Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.1 LAccepted-Finance | ₹20.1 L | L1 | Accepted-Finance Lowest Vendor |
| 2 | L2₹23.6 L+₹3.4 L (17.1%)Rejected-Finance | ₹23.6 L+₹3.4 L (17.1%) | L2 | Rejected-Finance Being not L1 |
| 3 | L3₹24.8 L+₹4.6 L (23.1%)Rejected-Finance D NO 65 6 500 2 MULAGADA COLONY HIMACHALNAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | ₹24.8 L+₹4.6 L (23.1%) | L3 | Rejected-Finance Being not L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not Recommended as not enlisted in appropriate category |
| Sl No | Description | Qty | Unit | SRI SIDDHI VINAYAKA ENTERPRISES L2 | SAI ENGINEERING WORKS L1 | ANAND ENTERPRISES AND ENGINEERS L3 |
|---|---|---|---|---|---|---|
| 1.00 | Preventive maintenance of ductable AC plant by carrying out routine check of the Plant complete for smooth functioning all as per manufacturer's instructions and as directed for 8.5TR x 04 Nos. installed at SSS bldg including attending to under mentioned jobs to ensure its satisfactory performance:-
Note: Quoted Rates are deemed to be for carrying out checks as under:-
(a) Contractor has to deploy sufficient number of technicians at the worksite to attend the breakdown calls received from representatives during two shifts throughout the week including sundays & holidays and on emergencies in third shift shall be attended ,preventive maintenance for the entire duration of contract.It is the contractors responsibility to make the unit functional and sufficient stock of spares shall be maintained to rectify the breakdown within scheduled period. Cleaning, stacking, sorting, handling and upkeeping of maintenance shall be carried out by contractor.
(b) Checking the system for visual leaks at all flare fittings and arresting | 11 | Per Month | 6,000 ₹66,000 Lowest | 30,000 ₹3,30,000 | 6,900 ₹75,900 |
| 1.02(c) Carrying out leak test with soap solution in case reports indicate frequent loss/recharging of refrigerant into the system whenever required (d) Checking operation ,suction& discharge pressures.In case of any abnormality identifying and correcting the same (e) Checking and setting of safety controls such as HP/LP cutouts,overload protections and thermostats etc. (f) Cleaning of pre air filters,evaparator coils and replacing the same if necessary (g) Checking lubricating oil level at the sight glass if found below the normal level the problem shall be analyzed and rectified. (h) Running of standby unit and observe for satisfactory performance. (i) Checking the incoming voltage and running currents and take appropriate measures (j) checking for any abnormal noise/vibration from moving parts such as compressors,motors,fans etc in case of any abnormality,investigating and correcting the same. (k) Checking and rectifying any water leaks and arresting them | ||||||
| 1.03(l) Checking the operation of controls and making them functional (m) Checking and cleaning of fan,runner blades and replace if required (n) Cleaning cooling coils by cleaning agent (CFC free) (o) Record of these shall be maintained and submitted monthly to engineer in charge Note :- The above quoted rate is inclusive of all spare parts apart from below mentioned spare parts which will be paid seperately to make the unit completely functional, T&P manpower required in the site | ||||||
| 2.00 | All as per item No. 1.00 above, but 7.5 TR x 4 Nos. installed at 62 bldg. | 11 | Per Month | 6,000 ₹66,000 Lowest | 7,000 ₹77,000 | 6,900 ₹75,900 |
| 3.00 | All as per item No. 1.00 above, but 8.5 TR x 3 Nos. installed at 17 MAT. | 11 | Per Month | 5,000 ₹55,000 Lowest | 6,500 ₹71,500 | 6,800 ₹74,800 |
| 4.00 | All as per item No. 1.00 above, but 5.5 TR x 2 Nos. instaled at 15 SAX. | 11 | Per Month | 4,000 ₹44,000 | 550 ₹6,050 Lowest | 6,500 ₹71,500 |
| 5.00 | All as per item No. 1.00 above, but 5.5 TR x 2 Nos. instaled at 25A bldg. | 11 | Per Month | 4,000 ₹44,000 Lowest | 5,500 ₹60,500 | 6,600 ₹72,600 |
| 6.00 | All as per item No. 1.00 above, but 16 TR x 3 Nos. instaled at 20 mout bldg. | 11 | Per Month | 8,000 ₹88,000 | 4,500 ₹49,500 Lowest | 14,500 ₹1,59,500 |
| 7.00 | All as per item No. 1.00 above, but 60 TR x 3 Nos. instaled at 25D bldg. | 11 | Per Month | 14,000 ₹1,54,000 | 7,500 ₹82,500 Lowest | 15,000 ₹1,65,000 |
| 8.00 | Material and labour for repair/overhauling of ODU unit of capacity for 16 TR to 60 TR which includes removal of outer body compressor, condenser,cooling/evaparator coil,transducers, etc internal wiring and circuit board,trip circuits and disconnecting all electrical connections, refrigerant lines, condenser water pipe lines etc and removing gas keeping into safe custody for reuse or for schedule of credit. Reassembling the unit by all the spares which are taken into custody and recharging the gas ,checking and rectifying the defects and replacing the defective spares,rectification of electrical circuits for all units and control wiring showing phase sequence with proper lugging, correcting alignment of , tightening of loose nuts, bolts,connecting wires,new cables of required length etc.,complete all as specified and directed.
Note : The quoted Rates are inclusive of reinstalling testing and commissioning the unit as earlier which require pressure testing with nitrogen gas under constant pressure of 250 PSI for 24 hours, vaccumization, performance test and commissioning and charging the gas to unit making alignment gas charging and necessary tinkering/brazing etc.The above quoted rate is inclusive of all spare parts apart from below mentioned spare parts which will be paid seperately to make the unit completely functional, T&P manpower required in the site | 3 | Each Job | 40,000 ₹1,20,000 | 10,000 ₹30,000 Lowest | 16,000 ₹48,000 |
Tender Value
₹35.1 L
EMD Value
₹70,160
Closing Date
9 Jul 2026, 6:00 pmClosed
GE (I) DM Visakhapatnam
GE (I) DM Visakhapatnam
COMPREHENSIVE MAINTENANCE OF DUCTABLE AC PLANTS AND IMPROVEMENT REPAIR REPLACEMENT OF UNSV SPARE PARTS AND ALLIED WORKS AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) DM VISAKHAPATNAM
2026_MES_771398_1
8544/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
Naval Dockyard Visakhapatnam
As per tender document
8 documents required · 8 mandatory
₹500
GE (I) DM Visakhapatnam
₹70,160
Yes
16 Sept 2026
11 Jun 2026
11 Jul 2026
11 Jun 2026
9 Jul 2026
25 Jun 2026
12 Jun 2026 - 23 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Preventive maintenance of ductable AC plant by carrying out routine check of the Plant complete for smooth functioning all as per manufacturer's instructions and as directed for 8.5TR x 04 Nos. installed at SSS bldg including attending to under mentioned jobs to ensure its satisfactory performance:-
Note: Quoted Rates are deemed to be for carrying out checks as under:-
(a) Contractor has to deploy sufficient number of technicians at the worksite to attend the breakdown calls received from representatives during two shifts throughout the week including sundays & holidays and on emergencies in third shift shall be attended ,preventive maintenance for the entire duration of contract.It is the contractors responsibility to make the unit functional and sufficient stock of spares shall be maintained to rectify the breakdown within scheduled period. Cleaning, stacking, sorting, handling and upkeeping of maintenance shall be carried out by contractor.
(b) Checking the system for visual leaks at all flare fittings and arresting | 11 | Per Month | - | - |
| 1.02 | (c) Carrying out leak test with soap solution in case reports indicate frequent loss/recharging of refrigerant into the system whenever required
(d) Checking operation ,suction& discharge pressures.In case of any abnormality identifying and correcting the same
(e) Checking and setting of safety controls such as HP/LP cutouts,overload protections and thermostats etc.
(f) Cleaning of pre air filters,evaparator coils and replacing the same if necessary
(g) Checking lubricating oil level at the sight glass if found below the normal level the problem shall be analyzed and rectified.
(h) Running of standby unit and observe for satisfactory performance.
(i) Checking the incoming voltage and running currents and take appropriate measures
(j) checking for any abnormal noise/vibration from moving parts such as compressors,motors,fans etc in case of any abnormality,investigating and correcting the same.
(k) Checking and rectifying any water leaks and arresting them | - | - | - | - |
| 1.03 | (l) Checking the operation of controls and making them functional
(m) Checking and cleaning of fan,runner blades and replace if required
(n) Cleaning cooling coils by cleaning agent (CFC free)
(o) Record of these shall be maintained and submitted monthly to engineer in charge
Note :- The above quoted rate is inclusive of all spare parts apart from below mentioned spare parts which will be paid seperately to make the unit completely functional, T&P manpower required in the site | - | - | - | - |
| 2 | All as per item No. 1.00 above, but 7.5 TR x 4 Nos. installed at 62 bldg. | 11 | Per Month | - | - |
| 3 | All as per item No. 1.00 above, but 8.5 TR x 3 Nos. installed at 17 MAT. | 11 | Per Month | - | - |
| 4 | All as per item No. 1.00 above, but 5.5 TR x 2 Nos. instaled at 15 SAX. | 11 | Per Month | - | - |
| 5 | All as per item No. 1.00 above, but 5.5 TR x 2 Nos. instaled at 25A bldg. | 11 | Per Month | - | - |
| 6 | All as per item No. 1.00 above, but 16 TR x 3 Nos. instaled at 20 mout bldg. | 11 | Per Month | - | - |
| 7 | All as per item No. 1.00 above, but 60 TR x 3 Nos. instaled at 25D bldg. | 11 | Per Month | - | - |
| 8 | Material and labour for repair/overhauling of ODU unit of capacity for 16 TR to 60 TR which includes removal of outer body compressor, condenser,cooling/evaparator coil,transducers, etc internal wiring and circuit board,trip circuits and disconnecting all electrical connections, refrigerant lines, condenser water pipe lines etc and removing gas keeping into safe custody for reuse or for schedule of credit. Reassembling the unit by all the spares which are taken into custody and recharging the gas ,checking and rectifying the defects and replacing the defective spares,rectification of electrical circuits for all units and control wiring showing phase sequence with proper lugging, correcting alignment of , tightening of loose nuts, bolts,connecting wires,new cables of required length etc.,complete all as specified and directed.
Note : The quoted Rates are inclusive of reinstalling testing and commissioning the unit as earlier which require pressure testing with nitrogen gas under constant pressure of 250 PSI for 24 hours, vaccumization, performance test and commissioning and charging the gas to unit making alignment gas charging and necessary tinkering/brazing etc.The above quoted rate is inclusive of all spare parts apart from below mentioned spare parts which will be paid seperately to make the unit completely functional, T&P manpower required in the site | 3 | Each Job | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
8544Tender.pdf
Tender Documents • 1.04 MB
BOQ_863834.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .