Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.7 CrAdmitted-Finance 216 C SIVA COLONY MAYO LINK ROAD AJMER RAJASTHAN 305007 | AJMER | RAJASTHAN | 305007 | ₹89.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹94.8 CrAdmitted-Finance MANATHA ENCLAVE 3RD FLOOR OLIMUGAL KAKKANAD P O KOCHI 682 030 KERALA | ERNAKULAM | KERALA | 682030 | ₹94.8 Cr | L2 | Admitted-Finance |
| 3 | L3₹109.8 CrAdmitted-Finance 5TH FLOOR ALPHA PLAZA K P VALLON ROAD KADAVANTHRA KOCHI KERALA PIN 682020 | KOCHI | ERNAKULAM | KERALA | 682020 | ₹109.8 Cr | L3 | Admitted-Finance |
| 4 | L4₹112.2 CrAdmitted-Finance PREMISES NO 5 30 5 N C SENGUPTA SARANI GROUND FLOOR MALL ROAD KOLKATA WEST BENGAL INDIA 700 080 | KOLKATA | KOLKATA | WEST BENGAL | 700080 | ₹112.2 Cr | L4 | Admitted-Finance |
| 5 | Rejected-Technical | - | - | Rejected-Technical JV work experiance not meeting the NIT criteria |
| Sl No | Description | Qty | Unit | CHERIAN VARKEY CONSTRUCTION CO PVT LTD L3 | JAIN BUILDER L1 | PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED L4 | Mecone Construction Contractors L2 |
|---|---|---|---|---|---|---|---|
| 1.00List of Works | |||||||
| 1.10 | Total amount of Sch 'A' part-I (Buildings/ Structures) | 1 | LUMPSUM | 45,56,57,934 ₹45.6 Cr | 30,49,99,999 ₹30.5 Cr | 44,75,00,000 ₹44.8 Cr | 30,56,24,500 ₹30.6 Cr |
| 2.00 | Total amount of Sch 'A' part-II (Excavation, Earthwork, Site Clearance & Site Development) | 1 | LUMPSUM | 86,74,081 ₹86.7 L | 20,00,000 ₹20 L | 56,40,000 ₹56.4 L | 70,53,911.85 ₹70.5 L |
| 3.00 | Total amount of Sch 'A' part-III (Internal water supply) | 1 | LUMPSUM | 87,16,607 ₹87.2 L | 35,00,000 ₹35 L | 56,83,674 ₹56.8 L | 92,15,043.6 ₹92.2 L |
| 4.00 | Total amount of Sch 'A' part-IV (Internal Electric Supply) | 1 | LUMPSUM | 1,67,06,990 ₹1.7 Cr | 88,68,493 ₹88.7 L | 1,48,94,070 ₹1.5 Cr | 1,90,20,977 ₹1.9 Cr |
| 5.00 | Total amount of Sch 'A' part- V (External Water Supply) | 1 | LUMPSUM | 10,44,629 ₹10.4 L | 6,00,000 ₹6 L | 9,22,185 ₹9.2 L | 11,04,363.9 ₹11.0 L |
| 6.00 | Total amount of Sch 'A' part-VI (External Electric Supply) | 1 | LUMPSUM | 44,91,212 ₹44.9 L | 23,99,999 ₹24.0 L | 65,11,185 ₹65.1 L | 58,43,729.68 ₹58.4 L |
| 7.00 | Total amount of Sch 'A' part-VII (Lightning Protection & Aviation Obstruction Light) | 1 | LUMPSUM | 2,21,408 ₹2.2 L | 2,09,999 ₹2.1 L | 2,67,075 ₹2.7 L | 2,52,073.5 ₹2.5 L |
| 8.00 | Total amount of Sch 'A' part-VIII (Area Drainage) | 1 | LUMPSUM | 46,38,928 ₹46.4 L | 25,99,999 ₹26.0 L | 47,89,968 ₹47.9 L | 49,04,193.3 ₹49.0 L |
| 9.00 | Total amount of Sch 'A' part-IX (Sewage Disposal) | 1 | LUMPSUM | 19,55,200 ₹19.6 L | 13,99,999 ₹14.0 L | 27,52,280 ₹27.5 L | 19,87,503 ₹19.9 L |
Updated dates
Tender Value
₹108 Cr
EMD Value
₹15 L
Closing Date
28 Apr 2026, 6:00 pmClosed
CE (NW) KOCHI
CHIEF ENGINEER NAVAL WORKS KOCHI MILITARY ENGINEER SERVICE NAVAL BASE POST KATARIBAGH KOCHI-682004
PROVISION OF DEFICIENT MARRIED ACCOMMODATION FOR OFFICERS (LT CDR AND ABOVE) AT KATARIBAGH, KOCHI (AMWP 75/24-25)
2026_MES_754713_1
891087
Open Tender
Civil Works
900 days
KOCHI
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,000
GE(P) KOCHI
₹15 L
Yes
18 May 2026
28 Feb 2026
30 Apr 2026
28 Feb 2026
28 Apr 2026
14 Apr 2026
28 Feb 2026 - 20 Mar 2026
Total amount of Sch 'A' part-I ( Buildings/ Structures)
Total amount of Sch 'A' part-II (Excavation, Earthwork, Site Clearance & Site Development)
Total amount of Sch 'A' part-III (Internal water supply)
Total amount of Sch 'A' part-IV (Internal Electric Supply)
Total amount of Sch 'A' part- V (External Water Supply)
Total amount of Sch 'A' part-VI (External Electric Supply)
Total amount of Sch 'A' part-VII (Lightning Protection & Aviation Obstruction Light)
Total amount of Sch 'A' part-VIII (Area Drainage)
Total amount of Sch 'A' part-IX (Sewage Disposal)
Total amount of Sch 'A' part-X ( Road/ Path/Hardstanding )
Total amount of Sch 'A' part-XI (Lift)
Total amount of Sch 'A' part- XII (Fire Fighting)
Total amount of Sch 'A' part-XIII (Demolition)
Total amount of Sch 'A' part-XIV (Rain Water Harvesting)
Total amount of Sch 'A' part-XV (Arboriculture)
SCH. 'A' PART -XI (Miscellaneous B/R & E/M Items ) Note :- This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
PILE Boring for cast in situ piles 450mm dia 15.875 m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified.
Boring for cast in situ piles 450mm dia 51.775 m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified.
Boring for cast in situ piles 600mm dia 51.38m depth through any type of soil/ strata by DMC method using bentonite slurry including removal of bored materials out side MD land complete all as specified.
RCC M35 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in cast in situ bored pile of 600mm dia all as specified and as shown in drg.
RCC M35 Design Mix as per IS- 456 with using 20mm graded stone aggregate as in pile cap and grade beam all as specified and as shown in drg.
Providing CRS TMT bars 10 mm dia and over, cut to length, bent to shape required incl cranking, bending, sprilly for hooping for columns etc for bored piles, grade beams, tie beams complete all as specified.
Providing CRS TMT bars 5 mm dia and over but up to 10mm dia as in stirrups and binding with mild steel wire etc for grade beams tie beams complete all as specified.
Providing CRS TMT bars 5 mm dia and over but up to 10mm dia as in helical stirrups for piles and binding with mild steel wire etc for bored piles complete all as specified.
PCC (1:2:4) type D2 using 40mm graded stone aggregate for concrete layer below grade beam and foundation complete all as specified and as shown in drg.
M&L for form work to sides of pile cap, grade beams and tie beams for rough finished flat concrete surface all as specified and as directed.
Testing of piles (initial load test) all as per IS (Vertical )for cast in situ 450 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (initial load test) all as per IS (Lateral)for cast in situ 450 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (Routine load test) all as per IS (Vertical )for cast in situ 450 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (Routine load test) all as per IS (Lateral)for cast in situ 450 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (initial load test) all as per IS (Vertical )for cast in situ 600 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (initial load test) all as per IS (Lateral)for cast in situ 600 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (Routine load test) all as per IS (Vertical )for cast in situ 600 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
Testing of piles (Routine load test) all as per IS (Lateral)for cast in situ 600 mm dia piles including mobilising and removing the testing equipment from site after testing is complete all as specified.
DEMOLITION Taking down Bib cock/ Stop cock 15mm dia complete all as specified and directed.
Taking down gate valve 25/ 20mm complete all as specified and directed.
Taking down shower 15mm dia complete all as specified and directed.
Taking down old kitchen sink of any description all as specified and directed.
Taking down DBs SPN/ main switches with all accessories all as specified and directed.
Taking down electric meter and depositing to MES store yard all as specified and directed.
Taking down service connection all as specified and directed.
Taking down water heater of capacity 25/ 50 ltr and depositing to MES store yard all as specified and directed.
SEWAGE DISPOSAL Supply and laying of DWCPE (SN8)(OD)/163(ID) mm diameter pipes laid on 200mm thick bed with excavation in any type of soil, including earth work excavation ,PCC bed and haunching of pipe,return filling and removal of surplus soil 1.5 Km to 5.0 Km inside the defence land line functional for depth all as specified and as directed.
STP Sewage Treatment Plant STP of capacity 80 KLD Designing (hydraulically, structurally & aesthetically), providing, constructing, hydraulic testing, commissioning and giving satisfactory trials of STP of 80 KLD capacity complete fully automated operation and provisioned with SCADA system including tertiary treatment. Note:- Input Parameters: Input Parameters to be considered out of parameters given in CPEEHO/TI/as per site (which ever is most stringent) (i) Biochemical Oxygen Demand (BOD) (ii) Chemical Oxygen Demand (COD) (iii) pH (iv) Total Nitrogen, Total Phosphorus (For disposal in lakes) (v) Total Suspended Solids (TSS) (vi) Fecal Coliform (vii) Water table during High Water Flow (viii) Water consumption (ix) Sample population
Output Parameters: Effluent (Treated) Sewage Parameter required is as follows or Kerala PCB parameters (which ever is most Stringent). (i) pH - 6.5-8.3 (ii) COD - <50mg/L (iii) BOD - <10mg/L (iv) TSS - <10mg/L (v) Total Nitrogen - 10mg/L (vi) Total Phosphorous - 1 mg/L (vii) Fecal Coliform - Nil (viiI) Odor - No foul odor (c) Technology : Suitable approved technology for optimum utilisation/ to obtain required output parameters to be adopted and to be get approved from Accepting Officer before commencement of work at ground. The plant shall be of working at any load/ compatable to work with any quantity of sewage load (0% to 110%) without affecting the performance of plant. (Suitable provisions for keeping microbes alive in varying sewage load conditions). (d) Approvals : Consent to establish (CTE) and consent to operate (CTO) to be obtained from Kerala State Pollution Contorl Board before commencement of work and commissioning of the plant respectively. Necessary charges need to remitted in PCB's shall be inclusive of the rate quoted above. (e) Civil Works : All civil works related to STP plant shall be provisioned and inclusive in the rate quoted above item.
(f) All electrical & mechanical equipments including connecting up with suitable capacity cable/ pipe etc shall be provisioned and inclusive in the rate quoted above item. (g) Training, testing charges during DLP, Consumables during DLP, Records maintenance cost during DLP for fully automated operation shall be included in the rate quoted above. (h) Cost of all consumables like Hypo chlorite, cost of potable monthly chemical consumption etc, is deemed to be included in the operation cost quoted by the contractor except electricity charges.
M&L 3-layer PP-R Polypropylene random copolymer concealed pipes 110 mm o/d SDR 7.4 (PN 16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass treaded polypropylene random fittings laid in trenches(for treated sewage water from plant to arboriculture) all as specified and as directed.
M&L 3-layer PP-R Polypropylene random copolymer concealed pipes 50 mm o/d SDR 7.4 (PN 16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass treaded polypropylene random fittings laid in trenches (for treated sewage water from plant to arboriculture) all as specified and as directed.
supply, install and testing Pumping sets 3HP,230V single phase, centrifugal, electric driven suction head 80mm and delivery head 65 mm, complete including suitable capacity of DOL starter and PCC foundation (for pumping treated water 2 pumpset ) (Treated Water pump to transfer treated water to arboriculture) all as specified and as directed.
Supply install of Non clog vertical submersible pumps of capacity 5 HP with chrome steel impeller and cutter, non-clog to pass 50 mm size particles including supply, installation with guide rail and lifting chain, cables, earthing, testing complete with 2 years maintenance (Flow and head= 700 lpm x 40 M) ( 1 working + 01 standby )
Supply and fixiing of LT panel board cubicle type, indoor panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Aluminium bus bar of rating 200 Amps for phases & neutral mounted on porcelain/epoxy insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2 mm CRCA sheet duly powder coated after nine tank process. The panel shall be front openable type adequate space all around cessories such as LT switchgear and metering instruments including internal wiring in the panel with FRLS non flamable insulated multi stranded/ solid copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessories.(Non Clog Pumps) "(a) MCCB 100 Amp 10 KA 4 pole - 01 No (b) MCCB 63 Amp KA 3 pole - 03 Nos (c) Provn of DOL starter suitable of required suitable capacity - 03 Nos (d) MCB SPN 16 Amp, 10 KA - 02 Nos (e) Aluminium bus bar 100 Amp TPN - 01 set (f) Multi function digital meter (VAF & PF) - 01 No (g) Indicating lamps - 01 (set of three) (h) Sigle Phase Preventer-03 No's
Supply and fix valves, NRV 80mm dia all as specified and as directed.
WET WELL Engineering, Design, preperation of Structural and Architectural Drg including pile foundation and Construction of RCC M35 Wet well 100000 ltr capacity including excavation of over areas in any type of soil, pile foundation, RCC walls, bottom slabs, top RCC slab with Cl man hole cover and 12mm thick CM plastering 1:3 uing water proofing compound. Epoxy paint inside the sump over the plastered surface, returning filling of earth and disposal of surface earth with in 50 mtr lead including all piping connections, walls, MS rings, Aluminium ladder, ventilation shaft, BB chambers with 5 mtr of outer wall of tank complete including testing for water tightness and hydroulic functioning complete with RCC framed structure with pile foundation all as shown on drgs and as specified. Note: (i) Pile foundation shall be measured and paid seperately. (ii) Soil investigation report will be provided by GE (P) kochi office.
RAIN WATER HARVESTING M & L for two coat of epoxy paint on steel surface over a coat of primer incl preperation of surfaces all as specified and directed.
Supply and fixing valves, NRV 40mm dia complete all as specified and as directed.
Supply and install submersible pumping sets, electric driven, 3 phase/ 440 volt, 50 hz, minimum 180 LPM, 48 mtr head complete inclusive fixing, incl provn of level sensor, with auto/manual operation all as specified and as directed.
Supply and fixing DOL starter upto 5 HP with suitable enclosure with connected circuit, mounted on wall panel all as specified and as directed.
Supply and fixing watermeter class 'B' 40mm dia flange type to register the amount of water passed through the softner complete all as specified and as directed. Make : Kranti or equivalent.
Supply and laying flat 3 core x 4 sqmm PVC insulated & PVC sheated industrial cable for submersible pump motor 1100 volts all complete all as specified and as directed.
ARBORICULTURE M&L for Excavation of pits size 30cm x 30cm x 30cm in loose soil and filling the pt with mixer of river sand and approved earth in the porportion of 1:3 mixed with 2 Kg of cow dung powder, 100gms of born meat and 10 gms of insectide 'furadan' all as specified and as directed.
All as per item No 58 above but pit size 60cm x 60cm x 60cm all as specified and as directed.
Supplying and planting red palm sapling having 30- 45cm height all as specified and as directed.
Supplying and planting Jasmine of different variety sapling having 30cm height all as specified and as directed.
Supplying and planting Areca Palm having 45 - 60 cm height all as specified and as directed.
Supplying and planting Ficus Panda Shrubs sapling having 45cm height all as specified and as directed.
Supplying and planting Ixora Red,Yellow,White & Pink colour sapling having 30cm height all as specified and as directed.
Supplying and planting Ixora coccinea Red,Yellow,White & Pink colour sapling having 30cm height all as specified and as directed.
Supplying and planting vereity of Hedges Golden duranta 20 nos per Rm sapling having 15-20cm height all as specified and as directed.
Supply and planting of Mexican grass (carpet) over prepared surfae with adequately developed root after providing antitermite treatment including preparation of surfaces, earth work excavation, removing surplus soil, filling of approved earth suitable for grassing 25 mm thick after mixing of fertilizer/organic manure and regular maintenance of developed grass for two year. Note : (i) No separate payment shall be paid for mixing of fertilizer on this account. (ii) After the completion of work Six Months maintainance period shall be done by contractor at his own cost.
Maintenance of planted trees and lawn area for six months after certified date of completion issued by GE by employing one experienced mali per day. The maintenance shall includes the following. (a) Periodical de-weeding of unwanted vegetation growth around the plants/lawn area (b) Watering all the trees/plants/grass and soil with required for proper growth. (c) Periodical prunning the shrubs. (d) Periodical lawn mowing (e) Treating the trees/plants grass and soil with required quantity of approved manure,pesticides and fertilizer including necessary toping of red earth (f) Replacement of dried/dead plants/grass/trees. (g) Hose pipe to be arranged by the contractor. (h) Water shall be supplied by Deptt only for watering to plants.
5 HP submersible motor including Delta starter all as specified and as directed.
PTMT sprinkler cover 9.0 r m all as specified and as directed.
Supply and fixing of Cast iron decorative benches frame with back and minimum seat capacity of 3 Nos. Thickness of seat slab minimum 100mm and back height 1000mm front height 450mm and base width 620mm and reinforced concrete 6 nos planks of size 1500mm x 200mm x 50mm. All parts are joint together wth galvanized nuts and bolts of suitable size and all bolts are sealled after assumbling. Bench top and back planks ar treated with anti coarosive and water proof coating.All coplonents are manufactured by using M30 grade of concrete using vibro complaction process all as specified and as directed.
S & F of paving stones of size 600mm x 600mm x 20mm thick with mat surface finish for garden footpath over 75mm thick of PCC 1:3:6 of 20mm graded aggregte all as specified and as directed.
S&F Poly carbonate solid sheet transulcent corrugated sheeting 3 mm thick with sealant and self driven screws all as specified.
M&l Hand rails, stainless steel pipe as on parapet top, drilled and counter sunk for balusters incl embeddeing in concrete & screwing drilling bolting welding reveting etc confirming to Grade 316L complete all as specified.
Supply and fixing LED Spike light 5 watt Outdoor IP 65, Dust tight and jet proof, lumen efficiency ≥ 70 lm/W along with connected internal wiring pre-wired up to terminal box complete all as specified and directed by Engr in charge.
Supply and fixing LED bollard garden light 10 watt IP 65 Dust tight and jet proof, lumen efficiency ≥ 90 lm/W along with connected internal wiring pre-wired up to terminal box complete all as specified and directed by Engr in charge.
Supply and fixing thermoplastic junction boxwith metric knock out for garden light fittings inside cable termination,earth connection to be fixed on garden light pipe complete all as specified.
INTERNAL WATER SUPPLY S&F Bip tap,cast copper alloy cromium plated fancy type of size 15mm long body with CP cup Make Jaquar code No VGP-81037 or equivalent in other makes listed in list of makes all as specified and as directed.
S&F angular stopcock chromium plated cast copper alloy screwed down screwed for iron pipe 15mm dia bore Make Jaquar code no KUP-35053PM or equivalent in other makes listed in list of makes all as specified and as directed.
S&F Brass CP mixer with hand shower 3 in 1 Make Jaquar code no FUS-29281 and hand shower HSH-1781 or equivalent in other makes listed in list of makes all as specified and as directed.
S&F two way Bip tap with wall flange ,cast copper alloy cromium plated fancy type of size 15mm long body with CP cup Make Jaquar code No FLP-5041PM or equivalent in other makes listed in list of makes all as specified and as directed.
S&F kitchen single liver sink mixer swinging spout table mounted tap,cast copper alloy cromium plated fancy type of size 15mm long body with CP cup Make Jaquar code No FLP-5173BPM or equivalent in other makes listed in list of makes all as specified and as directed.
S&F concealed stopcock chromium plated cast copper alloy screwed down screwed for iron pipe 15mm dia bore Make Jaquar code no SOL-6227K or equivalent in other makes listed in list of makes all as specified and as directed.
EXTERNAL WATER SUPPLY Supply and laying Ductile Iron pipes 100 mm dia centrifugally cast (spun), Class K-9, with spigot and socket ends conforming to IS 8329/2000 in any length suitable for push-on joints, laid in trenches complete all as specified and as directed.
Supply and fixing DI fittings such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs suitable upto 150 mm dia, class K- 12 complete all as specified and directed.
Supply and install Pumping sets, electric driven, centrifugal type, horizontal split case, 3 Phase/440 Volt, 50 Hz, minimum 780 LPM, 56 Mtr Head complete inclusive of suitable panel type starter and PCC foundation all as specified and as directed.
Supply and fix Foot Valve with gunmetalof sizes 100 mm all as specified and as directed.
S&F motor control panel indoor type made out of MS sheet 2 mm thick with locking arrangement and painting with following accessories suitable for incoming/outgoing arrangements all as specified and as directed:- (a) MCCB 63 Amp 25 KA 4 pole - 01 No (b) MCCB 40 Amp 25 KA 3 pole - 02 Nos (c) Provn of star delta starter suitable for 20 HP motor or as required, 415 volt AC-02 Nos (d) MCB SPN 10 Amp, 10 KA-02 Nos (e) Aluminium bus bar 100 Amp TPN-01 set (f) Multi function digital meter (VAF & PF) - 01 No (g) Indicating lamps - 01 (set of three) (h) Sigle Phase Preventer-02 No's
Supply, Installation, Testing and Commissioning of indoor type power coated PLC (Programmable Logic Controller) based 2 Nos PUMP AUTOMATION PANEL Slave Monitoring/Annunciating Control Panel made out of 1.6mm thick CRCA sheet for control and monitoring of 10 Nos of Magnetic Level Sensor, 6 Nos of motorised valves all as specified and as directed. The panel shall consist of the following equipments; (1) PLC with suitable Digital and analog Inputs/outputs, expansion modules, RTC. (ii) 4" LCD HMI (iii) Transformer with regulated output voltage of 230V +/-5%, (iv) SMPS of Suitable rating (v) Set of Control Relays and suitable MCB (vi) Audio visual generator (vii) Suitable No. of LED Indicators for easy visualisation (viii) Selecetor Swtiches (ix) Push Buttons / Illuminated Push Buttons (x) 0.5 sqmm multistrand internal wiring with ferruling and suitable lugs. (xi) Ethernet card (xii) Media Converter (xiii) Ethernet Switch (xiv) LIU(Light Interface Unit)box patch chord and mounting accessories with following specification. Communication: Primary- OFC, Stand by: GPRS Make of Control Panel: PSEC/JSP/RKOM/MARSH AUTOMATION
Up-gradation of the existing SCADA software to incorporate management and control of various OHTS and pump house, developing and adding the additional features as described below by altering the existing SCADA software a) Development of libraries and screens for display of the schematic b) Creation of additional soft keys for of the remote motorized valves remote / manual operation of the motorized valves in the OHTS. c) Modification of the Main SCADA screen to create a link to easily navigate to the newly developed OHTS and Pump schematic screen etc. as required. at Kataribag main pump house SCADA room all as specified and as directed.
Supply & fixing on wall/ laying in trench 2 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed. Make: POLYCAB/FINOLEX/RR CABLE
Supply & fixing on wall/ laying in trench 4 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed. Make: POLYCAB/FINOLEX/RR CABLE
Supply & fixing on wall/ laying in trench 6x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed. Make: POLYCAB/FINOLEX/RR CABLE (for motorised valve)
Supply & fixing on wall/ laying in trench 5 pair 0.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed. Make: POLYCAB/FINOLEX/RR CABLE/FSC (for magnetic senser)
Supply, Installation, Testing and Commissioning of Magnetic Level Sensor with the following specifications. Type: Magnetic Make: Rkom/JSP/PSEC
Supply and Fixing UPS / Inverter along of capacity 1.0 KVA with suitable battery bank with weatherproof enclosure with locking arrangement complete including electric connection from tapping and to PLC based control panel with armoured copper wire all as specified and as directed. Note: i) The scope of work includes integrating the UPS with the PLC based Panel so as to ensure that the Motorised valves are functional even in case of a power failure for a minimum of 6 hours. Make: APC / Luminous / Numeric
Supply, Installation Testing & Commissioning of pressure Transmitter with following specification including necessary power pack for supply of DC: Power supply: 10-36 V DC Process connection: G 1⁄2" Enclosure: whether proof IP 65 Process temperature: -30 to 120 celcius Accuracy: 0.25% Make: Danfoss / Siemens / E&H
Supply, Installation Testing & Commissioning of Solenoid valve suitable for 25 mm pipe for priming of pump including all necessary GI fittings with following specifications: Size: 25 mm Pressure rating: 10 kg / sq. cm. Make for Valve: L&T/ Honeywell/ Siemens/ Kirloskar/ Schneider/ Emtork.
Supply, Installation Testing & Commissioning of direct acting type release solenoid valve for air release during priming: with follwing specifications: Size: 10 mm Pressure rating: 10 kg / sq. cm. Type: Normally closed Make for Valve: L&T/ Honeywell/ Siemens/ Kirloskar/ Schneider/ Emtork.
Supply, Installation Testing & Commissioning of Motor Actuated Butterfly Valve made of SS- 304, stem material SS-410, EPDM seat in butterfly valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 50/65 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications & Features : Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches: 02 Nos. For open and close status Mounting: InDirect on valve Make for Actuator : Rotork/ Honeywell/ Rotex/ Siemens/ Schneider/ Emtork (The torque of actuator shall be atleast 25% higher than the valve). Make for Valve: L&T/ Honeywell/ Siemens/ Kirloskar/ Schneider/ Emtork.
Supply, Installation Testing & Commissioning of Motor Actuated Butterfly Valve made of SS- 304, stem material SS-410, EPDM seat in butterfly valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 75/80 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications & Features Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: Cl with nylon coating Limit Switches: 02 Nos. For open and close status Mounting: InDirect on valve Make for Actuator : Rotork/ Honeywell/ Rotex/ Siemens/ Schneider/ Emtork (The torque of actuator shall be atleast 25% higher than the valve). Make for Valve: L&T/ Honeywell/ Siemens/ Kirloskar/ Schneider/ Emtork.
Supply and laying 50 mm outer dia CPVC pipes SDR-13.5 & plain CPVC SDR 11 fittings, including jointed with yellow solvents cement including taking down old unserviceable GI tubing, laid in trenches complete all as specified and directed.
INTERNAL ELECTRIFICATION M&L Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 1.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and sheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty steel conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 1.5 Sqmm nominal cross sectional area single core F.R.L.S cable as earth continuity conductor to common earth and connecting to earth dolly and cutting chases for steel conduits/boxes etc complete all as specified and directed at site for one light/Bell point controlled by one 5/6 amps one way switch.
All as per item No 103 above but for one Ceiling fan point controlled by one 5/6 amps one way switch all as specified and as directed.
All as per item No 103 above but for one exhaust fan point controlled by one 5/6 amps one way switch all as specified and as directed.
All as per item No 103 above but for one Socket outlet, three/five pin, 5 Amp, independent controlled by one 5/6 amps one way switch or switch/socket combination 5 amps, 5 pin all as specified and as directed.
All as per item No 103 above but for one Socket outlet, three/five pin, 5 Amp, same board controlled by one 5/6 amps one way switch all as specified and as directed.
All as per item No 103 above but for one light point controlled by 2 Nos, 2 Way switches 5/6 Amps all as specified and as directed.
Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 2.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and sheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty, steel conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) , including PVC insulated multi-stranded copper conductor 2.5 Sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly and cutting chases for steel conduits/boxes etc complete all as specified and directed at site for the one 3/5 pin 15/16 amps socket outlet independent.
M&L for Starter switch of capacity 20A,including socket and plug top working on 240 Volts AC supply and suitable for Air conditioners all as specified and as directed.
S&F LED Tube light 1X20 Watt 4' inverter LED batten square profile and polycarbonate channel. Lithium Ion battery with charging time 8hours-10 hours and back up time upto 4 hours including 3 core 1sqmm PVC insulated multi stranded copper conductor's sleeve color matching to fitting and connecting up complete all as specified and directed. .
Design,fabrication, supply installation testing and commissioning of LT panel indoor type suitable to be mounted on PCC foundation/floor/duct all as per site requirement with cable entry from bottom with removable gland plates with required knockouts for incoming and outgoing cables. Panel shall be fabricated out of 2 mm thick CRCA sheet folded and brazed as necessary to provide rigid support for all components totally enclosed and degree of protection shall be IP-54 with front hinged lockable doors for the individual feeders / components treated by seven tank process & powder coated with approved colour. Doors and covers shall be fully gasket using good quality EPDM gasket and/or rubber strips, locking arrangement durable door opening and closing mechanism, Aluminium bus bar for three phases and nuetral busbar insulators, heat shrinkable Pvc sleeves etc. with necessary interconnection as specified comprising of the following switch gear. Note : Contractor shall submit GA drg for approval of GE before placing order (ii) Each switch gear shall be in separate cubicle.(iii) Cable alley shall be provided at side panel with adequate size width (iv) Each outgoing shall have Amp meter, CTs` ON /OFF indicator lamp. (Meter Panel at each floor) INCOMER: (a) MCCB 100 Amps 36 KA 4 Pole, Adjustable type – 01 No (b) Aluminium bus bar 200Amps (c) Multifunction digital meter (VAF& PF) – 01 No (d) indicator lamp R,Y,B – 01 set
OUTGOINGS: a) MCCB 4 pole 32 Amp 10 KA 05 Nos –( for meter) – 4 Nos + 01 spare (b) Provn of fixing smart meter 3 phase 415 volt 10-60 Amps as per IS -16444: 2015 (reaffirmed 2020) and Technical specification given in particular specification – 04 Nos.
Design Supply Testing and commissioning of 3L+N sandwitch type feeder/ Distributor of capacity 630 Amps BBT (required for entire length G+9 Bldg) with insulation class F (155 degree C) Dust and vermin proof made up of Hot galvanised Sheet Steel with four Aluminium bus bar coated electrolytic copper entire length with impulse voltage 12 KV Reference standard IEC 61439-6 Reference temperature 40 degree c Protection degree IP 55 Thickness 1.5 mm, N of Conductor 4 epoxy Paint shade of RAIL 7035 Halogen free. The insulation between bars is ensured by a multi sheath made with PET polyster Film including Flange end, Bend, End cover, internal fire barrier, Rigid support, Spring support, Normal support, End feed unit with 400 A 25 KA MCCB and Tapoff Box with 100 Amps 16 KA MCCB - 09 Nos (at each floors) complete.
EXTERNAL ELECTRIC SUPPLY Supply, install, testing & commissioning of 11 KV, 630A, 20 KA, Motor operated, Compact, outdoor, both side extensible, non drawout type, +V+ (01 No. fixed type motor operated Vaccum Circuit Breaker (VL) outgoing Safeplus compact gas insulated Ring main unit, including extension of existing HT panel, all live parts enclosed in a robotically welded stainless steel tank of IP 67 class of protection including coupling accessories and necessary PCC foundation complete all as specified and as directed. Make: Compatiable with existing HT Panel.
Supply and Installation Commissioning and testing of 11 KV Out door type Compact secondary SubStation CSS with HT side CV Module RMU,Transformer with resin cast with ECBC losses makes of Ames impex,ECS and other CSS Manufacturer approved by GE.and LT side compartment with ACB as per enclosed technical Bill of material with IP54 clause for CSS Enclosure and IP 23 for Transformer ,with IEC 62271-202,AC-AB. Transformer: 800KVA 11KV/433V Dyn11 Coppe wound cast Resin Dry Type (AN) distribution Transformer with off circuit Tap link. Make: Amps Impex.ECS. HT Switch Gear: 11KV ,630 Amps 21 KA for 3 sec.SF6 Insulated Non- Extinsible compact switch gear (Type CV) Consisting of one No's fixed Mortorised load break switches(LBS) and one No.Fixed mortorised Vaccum Circuit Breaker(VCB)having inbuild load break switch and earth switch within SF6 insulated robotically welded non ferrite non magnetic stainless steel enclosure of thickness steel enclosure of thickness 2.5mm having IP 67.with series trip, self powered microprocessor based numerical 3.0/C&1 E/F relay (IDMTL+Inst)protection.Interconnection between HT switchgear and shall be using 1CX3X95sg mm AL.unarmoured XLPE Cable.Make: ABB India Limited. INCOMER FROM TRANFORMER: 1250Amps,4pole,50HZ,50KA,fixed Manual type Air Circuit Breaker(ACB)With microprocessor based Ekip Dip release for over load (O/L),Short circuit,& Earth fault protection.Make:ABB.
S&F feeder pillar box out door type made out of MS sheet 3 mm thick welded on angle iron frame 40 x 40 x 6 mm duly grouted in earth incl PCC 1:3:6 type C-1 with locking arrangement and painting with following accessories suitable for incoming/out going arrangments:- (MAIN INCOMER) (a) ACB 1250 Amp 4 pole (microprocessor based release) - 01 No (b) MCCB 630 Amp 35 KA 4 pole - 03 Nos (Bldg 1 , 2 & Spare) (c) 4pole MCCB 200 Amp, 50 Hz, 415 volt 25 KA - 01 No (FF -01 No) (d ) MCCB 160 Amp 25 KA 4 Pole - 02 Nos ( DG Set & spare) (e) Aluminium bus bar 1600 Amp TPN - 01 set (f) Multi function digital meter (VAF & PF) - 01 No (g) Indicating lamp - 01 No (Set of three)
S&F feeder pillar box indoor type made out of MS sheet 2 mm thick welded on angle iron frame 40 x 40 x 6 mm duly grouted in earth incl PCC 1:3:6 type C-1 with locking arrangement and painting with following accessories suitable for incoming/out going arrangments:- (G+9) (a) MCCB 630 Amp 35 KA 4 pole - 01 No (Bldg Incomer) (b) MCCB 160 Amp 25 KA 4 pole - 05 Nos (Meter Rm1 , 2, 3, 4 +1 spare) (d) Aluminium bus bar 1000 Amp TPN - 01 set (e) Multi function digital meter (VAF & PF) - 01 No (f) Indicating lamp - 01 No (Set of three)
Supply and install hot dip galvanised octagonal poles with 1 mtr single arm bracket 40 mm dia for street light with camauflaged weather proof junction box ,electrical control gears,inside cable termination and earth connection of height 7 mtr top dia 70 mm.bottom dia 130 mm, sheet thickness 3 mm and base plate dimension 225x225x12 mm incl foundation bolts all as specified and directed including MCB SP 6 Amps.
Supply and fix sheethed cable, flexible 3 core 1.5 sqmm un armoured copper cable for connecting from junction box to street light fitting all as specified and as directed.
Supply and spread riddled soil in trenches for cable cushioning by using IS sieve to seperate the composite particle and refilling in trenches as cushining and rammed down to form a solid bed all as specified and directed. Note : Punned thickness shall be measured for payment purpose.The mesh of the screen through which the soil is riddled shall not exceed 12.5 mm IS sieve.
Supply and fixing VTPN DB 4 way, 4 pole double door IP-43 protection complete all as specified and directed.
Supply and fixing MCCB 63Amp 4 pole,415 volts breaking capacity 10KA complete all as specified and directed.
M &L for earthing complete with galvanised steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by alternate layer of common salt and charcoal 15 cm thick, connected to and including galvanised iron earth lead 32x6 mm GI strip by means of bolts, nuts, check nuts and washers of galvenised iron or steel and earth strip protected by GI pipe 40 mm dia light grade and connected from earth plate electrode to main switch board/ earthing test point or upto 7.5 mtr whichever is less including watering arrangement using 20mm GI pipe light grade, MS funnel with wire mesh, PCC chamber pit in PCC 1:3:6 type C-1, 40 mm thick pre-cast RCC cover re-inforced with 8mm dia TMT bars @ 10cm C/C on both sides and handle, excavation and earth work in any type of soil and removal upto 50 mtr complete all as specified and shown in electrical plate No 03 of SSR Part-I, all as specified and directed including testing on completion.
Items for rerouting Removing of HT cable XLPE 3 core 185 Sqmm carefully with connecting items all as directed by Engg-in-Charge. Note: If any damage occurs during excavtion, defect rectifications is under the scope of the contractor with his own expenses
Relaying of HT Cable XLPE 3 core 185 Sqmm carefully with all connecting items all as directed by Engg-in-Charge.
Supply & Fixing cable jointing kit for straight through heat shrinkable type joint with Each jointing material and all connected accessories for XLPE armoured conductor cable 1100 Volts grade of size 4 Core x 10 sqmm including taking down of old one, all as specified and as directed.
All as per item No 126 above but size 3.5/4 Core 16 sqmm all as specified and as directed.
All as per item No 126 above but size 3.5 Core 35 sqmm to 50 sqmm all as specified and as directed.
M&L for removing LT cable of any size all as directed.
M&L, for dismantling of old tubler poles duly removing all connection, dismatling PCC platform and taken out from the site all as specified and as directed.
M&L, for dismantling of old concrete poles duly removing all connection, dismatling PCC platform and taken out from the site all as specified and as directed.
M&L, for shifting of Panels of any size and type from one place to another place duly removing all connection care fullywithout any damages and losses any parts, dismatling PCC platform and mount on PCC at place and necessary Painting with two coats of aluminium paint over one coat anti corrossive paint, including preparation of surface, by removing old paint, proper cleaning, filling cavities with filler should applied internally and externally and reconnect the cable and all connected accessories, size all as as directed.
Cutting existing road/hardstand of any type by using crow bar chisel uprto a depth of 30 cm for laying Gl pipe including making good the surface by returning filling watering ramming in layers cold bitumen over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engineer- in-Charge.
M&L Removing and refixing of 6 m long octogonal Pole with street light any size and Ea any capacity and refixing in new location including foundation, nuts and bolts and connection complete, removing base plate and nut bolts incl earth work to brake the PCC foundation, all as specified and directed by Engg-in-Charge.
M&L removing of 3-4m post top Light, and post top latern of any size and any Ea capacity to MES Store and removing base plate and nut bolts incl earth work to brake the PCC foundation, all as specified and directed by Engg-in-Charge.
TELE/ TV SOCKET Supply and fix TV socket 1 module all as specified and as directed.
Supply and fix Tele socket 1 module all as specified and as directed.
Supply and fix inner and outer modular cover plate all as specified and as directed.
FIRE FIGHTING Supply, installation, testing & commissioning fire pump electrically driven horizontal end suction, centrifugal type confirming to IS- 12469 :1988 with CI Casing , bronze impeller and Stainless steel shaft mounted on heavy duty bearings suitable for continuous automatic operation with 'range of operation' 0% to 150% of rated capacity for 440 V, 3 Phase, 50 Hz, 70 mtr head, 2850 LPM discharge all as specified and directed. Note: Pump comman base frame (fabricated mild steel channel frame or cast iron type) placed of RCC 1:2:4 including foundation bolt and nut, including air release cock, priming valve, armoured copper cable from pump to panel through PVC conduit.
Supply, install, testing & commissioning Jockey pump horizontal end suction centrifugal type confirming to IS- 12469: 1988 with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous automatic operation with nonover loading power characteristics for frequent start / stop operations for 440 V, 3 phase, 50 Hz, 70 m head 180 LPM discharge all as specified and directed. Note : Pump comman base frame (fabricated mild steel channel frame or cast iron type) placed of RCC 1:2:4 including foundation bolt and nut, including air release cock, priming valve, armoured copper cable from pump to panel through PVC conduit.
Supply, install, testing & commissioning Fire pump diesel engine driven horizontal end suction, centrifugal type confirming to IS- 12469 1988 with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous automatic operation with 'range of operation' 0 % to 150 % of rated capacity for 440 V , 3 phase, 50 Hz AC supply, 70 mtr head, 2850 LPM discharge all as specified and directed Note : Necessary suitable arrangements for automatic integration of all motors including diesel tank of suitable capacity of pump with common base frame (fabricated mild steel channel frame or cast iron type) placed on RCC 1:2:4 including foundation bolt and nut, including air release cock, primimg valve, armoured copper cable from pump to panel through PVC conduit.
Supply, laying and testing of Flanged type Ductile Iron pipes 150 mm dia centrifugally cast (spun), Class K-9, with flanged ends conforming to IS 8329, in any lengths laid in trenches complete all as specified and as directed.
Supply and fix automatic gunmetal air release valve 25 mm dia complete all as specified and directed.
Supply, install, commissioning and testing of single loop fire alarm control panel with 99 detectors and 99 modules complying with BS EN 54 and up to 200 detectors and modules per loop, the panel is to be installed and commissioning with all necessary wiring, connections, testing etc. The panel is to be installed in non air conditioned environment. The equipment shall be suitable for the atmosphere with humid condition all as specified and directed.
Supply, lay, testing and commisioning of flexible 2 core 1.5 Sqmm copper conductor, PVC insulated, cross laid up, overall aluminium Mylar tape shielded along with ATC drain wire PVC outer sheated cable laid in existing complete as required and as directed (for MCP)all as specified and directed.
S&F wall mounted LED emergency Exit signage luminaire Lit up using regular mains supply comes with a unique rechargeable Ni-Cd battery capable of emergency back up upto 05 hours all as specified and directed.
Supply and installation, testing and commissioning of Analog Addressable type Active Loop Repeater (Loop power/ external power) Fire terminal with inbuilt turbo isolator, Backlit LCD Display 6x40 characters display, having Controls For Reset, Mute, Accept, Silence alarms and Self Test, with programmable free keys and Duly Approved by EN54/LPCB/VDS/FM Make: SIEMENS/ NOTIFIER/ BOSCH all as specified and directed.
S&F Foot valve, ball type 150mm dia, cast iron complete all as specified and as directed.
S&F Foot valve, ball type 100mm dia, cast iron complete all as specified and as directed.
S&F Ball valve ball type 40mm dia GM 200 brass vlave complete all as specified and as directed.
AVIATION OBSTRUCTION LIGHT Supply and fix avaiation obstruction light LED type comprising of aluminium housing with polycarbonate enclosure all as specified and as directed. Make : Bajaj Vat No BGAV 302 LED or equivalent in specification as approved by GE.
machine room and near ground floor landing door and over load indicator with suitable for three phase,415 Volts,50 Hz AC Supply for passenger lift including all connected civil works, Electrical works of every nature from the outgoing terminal of mainswitch/MCCB. Seperate circuit of power supply for light & machine,MCB/RCCB etc LED bulkhead fitting & power switch sockets in each floor landing in lift shaft complete all as per OEM Specification/ GA Drawing and including provisions as mentioned in particular specification all as specified and as directed.
All as per item No 153 above but suitable for capacity 544 Kg, 8 passenger and to serve ground floor and Nine upper floors (G+9), 10 Stops complete all as specified and as directed.
HOT WATER SUPPLY Supply and fix electric water heater,storage type steel body with copper inner tank and heating element upto 2 KW capacity 15 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc. all as specified and as directed.
ELECTRIC CHIMNEY Supply and fixing modular electric chimney of size not less than 60 cm, maximum air flow >1200(m3/h), glass filterless chimney with inverter technology, BLDC motor, oil filter, three speed motion control, LED light lamp, good colour finish, heat auto Clean Technology, Easy to clean, Touch controls, Max noise level 55-68dB complete including Aluminium flexible pipe, ducting and chimney insulation all as specified and directed.
DG SET Supply, installation, testing & commissioning , Out door type, Accoustic enclosed silent type diesel engine driven generating set comprising of capacity 100 KVA / 80 KW, 415 volts, 3 phase 4 wire, 1500 RPM 0.8 Power factor, 50 Hz directly coupled with diesel engine capable of taking 10% overload for one hour for every 12 hours (as per BS-5514/649) coupled directly to alaternator mounted on a rigid bed plate with suitable acoustic enclosure as per latest CPCB IV norms and complete with standard control panel ,battery and battery lead and fuel tank of suitable capacity with flexible coupling mounted on common base plate on vibration pads , foundation as recommended by manufacturer including AMF panel alongwith connected accessories with relay panel for automatic starting on main electric supply failure, control panel having meters, AVR control excitation. Genset Controller consists of Engine parameters like R.P.M, Liquid / Cylinder Temperature, Oil Pressure, Fuel level indication, Engine Hours run & Alternator parameters like Voltage, Frequency, Amps, KW, KVAR, PF etc. The DG set shall comprise of electric starter motor, turbo charger, water cooled and comprising all standard fittings/fixtures, first fill of Lube oil, coolent, fuel for testing and all piping etc as below:-
Note : The following are included in the scope of work :- (a) The panel will be complete with internal wiring with suitable size of multi stranded copper cable. The suitable control of AMF panel with all meters, control wires. (b) Tools as supplied by the manufacturer (c) Fuel tank shall be provided inside canopy (d) thermostat switch inside the acoustic enclosure shall be provided to shut off the DG set incase of temperature increases beyond its rated temperature inside the acoustic enclosure (e) there shall be proper air circulation and windows with glass in the acoustic enclosure suitably located to read the meters of various controls from outside (f) Necessary grouting including mild steel work and anti vibration pad shall be provided (g) necessary foundation of installation and plinth protection of the DG set shall be provided as per manufactuers recommendation (h) necessary 10% overload test shall be carried out in the presence of testing officer nominated by Accepting Officer. (j) Shifting of DG set from showroom/factory to the site by means of truck/crane is the responsibility of the contractor.
S&F feeder pillar box out door type made out of MS sheet 3 mm thick welded on angle iron frame 40 x 40 x 6 mm duly grouted in earth incl PCC 1:3:6 type C1 with locking arrangement and painting with following accessories suitable for incoming/outgoing arrangements :- (a) 4 pole MCCB 160, 50 Hz, 415 volt 25 KA - 01 No (Incoming) (b ) 4 pole MCCB 63 Amp, 50 Hz, 415 volt 25 KA - 03 No (Lift VTPN -01, VTPN -02 & Spare -01 No) (c ) 4 pole MCCB 40 Amp, 50 Hz, 415 volt 25 KA - 02 No ( WS-01 & spare- 01) (d) MCB SPN 32A 230Volts - 02 No( along with timer switch Astro type having longitude and latitude of Indian cities in memory) (e) MCB TPN 6-32 A - 02 No (e) Aluminium bus bar 300 Amp TPN - 01 set (f) Multi function digital meter (VAF & PF) - 01 No (g) Indicating lamp - 01 set of three S&F feeder pillar box out door type made out of MS sheet 3 mm thick welded on angle iron frame 40 x 40 x 6 mm duly grouted in earth incl PCC 1:3:6 type C1 with locking arrangement and painting with following accessories suitable for incoming/outgoing arrangements :-
(a) 4 pole MCCB 160, 50 Hz, 415 volt 25 KA - 01 No (Incoming) (b ) 4 pole MCCB 63 Amp, 50 Hz, 415 volt 25 KA - 03 No (Lift VTPN -01, VTPN -02 & Spare -01 No) (c ) 4 pole MCCB 40 Amp, 50 Hz, 415 volt 25 KA - 02 No ( WS-01 & spare- 01) (d) MCB SPN 32A 230Volts - 02 No( along with timer switch Astro type having longitude and latitude of Indian cities in memory) (e) MCB TPN 6-32 A - 02 No (e) Aluminium bus bar 300 Amp TPN - 01 set (f) Multi function digital meter (VAF & PF) - 01 No (g) Indicating lamp - 01 set of three
M&O - SCADA OPERATED STP Operation of MBBR based SCADA oprated STP 80 KLD in three shifts a day (each shift of eight hours) including sundays and holidays during defect liability period for First year. Minimum number of operator per shift per STP plant shall be one operator. Operator employed shall have experience of minimum 2 year to operate STP plant operation of SCADA complete all as specified. Note: (a) Record/ daily log sheet shall be maintained in log book by the operator and should be approved by Engineer-in-Charge. (b) daily cleaning of floor area and maintaining a good and hygineic sanitation around the installation. (c) sationery items such as registers, log book etc should be provided by the contractor. (d) Non providing of operator in a day by the contractor shall invite penalty of Rs 600/- per shift from his due amount. (e) All operator shall be provided with uniform as approved by Enineer in charge.
All as per item No 159 above but for second year all as specified and as directed.
All as per item No 161 & 161.1 above but for Second year all as specified and as directed.
All as per item No 161 & 161.1 above but for Third year all as specified and as directed.
All as per item No 161 & 161.1 above but for Fourth year all as specified and as directed.
All as per item No 161 & 161.1 above but for Fifth year all as specified and as directed.
All as per item No 161 & 161.1 above but for Sixth year all as specified and as directed.
All as per item No 161 & 161.1 above but for Seventh year all as specified and as directed.
All as per item No 161 & 161.1 above but for Eighth year all as specified and as directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.56 MB
Tender.pdf
Tender Documents • 1.99 MB
Prepriced_Sch.pdf
Tender Documents • 0.47 MB
BOQ_845314.xls
BOQ • 4.54 MB
Download all tender documents and submit your bid