SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF TRANSFORMERS AND ALLIED INFRASTRUCTURE
2026_OKIH_846087_2
RS-013(7)/TRANSFORMER
Open Tender
Equipments
Item Rate
Kasaragod
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹25,000
Yes
23 Apr 2026
23 Apr 2026
10 Aug 2026
23 Apr 2026
7 Aug 2026
23 Apr 2026
Transformner 02 Supply of 400 KVA outdoor type unitized substation (USS) comprising of cast resin Transformer with 630A, 4pole on LT. side as per technical details furnished below. Transformer portion consists of 400kVA 11kV/433V outdoor cast resin dry type(AN) transformer (copper wound) having a continuous rating for 11kV/433V 3 phase, vector DYN-11 with off load tap changing from +5% to -10% in step of 2.5. Transformer should have cable end box on HV side and LV side with all accessories, complete as required as per State electricity board and IE rules specifications. The class of winding insulation shall be correspond to class F. The transformer shall confirm to IS 2067/77, 11171/1985 with latest amendment etc. Transformer losses shall be as per ECBC 2017 (with amendments up to 2020). The LT portion shall be provided with 1No 4Pole 630A 50Hz 36kA microprocessor based MCCB with inbuilt earth fault release, shunt/UV coil, adjustable setting range of 50–100%, rotary handle, and spreader links. A low-set earth-fault relay shall be provided LT side, and CT of suitable ratio with accuracy class 5P10 shall be provided at the neutral earthing point. All inter connection from transformer to LT breaker shall be given using electrolytic copper bus bar insulated with heat shrink and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP standards for outdoor installation and shall be powder coated over suitable primer after seven tank processing.
Transformner 03 Supply of 315 KVA outdoor type unitized substation (USS) comprising of cast resin Transformer with 500A, 4pole on LT. side as per technical details furnished below. Transformer portion consists of 315kVA 11kV/433V outdoor cast resin dry type(AN) transformer (copper wound) having a continuous rating for 11kV/433V 3 phase, vector DYN-11 with off load tap changing from +5% to -10% in step of 2.5. Transformer should have cable end box on HV side and LV side with all accessories, complete as required as per State electricity board and IE rules specifications. The class of winding insulation shall be correspond to class F. The transformer shall confirm to IS 2067/77, 11171/1985 with latest amendment etc. Transformer losses shall be as per ECBC 2017 (with amendments up to 2020). The LT portion shall be provided with 1No 4Pole 500A 50Hz 36kA microprocessor based MCCB with inbuilt earth fault release, shunt/UV coil, adjustable setting range of 50–100%, rotary handle, and spreader links. A low-set earth-fault relay shall be provided LT side, and CT of suitable ratio with accuracy class 5P10 shall be provided at the neutral earthing point. All inter connection from transformer to LT breaker shall be given using electrolytic copper bus bar insulated with heat shrink and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP standards for outdoor installation and shall be powder coated over suitable primer after seven tank processing.
Transformner 04 Supply of 200 KVA outdoor type unitized substation (USS) comprising of cast resin Transformer with 320A, 4pole on LT. side as per technical details furnished below. Transformer portion consists of 200kVA 11kV/433V outdoor cast resin dry type(AN) transformer (copper wound) having a continuous rating for 11kV/433V 3 phase, vector DYN-11 with off load tap changing from +5% to -10% in step of 2.5. Transformer should have cable end box on HV side and LV side with all accessories, complete as required as per State electricity board and IE rules specifications. The class of winding insulation shall be correspond to class F. The transformer shall confirm to IS 2067/77, 11171/1985 with latest amendment etc. Transformer losses shall be as per ECBC 2017 (with amendments up to 2020). The LT portion shall be provided with 1No 4Pole 320A 50Hz 25kA microprocessor based MCCB with inbuilt earth fault release, adjustable setting range of 50–100%, rotary handle, and spreader links. All inter connection from transformer to LT breaker shall be given using electrolytic copper bus bar insulated with heat shrink and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP standards for outdoor installation and shall be powder coated over suitable primer after seven tank processing.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.83 MB
BoQtrans.xls
Tender Documents • 0.13 MB
extendaug.pdf
PDF • 0.48 MB
extendjune.pdf
PDF • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].