Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.6 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹12.0 L+₹49,019 (4.24%)Rejected-Finance RAGHUNATHPUR HOUSING ESTATE DESHBANDHUNAGAR KOLKATA 700 059 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700059 | L2 | Rejected-Finance Being L2 Bidder. | |
| 3 | L3₹13.8 L+₹2.3 L (19.7%)Rejected-Finance NICHUPATY BOLPUR P WEST BENGAL BIRBHUM PIN 731204 | BOLPUR | BIRBHUM | WEST BENGAL | 731204 | L3 | Rejected-Finance Being L3 Bidder. |
Tender Value
Refer Docs
EMD Value
₹32,500
Closing Date
18 Sept 2019, 5:00 pmClosed
Executive Engineer North 24 Pgs Electrical Divn
TOP FLOOR, MECHANICAL COMPLEX, BAGUIATI, KOLKATA 700 059.
Installaion of 415 V, 125 KVA silent type diesel generator set incl. E.I. Work for alternative stand-by power supply at Ashokenagar SGH.
2019_WBPWD_241653_1
WBPWD/EE/N24PRG/ELEC/44/19-20
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Ashokenagar
Please refer Tender documents.
6 documents required · 6 mandatory
₹32,500
6 Nov 2020
2 Sept 2019
20 Sept 2019
3 Sept 2019
18 Sept 2019
3 Sept 2019
Amount
Supply,Installation, Testing, & Commissioning of 125 KVA of silent DG set comprising of engine with generartor set controller and brushless alternator both mounted on a common base complete with Fuel tank, residential silencer, AVM pads, Low Maintenance free to IS: 14257 for high cranking performance 100 Ah batterys with its leads, First fill of lube oil, AMF control panel & Acoustic encloser having following specification Sheet Thickness 1.6 millimeter, Thickness of Foam 40 millimeter, Density of Foam for sound insulation 32, Noise level at 1 meter (dB) 75.(Make: CUMMINS /VOLVO-EICHER / CATERPILLAR) Generator Set specification Duty Prime Power Rating in KVA 125 No of Phase 3 Output Voltage 415V Frequency 50 Hz Power factor .8 lagging Currrent 217 Amp. RPM 1500 Engine Specification Make CUMMINS /VOLVO-EICHER / CATERPILLAR MoEF Certified Power (hp) 83 Cooling Liqued cooled Aspiration Turbocharge Charged AirCooled No of cylinders 6 Fuel High Speed Diesel Fuel consumption @75% load with radiator and fan* (litre/hr): 22.5; Fuel consumption @100% load with radiator and fan* (litre/hr):30.25; Lube oil specification :CI4+ 15W40 Performance class of generator set ISO 8528-V G2 Starting system 12 V DC Electrical Alternator Encloser IP 23 Volatge regulation grade VG 2 Class of insulation H class Maximum Unbalanced load across phase less than or equal to 25% . Winding Pitch: 2/3,Stator Winding :Double layer lap Rotor: Dynamically Balanced ,Waveform distortion/ Total Harmonic Distortion:No load < 1.5 %, Non distorting balanced linear load < 5 %; Maximum Unbalanced Load across phases: less than or equal to 25%; Telephonic Harmonic factor:<2 %. with test report for Engine from Central govt/NABL/ILAC accredited laboratory.
S & Laying of cable above Al/ A XLPE, 4 core 120 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy. mending good damages and painting.
S&F compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of 4 Core 120 sqmm XLPE/PVC armoured cables incl. finishing as per G.S. for following cables
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials 4 core 120 sqmm
Supplying and fixing 415V, 200A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc.(Make: L&T)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S&F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level in soft soil By ISI-Medium GI pipe.
S&F 80 mm dia medium guage protection with necessary fittin and jointing material as required for cable protection.
Supplying and fixing 415V, 200A TPN SFU with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc.(Make: L&T)
PIONEER AUTOMOBILE SERVICES
NARAYAN CHANDRA DAS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .