| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.0 LAccepted-AOC SOBHA ELECTRIC CHANGANASERY KOTTAYAM | L1 | Accepted-AOC being first lowest | |
| 2 | L2₹4.1 L+₹16,130 (4.05%)Rejected-AOC KARAKKATTIL CHENGARA PATTIMATTOM PO LSGD THRIKKAKARA MUNICIPALITY ERNAKULAM DISTRICT KERALA | THRISSUR | KERALA | 680667 | L2 | Rejected-AOC Being second lowest | |
| 3 | L3₹4.2 L+₹17,790 (4.47%)Rejected-AOC 6 573D BHASKARA BUILDING NADAKKAVU P O UDAYAMPEROOR ERNAKULAM KERALA 682307 | ERNAKULAM | KERALA | 682307 | L3 | Rejected-AOC Being third lowest | |
| 4 | L4₹4.3 L+₹31,915 (8.02%)Rejected-Finance VELLAPLACKAL HOUSE VARANDARAPPILLY PO THRISSUR 680303 | THRISSUR | THRISSUR | KERALA | 680303 | L4 | Rejected-Finance Being fourth lowest | |
| 5 | Rejected-Technical | - | Rejected-Technical All technical documents submitted in online verified and not satisfied as per tender condition |
Tender Value
₹4.8 L
EMD Value
₹12,100
Closing Date
21 Jun 2024, 5:00 pmClosed
The Managing Director
Kerala State Warehousing Corporation, Head Office Ernakulam, P.B.No.1727, Warehousing Corporation Road, Kochi-682016
Electrification Work for Providing Exhaust Fans and Rewiring of Godown at State Warehouse Wadakkanchery in Thrissur District.
2024_KSWC_674277_1
KSWC/Cnstn/Ele/SW/Wdky/24-25
Open Tender
Electrical Works
Item Rate
90 days
State Warehouse Wadakkanchery in Thrissur District
Please refer Tender documents
9 documents required · 9 mandatory
₹1,180
₹12,100
Yes
4 Jan 2025
5 Jun 2024
24 Jun 2024
5 Jun 2024
21 Jun 2024
5 Jun 2024
5 Jun 2024 - 21 Jun 2024
Amount
Electrical
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group B
Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 6.00 sq mm
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
Supply ,installation ,testing and commissioning of 450mm 18 inch sweep heavy duty ,1400 rpm ,230 v ,410w ,4 nos blades and metal frame ,single phase exhaust fan
1x20 W LED box type tube fitting .The fittings shall be made from CRCA MS sheet of minimum thickness 0.50mm nominal thickness inside & outside (including LED Tube)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch connection etc. as required. (For light plugs to be used in non residentialbuildings).
20 W, 2000 lumen LED, IP 65 street light fitting with aluminium housing, stove enameled CRCA sheet steel reflector cover, acrylic cover complete with THD <10%, power factor >0.98, RoHS compliant, duly wired up for use on 230 V AC supply
Supplying and fixing Wall mounting fan (400 mm sweep Wall Mounting fan MR1193)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4 + 12), Double door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and netural
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator6 way, Double door
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Supply and fixing meter board of size 650X350X250 of Syntex type suitable for providing 3 Phase meter board and CT
AJAS K P
BPE BHARATH POWER ENGINEERS PVT LTD
BINSON JOSEPH
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .