| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.6 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹32.6 L+₹3.9 L (13.7%)Rejected-AOC | L2 | Rejected-AOC second lowest | |
| 3 | L3₹35.2 L+₹6.5 L (22.8%)Rejected-AOC | L3 | Rejected-AOC Third Lowest | |
| 4 | Rejected-Technical CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | - | Rejected-Technical as per cllause 4.3.10 in SBD necessary documents are not uploaded |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
2 Nov 2023, 6:00 pmClosed
Executive Engineer
The Executive Engineer PWD Electrical Division Thrissur
DEPOSIT Annual plan budget 2017 18 Implementation of plan scheme at Govt Mental Health centre Thrissur SITC of 315 KVA Transformer general Electrical Work
2023_PWD_616347_1
PWD/BLDG/9518/2023-2024
Open Tender
Electrical Works
Item Rate
120 days
Thrissur
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,760
₹50,000
30 Nov 2023
26 Oct 2023
4 Nov 2023
26 Oct 2023
2 Nov 2023
26 Oct 2023
Amount
Transformer
OD90275/2023-2024:Supply installation testing and commissioning of both sides extensible 12kV, 630A, 21kA, Motor operated, Compact, Outdoor, 12 kV, SF6 Ring Main Unit complete(Extensible / Outdoor)( 2 Isolator+ 1Breakers+FRTU+APT )FBX-E /12-20/ CCT2+FRTU+APT/Outdoor – Motorised + Battery Charger. (2nos. Load Break Switch (OD) incomer and 1no. fixed type motor operated Vacuum Circuit Breaker (T2) outgoing) compact gas insulated Ring Main Unit, The switching-unit is designed as a three-position-switch. This three-position-switch combines the functions of switch-disconnector and earthing-switch. The switch-disconnector as well as the earthing-switch is equipped with a separate drive-unit . All live parts enclosed in a robotically welded stainless steel tank of IP 67 class of protection. With Battery and Battery Charger.1 No SF6 insulated arc quenching load break switch with SF 6 breaker suitable for 11KV/433V Transformer. Protection:- Self powered OC/EF Protection relay DPX-1 with suitable protection CTs for Xfer Rating 100 kVA and above With O/C Setting ranging 20% to 250% and E/F Settings 10% to 250%. Add on shall be with terminal protectors protection relays with all materials complete conforming to relevant IS/ IEC standards with 3 years maintenance from date of commissioning
OD80608/2023-2024:Supply, installation, testing and commissioning of outdoor HT metering cubicle consists of the following; A) Resin cast CT 3Nos., ratio; -20/5 , 15 VA Class 0.2S B) Resin cast PT 1No., 11kV/110V, 15VA, Class 0.2S C) Test terminal block for TOD meter D)3 Phase, 4 wire, 110 V (L-L), -/1 A CT or -/5A CT, accuracy class 0.2, TOD meter as per KSEB Standards E) The enclosure shall fabricated using 2mm MS sheet and shall comply with IP 65 standards with dust and vermin proof outdoor type and shall be powder coated after seven tank processing and phosphatising. 11 KV bus bar arrangement with insulator, HT cable termination, Locking facility etc as required.
OD80621/2023-2024:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 11 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required 3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments
OD80622/2023-2024:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 11 KV grade of the following sizes in the existing masonry open duct as required. 3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments
OD80623/2023-2024:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 11KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments
90.12.7.36:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 300 sq mm
90.12.7.22:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 150 sq mm
9.1.15:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 150 sq. mm (50mm)
90.12.12.8:Supply & laying of DWC pipe in ordinary soil 1.2 m below ground level including excavation125/109 mm or nearest size
10.2.4:Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
4.1.9:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.375 mm width X 62.5 mm depth X 2.0 mm thickness
7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
OD157565/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50sq mm wire single run
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD89902/2023-2024:Supply&fixing 400/5 A 15VA accuracy class 0.5 tape wound metering CT
OD90865/2023-2024:Supply & fixing 200/5 A, 10 VA, accuracy class 1, Tape wound Metering CT
OD92812/2023-2024:Supply & fixing 150/5 A, 5 VA, accuracy class 0.5, Tape wound Metering CT
OD89760/2023-2024:Suply & fixing the following multi-function meters in the panel assembly.Multifunction meter to read: V, A, F, 3 phase accuracy class 1
OD89761/2023-2024:supply and fixing Red, Green, blue, Yellow, Orange colours LED indicator, AC/DC, as required
90.14.24.1:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.1 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.2:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.2 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.3:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.3 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type suitable for direct connection to motors.
90.14.24.5:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor suitable for direct connection to motors.
90.14.24.8:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor suitable for direct connection to motors.
90.14.24.11:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor, suitable for direct connection to motors.
90.14.24.12:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.25 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor, suitable for direct connection to motors.
90.14.24.13:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.30 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor, suitable for direct connection to motors.
OD90596/2023-2024:Supply & fixing the3 Pole Capacitor duty contactors for switching capacitor banks 7.5 - 10 kVAR with AC Coil,
OD90597/2023-2024:Supply & fixing the3 Pole Capacitor duty contactors for switching capacitor banks 4 - 7 kVAR with AC Coil,
OD90631/2023-2024:Supply &fixing 3 Pole Capacitor duty contactors for switching capacitor banks 25 kVAR with AC Coil,
OD90632/2023-2024:Supply&Fixing the 3 Pole Capacitor duty contactors for switching capacitor banks 20- kVAR with AC Coil,
OD92544/2023-2024:Supply & Installation of 3 Pole Capacitor duty contactors for switching capacitor banks 30 kVAR with AC Coil,
OD90303/2023-2024:Supply & Installation of 8 stage 440 / 110 V 5A/1A , Intelligent Power Factor Controllers (IPFC)
90.14.10.13:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.22:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.630A, 70 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.1:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.14.11.4:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 630A to 800A with CBCT.
90.14.11.8:MCCB AccessoriesSupply and fixing CBCT suitable for 630 - 800A earth fault module.
90.14.11.10:MCCB AccessoriesSupply and fixing auxiliary switch + alarm switch (1 NO + 1 NC & 1 NO) in the existing MCCB of rating up to 630A.
90.14.11.14:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.11.16:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 630A.
OD102792/2023-2024:Supply and fixing extended terminal ( Spreader / Terminal adapter kit ) for 4pole MCCB of rating 200A and 250A ( 8 Pcs )
OD102793/2023-2024:Supply and fix one Set of Spreader/ terminal adapter kit with shroud in the existing 4 pole MCCB up to 125 A (8 pcs)
OD102794/2023-2024:Supply and fix one Set of Spreader/ terminal adapter kit with shroud in the existing 4 pole MCCB up to 320 A to 630 A (8 pcs)
1.17.2:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.16.3.10:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm copper strip
90.16.4.8:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm copper strip
90.16.4.9:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 6 mm copper strip
90.16.3.2:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm GI strip
90.16.3.3:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm GI strip
90.16.4.2:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm GI strip
90.16.4.3:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 6 mm GI strip
OD89573/2023-2024:Supply and providing plate earthing as per IS 3043 with 1200x1200x12 mm GI/CI earth plate, 50 mm GI watering pipe fixed to the earth plate with 25 x 3mm GI clamps, GI funnel with weld mesh, filling required quantity of charcoal including construction of inspection chamber with a bed concrete of 1:4:8 PCC using 40 mm broken stone (10 cm thick), brick work in cement mortar 1:6, plastering the surface of brick masonry and the exposed surface of PCC bed with cement mortar 1:4, 12 mm thick, (the finished inside dimension shall be 450 x 450 x 450 mm) but excluding test joint, earth continuity conductor to the plate, and covering at the top. (in ordinary soil)
OD92584/2023-2024:Supply & providing 2.00 mm thick, 3.3 kV, Synthetic elastromeric fire retardant insulating mat as per the IS 15652/2006 tto withstand 3.3 KV dielectric strength
OD92625/2023-2024:Supply and providing ABC type fire extinguisher 5kg capacity with installation brackets conforming to IS 15222 as required
OD92773/2023-2024:Supply & providing first aid chart duly framed and placed in a conspicuous location for clear vision
OD157591/2023-2024:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required
OD92730/2023-2024:Supply and fixing Aluminium anodised Danger Notice Board of size 200 x 150 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour
OD92739/2023-2024:Supply and providing and fixing 25 mm X 3 mm Copper. strip earth lead from the test joint to the earth plate
OD92740/2023-2024:Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
OD92741/2023-2024:Supply and providing 25x6mm brass nut and bolt etc. as required.<>br
OD92742/2023-2024:Supply and providing 12x3mm brass nut and bolt etc. as required.
OD92743/2023-2024:Supply and providing 25x3mm brass nut and bolt etc. as required.
OD92602/2023-2024:Charges for preparation of electrical/fire and drawing per A3 sheet additional copy
OD92603/2023-2024: Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB (for preparing scheme & records for scrutiny & completion) first A3 Sheet
OD132397/2023-2024:SITC of MC 12 EARTH Fault Relay 88-264V CT5A
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
90.3.20.3:Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
SABI ENGINEERING COMPANY
Biju E.M
Kittu Electricals private limited
Bidder Name
SABI ENGINEERING COMPANY
Biju E.M
Kittu Electricals private limited
ELCON ELECTRICALS
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_923998.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .