| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹54.1 LAccepted-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹54.1 L | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹54.9 L+₹79,614 (1.47%)Rejected-Finance NO 5 MAIN CHANNEL ROAD ULSOOR BANGALORE KARNATAKA 560008 | BENGALURU URBAN | KARNATAKA | 560008 | ₹54.9 L+₹79,614 (1.47%) | L2 | Rejected-Finance Not the lowest |
| 3 | L3₹55.9 L+₹1.8 L (3.32%)Rejected-Finance CHENNAI TAMIL NADU 600015 | CHENNAI | TAMIL NADU | 600015 | ₹55.9 L+₹1.8 L (3.32%) | L3 | Rejected-Finance Not the lowest |
Tender Value
₹44.3 L
EMD Value
₹88,640
Closing Date
20 Mar 2025, 3:30 pmClosed
Managing Director, CIAL
MD Cochin International Airport Ltd Kochi Airport PO Nedumbassery 683111
2 Nos of New Cold-room Works for the Export Cargo and Modification of Temperature controlled rooms in Duty-free Warehouse CIAL
2025_CIAL_738416_1
CIAL/ELE/404/ET 08
Open Tender
Miscellaneous Works
Item Rate
183 days
Export Cargo and Dutyfree Warehouse CIAL
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹88,640
8 Apr 2025
17 Feb 2025
21 Mar 2025
17 Feb 2025
20 Mar 2025
19 Feb 2025
Amount
New Coldroom 1 and 2 - Export Cargo
SITC of 6 kW DX Split unit for the cold room 1 at the Export cargo. The room temperature to be maintained is 2-8 °C. The ambient temperature to be considered is 40 °C. Each indoor unit (COIL: Al fin and Cu tube) shall contain min 2 fans of min 300mm. Refrigerant shall be R404a/R407c. The outdoor unit shall contain Hermitically sealed Scroll compressors. It should contain a suitably rated starter panel, and power wiring from DB/isolator with all accessories.The compressor on/off based on the load shall be controlled by a microprocessor-based control panel with an automatic digital display of temperature and humidity and shall be provided near the sliding door in each compartment. It sjhall also includes up to 20ft of interconnecting pipe and wire between each Indoor and Outdoor unit. Insulation for pipelines should be 25mm thick closed cell elastomeric class 0 insulation with 7 mils woven fibreglass cloth covering adhered between two coats of fungicidal protective coating. CPVC drain pipe of suitable size connecting drain lines from indoor to drain sump outside the building with suitable insulation. Platforms for Indoor and Outdoor units shall be with vibration isolator pads. Both the Indoor and Outdoor unit cabin should be made of PCGI casing and the Outdoor unit should be IP54 rated. Charging of gas, and safety devices like thermal protectors, pressure relief valves, overload relays, single phase preventers, high-low pressure cut off, earth connections, DB, and Power sockets as per Kerala State Electricals Inspectorate guidelines suitable for 3-phase 440v incomer supply. Room size: 4m*2.5m*3.5m Note: The proposed quantity is 1W and 1S
SITC of 8kW DX Split unit for the cold room 2 at the Export cargo. The room temperature to be maintained is 2-15 °C. The ambient temperature to be considered is 40 °C. Each indoor unit (COIL: Al fin and Cu tube) shall contain min 2 fans of min 300mm dia. Use refrigerant R404a/R407c. The outdoor unit shall contain Hermitically sealed scroll-type compressors. It shall contain a suitably rated starter panel, and power wiring from DB/isolator with all accessories. The compressor on/off based on the load shall be controlled by a microprocessor-based control panel with an automatic digital display of temperature and humidity and shall be provided near the sliding door in each compartment. It also includes up to 20ft of interconnecting pipe and wire between each Indoor and Outdoor unit. Insulation for pipelines should be 25mm thick thick closed cell elastomeric class 0 insulation with 7 mils woven fibreglass cloth covering adhered between two coats of fungicidal protective coating. CPVC drain pipe of suitable size connecting drain lines from indoor to floor sump with appropriate insulation. Platforms for Indoor and Outdoor units shall be built with vibration isolator pads. Both the Indoor and Outdoor unit cabin should be made of PCGI casing and the Outdoor unit should be IP54 rated. Charging of gas, and safety devices like thermal protectors, pressure relief valves, overload relays, single phase preventers, high-low pressure cut off, earth connections, DB, and Power sockets, as per Kerala State Electricals Inspectorate guidelines suitable for 3-phase 440v supply. Room size: 4m*5m*3.5m Note: The proposed quantity is 2W and 1S
SITC of Wall and Ceiling Insulation panels for Cold Rooms 1 and 2 at the Export cargo. Pre-fabricated panels with RPUF of a minimum density of 40kg/m3 should be used. It should have heat conductivity less than 0.023 W/m°C at 10°C. The panel should be of a thickness of 80mm. The material used to sandwich RPUF should be PPGI sheets of 0.5mm thickness. Panel-to-panel locks shall be cam-lock with tongue and groove assembly. 90° Corner panels should be used for corners. The wall-to-ceiling joinery shall be held using flashing from inside and outside. All joints should be silicon-sealed. The panel should have grooves for increased strength. RPUF material should strictly adhere to the IS standard 661. The panels shall have Fire self-extinguishing/Fire-resistance/ Fire retardant properties. Room size of C1 is: 4m*2.5m*3.5m (L*W*H) Room size of C2 is: 4m*5m*3.5m (L*W*H)
SITC of Floor Insulation panels for Cold Rooms 1 and 2 at the Export cargo. The flooring shall be a 60 mm PUF slab with a Tar felt sheet of minimum 2mm thickness (concrete flooring, customer scope).
Panelling for Existing Temperature controlled rooms C1 and C2 at dutyfree warehouse
SITC of Wall and Ceiling Insulation panels for Cold Room C1 and C2 at duty-free warehouse CIAL. Pre-fabricated panels with RPUF of a minimum density of 40kg/m3 should be used. It should have heat conductivity less than 0.023 W/m°C at 10°C. The panel should be of a thickness of 60mm. The material used to sandwich RPUF should be PPGI sheets of 0.5mm thickness. Panel-to-panel locks shall be cam-lock with tongue and groove assembly. 90° Corner panels should be used for corners. The wall-to-ceiling joinery shall be held using flashing from inside and outside. All joints should be silicon-sealed. The panel should have grooves for increased strength. RPUF material should strictly adhere to the IS standard 661. The panels shall have Fire self-extinguishing/Fire-resistance/ Fire retardant properties. Room size of C1 is: 9.50m*9.75m*3.60m (L*W*H) Room size of C2 is: 9.50m*8m*3.60m (L*W*H) Note: RPUF panel not needed for the floor
Common Items
SITC of sliding door for the cold room. The door should be of 80mm thickness. RPUF sandwiched between PPGI grooved sheets should be used. The door should have a kick plate at the bottom. Airtight heavy-duty sealing sweep gasket below door with a double sweep. Posi seal closure for firm shut. Safety systems such as a safety release knob inside should be provided. The door should have a vacuumed vision panel of size 300 mm*300 mm. The dimension of the door opening is 1.5m*2.2m (W*H)
SITC of vapour proof LED Batten lights of 40W- minimum IP65 rated
SITC of Temperature and RH Indicator (Thermo-hygrometer ). It shall have a temperate and RH data logging facility (maximum 30 minutes interval). Data retrieval shall be possible in electronic format with a one-month data backup and USB port Interface.
SITC of wired type safety alarm hooter
CAMC for the two Coldrooms at the Export cargo- 1st year after 2 Years DLP
CAMC for the two Coldrooms at the Export cargo- 2nd year after 2 Years DLP
CAMC for the two Coldrooms at the Export cargo- 3rd year after 2 Years DLP
CAMC for the two Coldrooms at the Export cargo- 4th year after 2 Years DLP
CAMC for the two Coldrooms at the Export cargo- 5th year after 2 Years DLP
RINAC INDIA LIMITED (BID ID -2163670)
Eakcon systems pvt ltd (BID ID -2156795)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .