Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.7 LAccepted-AOC | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹23.5 L+₹80,827.70 (3.57%)Rejected-Finance | L2 | Rejected-Finance highest bidder | |
| 3 | L3₹23.9 L+₹1.2 L (5.34%)Rejected-Finance | L3 | Rejected-Finance highest bidder | |
| 4 | L4₹24.0 L+₹1.4 L (6.05%)Rejected-Finance HIMACHAL PRADESH | L4 | Rejected-Finance highest bidder | |
| 5 | L5₹25.6 L+₹3.0 L (13.1%)Rejected-Finance | L5 | Rejected-Finance highest bidder |
Tender Value
₹37.6 L
EMD Value
₹63,862
Closing Date
20 Aug 2020, 11:00 amClosed
Executive Engineer
Jal Shakti Division Jawali
Urban Water Supply Scheme in Tehsil Jawali Distt Kangra sub head Laying jointing testing of GI pipe Medium class in Rising Main and providing and installation of Pumping Machinery with allied accessories
2020_HPIPH_39352_1
EE/JSV/DIV/JWL-2020/2952-53 dt. 25.07.2020
Open Tender
Civil Works - Water Works
Item Rate
180 days
Jawali
Please refer Tender documents.
8 documents required · 8 mandatory
₹400
EE Jawali
₹63,862
Yes
18 Nov 2020
28 Jul 2020
20 Aug 2020
28 Jul 2020
20 Aug 2020
28 Jul 2020
Amount
Sub-Head:- Laying, jointing & testing of Rising Main Excavation in foundation and trenches ( For pipes and pits ) up to all depths in all classification of earth work such as pick work ,jumper work ,saturated soil including bailing or pumping out water ,blasting soft/hard rock or chiseling soft/hard rock where blasting is prohibited in all lifts including trimming & dressing of sides, leveling of beds to correct grade i/c shoring /strutting ,planking ,timbering & dewatering wherever required ,stacking the usable & unusable material /soil separately & after laying ,jointing & testing of pipes ,returning the useable soil in trenches in 15 cm ,layers including consolidating of such deposited layer by ramming & watering & then deposing of all surplus excavated soil / unusable material as directed with in all leads and lifts including restoration of unmetalled surfaces to its original condition and including cost of diversion for traffic , night signals ,fixing caution boards ,crossing over trenches for access to houses ,fencing etc. including jungle clearing, uprooting of rank, vegetation, grass bursh wood, trees and sapling of all girth/ depth complete in all respects with in all lead and lifts as per direction & satisfaction of Engineer - in - charge.
Laying, jointing & testing in trenches to be levelled to grades, BIS marked GI pipes conforming to BIS:1239 ( latest with up to date amendments ) of following dia ( Medium class ) duly flanged after every 5th pipe with intermediate butt welded joints including the cost of flanges, bends of required degree, tee/ short pieces made from parent tubes of different degrees cutting , welding & jointing with flanges conforming to table as specified below of BIS:6392 ( latest with up date ammendments ) two layers on both faces welded as per BIS:816 ( latest with up date ammendments ) with electrodes conforming to BIS 814 (latest with up date ammendments ) & provided with nuts & bolts BIS 1369 (latest with up date ammendments) of required sizes, 4.80 mm thick ( Champion make ) compressed asbestos fiber gasket or synthetic rubber gaskets conforming to BIS 2712 (latest with up date ammendments ) & approved specification as per site conditions including flushing, cleaning and hydraulic testing complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
(TW Bhanai to CT)
125 mm dia (Medium Class) Table - 17
(TW Kiyari to CT)
100 mm dia (Medium Class) Table - 17
Collection tank to U/G Existing storage tank OHSR tank Bhanai.
100 mm dia (Medium Class) Table - 17
Collection tank to U/G Existing storage tank tank Kimmen.
125 mm dia (Medium Class) Table - 28
125 mm dia (Medium Class) Table - 17
125 mm dia (Medium Class) Table - 5
Providing and fixing of Cast iron double flanged 100 mm dia Reflex Valve P.N.1.0 ISI body weged/ Bronze rings having test pressuure of 10.20 Kg/cm sqm including fitting ( with hand whel) iincluding brass spindle complete with nuts, bolts, rubber inserection etc. Make Kartar /Bir building The MS flanges on both faces to be confirmed as per table-17 IS 6392-1971 with up to date ammendement including required number and size of nuts and bolts including asbestest fiber jointing gasket 3mm thick and confirming to IS: 2712:1965 with latest ammendements. The welding of flange to be done on both faces in two layer as per IS: 814-1967 to make the joint leak proof complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
Providing and fixing of Cast iron double flanged 125 mm dia Reflex Valve P.N.1.0 ISI body weged/ Bronze rings having test pressuure of 10.20 Kg/cm sqm including fitting ( with hand whel) iincluding brass spindle complete with nuts, bolts, rubber inserection etc. Make Kartar /Bir building The MS flanges on both faces to be confirmed as per table-17 IS 6392-1971 with up to date ammendement including required number and size of nuts and bolts including asbestest fiber jointing gasket 3mm thick and confirming to IS: 2712:1965 with latest ammendements. The welding of flange to be done on both faces in two layer as per IS: 814-1967 to make the joint leak proof complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
Providing & fixing of 100 mm dia cast iron air valve of Bir make having test pressure of 11.20 Kg/Cm2 conforming to BS: 1452-90 complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
Providing & fixing of 125 mm dia cast iron air valve of Bir make having test pressure of 11.20 Kg/Cm2 conforming to BS: 1452-90 complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
Sub-Head:- Supply & errection of Submersible Pumping Machinery along with allied accessories. T/well Bhanai
Supply of submersible pumping set of KSB/ Kirloskar/Crompton / Johnston / BS/ SU/Lubi/Sabar confirming to BIS - 8034 -1979 (latest) suitable for clear water fitted with bronze impellers or suitable alloys directly coupled to squirrell cage electric induction motor of same make as that of pump confirming to IS: 9238-1979 latest with up to date amendments ) and totally water proof for submersible duty.,isolated from the pump by intermediate casing with double mechanical seal in oil chamber grease packed lubricated bearing & provided with stainless steel thurst bearing plate to with stand non vertical loads with minimum wear & tear. It should also be fitted with device to a take up expansion of water with heating of motor including water level guard errection clamps, cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Location of site :- The site is located at a distance of 4 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 452 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of T/well assembly 125.00 mtr.
L.W.L. in Tube-well 396 mtr
Centerline level of pump 396 mtr
Suction Head ________
Discharge level of highest point 460.00 mtr
No. of pump required 2 Nos
Discharge required from each Pump 9.00 LPS
Maximum draw down --- mtr.
Total head in mtr 69.33 mtr.
Length of R/Main 350.00 mtr.
Dia of R/Main 125 mm dia G.I. Pipe Medium class
No of working hours P/day 16.00 Hours
Limits of pump operction ( - ) 15 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
Test Run 20 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 65 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 65 mm & class PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 125 mm dia and class -PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) conforming to IS :5312-1984
Providing and laying of suitable size copper PVC insulated armoured power 3.5 core cable .confirming to BIS 1554 (Part-I) 1988 of latest with up to date amendements of siemen / Gloster /ICC finollex make from meter of HPSEB-to-MCB / & from OCB to Busbar switch and starter (one cable carrying all three phases ) including all other electrical equipment /accessories such as thimbles ,flexible pipe solder ,nuts and bolts ,cable glands etc. laid in pipes of trenches under floor . The type size and make will be subject to approval of HPSEB autherities . In case of non -acceptance by HPSEB autherities it shall have to be replaced by the tenderer free of coat. The size of the cable shall be specified by the Tenderer. a ) Supply side of size __ mm Sqm
Providing and laying of PVC jointless flat water proof cable as per BIS,694-1990 (latest with up to date amendements ) suitable for the pump sets offered from OCB to motor , Motor to starter including all other electric equipment such as thimbles ,flexible pipe , solder , nut & bolt ,cable , glands etc . laid in pipes or trenches under floor . The type & make will be subject to approval of HPSEB authorities . In case of non acceptance by HPSEB authorities it shall have to be replaced by the tender free of cost. The size of the cable shall be specified by the Tenderer. a ) Motor side of size ___ mm²
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply & Errection of floor / wall mounted power factor shunt capacitor conforming to BIS : 2834-1986 latest with upto date amendements L & T / BHEL/ GEC/ Machneil /Mager / Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of required KVAR according to HP of motor offered including cable siemens/Gloste/ICC make form busbar chamber to capacitor and also including L&T/LK/Kilburn make ICTP Switches conforming to BIS-4064-1978 or latest with HRC fuses.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying of column assembly of 65 mm dia G.I pipe confirming to BIS: 1239 considering site requirement duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -5 ) including tapers , flanges , rubber , gasket 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to collection tank as per direction of Engineer in Charge as per layout approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) ( The size of pipe shall be suppling by the tenderer ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Erection of all equipment from Sr. No. 2 to 8 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
Sub-Head:- Supply & errection of Submersible Pumping Machinery along with allied accessories. T/well Kiyari
Supply of submersible pumping set of KSB/ Kirloskar/Crompton / Johnston / BS/ SU/Lubi/Sabar confirming to BIS - 8034 -1979 (latest) suitable for clear water fitted with bronze impellers or suitable alloys directly coupled to squirrell cage electric induction motor of same make as that of pump confirming to IS: 9238-1979 latest with up to date amendments ) and totally water proof for submersible duty.,isolated from the pump by intermediate casing with double mechanical seal in oil chamber grease packed lubricated bearing & provided with stainless steel thurst bearing plate to with stand non vertical loads with minimum wear & tear. It should also be fitted with device to a take up expansion of water with heating of motor including water level guard errection clamps, cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Location of site :- The site is located at a distance of 4 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 456 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of T/well assembly 125.00 mtr.
L.W.L. in Tube-well 375 mtr
Centerline level of pump 375 mtr
Suction Head ________
Discharge level of highest point 460.00 mtr
No. of pump required 2 Nos
Discharge required from each Pump 4.71 LPS
Maximum draw down 71.00 mtr.
Total head in mtr 88.43 mtr.
Length of R/Main 30.00 mtr.
Dia of R/Main 100 mm dia G.I. Pipe Medium class
No of working hours P/day 16.00 Hours
Limits of pump operction ( - ) 15 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
Test Run 20 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 65 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 65 mm & class PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 100 mm dia and class -PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) conforming to IS :5312-1984
Providing and laying of suitable size copper PVC insulated armoured power 3.5 core cable .confirming to BIS 1554 (Part-I) 1988 of latest with up to date amendements of siemen / Gloster /ICC finollex make from meter of HPSEB-to-MCB / & from OCB to Busbar switch and starter (one cable carrying all three phases ) including all other electrical equipment /accessories such as thimbles ,flexible pipe solder ,nuts and bolts ,cable glands etc. laid in pipes of trenches under floor . The type size and make will be subject to approval of HPSEB autherities . In case of non -acceptance by HPSEB autherities it shall have to be replaced by the tenderer free of coat. The size of the cable shall be specified by the Tenderer. a ) Supply side of size __ mm Sqm
Providing and laying of PVC jointless flat water proof cable as per BIS,694-1990 (latest with up to date amendements ) suitable for the pump sets offered from OCB to motor , Motor to starter including all other electric equipment such as thimbles ,flexible pipe , solder , nut & bolt ,cable , glands etc . laid in pipes or trenches under floor . The type & make will be subject to approval of HPSEB authorities . In case of non acceptance by HPSEB authorities it shall have to be replaced by the tender free of cost. The size of the cable shall be specified by the Tenderer. a ) Motor side of size __ mm²
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply & Errection of floor / wall mounted power factor shunt capacitor conforming to BIS : 2834-1986 latest with upto date amendements L & T / BHEL/ GEC/ Machneil /Mager / Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of required KVAR according to HP of motor offered including cable siemens/Gloste/ICC make form busbar chamber to capacitor and also including L&T/LK/Kilburn make ICTP Switches conforming to BIS-4064-1978 or latest with HRC fuses.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying of column assembly of 65 mm dia G.I pipe confirming to BIS: 1239 considering site requirement duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -5 ) including tapers , flanges , rubber , gasket 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to collection tank as per direction of Engineer in Charge as per layout approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) ( The size of pipe shall be suppling by the tenderer ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Erection of all equipment from Sr. No. 2 to 8 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
Sub-Head:- Supply & errection of Centrifugal Pumping Machinery along with allied accessories. Collection tank to U/G Existing storage tank OHSR tank Bhanai.
Supply & Errection of horizontal spindle, horizontal/ radial split casing and suction (backpull out arrangement ) single/ Double/ multi stage Centrifugal Pumps or combination of pumps in series / Parallel of KSB/ Kirloskar/ Mathar & Platt / Jyoti/ BE/ Beaconwire make conforming to BIS :1520-1980 (latest with upto date amendments) read with BIS :9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics wih impellers of bronze/suitable alloy, priming funnels, casing ring & shaft sleeves of bronze /suitable alloy, shaft of suitable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be form the principle manufacturer of pumping set) to slippering /squired cage screen protected drip proof electric induction motor of KSB/ Kirlokar /Cropton /Sieman & Jyoti/ BE/ Beaconweir/ BHEL/ GEC/ ABB Conforming to BIS 325-1978 read with BIS: 900-1968 ( latest with upto date amendments ) It should include the cost of bearings . Nuts & bolts , painting etc. and shall be suitable for operation as per data given below.
Location of site :- The site is located at a distance of 4 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 456 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Type of water (Raw/ Treated) Clear Water
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of well assembly 0 mtr.
L.W.L. in C/Tank 456.00 mtr
Centerline level of pump 456.00mtr
Suction Head 3.00 mtr.
Discharge level of highest point 488.20 mtr
No. of pump required 2 Nos
Discharge required from each Pump 4.15 LPS
Maximum draw down ___ mtr.
Static Head in mtr 456.60 mtr.
Total head in mtr 39.01 mtr.
Length of R/Main 960 mtr.
Dia of R/Main 100 mm dia G.I. Pipe Medium class
No of working hours P/day 16.00 Hours
Limits of pump operction ( - ) 15 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
R.M.P. of Pump (2900/1450) 2900 RPM
MNPSH available 450 M
Test Run 16 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 80 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 80 mm & class PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 100 mm dia and class -PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) conforming to IS :5312-1984
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make of size 80 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Proiding and laying PVC insulated jointless.flat water proof copper cable of Siemens/Finolex/Grandlay/Gloster make conforming to BIS1554 ( Part-I)-1988 latest with upto date ammendments of suitable size for the pump sets (One cable carrying all three phases) including all other electrical equipment /accessoruies such as thimbles, flexibles pipe, solder, nuts & bolts cable glands etc. laid ln pipes or trenches under floor. The type, size and make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost. The size of the cable shall be specified by the Tenderer.
On Supply side of 3.5 core (From HPSEB meter to switch & starter) Size __ mm sqm
On Motor side of 3 core (From Switch & starter to motor) Size ___ mm sqm
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply & Errection of floor / wall mounted power factor shunt capacitor conforming to BIS : 2834-1986 latest with upto date amendements L & T / BHEL/ GEC/ Machneil /Mager / Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of required KVAR according to HP of motor offered including cable siemens/Gloste/ICC make form busbar chamber to capacitor and also including L&T/LK/Kilburn make ICTP Switches conforming to BIS-4064-1978 or latest with HRC fuses.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying and fixing G.I pipe confirming to BIS: 1239 of suitable size for suction, delivery and common header considering site requirement & NPSH required/ available. The pipe sizes for suction & delivery shall be as per the requirement of offered pump and common header shall be equal to dia of R/Main duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -17 ) including cost of tapers, flanges , bends, rubber gasket, 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to 5 mtr away from the outer wall of pump house as per direction of Engineer in Charge as per layout drawing approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) ( The size of pipe shall be suppling by the tenderer ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Suction pipe 100 mm dia
Delivery pipe 80 mm dia
Common header 80 mm dia
Erection of all equipment from Sr. No. 2 to 8.3 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
Sub-Head:- Supply & errection of Centrifugal Pumping Machinery along with allied accessories. Collection tank to U/G Existing storage tank tank Kimmen.
Supply & Errection of horizontal spindle, horizontal/ radial split casing and suction (backpull out arrangement ) single/ Double/ multi stage Centrifugal Pumps or combination of pumps in series / Parallel of KSB/ Kirloskar/ Mathar & Platt / Jyoti/ BE/ Beaconwire make conforming to BIS :1520-1980 (latest with upto date amendments) read with BIS :9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics wih impellers of bronze/suitable alloy, priming funnels, casing ring & shaft sleeves of bronze /suitable alloy, shaft of suitable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be form the principle manufacturer of pumping set) to slippering /squired cage screen protected drip proof electric induction motor of KSB/ Kirlokar /Cropton /Sieman & Jyoti/ BE/ Beaconweir/ BHEL/ GEC/ ABB Conforming to BIS 325-1978 read with BIS: 900-1968 ( latest with upto date amendments ) It should include the cost of bearings . Nuts & bolts , painting etc. and shall be suitable for operation as per data given below.
Location of site :- The site is located at a distance of 4 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 456 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Type of water (Raw/ Treated) Clear Water
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of well assembly 0 mtr.
L.W.L. in C/Tank 456.00 mtr
Centerline level of pump 456.00mtr
Suction Head 3.00 mtr.
Discharge level of highest point 563.00 mtr
No. of pump required 2 Nos
Discharge required from each Pump 9.56 LPS
Maximum draw down ___ mtr.
Static Head in mtr 456.60 mtr.
Total head in mtr 132.25 mtr.
Length of R/Main 3240 mtr.
Dia of R/Main 125 mm dia G.I. Pipe Medium class
No of working hours P/day 16.00 Hours
Limits of pump operction ( - ) 15 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
R.M.P. of Pump (2900/1450) 2900 RPM
MNPSH available 450 M
Test Run 16 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 80 mm dia suitable as per offered pump and class PN- 1.6 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 80 mm & class PN-1.6 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 125 mm dia and class -PN-1.6 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) conforming to IS :5312-1984
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make of size 80 mm dia suitable as per offered pump and class PN- 1.6 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984
Proiding and laying PVC insulated jointless.flat water proof copper cable of Siemens/Finolex/Grandlay/Gloster make conforming to BIS1554 ( Part-I)-1988 latest with upto date ammendments of suitable size for the pump sets (One cable carrying all three phases) including all other electrical equipment /accessoruies such as thimbles, flexibles pipe, solder, nuts & bolts cable glands etc. laid ln pipes or trenches under floor. The type, size and make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost. The size of the cable shall be specified by the Tenderer.
On Supply side of 3.5 core (From HPSEB meter to switch & starter) Size __ mm sqm
On Motor side of 3 core (From Switch & starter to motor) Size __ mm sqm
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply & Errection of floor / wall mounted power factor shunt capacitor conforming to BIS : 2834-1986 latest with upto date amendements L & T / BHEL/ GEC/ Machneil /Mager / Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of required KVAR according to HP of motor offered including cable siemens/Gloste/ICC make form busbar chamber to capacitor and also including L&T/LK/Kilburn make ICTP Switches conforming to BIS-4064-1978 or latest with HRC fuses.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying and fixing G.I pipe confirming to BIS: 1239 of suitable size for suction, delivery and common header considering site requirement & NPSH required/ available. The pipe sizes for suction & delivery shall be as per the requirement of offered pump and common header shall be equal to dia of R/Main duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -17 ) including cost of tapers, flanges , bends, rubber gasket, 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to 5 mtr away from the outer wall of pump house as per direction of Engineer in Charge as per layout drawing approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) ( The size of pipe shall be suppling by the tenderer ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Suction pipe 100 mm dia
Delivery pipe 80 mm dia
Common header 80 mm dia
Erection of all equipment from Sr. No. 2 to 8.3 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
sadeep kumar
A.K. Traders
Ravinder Kumar
TARSEM SINGH
SANJAY SAINI
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .