Tender Value
₹15.2 L
EMD Value
₹30,300
Closing Date
31 Jul 2023, 2:00 pmClosed
EXECUTIVE ENGINEER, ED-RAJOURI, JPDCL
Office of Executive Engineer, JPDCL, Electric Division, Rajouri
SUPPLY, INSTALLATION, TESTING AND COMMISSIONING ON TURNKEY BASIS FOR CREATION OF SUBSTATIONS AT GAKHROTE- A, DHAR, MASJID MOH. GAKHROTE - A, W NO. 4 GAKHROTE - A AND W NO. 6 GAKHROTE - A
2023_PDD_220987_1
EDR/21 of 2023-24 Dated 11.07.2023
Open Tender
Electrical Works
Turn-key
60 days
GAKHROTE
AS PER SECTION-III OF SBD
5 documents required · 5 mandatory
₹1,000
EXECUTIVE ENGINEER, ED-RAJOURI, JPDCL
₹30,300
4 Aug 2023
11 Jul 2023
2 Aug 2023
11 Jul 2023
31 Jul 2023
19 Jul 2023
Amount
QUOTED TOTAL OF RESPECTIVE BOQ TO BE ENTERED
SCHEDULE-A (BOQ2)
SCHEDULE-B (BOQ3)
SCHEDULE-C (BOQ4)
SCHEDULE-D (BOQ5)
SCHEDULE-E (BOQ6)
Description of Work / Item(s)
Amount
11 kV HT Line Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
S.T Pole 8 mtrs long (410-SP15)
30 mm2 ACSR Wsl Conductor
Galvanisied Channel cross-arm/ Angle/ Flat including clamps and braces.
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Al. Painting
Red Oxide
Galvansied Nuts and Bolts of sorts
11/0.44 kV S/Stn Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
25 KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Aluminium Wound and with LV Cable Box having detachable Aluminium Gland plate.
S.T Pole 8 mtrs long (410-SP15)
Surge Arrester Station Type 9KV, 10 kA (Polymer Type)
11 KV Horn Gap Set, 3 Phase, 200 Amp
Channel/Flate/Angle in shape of fabricated X-arms, Top bracket, Angle braces, clamps etc.
PVC insulated stranded conductor FRLS type 1.1kv Grade Cable 120 mm sq with Thimbles
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Nuts and Bolts of sorts
Earthing of Sub-station ,excavation of earth pit of dia 650mm and depth 3000mm,installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5 mtr.long as per IS 1239.GI strip for neutrl earthing of size 25 mm*3 mm for connection of transformer body ,G.O set and lightening arrestor as per IS 2629/85,GI nuts and bolts ,refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. (Specification as per cost data)
Al. Painting
Red Oxide
Description of Work / Item(s)
Amount
11 kV HT Line Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
S.T Pole 8 mtrs long (410-SP15)
30 mm2 ACSR Wsl Conductor
Galvanisied Channel cross-arm/ Angle/ Flat including clamps and braces.
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Al. Painting
Red Oxide
Galvansied Nuts and Bolts of sorts
11/0.44 kV S/Stn Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
25 KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Aluminium Wound and with LV Cable Box having detachable Aluminium Gland plate.
S.T Pole 8 mtrs long (410-SP15)
Surge Arrester Station Type 9KV, 10 kA (Polymer Type)
11 KV Horn Gap Set, 3 Phase, 200 Amp
Channel/Flate/Angle in shape of fabricated X-arms, Top bracket, Angle braces, clamps etc.
PVC insulated stranded conductor FRLS type 1.1kv Grade Cable 120 mm sq with Thimbles
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Nuts and Bolts of sorts
Earthing of Sub-station ,excavation of earth pit of dia 650mm and depth 3000mm,installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5 mtr.long as per IS 1239.GI strip for neutrl earthing of size 25 mm*3 mm for connection of transformer body ,G.O set and lightening arrestor as per IS 2629/85,GI nuts and bolts ,refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. (Specification as per cost data)
Al. Painting
Red Oxide
Description of Work / Item(s)
Amount
11 kV HT Line Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
S.T Pole 8 mtrs long (410-SP15)
30 mm2 ACSR Wsl Conductor
Galvanisied Channel cross-arm/ Angle/ Flat including clamps and braces.
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Al. Painting
Red Oxide
Galvansied Nuts and Bolts of sorts
11/0.44 kV S/Stn Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
63 KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Aluminium Wound and with LV Cable Box having detachable Aluminium Gland plate.
S.T Pole 8 mtrs long (410-SP15)
Surge Arrester Station Type 9KV, 10 kA (Polymer Type)
11 KV Horn Gap Set, 3 Phase, 200 Amp
Channel/Flate/Angle in shape of fabricated X-arms, Top bracket, Angle braces, clamps etc.
PVC insulated stranded conductor FRLS type 1.1kv Grade Cable 120 mm sq with Thimbles
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Nuts and Bolts of sorts
Earthing of Sub-station ,excavation of earth pit of dia 650mm and depth 3000mm,installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5 mtr.long as per IS 1239.GI strip for neutrl earthing of size 25 mm*3 mm for connection of transformer body ,G.O set and lightening arrestor as per IS 2629/85,GI nuts and bolts ,refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. (Specification as per cost data)
Al. Painting
Red Oxide
Galvansied Stay set with 50x8mm stay clamp, guy insulator (02nos.) anchor plate (200x200x6mm) nut bolts, 2nos. Turn bukles, 1.80m long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
LT Line Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
S.T Pole 8 mtrs long (410-SP15)
30 mm2 ACSR Wsl Conductor
Shakle Insulator (16KN)
Mukky Clamps
Red Oxide
Al. Painting
Nuts and Bolts of sorts
Description of Work / Item(s)
Amount
LT Line Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
S.T Pole 8 mtrs long (410-SP15)
30 mm2 ACSR Wsl Conductor
Shakle Insulator (16KN)
Mukky Clamps
Red Oxide
Al. Painting
Nuts and Bolts of sorts
Description of Work / Item(s)
Amount
11 kV HT Line Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
30 mm2 ACSR Wsl Conductor
Galvanisied Channel cross-arm/ Angle/ Flat including clamps and braces.
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Galvansied Nuts and Bolts of sorts
11/0.44 kV S/Stn Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and then complete Erection, Testing and Commissioning as per REC/PDD Standard of
25 KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Aluminium Wound and with LV Cable Box having detachable Aluminium Gland plate.
S.T Pole 8 mtrs long (410-SP15)
Surge Arrester Station Type 9KV, 10 kA (Polymer Type)
11 KV Horn Gap Set, 3 Phase, 200 Amp
Channel/Flate/Angle in shape of fabricated X-arms, Top bracket, Angle braces, clamps etc.
PVC insulated stranded conductor FRLS type 1.1kv Grade Cable 120 mm sq with Thimbles
11 kv Pin insulators with pins (10KN)
11 kv Disc insulators with fittings (45 KN)
Nuts and Bolts of sorts
Earthing of Sub-station ,excavation of earth pit of dia 650mm and depth 3000mm,installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5 mtr.long as per IS 1239.GI strip for neutrl earthing of size 25 mm*3 mm for connection of transformer body ,G.O set and lightening arrestor as per IS 2629/85,GI nuts and bolts ,refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. (Specification as per cost data)
Al. Painting
Red Oxide
Sundry Item/Fuse
Galvansied Stay set with 50x8mm stay clamp, guy insulator (02nos.) anchor plate (200x200x6mm) nut bolts, 2nos. Turn bukles, 1.80m long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
SNAZZY ELECTRICAL AND CONTRACTORS
Mohammand Shafiq
New Age Construction
M/s Destiny Builders
SNAZZY ELECTRICAL AND CONTRACTORS
M/s Destiny Builders
Mohammand Shafiq
New Age Construction
SNAZZY ELECTRICAL AND CONTRACTORS
M/s Destiny Builders
Mohammand Shafiq
New Age Construction
SNAZZY ELECTRICAL AND CONTRACTORS
Mohammand Shafiq
New Age Construction
M/s Destiny Builders
SNAZZY ELECTRICAL AND CONTRACTORS
Mohammand Shafiq
New Age Construction
M/s Destiny Builders
VEENA CONSTRUCTION CO.
Mohammand Shafiq
New Age Construction
M/s Destiny Builders
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .