Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹10.8 LAccepted-Finance KUNZER KUNZER TANGMARG BARAMULLA JAMMU KASHMIR 193401 | BUDGAM | JAMMU AND KASHMIR | 193401 | 1 | Accepted-Finance FIRST LOWEST BIDDER | |
| 2 | 2₹13.3 L+₹2.6 L (23.7%)Rejected-Finance | 2 | Rejected-Finance 2ND LOWEST BIDDER | |
| 3 | 3₹14.7 L+₹3.9 L (36.6%)Rejected-Finance | 3 | Rejected-Finance 3RD LOWEST BIDDER | |
| 4 | 4₹15.7 L+₹4.9 L (45.5%)Rejected-Finance | 4 | Rejected-Finance 4TH LOWEST BIDDER |
Tender Value
₹17.8 L
EMD Value
₹35,502
Closing Date
29 Nov 2024, 2:00 pmClosed
EXECUTIVE ENGINEER STD SOPORE
EXECUTIVE ENGINEER STD SOPORE
Augmentation of 4 MVA Power Transformer of Receiving Station Dobiwan to 6.3 MVA under Capex Budget 2024-25
2024_PDD_264005_1
STDS/15 of 2024-25
Open Tender
Electrical Works
Turn-key
90 days
STD SOPORE
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,000
Yes
EXECUTIVE ENGINEER STD SOPORE
₹35,502
Yes
5 Dec 2024
9 Nov 2024
30 Nov 2024
9 Nov 2024
29 Nov 2024
12 Nov 2024
9 Nov 2024 - 12 Nov 2024
Amount
Shifting of 6.3 MVA Power Transformer from ECSD Pampore to Receiving Station Dobiwan ( The job includes Loading / Carriage upto site/ Unloading /Dragging /Installation, Testing and Commissioning of Power Transfomer at site including insurance during transit (Complete Job)( Power Transformer to be provided by the Department)
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 KV Current Transformer (33 KV, 1Φ, 2 Ratio 3 Core, Outdoor Type ; 300-150/5-5A) of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less (1 No. per Φ) of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 KV VCB (36 kV, 1250A, 26.2 kA, Outdoor Type) of reputed make including suitable GI stand as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 33 KV C&R Panel along with O/C, E/F ,REF and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of G.I Pipe of Dia 150mm, 5.9 mm Thick 3 m long with G.I Base Plate 8 mm Thick as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing, Laying ,Stringing, Tensioning & Binding of ACSR Conductor, (100mm2 ACSR Conductor) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GT Clamps/ CT Clamps Al. Make (800 Amp) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Fabrication, Testing & Fixing of Galvanised Steel Structures of various sizes as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Galvanised Nuts & Bolts as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator without Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Fabrication, Testing & Fixing of GI Flat for earthing (50x6) mm as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip (50x6)mm as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
Supply,Carriage upto site (including Loading/Unloading), Laying & Testing of Reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size for construction of foundations including shutring and 15mm plastering (1:6) as per approved drawings/standards
Providing & Painting of Welding Joints with Red Oxide (reputed make) as per approved standards as per approved standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Lugs, Ferrules etc.
KAPH TECH CONSULTANCY (P) Ltd. (BID ID -2260757)
KHAN ELECTRICAL CONSTRUCTION AND SUPPLIERS (BID ID -2263205)
Barraq Enterprises (BID ID -2257269)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .