| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.3 LAccepted-AOC | L1 | Accepted-AOC OK | |
| 2 | L2₹23.4 L+₹1.5 L (6.70%)Rejected-AOC | L2 | Rejected-AOC OK | |
| 3 | L3₹24.7 L+₹2.7 L (12.3%)Rejected-AOC | L3 | Rejected-AOC OK | |
| 4 | L4₹26.0 L+₹4.0 L (18.3%)Rejected-AOC | L4 | Rejected-AOC OK | |
| 5 | L5₹28.9 L+₹7.0 L (31.7%)Rejected-AOC 1ST FLOOR H NO 165 GALI NO 16 S B S COLONY KARAWAL NAGAR DELHI EAST DELHI DELHI 110094 | NORTH EAST DELHI | DELHI | 110094 | L5 | Rejected-AOC OK |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
8 Apr 2021, 6:00 pmClosed
GE WEST BAREILLY
GE WEST BAREILLY
REPAIR AND REPLACEMENT OF RUNWAY LIGHT TAXI TRACK DISPERSAL LIGHT APPROACH LIGHT AND CONNECTED WORKS UNDER GE WEST BAREILLY
2021_MES_428963_1
8917/C/E8
Open Tender
Civil Works
Item Rate
180 days
GE WEST BAREILLY
SCANNED COPY OF ENLISTMENT LETTER IN MES IN RELEVANT CLASS CATEGORYSCANNED COPY OF APPLICATION ON LETTER HEAD OF FIRM
SCAN COPY OF DD OF RS 500.00 IN FAVOUR OF GE WEST BAREILLY FROM ANY NATIONALISED OR SCHEDULED BANK SCANNED COPY OF REGISTRATION
6 documents required · 6 mandatory
₹500
Yes
GE WEST BAREILLY
₹60,000
Yes
3 Jun 2021
8 Mar 2021
13 Apr 2021
8 Mar 2021
8 Apr 2021
24 Mar 2021
8 Mar 2021 - 23 Mar 2021
Amount
Periodical maintenance of complete runway lighting system and repair by dismantling of air field/taxi track light fitting , AFL cable & connection of any description and segregatting to servicable and unserviceable parts and make it in serviceable condition by deploying person who have knowledge about Air field light system, Constant current regulator and Beacon light compelte all as specified and directed. Note -(i) Replacement of spare parts will be measure and paid separately under respective item of schedule. (ii) T&P and HT insulation tape required for repair will be arrange by the contractor with his own cost. (iii) Day of maintanence/ repairs intimate by the Dept prior to flying twice in a month. (iv) Failed to maintaining Runway light system for flying will be penalty of Rs 2000/- borne per job by the contractor.
S&F bipin halogen lamp 200 watt 6.6 Amp 50 HZ all as directed by Engr In Charge.
S&F bipin halogen lamp 45 watt 6.6 Amp 50 HZ all as directed by Engr In Charge.
S&F Bipin halogen holder for 200/45 watt lamps complete with chord complete all as specified and directed
S&F isolating transformer 200W, 6.6 Amp, 50 HZ all as directed by Engr In Charge. Make- Bildal
S&F isolating transformer 45W, 6.6 Amp, 50 HZ all as directed by Engr In Charge.
S&F Protection Glass cover with washer for 200 watt runway light (Clear white) complete all as specified and directed.
S&F Protection Glass cover with washer for 200 watt runway light (Yellow) complete all as specified and directed.
S & F Protection Glass cover with washer for 45 watt Taxi track light (Blue) complete all as specified and directed.
Servicing, Oiling, greasing and testing of Beacon light all as specified and directed by Engr-in-charge.
S&F 6 Sqmm AFL cable connector (male female) kit complete all as specified and directed.
S&F in repiar LED aviation obstruction light 12 Watt with fitting complete and making electric connections.. Note :- Obstruction lights are to be replaced/fixed at Hangers/ATC
S& F in repair LED Bollard light 8 watt in cylindrical shape with opal acrylic diffuser and IP65 protection, all as per directed by Engr In Charge
S & F in repair light fitting hanging at roof of hanger with GI Tubing light grade Size 25/20 mm apporox 3.5 mtr long ENDURA HIGHBRITE Energy saving environmental friendly, and robust open type vertical Highbay 150 WATT LED luminaire with high power COB LED. Lamp type 150W LED 6500K Make : Havells code No LHELAWUDPC5K150.
Supply and fix in repair rectangular flood light luminaire 120W LED fitting with innovative thermal management with IP66 protection complete all as specified and directed.
S&F in repair decorative LED post top lanterns with diffuser and painted spun aluminium deflector 40/35 watt LED fitting with IP66 protection fixing the fitting on steel pole/brick pillar and making good the disturbed surfaces all as directed at site by Enge-in-Charge.
S&F in replacement PVC insulated and PVC round sheathed , copper conductor (flexible) industrial cable, 2.5 Sqmm 2 core, 1100 volts conforming to IS: 694 - Note :- Cable to be replaced/fixed at Hangers/ATC//OH water tank/ Search Tower.
Excavating in trenches exc. 1.5 mtr wide and not exc.1.5 M wide for foundation for fixing pole/stay assembly and laying and taking out cables etc in soft/loose soil all as specified and directed.
Removing excavated material/soil to a distance not exc 50M and above the starting point all as specifed and directed
Retruning filling including spreading, levelling watering and well ramming in layers not exceeding 2.5 CM in any type of soil all as specified and directed.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified.
Material and labour for Brick protection with sub class 'B' bricks old size, laid dry, flat over cable, perpendicular across the cable in trenches complete all as specified and directed.
All as per srl item 22 here-in-before but using old bricks obtained under excavation
Dismantaling and taking out old unsv electric cables and taking out old bricks and stacking complete bricks outside for re-use.
Supply and laying in repair LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoure, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 core.
do- but 95 Sqmm 3.5 Core
do- but 50 Sqmm 3.5 Core
do- but 35 Sqmm 3.5 Core
do- but 25 Sqmm 4 Core
do- but 70 Sqmm 3.5 Core
S&F in repair HT tropodome PVC insulated sheathed, AFL cable 6.6 Amps 5000 volts, with copper conductor 16sqmm multistranded complete all as specified and directed.
M&L in repair for boring of holes under road /pavement/hard standing or any other situation by mannual means for 80/50mm bore for crossing the cable and making good both the ends all as specified and directed at site. Note :- GI pipe shall be measure and paid separately under respective item.
S&F in repair G I tube 80mm bore light grade galvanised with all fittings and fixed complete for road crossing /on wall/floor and crossing culvert or laid in floor.
M&L in repair for MS Cage for protection for Run way light and Taxi light, made out from steel framed bracket, nosing to steps including embeding in concrete and screwing etc. posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire,wire mesh etc, flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc.and similar work conforming to Fe-290 Gde E-165, as per sample all as directed by Engr In Charge.
Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 mm indoor/Outdoor type all as directed by Engr In Charge.
Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70 to 150 sqmm,Indoor/Outdoor type all as directed by Engr In Charge.
M&L Scraping of old paint from the steel tubular pole with out removing accessories and preparation of surfaces for repainting . Repainting the pole with one coat of alternative White and Red strips of 30 cm each upto 1.5 mtr height using synthetic enamel paint including numbering of pole by lettring height 40mm of black paint on 180mm black bordered luminious yellow circle. Repainting the remaining pole and clamps GI bkt etc above 1.5 mtr height by applying one coat of synthetic enamel aluminium paint all as required at site or directed.
Looping /prooning of tree branches upto the extend to obtain clearance all around the LT OH lines conductor upto 3 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as specified and directed. Note : (a) The tree branches etc will be left as as it is and will not be carried away by the contractor / DEL as wood belongs to CEO/DEO and they will be responsible to lift the wood. (b) Prooning of all tree branches in one tree shall be measured as one job. (c) Contractor will employ sufficient labour to complete the job with in time as required. (d) Contractor will be responsible for any type of mishapening / accident while proning the trees. (e) Contractor supervisor will take proper shut down from the MES installations before starting the work and clear it before resuming power supply. However full assistance will be provided by MES Staff. (f) The contractor will provide proper tools and safety devices to his staff for prooning of trees.
M&L in repair Earthing complete with galvanized steel plate electrode 60cm x 60cm x 6mm thick buried directly in ground earth pit not less than 2.25 meter deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead GI strip 32x6mm dia by means of bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to continuous earth wire/lead on DG set/ LT panel board. all as specified and testing on completion, including provision of earth wire protected by 15 mm dia GI light grade protection pipe from test point to main board and 40mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as directed at site.
Dismantling and taking down of street light of any cap any size any make from the pole all as specified and dierected
Supply and fix in repair energy saving and environemntal friendly long life versatile pressure die-cast aluminium IP-65 roadway luminaire 60 W LED fitting with high power LEDs light source and electronic driver .Make C&S, Havells
Re-stretching of existing ACSR conductor and earth wire including cradles of any description any size and shape and in new position as in LT/HT over head lines, on existing poles including opening of connections and binding wires, Restringing and tightening of conductors/earth wires in position, removing sag, binding to insulators with new aluminium wires, making and connecting jumpers connections etc including commsiiioning and testing complete all as specified and directed. The quoted rates, shall deemed to be included the following provisions also :- (a) Seting/adjusting etc in position of cradles (b) Adjusting and tightning of stay assembly wherever required (c) Trimming/cutting of all trees barnches upto 03M distance from nearest conductors/earth wire as directed at site. Note: one RM length will be measured for 03 phase and one neutral one street light and one earth wire.
Dismantling earth wire of any type and size all as specified and directed
M&L in repair for 8 SWG GI continuous earth wire of size 3.15 mm or 4.00 dia for cradles, gurading and earth continuity on LT OH pole including suitable, binding wires etc compelte all as specifeid and directed
Dismantling of ACSR conductors of any type and size all as specified and directed
M&L in repair aluminium conductor steel reinforcd (ACSR) of any size over head conductor on poles including stringing, tightening binding to insulators with aluminium wire making and connecting commissioning and testing compelte all as specified and directed.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts, in any hape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint.
Dismantling of cross arms of MS channel or angle sections etc complete and setting aside for re-use with in 50 m
Supply and fix in repair shackle type insulator, porcelain, white brown, or green insulator of size 100x115mm (Height 100 mm and 115 mm dia) with section strip 31/5 mm and 14 mm bolt complete all as specified and directed.
Supply & fix repair 1100 volts grade heavy duty cable PVC insulated aluminum conductor screenedserved with inner sheathing of PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4mm GI suspension wire , one twin core cables flat or circular of size 10 Sqmm.
S&F in repair Off load change over switch 200 Amp 4pole 415 Volt, Make- C&S /L&T and Equavalent Approved
Supply and fix in repair energy saving and environemntal friendly long life versatile pressure die-cast aluminium IP-65 roadway luminaire 72 W LED fitting with high power LEDs light source and electronic driver . Make C&S/Crompton/Surya
S&F in repair Run way light fitting 200 watt including lamp, 6.6Amp, Complete with outer lens, inner lens/filters, base plate rubber gasket, lamp, lamp holder isolating transformer etc complete all as specified and directed Make AMA ALN/Metro or equivalent
S&F in repair Taxi way light fittings 45 watt including lamp, 6.6Amp, Complete with outer lens, inner lens/filters, base plate rubber gasket, lamp, lamp holder isolating transformer etc complete all as specified and directed Make AMA ALN/Metro or equivalent
S&F in repair Approach light fittings 200 watt including lamp, 6.6Amp, Complete with outer lens, inner lens/filters, base plate rubber gasket, lamp, lamp holder isolating transformer etc complete all as specified and directed Make AMA ALN/Metro or equivalent
S&F in repair bulk head fittings for landing T with 100W warm white lamp,holder with glass top cover and including connecting up with twin core twisted flexible copper conductor cable with suitable size of 230 volt 50 Hz complete all as specified and directed.
Taking down from pole bracket non functional LED light fittings & replacing of defective parts, refixing the LED fittings back on pole bracket including fixing of 6 sqmm 2 core PVC Aluminum conductor (as required at site), and testing complete all as specified and directed by Engineer-in-Charge. Make : Crompton/Bajaj/Philips/Havells (Spare parts measured and paid separately).
(a) S&F LED street light driver up to hpf 1500 ma suitable for existing LED light as per make & wattage.
(b) S&F LED Street light plate for existing LED light as per make & wattage.
(c ) S&F LED Street light Housing for existing LED light as per make & wattage
S & F in replacement MCCB of following sizes existing make/model and type alongwith spreader terminal with adjustable thermal setting including lugs/thimbles of suitable size in existing panels complete all as specified and directed by Engr-in-Charge. Note : Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. (a) MCCB 400 Amps 4 pole 50 Hz 415 V, 36 KA
(b) MCCB 250 Amps 4 pole 50 Hz 415 V, 36 KA
(c) MCCB 200 Amps 4 pole 50 Hz 415 V, 36 KA
(d) MCCB 125 Amps 4 pole 50 Hz 415 V, 16 KA
(e) MCCB 100 Amps 4 pole 50 Hz 415 V, 16 KA
Supply & installation commissioning and testing cubical type LT panel factory made out door type structure fabricated from 3.15 mm thick CRCA sheet compartmentalized design not less than 1.5x1.4x0.7 mtr including mild steel channel frame of ISMC 75 at the base of panel only for grouting purpose, and grouted in PCC 1:2:4 type B-1 using 20mm graded stone aggregate. The panel shall be dust & vermin proof by providing good quality gasket on doors removal covers, gland plates etc. The sheet metal work of the panel shall be painted, with two coats of synthetic enameled paint over a coat of red oxide primer complete Including all internal connection with aluminum bus bar strips 1100 volts grade of suitable ampere rating. The panel shutter / doors shall be provided with detatchable & flush type hinges including flush cylindrical locks. Provision for cable entry shall be from either side. All joints and connection shall be done by galvanised or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided and complete with the following accessories:-
Incoming :-
(a) Bus bar chamber comprising of 4 Nos aluminium strip bus bars of adequate length, air insulated and PVC sheathed capacity 600 amps rating with color coding.And mounted on porcelain insulators.
(b) MCCB 400 Amps rating 4 pole equipped with service power micro processor based protection release with short circuit over load and earth fault protection and breaking capacity not less than 36KA -01 Nos
(e) Phase Indicator lamp assy RYB - 01 Set.
(f) CT of Ratio 400/5 - 01 Set
Out going-:
(a) MCCB, 4 pole 415 Volt - 250 Amps, 36 KA. Thermal release current fixed type 70% to 100% magnetic setting 5 to 10 times - 02 Nos for out going.
(b) MCCB, 4 pole 415 Volt - 50Hz, 100 Amps, 16 KA. Thermal release current fixed type 70% to 100% magnetic setting 5 to 10 times - 02
(c) MCCB, 4 pole15 Volt - 50Hz, 63 Amps, 16 KA. Thermal release current fixed type 70% to 100% magnetic setting 5 to 10 times - 02
Notes:- 1.The time limit for attending the job/complaints complaints within 24 hour. 2. In case the contracts fails to attend/rectify the defects within the above time limit, penalty will the imposed as under:- (a) Rs 500/- per day per complaints for first seven days after that Rs 1000/- per day per complaint. 3. The contractor or his authorised representative shall report to the Engineer-in-charge or concered JE at 0900 hour daily on all working days to receive order/instructions of the work.
LEEJA ENTERPRISES
sunder and company
M/S HINA ELECTRICALS
R. S. Associates
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .