SE MB CIRCLE ADILABAD
New Housing board ADILABAD
Carry Out Routine Maintenance with Round the clock services for Operation and Maintenance of 33/11KV substation with connected Distribution Transformers and switchgear at head works and various intermediate pumping stations under SRSP Adilabad segment for the year 2026-27 for the period October 2026 to March 2027
731446
01/AEE/DEE/MB/Adilabad/Tender/2026-27, Dt:03.09.2026 of the Superintending Engineer, MB Circle, Adilabad
OPEN
Annual maintenance works
NIRMAL, TELANGANA
14 documents required · 14 mandatory
₹1,726
₹48,730
7 Sept 2026
7 Sept 2026
8 Sept 2026
Man Power - For Nirmal District
Engaging of ITI qualified Electrician 3 No' with 5 years experince in substations from 01.10.2026 to 31.03.2027 for 33/11KV sub stations (3 No.s x 182 days = 546)
33/11KV substation at Local Velmal
33/11KV substation at Madegaoan
33/11KV substation at Bhainsa
Engaging of ITI qualified Electrician with 5 years experince in substations from 01.10.2026 to 31.03.2027 for 11KV sub stations (1 No.s x 182 days = 182)
At Gandhinagar Filter bed & Intake well
Engaging of ITI qualified Electrician with 5 years experince in substations from 01.10.2026 to 31.03.2027 for 11KV sub stations (1 No.s x 182 days = 182)
At Gaddenna vagu, Bolsa 315 KVA, RGUKT Basara intakewell
Essential Items - For Nirmal District
Work of repairs/servicing and overhauling of on load tap changer (OLTC) of upto 33KV/11KV 5MVA transformer as specified below: Painting of transformer including platform CTS etc., with one cost of red oxide to the rusted portion of transformer, 2 coats of M/s grey enamel paint, RYB color paint to CT caps for identification etc., Rates should quote inclusive of cleaning of the transformer of all sizes.
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaoan WTP
33/11KV substation at Local Velmal
Carryout routine maintenance, servicing and testing of 630A to 3000A (33KV/11KV) HT VCB by cleaning fixed contacts, moving contacts and arcchutes including servicing and putting the VCB in perfect working condition after detting all relay and ON, OFF mechanism etc done with only manufacturing companies / Authorised dealers of respective switch gears every 6 months @ 2*12401.08 = 24802.15
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaoan WTP
33/11KV substation at Local Velmal
Routine maintenance of transformer in operation covering insulation resistance oil, break down strength. Reconditioning / replacement of silicazel, cleaning of transformer and topping upto oil level if required (extra cost will be paid for oil).
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Testing of Transformer oil for dielectric breakdown strengt at:
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Attending day to day emergencies(Sub-station check up & maintenance Day to day Protection related emergency works attending and maintenance works of various 33/11KV Substations including Initial assessing the exact faults in the protective device in the VCBs & other protective devices to take up the further works, Rectification/ Replacement of AC/DC fuses, Selector switches, TnC Switches, Push buttons, Hooters, bells, TBs, Ammeters, voltmeters, MW/ KW meters, MVA/ KVA meters, Indication lamps, MVAR/ KVAR meters, PF meters, Panel type energy meters, Terminals, Trip Coils, Close Coils, Spring Charging motors, Relays, Big Gears,Pinion gears, Small gears, 12 V Batteries, 2V Batteries, 24v Chargers, damaged/ defective wiring, etc , measurement of earth resistance, Breaker Operation time (O-CCO) with Breaker timer kits, checking for continuity/ interconnections between earth pits & equipments with primary injection kits, insulation resistance of CTs, PTs, Breakers with Insulation resistance measurement tester (megger), Ratio of CTs with primary injection kits, Tightening of all connections inside the breaker panel, Control Panel, CR Panel, Control Circuit, Battery chargers, battery connections, PTR marshalling boxes, Wiring of CTs and PTs when defective CTs and PTs replaced with new one, Restoration of PT supply to the panel when it fails, Balancing of capacitor bank when cells failed, Fixing up of desired relay settings for feeder, LV, HV, GC breakers, Checking up of VCB mechanical spring charging problem, Checking up of trip circuit healthy of CBs, AC Supply restoration to the breaker when fails, 220V DC supply extension to the VCBs, 24V DC battery chargers connections extension to the VCB when the existing charger fails, Minor alignment of breaker for CB operations, Snatch gap adjustment of breaker to take CB in to service, Identification and rectification of wiring problem of breaker, DC system, AC system for protective equipment, Rectification of mechanical/ slow closing problem of CB where material is not required for the work, Attending the Minor mechanical problems of CBs (Closing / tripping may be electrical or mechanical), Testing of new VCBs (Primary injection, IR values, DC resistance, etc), attending & rectification of oil leakages problems of CTs & PTs, Oil topup in CTs & PTs wherever required, Replacements of Clamps, jumpers, studs, bush rods, bolts & nuts, gaskets, connections of CTs & PTs and other protection related works entrusted by the concerned Engineer for every month
Testing of static/electro mechanical Relay elements for proper operation including recording of all name plate details of Relays & Circuit Breakers, recording of existing relay settings, testing of each element of relay with calibrated relay test kit, recording of re;ay test results in systematic procedure, adjusting & fixing up of time settings of relays wherever required for proper functioning, fixing up of relay settings & grading as per department requirement, recording of revised relay settings of wherever revised, testing of relays by conducting primary injection to the CTs, verification & correcting of connections from CTs to Relays wherever required for proper functioning, carrying out minor rectifications, Measurement & recording of Insulation Resistance values of Current Transformers & Circuit Breakers & connected equipment with suitable calibrated Insulation Measurement Tester, recording of all test results in a systematic way & submission to the department in five copies, execution of work by qualified & experienced persons with contractor owned/ hired calibrated suitable testing equipment as per standards in presence of the concerned AE/ DEE/ EE by proper advance planning, intimation & coordination with the concerned officials, etc for completion of work within schedule time for proper operation of equipment and the rate is inclusive of testing charges transport, loading, unloading, local movement, hire charges, calibration charges, insurance to the working persons, etc complete.
Testing of IED Relay complete all required elements for proper operation including recording of all name plate details of Relays & Circuit Breakers, recording of existing relay settings, testing of each element of relay with calibrated relay test kit, recording of relay test results in systematic procedure, adjusting & fixing up of time settings of relays wherever required for proper functioning, fixing up of relay settings & grading as per department requirement, recording of revised relay settings of wherever revised, testing of relays by conducting primary injection to the CTs, verification & correcting of connections from CTs to Relays wherever required for proper functioning, carrying out minor rectifications, Measurement & recording of Insulation Resistance values of Current Transformers & Circuit Breakers & connected equipment with suitable calibrated Insulation Measurement Tester, recording of all test results in a systematic way & submission to the department in five copies, execution of work by qualified & experienced persons with contractor owned/ hired calibrated suitable testing equipment as per standards in presence of the concerned AE/ DEE/ EE by proper advance planning, intimation & coordination with the concerned officials, etc for completion of work within schedule time for proper operation of equipment and the rate is inclusive of testing charges transport, loading, unloading, local movement, hire charges, calibration charges, insurance to the working persons, etc complete.
Attending day to day emergency works Day to day Power Transformers related emergency works attending and maintenance works of various 33/11KV Substations including initial identification of the defects of PTR on complaints from field to take up the further works, General Checkup of PTRs for healthiness, Attending of minor Oil Leakage complaints, Toping up of oil to the Main & OLTC conservator tanks, Attending the Low Oil Complaints, etc all complaints, Carrying of periodical maintenance of PTRs, Conducting tests periodically as per the norms, Preventive, Breakdown, Predictive & proactive maintenance of PTRs, Conducting pre-Commissioning & Commissioning tests for new & repaired transformers, Replacement of Oil Seals, Silicagel, breathers, Oil cups, PTR Clamps, WTIs, OTIs, PRVs, MOGs, Terminals, Marshalling boxes, probes, Jumpers, Termination of Cables in marshaling box, etc , Measurement of Insulation resistance, DC Resistance, ratios, voltages, Currents, earth resistance of individual earth pits & combined SS earth mat, etc, Checking up of alarms pertains to OT/WT/OLTC/MOG/Bucholtz, Conducting pre commissioning Tests of PTRs when commissioning at existing substations for every month
Supply and Transportation of 1.00HP 10 Stages single phase ISI submersible motor pumpset suitable for 4" Bore well. (Make:Texmo, GRI, KSB, LUBI) at Local Velmal
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks
At Local velmal substation
At Madegaon Substation
At Bhainsa substation
S&F premium make CPVC Pipes of 15.90mm OD Pipe- SDR 13.5 including the cost of pipe, requirednumber of connectors such as elbows, tees,couplers, connectors, solvent cement etc., and labour charges complete including cost and conveyance of all materials to site, all operational,incidental , labour charges, etc. complete for finished item of work as directed by Engineer-in-charge- TBSC-J.IV-02
At Local velmal substation
At Madegaon Substation
At Bhainsa substation
S&F premium make CPVC Pipes of 15.90mm OD Pipe- SDR 13.5 including the cost of pipe, requirednumber of connectors such as elbows, tees,couplers, connectors, solvent cement etc., and labour charges complete including cost and conveyance of all materials to site, all operational,incidental , labour charges, etc. complete for finished item of work as directed by Engineer-in-charge- TBSC-J.IV-02
At Local velmal substation
At Madegaon Substation
At Bhainsa substation
Labour charges for installation, erection, earthing, testing and commissioning of submersible pumpset including fixing of GI pipes valves and specials and all other items including C/C of all materials and earthing etc with a trial run for one week
Provisional Items - For Nirmal District
Supply, transportation and Erection of 33KV HG Fuse Sets with Insulators with Insulatorswith all standard accessories etc., complete with cost and conveyance of all materials
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Supply and erection of approved make 11KV, H.G fuse set with insulation complete with Fuse holders, Fuse barrel with metal fittings, fuse element mounted on M.S. channel with working current 15A capacity complete with cost and conveyance of all materials.
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Supply, transportation and Erection of 33KV Polymer Insulators (B&S)with all standard accessories and metal parts etc., complete with cost and conveyance of all materials
33/11KV substation at Bhainsa
Supply, transportation and Erection of 11KV Polymer Insulators (B&S)with all standard accessories and metal parts etc., complete with cost and conveyance of all materials
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Supply, transportation and Erection of 33KV 800A AB Switch (Double Breaker) with all accessories
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Supply, transportation and Erection of 11KV 800A AB Switch (Conventional) SB AB Switch with post type porcelain insulators with all accessories
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Supply, transportation and Erection of 11KV 400A AB Switch(Conventional) SB AB Switch with post type porcelain insulators with all accessories
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Providing independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange 2.5m long enclosed in C.C/ brick massonry chamber of 450m x 450m x400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through flange with all accessories and labour charges complete, as per IS specifications 732/1982 (Part II)
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Supply and Run of 100mm x 50mm G.I strip (Cuurrent Carrying Capacity 1380A) including cost of all accessories and labour charges etc., complete. (5.36Kgs/1Mtr)
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Suppy and Fixing of 24 V, 40 AH Batteries with Charger with all accessories
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Providing Transformer oil tested as per IS-335 - 1972 (per Ltr)
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Filteration of transformer oil as per ISS specifications filters to die electric strength above 40 KV at site
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Replacement of worn out Pad clamps with Hardware material by new supply and fixing Pad clamps.
33/11KV substation at Bhainsa WTP
33/11KV substation at Madegaon WTP
33/11KV substation at Local velmal
Filteration of transformer oil as per ISS specifications filters to die electric strength above 40 KV at site
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Providing Transformer oil tested as per IS-335 - 1972 (per Ltr)
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Providing and errecting heat shrinkable indoor termination kit for 11 KV HT XLPE insulated armoured cable 70-95 Sqmm 3 core with necessary materials etc., complete. Makes : Raychem / Transeal / M Seal
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Providing and errecting heat shrinkable indoor termination kit for 11 KV HT XLPE insulated armoured cable 120 Sqmm 3 core with necessary materials etc., complete. Makes : Raychem / Transeal / M Seal
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Supply and erection of approved make 11 KV outdoor type gang operated Air Break switch of 400 A capacity with 3 post pin type insulator per phase, mounted in Horizantal / Vertical position with necessary channels on cross arms with adequate length of 'C' class GI pipe for operating handle provided with Lock & Key at suitable height from ground level with necessary clamps.
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Supply and erection of approved make 11 KV outdoor type gang operated Air Break switch of 200 A capacity with 3 post pin type insulator per phase, mounted in Horizantal / Vertical position with necessary channels on cross arms with adequate length of 'C' class GI pipe for operating handle provided with Lock & Key at suitable height from ground level with necessary clamps.
800KVA DTR locations:
Madegoan head works-RWPS-800KVA, Toshiba S.no.2208475
Bhainsa Head works-DTR -1: 800KVA,Make:Toshiba SlNo. 2208497. DTR -2: 800KVA,Make:Toshiba SlNo. 2208500. DTR -3: 800KVA,Make:Toshiba SlNo. 2208494.
Bhainsa intake well-DTR -1: 800KVA,Make:Toshiba SlNo. 2208498 . DTR -2: 800KVA,Make:Toshiba SlNo. 2208493.
500KVA DTR locations:
Madegoan head works-DTR: 500KVA, Toshiba make, s.no.2204116
Gandhinagar WTP-1 Nos 500KVA DTR, Toshiba make, S.No.2204118
315KVA DTR locations:
Gandhinagar IW-1 Nos 315 KVA DTR, Toshiba make, S.No.2208559
Bolsa -DTR 315KVA,Make:Toshiba SlNo. 2208560.
160KVA DTR locations:
SRSP Intake well –Local Velmal-DTR:160KVA, Toshiba make, s.no.2204130
Intake well of RGUKT Basar WTP-160KVA
100KVA DTR locations:
Kubber OHBR-DTR 100KVA,Make:High Power SlNo. 2208560.
Rajura OHBR-DTR 100KVA,Make:Hi-power SlNo. HI-1006292
Supply and erecting porcelain Disc type insulator suitable for 11KV line with suitable hardware on existing cross arms.
Supply and erecting porcelain Pin type insulator suitable for 11KV line with suitable hardware on existing cross arms.
Supply and erecting porcelain Post type insulator suitable for 11KV line with suitable hardware on existing cross arms.
Supply and erection of approved make 11KV, H.G fuse set with insulation complete with Fuse holders, Fuse barrel with metal fittings, fuse element mounted on M.S. channel with working current 15A capacity complete with cost and conveyance of all materials.
Providing independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange 2.5m long enclosed in C.C/ brick massonry chamber of 450m x 450m x400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through flange with all accessories and labour charges complete, as per IS specifications 732/1982 (Part II)
Supply and Run of 100mm x 50mm G.I strip (Current Carrying Capacity 1380A) including cost of all accessories and labour charges etc., complete. (5.36Kgs/1Mtr)(Data No.28.1.28 )
9 KV 10 KA Metal Oxide Lightning Arresters (station type)
At Local velmal substation
At Madegaon Substation
At Bhainsa substation
Nirmal District Total
Essential Items - For Adilabad District
Routine maintenance of transformer in operation covering insulation resistance oil, break down strength. Reconditioning / replacement of silicazel, cleaning of transformer and topping upto oil level if required
800KVA DTR locations:
Babudole GLBR-800KVA,1no. Make:KRK power ltd,1493& DTR
500KVA DTR locations:
ADDAGUTTA, H/O RAMAI(VG),ADILABAD RURAL(M),
Sunkidi-500KVA,Talamadugu(M),Adilabad
Suryanagar OHBR-DTR 500KVA,Make:Toshiba SlNo. 2208819.
315KVA DTR locations:
Dahegaon GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208561.
Jandaguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208812.
Karthwada OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208811.
Daheguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208810.
Testing of Transformer oil for dielectric breakdown strength.
500KVA DTR locations:
ADDAGUTTA, H/O RAMAI(VG),ADILABAD RURAL(M),
Sunkidi-500KVA,Talamadugu(M),Adilabad
Suryanagar OHBR-DTR 500KVA,Make:Toshiba SlNo. 2208819.
800KVA DTR locations:
Babudole GLBR-800KVA,1no. Make:KRK power ltd,1493& DTR
315KVA DTR locations:
Dahegaon GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208561.
Jandaguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208812.
Karthwada OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208811.
Daheguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208810.
Provisional Items - For Adilabad District
Filteration of transformer oil as per ISS specifications filters to die electric strength above 40 KV at site
500KVA DTR locations:
ADDAGUTTA, H/O RAMAI(VG),ADILABAD RURAL(M),
Sunkidi-500KVA,Talamadugu(M),Adilabad
Suryanagar OHBR-DTR 500KVA,Make:Toshiba SlNo. 2208819.
800KVA DTR locations:
Babudole GLBR-800KVA,1no. Make:KRK power ltd,1493& DTR
315KVA DTR locations:
Dahegaon GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208561.
Jandaguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208812.
Karthwada OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208811.
Daheguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208810.
315KVA DTR locations:
Dahegaon GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208561.
Jandaguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208812.
Karthwada OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208811.
Daheguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208810.
Suryanagar OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208819.
Providing Transformer oil tested as per IS-335 - 1972 (per Ltr)
500KVA DTR locations:
ADDAGUTTA, H/O RAMAI(VG),ADILABAD RURAL(M),
Sunkidi-500KVA,Talamadugu(M),Adilabad
Suryanagar OHBR-DTR 500KVA,Make:Toshiba SlNo. 2208819.
800KVA DTR locations:
Babudole GLBR-800KVA,1no. Make:KRK power ltd,1493& DTR
315KVA DTR locations:
Dahegaon GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208561.
Jandaguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208812.
Karthwada OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208811.
Daheguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208810.
Replacing the breather of the DTR/PTR.
500KVA DTR locations:
ADDAGUTTA, H/O RAMAI(VG),ADILABAD RURAL(M),
Sunkidi-500KVA,Talamadugu(M),Adilabad
Suryanagar OHBR-DTR 500KVA,Make:Toshiba SlNo. 2208819.
800KVA DTR locations:
Babudole GLBR-800KVA,1no. Make:KRK power ltd,1493& DTR
315KVA DTR locations:
Dahegaon GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208561.
Jandaguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208812.
Karthwada OHBR-DTR 315KVA,Make:Toshiba SlNo. 2208811.
Daheguda GLBR-DTR 315KVA,Make:Toshiba SlNo. 2208810.
Supply and erection of approved make 11 KV outdoor type gang operated Air Break switch of 200 A capacity with 3 post pin type insulator per phase, mounted in Horizantal / Vertical position with necessary channels on cross arms with adequate length of 'C' class GI pipe for operating handle provided with Lock & Key at suitable height from ground level with necessary clamps.
Supply and erecting porcelain Pin type insulator suitable for 11KV line with suitable hardware on existing cross arms.
Supply and erecting porcelain Post type insulator suitable for 11KV line with suitable hardware on existing cross arms.
Supply and erection of approved make 11KV, H.G fuse set with insulation complete with Fuse holders, Fuse barrel with metal fittings, fuse element mounted on M.S. channel with working current 15A capacity complete with cost and conveyance of all materials.
Providing independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange 2.5m long enclosed in C.C/ brick massonry chamber of 450m x 450m x400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through flange with all accessories and labour charges complete, as per IS specifications 732/1982 (Part II)
Adilabad District Total
Design, Supply, installation, testing & commissioning of Vertical Turbine pump motor set of specified duty parameters & guaranteed efficiency of following MOC with specified capacity horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated speed 1450 RPM along with column and bowl assembly, discharge head, base channel/RSJ etc. complete as per relevant IS. M.O.C.: Impeller & Sealing Rings: CF8M, Bowl & Suction Bell: Cast Steel WCB , Shaft with coupling: SS 410, Column Pipe: M.S. Mechanical Seal (above 30 kW),ERW, , Base Plate: MS, Line Bearing: Thordon type, Suction Strainer: S.S. as per specifications for finished item of work excluding GST , with discharge 3635LPM and head 43.90 Mts for each Pump for Pumping from Intakewell at parevula to Head works at Parevula
Providing independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange 2.5m long enclosed in C.C/ brick massonry chamber of 450m x 450m x 400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through G.I strip of 40 x 6mm x 200mm length with all accessories and labour charges complete, as per IS specifications 732/1982 (Part II) for finished item of work excluding GST
Supply and Run of 25mm x 6mm G.I Strip including cost of all accessories and labour charges etc. complete. (1.18Kgs1Mtr)(Data No. 141527.1.5) for finished item of work excluding GST
Supply and run of 240 Sqmm 3.5 Core XLPE insulated, 1100V grade armoured alluminium cable as per specification confirming to IS:7098 (Part - I) in exsting trench/wall including providing end terimations with glands. lugs , crimping job etc complete for finished item of work for finished item of work excluding GST
Supply and run of 185 Sqmm 3.5 Core XLPE insulated, 1100V grade armoured alluminium cable as per specification confirming to IS:7098 (Part - I) in exsting trench/wall including providing end terimations with glands. lugs , crimping job etc complete for finished item of work excluding GST
Supply installation testing and commissioning of 3 phase and neutral 415V free standing floor mounted MV panel made out of No.14/16 gauge CRCA sheet steel after 7 tank process and painting with powder coating. The panel shall consists of suitable rating TPN with suitable bus bars (with rating of 0.8A/ Sqmm) supported with DMC /SMC barriers and colour coaded with heat shrinkable sleeves. The metering shall be provided as specified. The panel shall have short-circuit with standing capacities of minimum 50KA and consists of switchgear as mentioned below.The panel shall be got manufactured from the manufacturers of CPRI test certificate only. The panel shall be mounting on U channels including supply and fixing including painting with powder coating including internal connections cost and conveyance of all materials & labour charges. Supply of 630A 4 Pole 50KA Air Circuit Breaker Confirms to IS 13947-2, IEC 60947-2 and BS-EN 60947 with Micro processer based having over load, shot circuit and earth fault Protection. Makes : Siemens (Sentron- 3W) / L&T U Power / Schneider Master Pact / ABB Emax / C&S.Winmaster2 / Legrand DMXSupply of 250A 3 Pole MCCB, Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity 36/35 KA with thermal magnetic release Panel Mounted.Supply of 160A 3 Pole MCCB, Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity 25 KA with thermal magnetic release Panel Mounted.Supply of 40-63A 10KA TP MCB, C/D Curve ISI Mark.Supply, installation, testing & commissioning of 415 V Fully automatic Microprocessor based soft starter with built in bypass arrangement for pump control application as per general specification as under: Control Method -Torque Control, Input voltage- 415 V, 3 Phase, Input frequency - 50/ 60 Hz (± 5%), Confirmative to standard - IEC 61947-4- 2UL, CSA, CE, Motor protection - inbuilt Thermal Protection, Starter protection - SC UV, Phase unbalance, Phase failure, EMC Std- IEC 61000-4-2 Level-3 & IEC 61000-4-3-Level-3, Built in communication as per RS 485. Digital Soft starter, 45KWSupply and Run of 40mm x 6mm Alluminium strip (Cuurrent Carrying Capacity 350A) including cost of all accessories and labour charges etc., complete. (0.644Kgs/1Mtr)Supply and Run of 50mm x 10mm Alluminium strip (Cuurrent Carrying Capacity 625A) including cost of all accessories and labour charges etc., complete. (1.35Kgs/1Mtr)Supply and erection of L.T. 3phase Digital multifunction energy meterClass 0.5 RS 485 with LCD display for measuring all the parameters (voltage / Current / Power / frequency / power factor / kw / kwh / KVAR/ KVARH/) on existing box panel board including connections etc., complete.Digital Voltmeter 0-500V AC 96X96 Sqmm 230V AC AE MakeDigital Ammeter 0-5A, /5A AC 96X96 Sqmm 230V AC AE MakeSupply and erection Makes : L&T / C&S / SALZAR / HPL / Siemens Selector switch for Voltmeter / Ammeter on the existing panel including connections etc., complete.Start & Stop push buttonsSupply and erection of LED indicator lamps on the existing box / panel board.Supply and erection of LT current transformer with bar primary 100/5A to 1000 / 5A ratio in the existing box / panel including connections etc., complete.MAKE : KAPPA9A Power Contactor TP AC3Control Transformer 0.415/0.230 2 kVACooling Fan6A 10KA DP MCB C-Curve6A 10KA SP MCB C-Curve32A 10KA DP MCB C-Curve32A 10KA TP MCB C-CurveThermal Overload RelayControl RelaySemi Conductor Fuse Link - Eaton/SieGlass Fuse200A Fuse Base + Link50A Fuse Base + Link20A Fuse Base + LinkSupply and errecting pump protection relay comprising current sensing phase failure and UV+OV relay with dry run and over load protection suitable for 3 phase pumps.Supply and fixing of 8 Stage APFC Relay with connection etc complete.Makes : L&T / Siemens / EPCOS / Schneider / Elmeasure.Supply and fixing of 20 KVAR Rating capacitor duty contactor Makes : L&T / Siemens / MeherSupply and fixing of 10 KVAR Rating capacitor duty contactor Makes : L&T / Siemens / MeherSupply and fixing of 5 KVAR Rating capacitor duty contactor Makes : L&T / Siemens / MeherSupply of MPP type heavy duty capacitor of 20 KVAR 480V operating voltage Makes:L&T/Siemens/Schneider/Epcos.Supply of MPP type heavy duty capacitor of 10 KVAR 480V operating voltage Makes:L&T/Siemens/Schneider/Epcos.Supply of MPP type heavy duty capacitor of 5 KVAR 480V operating voltage makes:L&T/Siemens/Schneider/Epcos.Fabrication, tarnsportation & erection of panel with No.14/16 guage CRCA sheet after 7 tank process including compartments and suitable for fixing above switch gears, Bus bars and metering equipment as per CPRI test certificate etc., complete. (Rate as per 35% on Cost of above material) complete for finished item of work excluding GST
Manufacturesupply delivery erection testing and commissioning of 200mm dia. Dual plate DI check valves PN20 rated confirming to API 5946D and epoxy coated to AWWA C 210 specification complete for finished item of work excluding GST
Manufacture, Supply and delivery of DI DF Sluice Valves of PN 16 with body bonnet of ductile cast iron of grade GGG40 SG 40012 or equivalent grade I the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS1538. 200 mm Dia-Delivery side complete for finished item of work excluding GST
Manufacture Supply and Delivery erection testing and commissioning of MS Dismantling Joints with both side flange end suitable for installation in between flanged end pipes. Thickness as per IS 7322 of pressure rating 16 Kgcm2 of size 200 mm Dia complete for finished item of work excluding GST
Manufacture supply laying testing & Commissioning of MS pipes of 200 mm dia of pressure rating 16 Kgcm2 conforming to IS 3589 and 1239 including fittings like elbows tees flanges tapers etc. completeincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Wall Thickness 8mm (Minimum) complete for finished item of work excluding GST
Manufacture Supply erection testing and joining at site of works and testing of MS Manifold of 500mm dia. including jointing of individual pump riser to common header complete conforming to detailed specificationincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Including connection between manifold and delivery pipe complete for finished item of work excluding GST Wall Thickness 8 mm
Kinetic Air Release Valve Manufacture Supplydeliverylaying and Jointing of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 40012 or equivalent grade as per I.S.3896part21985 and subsequent revisions on pipe line including supply of Air valve PN16 Grade and with isolated DI Sluice Valve of PN16 DI Specials to suit the pressure class of pipe Valve should be electrostatically powder coated from inside & outside. Size 100 mm dia. complete for finished item of work excluding GST
Design, Supply, installation, testing & commissioning of horizontal split casing centrifugal pump motor set of specified duty parameters & guaranteed efficiency of following MOC with specified capacity, horizontal foot mounted TEFC squirrel cage induction motor (with minimum IE-3 efficiency class), working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS. M.O.C.: Impeller & Wearing Rings: CF8M, Casing: Cast Steel WCB , Shaft: SS 410, Shaft Sleeve: SS 410, Mechanical Seal (Above 30 kW), Base Frame: MS, Line Bearing: Thordon type, Suction Strainer: S.S. as per specifications with 5 years O&M. The prices are excluding GST .with discharge 3461 LPM and head 50.0 Mts for Pumping from parevula head works to Parevula OHBR.complete for finished item of work excluding GST
Supply, Testing & Commissioning of End Suction Back Pull-out centrifugal pump motor set with base frame of specified duty parameters & guaranteed efficiency of following MOC with specified capacity horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS. M.O.C.: Impeller & Wearing Rings: CF8M, Casing: Cast Steel WCB , Shaft: SS 410, Shaft Sleeve: SS 410, Mechanical Seal (above 30 kW), Base Frame: MS., Suction Strainer: S.S.with Head 62.50 mts and discharge 692 Lpm for Pumping from parevula head works to Gaddampally Sump.complete for finished item of work excluding GST
Supply, installation, testing & commissioning approved make coupled vacuum pump set with horizontal foot mounted TEFC squirrel cage motor having under mentioned capacity working on 3 phase, 50 ± 3% Hz, 415 V ± 10%, with base plate, DOL starter, cable, GI medium duty suction pipes 12 meters long, specials, valve, PVC tank of 250 litres capacity etc. complete. Material of Constructions: Impeller- SS/CF8M, Shaft: SS410, Casing: CIFG260 with 3 HP. complete for finished item of work excluding GST
Providing independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange 2.5m long enclosed in C.C/ brick massonry chamber of 450m x 450m x 400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through G.I strip of 40 x 6mm x 200mm length with all accessories and labour charges complete, as per IS specifications 732/1982 (Part II).,complete for finished item of work excluding GST
Supply and Run of 25mm x 6mm G.I Strip including cost of all accessories and labour charges etc. complete. (1.18Kgs1Mtr)(Data No. 141527.1.5) complete for finished item of work excluding GST
Supply and run of 1 of 240Sqmm 3.5 Core XLPE insulated, 1100V grade armoured alluminium cable as per specification confirming to IS:7098 (Part - I) in exsting trench/wall including providing end terimations with glands. lugs , crimping job etc complete for finished item of work.
Supply and run of 50Sqmm 3.5 Core XLPE insulated, 1100V grade armoured alluminium cable as per specification confirming to IS:7098 (Part - I) in exsting trench/wall including providing end terimations with glands. lugs , crimping job etc complete for finished item of work.
Supply installation testing and commissioning of 3 phase and neutral 415V free standing floor mounted MV panel made out of No.14/16 gauge CRCA sheet steel after 7 tank process and painting with powder coating. The panel shall consists of suitable rating TPN with suitable bus bars (with rating of 0.8A/ Sqmm) supported with DMC /SMC barriers and colour coaded with heat shrinkable sleeves. The metering shall be provided as specified. The panel shall have short-circuit with standing capacities of minimum 50KA and consists of switchgear as mentioned below.The panel shall be got manufactured from the manufacturers of CPRI test certificate only. The panel shall be mounting on U channels including supply and fixing including painting with powder coating including internal connections cost and conveyance of all materials & labour charges. Supply of 630A 4 Pole 50KA Air Circuit Breaker Confirms to IS 13947-2, IEC 60947-2 and BS-EN 60947 with Micro processer based having over load, shot circuit and earth fault Protection. Makes : Siemens (Sentron- 3W) / L&T U Power / Schneider Master Pact / ABB Emax / C&S.Winmaster2 / Legrand DMXSupply of 160A 3 Pole MCCB, Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity 25 KA with thermal magnetic release Panel Mounted.Supply of 63A 3 Pole MCCB, Adjustable, Confirms to IS/IEC 60947-2 having Breaking Capacity 16 KA with thermal magnetic release Panel Mounted.Supply of 40-63A 10KA TP MCB, C/D Curve ISI Mark.Supply, installation, testing & commissioning of 415 V Fully automatic Microprocessor based soft starter with built in bypass arrangement for pump control application as per general specification as under: Control Method -Torque Control, Input voltage- 415 V, 3 Phase, Input frequency - 50/ 60 Hz (± 5%), Confirmative to standard - IEC 61947-4- 2UL, CSA, CE, Motor protection - inbuilt Thermal Protection, Starter protection - SC UV, Phase unbalance, Phase failure, EMC Std- IEC 61000-4-2 Level-3 & IEC 61000-4-3-Level-3, Built in communication as per RS 485. Digital Soft starter, 45KWSupply & Fixing of Star Delta Starter 415V, Three phase, 50Hz. With SS enclouser comprising of contactor with bi-metalic relay with necessary push buttons, etc., complete -11KWSupply and Run of 40mm x 6mm Alluminium strip (Cuurrent Carrying Capacity 350A) including cost of all accessories and labour charges etc., complete. (0.644Kgs/1Mtr)Supply and Run of 50mm x 10mm Alluminium strip (Cuurrent Carrying Capacity 625A) including cost of all accessories and labour charges etc., complete. (1.35Kgs/1Mtr)Supply and erection of L.T. 3phase Digital multifunction energy meterClass 0.5 RS 485 with LCD display for measuring all the parameters (voltage / Current / Power / frequency / power factor / kw / kwh / KVAR/ KVARH/) on existing box panel board including connections etc., complete.Digital Voltmeter 0-500V AC 96X96 Sqmm 230V AC AE MakeDigital Ammeter 0-5A, /5A AC 96X96 Sqmm 230V AC AE MakeSupply and erection Makes : L&T / C&S / SALZAR / HPL / Siemens Selector switch for Voltmeter / Ammeter on the existing panel including connections etc., complete.Start & Stop push buttonsSupply and erection of LED indicator lamps on the existing box / panel board.Supply and erection of LT current transformer with bar primary 100/5A to 1000 / 5A ratio in the existing box / panel including connections etc., complete.MAKE : KAPPA9A Power Contactor TP AC3Control Transformer 0.415/0.230 2 kVACooling Fan6A 10KA DP MCB C-Curve6A 10KA SP MCB C-Curve32A 10KA DP MCB C-Curve32A 10KA TP MCB C-CurveThermal Overload RelayControl RelaySemi Conductor Fuse Link - Eaton/SieGlass Fuse200A Fuse Base + Link50A Fuse Base + Link20A Fuse Base + LinkSupply and errecting pump protection relay comprising current sensing phase failure and UV+OV relay with dry run and over load protection suitable for 3 phase pumps.Supply and fixing of 12 Stage APFC Relay with connection etc complete.Makes : L&T / Siemens / EPCOS / Schneider / ElmeasureSupply and fixing of 50 KVAR Rating capacitor duty contactor Makes : L&T / Siemens / MeherSupply of MPP type heavy duty capacitor of 45 KVAR 480V operating voltage Makes:L&T/Siemens/Schneider/Epcos.Fabrication, tarnsportation & erection of panel with No.14/16 guage CRCA sheet after 7 tank process including compartments and suitable for fixing above switch gears, Bus bars and metering equipment as per CPRI test certificate etc., complete. complete for finished item of work excluding GST
Manufacturesupply delivery erection testing and commissioning of 150mm dia. Dual plate DI check valves PN20 rated confirming to API 5946D and epoxy coated to AWWA C 210 specification complete for finished item of work excluding GST
Manufacturesupply delivery erection testing and commissioning of 100mm dia. Dual plate DI check valves PN20 rated confirming to API 5946D and epoxy coated to AWWA C 210 specification complete for finished item of work excluding GST
Manufacture Supply and Delivery erection testing and commissioning of MS Dismantling Joints with both side flange end suitable for installation in between flanged end pipes. Thickness as per IS 7322 of pressure rating 16 Kgcm2 of size 150 mm Dia, complete for finished item of work excluding GST
Manufacture Supply and Delivery erection testing and commissioning of MS Dismantling Joints with both side flange end suitable for installation in between flanged end pipes. Thickness as per IS 7322 of pressure rating 16 Kgcm2 of size 100 mm Dia, complete for finished item of work excluding GST
Manufacture, Supply and delivery of DI DF Sluice Valves of PN 16 with body bonnet of ductile cast iron of grade GGG40 SG 40012 or equivalent grade I the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS1538. 200mm Dia- Suction side, complete for finished item of work excluding GST
Manufacture, Supply and delivery of DI DF Sluice Valves of PN 16 with body bonnet of ductile cast iron of grade GGG40 SG 40012 or equivalent grade I the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS1538. 150mm Dia- Delivery side, complete for finished item of work excluding GST
Manufacture, Supply and delivery of DI DF Sluice Valves of PN 16 with body bonnet of ductile cast iron of grade GGG40 SG 40012 or equivalent grade I the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS1538. 100mm Dia- Suction side & Delivery side, complete for finished item of work excluding GST
Manufacture supply laying testing & Commissioning of MS pipes of 200 mm dia of pressure rating 16 Kgcm2 conforming to IS 3589 and 1239 including fittings like elbows tees flanges tapers etc. completeincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Wall Thickness 8mm (Minimum), complete for finished item of work excluding GST
Manufacture supply laying testing & Commissioning of MS pipes of 150 mm dia of pressure rating 16 Kgcm2 conforming to IS 3589 and 1239 including fittings like elbows tees flanges tapers etc. completeincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Wall Thickness 8mm (Minimum), complete for finished item of work excluding GST
Manufacture supply laying testing & Commissioning of MS pipes of 100 mm dia of pressure rating 16 Kgcm2 conforming to IS 3589 and 1239 including fittings like elbows tees flanges tapers etc. completeincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Wall Thickness 6mm (Minimum), complete for finished item of work excluding GST
Manufacture Supply erection testing and joining at site of works and testing of MS Manifold of 400mm dia. including jointing of individual pump riser to common header complete conforming to detailed specificationincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Including connection between manifold and delivery pipe Wall Thickness 8 mm complete for finished item of work excluding GST
Manufacture Supply erection testing and joining at site of works and testing of MS Manifold of 250mm dia. including jointing of individual pump riser to common header complete conforming to detailed specificationincluding providing & applying of epoxy coating ( 2 coat) as per the drawing Including connection between manifold and delivery pipe Wall Thickness 8 mm complete for finished item of work excluding GST
Kinetic Air Release Valve Manufacture Supplydeliverylaying and Jointing of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 40012 or equivalent grade as per I.S.3896part21985 and subsequent revisions on pipe line including supply of Air valve PN16 Grade and with isolated DI Sluice Valve of PN16 DI Specials to suit the pressure class of pipe Valve should be electrostatically powder coated from inside & outside. Size 50 mm dia.
Kinetic Air Release Valve Manufacture Supplydeliverylaying and Jointing of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 40012 or equivalent grade as per I.S.3896part21985 and subsequent revisions on pipe line including supply of Air valve PN16 Grade and with isolated DI Sluice Valve of PN16 DI Specials to suit the pressure class of pipe Valve should be electrostatically powder coated from inside & outside. Size 100 mm dia.complete for finished item of work excluding GST
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
BOQ Transformer Yard O&M.xlsx
TENDER_DOCUMENT • 2.14 MB
TY O&M 26-27 Bid document.docx
TENDER_DOCUMENT • 0.39 MB
~$BOQ Transformer Yard O&M.xlsx
TENDER_DOCUMENT • 0.00 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .