568
NIT-16 of 2025-26
Open
Electrical - All
Works
Vadodara
14 documents required · 13 mandatory · 1 optional
₹900
Yes
Executive Engineer, Irrigation Mechanical Division No.1, Vadodara
₹15,000
Yes
16 Jan 2026
16 Jan 2026
16 Jan 2026
31 Jan 2026
16 Jan 2026
BILL OF QUANTITIES
1. The bill of Quantities shall be read in conjunction with the Instructions to Bidder,
Conditions of Contract, Technical Specifications and Drawings.
2. The quantities given in the Bill of Quantities are estimated and provisional, and are
given to provide a common basis for bidding. The basis of payment will be the actual
quantities of work ordered and carried out, as measured by the Contractor and verified by
the Engineer and valued at the rates and prices tendered in the priced Bill of Quantities,
where applicable, and otherwise at such rates and prices as the Engineer may fix within
the terms of the Contract.
3. The rates and prices tendered in the priced Bill of Quantities shall, except in so far as
it is otherwise provided under the Contract, include all constructional plant, layout,
supervision, materials, erection, maintenance, insurance, profit, taxes and duties,
together with all general risks, liabilities and obligations set out or implied in the Contract.
4. The rates and prices shall be quoted entirely in Indian Currency.
5. A rate or prices shall be entered against each item in the Bill Quantities, whether
quantities are stated or not. The cost of Items against which Contractor has failed to enter
a rate or price shall be deemed to be covered by other rates and prices entered in the Bill
of Quantities (in case of Item rate contract).
6. The whole cost of complying with the provisions of the Contract shall be included in
the items provided in the priced Bill of Quantities, and where no Items are provided
the cost shall be deemed to be distributed among the rates and prices entered for the
related items of Work.
7. General direction and descriptions of work and materials are not necessarily
repeated or summarized in the Bill of Quantities. References to the relevant sections
of the contract documentation shall be made before entering rates or prices against
each item in the Bill of Quantities.
8. The method of completed work of payment shall be in accordance with the
specification for Road and Bridge works. For building works specifications for
building are to be followed.
9. Errors will be corrected by the Employer for any arithmetic errors pursuant to
Clause 29 of the Instructions to Bidder.
10. Rock is defined as all materials which, in the opinion of the Engineer, required
blasting, or the use of metal wedges and sledgehammers, or the use of
compressed air drilling for its removal, and which cannot be extracted by ripping with a
tractor of at least 150 kw with a single rear mounted heavy duty ripper.
BILL OF QUANTITIES
(A) Percentage Rate Tender (Up to INR 50 Cr. )
Name of Work: Providing & Erecting Indoor E.I. & Outdoor Lighting at Diesel Section under
IMSD 2/1, Ukai.
Item Quantities Item of Work Estimated Unit Total amount
Item Quantities Item of Work Estimated Unit Total amount
s estimated Rates(In according to
No. figures) estimated
1a 126 Providing & Erecting following Shockproof 31.31 No.
tissino type accessories erected on 3 mm thick PC
(Polycarbonate) sheet in PVC/ Metal Box. erected
on wall/ ceiling.
(a) One no Single pole 6 A Switch / Bell push
[Approved make - Anchor, GreatWhite, Havells,
1b 32 (b) One no 3/5 pin 6 A Socket [Approved make - 31.31 No.
Anchor, GreatWhite, Havells, Vinay, Fybros]
1c 16 (c) One no Single pole 16 A Switch & One no 94.94 No.
6/16 A Universal Socket combined [Approved
make - Anchor, GreatWhite, Havells, Vinay,
1d 53 (d) Bakelite ceiling rose [Approved make - 18.18 No.
Anchor, GreatWhite, Havells, Vinay, Fybros]
1e 45 (e) Bakelite lamp holder [Approved make - 22.22 No.
Anchor, GreatWhite, Havells, Vinay, Fybros]
1f 27 (f) Electronic Hum free EME Socket Type Steps 219.17 No.
Fan Regulator [Approved make - Anchor,
GreatWhite, Havells, Vinay, Fybros]
2 45 Bakelite adopter for Holder to be 9.09 No.
erected.[Approved make - Anchor, GreatWhite,
Havells, Vinay, Fybros]
3 4 Providing & erecting Switch board for Computer 332.29 No.
or electric apparatus consisting of following items
in single board erected on PVC / Metal/Wooden
board concealed/open with 3 mm thick PC
(Polycarbonate) / Acrylic sheet erected as
directed1 no. 6A/16A universal plug-switch
combined.3 nos. 6A Switch3 nos. 6A 5 pin Plug
[a] For Tissino Type Accessories [Approved make
- Anchor, GreatWhite, Havells, Vinay, Fybros]
4a 2500 Providing and erecting Mains with 1.1 KV grade 46.46 Mtr.
FRLS PVC insulated ISI marked stranded Copper
conductor wire in following type of pipe to be
erected concealed in /flushed on wall/ceiling, with
1.5 sq. mm copper conductor FRLS PVC insulated
stranded wire of green colour for earth continuity
of following size.(A) in existing pipe
(a) 2 wire 1.5 sq. mm [Approved make - Polycab,
Havells, RRKabel, Finolex, Anchor]
4b 600 (b) 2 wire 2.5 sq. mm [Approved make - Polycab, 62.62 Mtr.
Havells, RRKabel, Finolex, Anchor]
5a 700 Providing and erecting ISI mark Medium class 24.24 Mtr.
RIGID PVC PIPES of following size complete to
be erected on/in wall or ceiling erected with
necessary PVC fittings & Junction boxes fixed
with adhesive solution & Clamps with following
dia of pipes, in approved manner as directed
(a) 20 mm [Approved Make - Finolex, Dutron,
Swastik, Aashirwad, Suprime]
5b 200 (b) 25 mm [Approved Make - Finolex, Dutron, 33.33 Mtr.
Swastik, Aashirwad, Suprime]
6 100 Supplying & erecting UPVC Mini trunking (PVC 36.36 Mtr.
Casing-n-Capping) having double-locking
arrangement with grooves, trunking of size not
below 12.5 mm in height as per IS with accessories
of PVC/Resin polypropylene not below 1.8 mm
thick duly sealed in joint & erected on wall /
ceiling of following size .(a) 32 mm [Approved
Make - Polycab, Precision, Nihir, Anchor, Vraj]
7 45 Supplying and erecting LED indoor fittings with 373.70 No.
LEDs of wattage 0.2 Watt to 0.5 Watt assembled
on single MCPCB, with housing used as a heat
sink shall be made of thick sheet Steel conforming
to IS: 513/CRCA/ aluminium die cast powder
coated and high U.V. & corrosion resistance with
diffuser with company mark/name 160V to 270V,
Power Factor more than 0.9, THD < 15%,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt ,LED
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80
Certificates)(NOTE: Below description have
shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.) (A)
Tube Light with integral driver (a) 22-24 Watts,
Surge - 2KV,IP-20, conventional 4 feet [Approved
Make - Philips, Wirpo, Crompton, Surya, Havells,
8 27 Providing and erecting Approved make Ceiling fan 1596.81 No.
with double ball bearing ISI mark with condenser
A.C. 23OV.50 c/s.1200 mm. sweep complete,
canopy erected on existing hook or clamp with
earthing. [Make shall be approved by Engineer in
9 27 Supplying and erecting 19 / 20 mm. nominal bore 108.07 No.
Medium Class M.S. Pipe down rod erected duly
painted for fan complete with proper insulation
without leakage and earthing.
10 27 Providing Fan clamp of 30 x 5 mm flat of required 98.98 No.
length & 10 mm M.S. Bolt & Nuts erected with
necessary hook of 10 mm M.S. Round Bar.
11 2 Supplying and erecting approved make pedestal 2141.20 No.
fan A.C. 230V. 50 Cy/s. 400 mm sweep oscillating,
type and adjustable, height complete with guard
regulator, & standard lead flexible wires and plug
top.[Approved Make - Usha, Crompton, Almonard,
Orient, Havells]
12 2 Supplying & erecting single phase approved make 2054.34 No.
industrial exhaust fan suitable for medium duty
ring mounted low noise operation suitable for
medium duty having following dia size and
maximum speed in RPM [a] 305 mm dia 900 RPM
[Approved Make - Usha, Crompton, Almonard,
Orient, Havells]
13 48 providing and erecting Miniature circuit breaker 112.11 No.
single pole 6A to 25A suitable to operate on 240 V
A.C. system and having breaking capacity 10 KA
to be erected in existing box. confirming to IS
8828/1996 with ISI Mark [Approved Make -
Schneider, L&T, ABB, Siemens, Havells, MDS,
14 44 Providing & erecting 240 V MCB double pole 278.76 No.
switch for lighting Load (B Curve) having 10 KA
breaking capacity & confirms to IS : 8828 in
existing box having following capacity. (a) 6 to
Amp. [Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
15 13 Providing & erecting 415V MCB Four Pole Switch 578.73 No.
for Lighting Load (B curve) having 10KA breaking
capacity & confirms to IS :8828 in existing box
having following capacity.(a) 6 to 32 Amp.
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
16 10 Sheets steel powder coated enclosure suitable for 176.75 No.
incorporating One/Two nos. MCB.
17a 3 Providing and erecting Sheet Steel powder coated 629.23 No.
MCB distribution board - flush / surface mounted
fitted with busbar, neutral link, earth bar and DIN
rail, Conforms to IS 8623-1 & 3, IEC 61439-1 &
without MCB to house appropriate nos. of
MCBs.(The DBs should be used of same company
of MCB to be used) suitable for (A) single phase
incoming and horizontal single phase outgoing
(i)sheet steel double door (IP-43) (a) 4 way .
17c 5 (c) three phase incoming and single phase 2339.16 No.
horizontal type outgoing Per phase isolation type
(PPI) (a) sheet steel double door (i) 4 way
18 4 Providing and erecting Approved make RCCBs 2235.13 No.
conforming to IS: 12640 and having sensitivity of
30 mA and Short Circuit withstand capacity of
KA and suitable for operation on single phase
V,50Hz. having characteristic of quick action &
tripping with all advance feature & do not
incorporate any electronic component. for
following Max. rating erected as directed. (a)
40Amps. DP [Approved Make - Schneider, L&T,
ABB, Siemens, Havells, MDS, C&S]
19 4 Providing and erecting Approved make RCCBs 2637.11 No.
conforming to IS: 12640 and having sensitivity of
30 mA and Short Circuit withstand capacity of
KA and suitable for operation on 3 phase and
neutral 415V,50Hz. having characteristic of quick
action & tripping with all advance feature & do not
incorporate any electronic component for following
Max. rating erected as directed (a) 40Amps. FP
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
20 10 Providing and erecting Approved make Four pole 6173.12 No.
moulded case circuit breaker having breaking
capacity ICU of 25 KA. at 415 V,having normal
current rating up to 25 A to 100A. with Fixed
thermal & magnetic release suitable to work on
A.C. supply 50 c/s. with all internal connections,
spreader tinned copper & complete erected in
existing 16 G.M.S. housing. ICS=100% of ICU
only [Approved Make - Schneider, L&T,
ABB, Siemens, Havells, MDS, C&S]
21 2 Providing and erecting Approved make Four pole 16221.61 No.
moulded case circuit breaker having breaking
capacity ICU of 35 KA. at 415 V. having Normal
current rating 200A.with variable Thermal &
magnetic release suitable to work on A.C.supply
c/s. with all internal connections, spreader tinned
copper & complete erected in existing
G.M.S.housing. ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
22 1 Providing and erecting Approved make Four pole 25228.79 No.
moulded case circuit breaker having breaking
capacity ICU of 50 KA and above at 415 V
having Normal current rating 400A. with variable
Thermal & magnetic release suitable to work on
A.C.supply 50 c/s. With all internal connections,
spreader tinned copper & complete erected in
existing 16 G.M.S. housing. ICS=100% of ICU
only [Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
23a 1 Supplying and erecting triple pole & neutral 440V/ 660.54 Rmt.
500V panel mounting Aluminium Busbars with
four equal Nos. of bus having current density not
more than 0.8 Amp. / sq.mm (Rated current / cross
section area) duly wrapped with colour insulating
tape for phase sequence of following current
carrying capacity, erected with necessary bus bar
supports /insulators, main cable socket to each
busbar,erected in existing cubical panel with
necessary connections.(a) Suitable for 100 Amp.
23b 3 (b) Suitable for 200 Amp. Capacity 1037.27 Rmt.
23c 2 (c) Suitable for 400 Amp. Capacity 2204.83 Rmt.
24a 1 Supplying & erecting approved make Four Pole 7790.13 No.
415V change over switch interior for panel
mounting with operating mechanism A.C.23 duty
confirming to IS for (a)100-125A [Approved Make
- Schneider, L&T, ABB, Siemens, Havells, MDS,
24b 1 (b)400A [Approved Make - Schneider, L&T, 22255.35 No.
ABB, Siemens, Havells, MDS, C&S]
25 5 Providing & erecting weather proof, dust & vermin 14902.55 Sq.
proof, floor mounted front operated indoor type Mtr.
cubical panel board necessary IP-42 and above
protection as per approval from engineer incharge
made from 14 SWG thick CRC M.S. sheet for
outer body & doors, 16 SWG thick CRC M.S.sheet
for internal partitions with necessary accesories
supporting angles/ flats channel including cutting,
bending, drilling, welding, riveting with internal
partitions & cable alley as per requirements &
instruction of engineer-in-charge with erection of
supplied switch gears, BUSBARS, suitable size of
inter connecting PVC copper wire / copper-
aluminium strips, rubber grommets, rib, bakelite
control fuses/MCB for measuring instruments,
earth bus & earth bolts, foundation flange - bolts-
base Plates, sufficient nos. of hinged doors, handles
with locking arrangement and rubber gasket,heavy
duty end terminal connection,danger notice
board,necessary ventilation,earthing strip
complete. The Panel shall be painted with epoxy
powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains &
Copper Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base
beams) The panel shall be supplied with following
approved manufacturers with following size.(A)
The standard companies switch gear shall be used
and only manufacturers at CPRI approved factory
(i) with 350 mm depth [Make Approved By
Engineer in charge]
26 3 Supplying and erecting approved make panel 1275.63 No.
mounting type Digital Voltmeter having 3 digits
LED display, 0 to 750 AC Volts range erected on
existing panel board with all connection, wiring
etc .with manufacturers calibration
certificate.[Approved Make-Gelco, Meco,
Schneider, Siemens, Techno]
27 3 Supplying and erecting approved make panel 1558.43 No.
mounting type Digital Ammeter having 3 digits
LED display, external CT operated, calibrated for
to 1000 Amps suitable to operate on 500 Volt AC
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate.[Approved Make-Gelco,
Meco, Schneider, Siemens, Techno]
28 9 Supplying and erecting approved make suitable 43.43 No.
panel indicator LED type lamp, lens cover,
complete erected with necessary connections.
29 1 Supply of Approved make Iron Clad or metal clad 12240.19 No.
four pole change over switch 415V. confirming to
IS of following capacity. (a) 100 A / 125 A
[Approved Make - Siemens, Schneider, L&T,
ABB, Havells, C&S]
30 1 Erection & connection charges for 63 A / 100A / 68.68 No.
125 A change over switch as following. (a)on
existing wooden block / A.I.frame
31 1 Providing Approved make Triple Pole Metal Clad 5812.55 No.
Switch Fuse Unit 415/500 V. with HRC fuse of
suitable load and neutral link confirming to IS. (a)
100 A/125 A Cat.III
32 1 Providing Approved make Triple Pole metal clad 13353.21 No.
switch fuse unit 415 / 500V. 400 A with HRC fuse
of suitable load and neutral link confirming to IS
[Approved Make - Havells, L&T, Crompton, C&S,
HPL, Indoasian]
33 1 Erection & connection charges for 32A/ 63 A / 100 73.73 No.
A HRC TPN as following. (a)on existing wooden
block / A.I.frame
34 1 Erection & connection Charges for 200A/ 250A/ 73.73 No.
300 A /325 A/400 A HRC TPN as following
(a) on existing wooden block / A.I. frame
35 8 Providing and erecting HOT deep Galvanised iron 77.77 Kg.
strip / wire 8 to 16 SWG.
36 2 Supplying & erecting earth pit of minimum bore 4591.46 No.
dia.150mm size approved make Earthing Electrode
consisting Pipe-in-Pipe Technology as per IS 3043-
1987 made of corrosion free hot dipped G.I.Pipes
having Outer pipe dia of 50mm having 80-200
Micron galvanising, Inner pipe dia of 25 mm
having 200-250 Micron galvanising, connection
terminal dia of 12mm with constant ohmic value
surrounded by highly conductive compound with
high charge dissipation suitable for following type
of applications with chamber and heavy duty
cover. (A)(approved make OEM has to submit test
certificate including value of earth resistance of
installation duly stamped and signed by agency and
officer Incharge has to ensure the value of earthing
resistane mentioned in test Certificate) & having
back filling compound of (B) Inner chemical
(CCM Compound)- Resistivity:- 0.2 ohm / meter
testing as per IEC 62561-2017, Voltage drop:- <
volt at no load & dry form, Sulphar content:-
<2%(C) Back fill Compound :- Earthing
compound should be capable to retain moisture for
long time Necessary test report must be submitted
by Agency. .(a) For Electrical Installation up to
440V in normal soilLength of pipe - 1 MtrBack
filling compound - 1 Nos Bag of 15 Kg.[Make will
be approved by Engineer in Charge]
37 1 Supplying 3 Phase Isolation Transformer followed 126144.86 No.
by 3-Phase automatic digital microprocesser. based
servo control voltage stabilizer, air cooled, with
indoor enclosure with bottom cable entry with
MCB at input & contactor at output for tripping at
various fault condition. Stabilizer suitable for
unbalanced input voltage & unbalanced load.
Protection for over voltage, under voltage, over
load, short circuit & single phasing preventer. With
LCD display, with back light for displaying
input/output voltages & load current along with
fault/trip messages/Class-C surge protection device
included copper wound winding.Input:
320‐500/400V, 3‐Phase, 50 Hz, 3‐Wire + Earth,
Output: 400VAC+/-1%, 3‐phase, 4‐Wire + N +
Earth FOLLOWING Rating.(a) Rating 15 KVA
38a 6 Supplying and erecting LED street light / Flood 3345.12 No.
light fittings with High power White LEDs wattage
of 3 Watt and above assembled on single MCPCB,
efficiency more than 130 lm/w and corrosion free
High pressure die cast aluminum housing with
smooth finish powder coated and heat sink
extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened glass
with company mark/name engraved or embossed
160 to 270 V,Power Factor more than 0.95, THD <
10 %, CCT 3000 K to 5700K,Uniformity ratio
>0.45, Luminaire efficacy> 100 lumens/watt . LED
driver efficiency > 85 %.( fittings required LM-79
& LM-80 certificates)(NOTE: Below description
have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.) (A)
Street Light (IP-65), Surge protection -4KV
integral and ,Light must have 440VAC line supply
with over-voltage protection. (a) 48 watts
[Approved Make - Philips, Wipro, Crompton,
Havells, Surya, Bajaj, Orient]
38b 27 (B)Flood Light (IP-65), Surge protection -4KV 5599.44 No.
integral and ,Light must have 440VAC line supply
with over-voltage protection. (a) 60 Watts
[Approved Make - Philips, Wipro, Crompton,
Havells, Surya, Bajaj, Orient]
39 10 Supplying and erecting Flexible PVC insulated 46.46 Mtr.
multi strand multi core 1.1 kv grade ISI marked
copper wires of following size to be erected as
directed.(a) 1.50 Sq.mm 3 core round PVC
sheathed. [Approved make - Polycab, Havells,
RRKabel, Finolex, Anchor]
40 27 Supplying and erecting approved make Octagonal 6874.06 No.
pole made from HR sheet steel. The pole should be
made as per IS. and shall be coated with hot dip
galvanizing as per IS 2629/2633/4759, suitable
suspend local wind speed with integral Junction
box consist of terminal plate of min 6mm Hylam
sheet, standard profile 35mmX7.5mm Din-Rail for
MCB Mounting, stud type terminal and
arrangement for cable termination to be erected
With Suitable foundation (Included) as per details
given by manufacturer considering site
requirement. C) 5 Mtr. Long 70 mm Top X
mm bottom dia, 3 mm thickness with
200mmX200mmX12mm base plate, 4-M16 Bolts
and 600mm long with necessary G.I. J Bolts
.Approx Pole weight 46 kg [Approved Make-
Utkarsh, Bajaj, RR ISPAT, FAB, Crompton,
41 6 Supplying & erecting approved make SMC press 515.10 No.
moulded composite FRP. loop-in, loop-out approx.
2mm thick box complete with Bakelite connector
strip 5way(3P+N+E),DIN rail for mounting mob
& hinged doors as per requirement having locking
arrangements with mounting clamp with nuts, bolts
& washers suitable for erection on pole with cable
clamps& earth bolt of following size of box.(b)
250mm x 200mm x 100mm [deep] [Approved
Make - Sintex, National, EPP, Hensel, Green
42 27 Supplying and erecting Street light pole bracket 491.87 No.
comprising main B Class GI pipe of 4.2 cm/require
outside dia. complete with suitable B Class G.I.
sleeve tubing of approx. 45cms.length and suitable
for 76.5mm/80mm/require size of pole top having
nuts and bolts for fixing the brackets and having
spread of 0.5 mtr. Length with 110 deg.with
vertical plane and suitable welded stiffener reducer
and nipple with check nut complete painted with
one coat.of Red oxide / PU base primer and two
coats of Aluminium / PU paint. paint with
following nos of arms. [a] Single Arm bracket
Mtr. [Approved Make - Sintex, National, EPP,
Hensel, Green composites]
43 1 Supplying & erecting approved make Digital time 3168.37 No.
switch having lithium cell 6 years operative and
operate battery backup 1 channel day clock with
memory programme, suitable to operate on 240V +
5%, 16A with, floating contacts Minimum
switching setup time 1 minimum & LCD display.
Also comprised permanent ON/OFF switching.
Programming switches & housed in fire proof
thermoplastic enclosure & transparent cover
erected as required with necessary connection
erected as directed.[Approved Make - L&T, GIC,
Gelco, Ellico, Shneider, Selec, MDS]
44a 1 Supplying & erecting power contactor, AC3 duty 796.89 No.
for time switch complete erected as per direction
Cat-III (a) 2 Pole 250V 12 Amp.[Approved Make
- Schneider, L&T, ABB, Siemens, Havells, MDS,
44b 1 (b) 4 pole 440V 16 Amp.[Approved Make - 857.49 No.
Schneider, L&T, ABB, Siemens, Havells, MDS,
45 81 Providing and erecting ,Fabricating the box type 180.79 Kg
items made from M.S. Sheet with A.I. supports,
wings, doors, handles other hardware materials as
per requirement design with finishing by three tank
powder coating processed inside and outside
painted, erected as directed including minor civil
46 4 Excavating hard rock or bituminous road (B.T.) by 599.94 Cu.
chiselling or using tool and tackles for preparing Mtr
pit for poles or earth plates or for laying pipes &
clearing the site by removing debris & making site
47 100 Providing and erecting XLPE(IS:7098)(I)-88 ISI 79.79 Mtr.
armoured cable Aluminium conductor for 1.1 KV.
to be laid on wall with necessary clamps or in
existing trench / pipe of following size of cables.
(A) 2 core 4 Sq. mm
48a 500 Providing and erecting XLPE (IS:7098)(I)-88 ISI 126.25 Mtr.
armoured cable multistrand / Solid Aluminium
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe of
following size of cables. (a) 4 core 6 Sq. mm
[Approved Make - Avocab, Havells, Finolex,
RRKabel, L&T, Polycab]
48b 600 (b) 4 core 10 Sq. mm [Approved Make - Avocab, 140.39 Mtr.
Havells, Finolex, RRKabel, L&T, Polycab]
49 100 Providing and erecting XLPE (IS:7098)(I)-88 ISI 153.52 Mtr
armoured cable multistrand Aluminium conductor
for 1.1 KV. to be laid on wall with necessary
clamps or in existing trench / pipe of following
size of cables(A) 4 core 16 Sq. mm. [Approved
Make - Avocab, Havells, Finolex, RRKabel, L&T,
50a 120 Providing and erecting XLPE(IS:7098)(I)-88 ISI 183.82 Mtr
armoured cable multistrand Aluminium conductor
for 1.1 KV. to be laid on wall with necessary
clamps or in existing trench / pipe of following
size of cables (A) 3 1/2 core 25 Sq. mm ( 16 Sq.
mm 1/2 core) [Approved Make - Avocab,
Havells, Finolex, RRKabel, L&T, Polycab]
50b 80 (b) 3 1/2 core 35 Sq. mm ( 16 Sq. mm 1/2 core) 220.18 Mtr.
[Approved Make - Avocab, Havells, Finolex,
RRKabel, L&T, Polycab]
51a 24 Providing and, fixing heavy duty flange type brass 38.38 No.
cable gland with rubber ring for PVC insulated
armoured cable complete with out going tails,
insulating tape etc for following size of cables. (a)
2 to 4 core 6 Sq. mm
51b 2 (b) 2 to 4 core 10 Sq. mm 38.38 No.
51c 8 ( c ) 2 to4 core 16sqmm 47.47 No.
52a 8 Providing and, fixing heavy duty flange type brass 66.66 No.
double compression type cable gland with rubber
ring for PVC insulated armoured cable complete
with out going tails, insulating tape etc for
following size of cables.(A) 3 & 1/2 / 4 core 25 Sq.
53a 56 Solder less crimping type Aluminium lugs 6.06 No.
conforming to IS suitable for cable of following
size evenly crimped with high pressure tool &
connected to switchgear terminals with
brass/cadmium plated nut bolts in an approved
manner. (a) 1.5/ 2.5/4/6 Sq.mm
54 900 Providing & laying approved make Double walled 62.62 Mtr.
corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II )with
necessary connecting accessories of same material
at required depth in existing trench for laying of
cable. below ground / road surface for enclosing
cable . (a)50 mm outer dia. [Approved Make -
Veronica, Dutron, Rex, Gemini, Duraline]
55 900 Making trench in Hard Murrum / Tar Road of 74.74 Mtr.
suitable width of 90 cm or required depth for
laying any size of cable or locating the fault all
over the run and back filling the same and making
the surface as normal ground.
56 6 Supplying and erecting B class galvanised iron 343.40 No
pipe 32 mm outside dia 45 cm long duly welded on
20 cm x 20 cm x 3 mm thick M.S. base plate,
erected on wall or corner for mounting street light
luminaire with necessary hardware materials duly
Total without GST ₹
*All Rates are Exclusive of GST
I/We am/are willing to carry out the work at…………………….% above/below
percent(Should be written in figures and words) of the estimated rate mentioned above.
Amount of my /our tender works out as under.
Estimated amount put to tender Estimated amount put to tender
Deduct……………% below Add……………….…% Above
1. The Contractor shall exhibit a board with detailed specification and details of work as directed by the
Engineer-In-Charge and as per GR No. MIS/102010/17(2)/k-1 of dtd. 29/01/2011 for which no extra
payment shall be made.
2. The labour cess will be deducted as per prevailing rules i.e. 1% of the work done.
3. GST and Income tax TDS will be deducted at a source while making payments of bills.
4. Rates quoted include clearance of site (prior commencement of work and at its close) in all respects and
hold good for work under all conditions, site, moisture, weather etc.
5. The quoted rates should be inclusive of cost of minor rectification work which may have to be done for
correcting the distoration caused during transportation of the gate components.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NIT-16 of 2025-26 (Electrical Work - Ukai Section).pdf
SBD - Ukai SDO 2.1 Electrical Work.pdf
BOQ Nprocure.pdf
Mendatory Documents(1).pdf
Mendatory Documents(2).pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .