Augmentation and Improvement of Power Supply System of Service buildings with Rewiring in various sections of Kota Division
EL-50-326-2026-27
EL-50-326-2026-27
Open
Works - General
9 Months
Kota, Rajasthan
₹0
₹4.9 L
16 Jul 2026
16 Jul 2026
23 Jul 2026
A-Electrical Schedule A
Supply and fabrication of (A) complete uni pack CSS 1 of with 01 no. 11 KV 500 KVA Dry type Transformer, HT Switchgear with 03 VCB arrangement, GI enclosure and LT distribution 01 board Incoming - ACB 800 Amp. - 02 Nos. and Outgoing - MCCB 400 AMP. 4 Pole - 6 Nos. with tie- feeder as per specification. (B) complete uni pack CSS 2 of with 01 no. 11 KV 500 KVA Dry type Transformer, HT received from CSS-1, GI enclosure and LT distribution board Incoming - A CB 800 Amp. - 02 Nos. and Outgoing - MCCB 400 AMP. 4 Pole - 6 Nos. with tie-feeder and 150 KVAR APFC Panel as per specification.
Installation, testing & commissioning including civil work of (A) complete uni pack CSS 1 of with 01 no. 11 KV 500 KVA Dry type Transformer, HT Switchgear with 03 VCB arrangement, 02 GI enclosure and LT distribution board Incoming - ACB 800 Amp. - 02 Nos. and Outgoing - MCCB 400 AMP. 4 Pole - 6 Nos. with tie-feeder as per specification. (B) complete uni pack CSS 2 of with 01 no. 11 KV 500 KVA Dry type Transformer, HT received from CSS-1, GI enclosure and LT distribution board Incoming - ACB 800 Amp. - 02 Nos. and Outgoing - MCCB 400 AMP. 4 Pole - 6 Nos. with tie- feeder and 150 KVAR APFC Panel as per specification.
Supply of 75 KvAr Automatic Power Factor Correction Panel (APFC Panel) as per specification attached.
Installation, Testing & Commissioning including civil work of 75 KvAr Automatic Power Factor Correction Panel (APFC Panel) as per specification attached.
Supply and installation of unit maintenance free earth material as per RDSO Specs.No. RDSO/SPN/197/2008 orlatest as pertechnical spec. 1861000.0
Supply & fabrication of 315 KVA, 11/0.433 KV CRT DRY Type Copper Wound Package Sub Station as per detailed specification.
Installation, testing & commissioning including civil work of 315 KVA, 11/0.433 KV CRT DRY Type Copper Wound Package Sub Station as per detailed specification.
Supply of HT Vaccum Circuit Breaker 11 kV, 400 to 800 Amps. With standard fitting as per IS 13118/1991 or latest along with power pack as per details.
Erection, Wiring, Testing & Commissioning including civil work of HT Vaccum Circuit Breaker 11 kV, 400 to 800 Amps. With standard fitting as per IS 13118/1991 or latest along with power pack as per details.
Supply of 11 KV Outdoor type extensible 03 way Ring Main Unit (RMU) Floor Mounted, Consisting of 02 no. Incoming 630 Amp. Fixed Manual Load Break Switch and 01 no. Outgoing Fixed Manual Vaccum Circuit Breaker as per attched Detailed Specification Annexure.
Installation, Testing & Commissioning including civil work of 11 KV Outdoor type 11 extensible 03 way Ring Main Unit (RMU) Floor Mounted, Consisting of 02 no. Incoming 630 Amp. Fixed Manual Load Break Switch and 01 no. Outgoing Fixed Manual Vaccum Circuit Breaker as per attched Detailed Specification Annexure.
Supply of Stranded compacted circular aluminium conductor A2XFY conductor screened with extruded , semi conducting compound XLPE insulated screened with extruded semi 12 conducting compound in combination with copper tape (0.3 kA to 1 sec) core laid up inner sheath (ST-2) PVC galvanized steel strip armoured and overall PVC sheathed black cable HT cable size 3 core x 95 sqmm suitable for 11 kV(E) 6.6 kV (UE) confirming to IS 7098 (Part-II) 1985 /with latest amendments.
Supply of Stranded compacted circular aluminium conductor A2XFY conductor screened with extruded , semi conducting compound XLPE insulated screened with extruded semi 13 conducting compound in combination with copper tape (0.3 kA to 1 sec) core laid up inner sheath (ST-2) PVC galvanized steel strip armoured and overall PVC sheathed black cable HT cable size 3 core x 70 sqmm suitable for 11 kV(E) 6.6 kV (UE) confirming to IS 7098 (Part-II) 1985 /with latest amendments.
Laying, testing and commissioning of Stranded compacted circular aluminium conductor A2XFY conductor screened with extruded , semi conducting compound XLPE insulated 14 screened with extruded semi conducting compound in combination with copper tape (0.3 kA to 1 sec) core laid up inner sheath (ST-2) PVC galvanized steel strip armoured and overall PVC sheathed black cable HT cable size 3 core sqmm suitable for 11 kV(E) 6.6 kV (UE) confirming to IS 7098(Part-II) 1985 /with latest amendments.
Laying of 4 core circular armoured ISI marked XLPE cable size 4 core aluminum conductor 1100 volt with connection etc. Note : Cable will be supplied by Railway.
Supply of 11 kV cable end box outdoor type heat shrinkable type for 11kV XLPE 3 core 50-95 sqmm size and connection with crimped lugs on cable end box.
Fixing, testing & commissioning of 11 kV cable end box outdoor type heat shrinkable type for 11kV XLPE 3 core 50-95 sqmm size and connection with crimped lugs on cable end box.
Supply of GO switch 11KV 400Amp 3pole with 9 Nos insulators operating handle along with locking arrangement system hot deep galvined vertical type .
Erection, testing & commissioning of GO switch 11KV 400Amp 3pole with 9 Nos insulators operating handle along with locking arrangement system hot deep galvined vertical type .
Supply of DO switch fuse 11KV 400Amp pole operated outdoor vertical mounting expulsion type having hot deep galvined base post type insulator and fiber glass fuse carrier.
Erection, testing & commissioning of DO switch fuse 11KV 400Amp pole operated outdoor vertical mounting expulsion type having hot deep galvined base post type insulator and fiber glass fuse carrier.
Supply of 11KV gapless metal oxide lighting arrester complete with hardware, fixtures, hot dipped galvanised pin, nut, bolts, washers etc to relevant ISS.
Erection,testing & commissioning of 11KV gapless metal oxide lighting arrester complete with hardware, fixtures, hot dipped galvanised pin, nut, bolts, washers etc to relevant ISS.
Supply of material and Providing of copper plate Earthing arrangement by digging the Pit. Copper Plate size 600 X 600 X 3 mm as per drg.No.DRM/KOTA/01927/ELR.
Supply of material & providing GI. pipe earthing arrangement by digging the pit as 25 per DRM/KTT's Drg. No. 01913EL/R1 or latest complete in all type of soils including rocky area. Earth value will be taken by the contractor in the presence of Railway representative and written on the earth pit by the contractor.
Supply of service pipe 'B' class G.I. 25 mm. dia 3 meters long complete with G.I bend, 26 painted MS clamps of 40x6 mm flat, stay wire, stay insulators and fixing of 2 nos. MS clamp on rigid support or reg bolts, washer & nuts as per Drg. No. Ktt/01624/EL or latest. One no. MS Clamp to be provided for binding of LT armoured cable.
Fixing & commissioning of service pipe 'B' class G.I. 25 mm. dia 3 meters long 27 complete with G.I bend, painted MS clamps of 40x6 mm flat, stay wire, stay insulators and fixing of 2 nos. MS clamp on rigid support or reg bolts, washer & nuts as per Drg. No. Ktt/01624/EL or latest. One no. MS Clamp to be provided for binding of LT armoured cable.
Digging of trench in pucca trench in yard /platform 50cm. deep and 35cm. wide including replaster on surface by cement oncrete after laying of cable.
Digging of trench in all type of soils/road cutting 100 cm. deep and 50cm. wide including supply and laying of "B" class bricks on both side & top of the cable and refilling the trench after laying of cable.
Drilling of Horizontal bore below track/road by pushing method for laying of HDPE/DWC pipe of various size.
Supply of material, providing, commissioning and laying of DWC/HDPE pipe of 160/138 mm dia cabling under road/track. As per explanatory notes.
Supply of heavy duty ISI marked B class GI pipe of 3.65 mm wall thickness & 50 mm diameter to be laid along the wall or floor with proper galvanized clamp through the wall or underneath the floor in cement concrete.
Laying & fixing of heavy duty ISI marked B class GI pipe of 3.65 mm wall thickness & 50 mm diameter to be laid along the wall or floor with proper galvanized clamp through the wall or underneath the floor in cement concrete.
Supply of heavy duty ISI marked B class GI pipe of 80 mm diameter with suitable clamps on rail/pole/joists with nut/bolts and GI socket as per site requirement.
Laying & fixing of heavy duty ISI marked B class GI pipe of 80 mm diameter with suitable clamps on rail/pole/joists with nut/bolts and GI socket as per site requirement.
Supply of material of RCC hume pipe 6" dia (150mm) as per IS: 456-1978 or latest in existing trench under Railway track including jointing and all required accessories etc.
Laying of RCC hume pipe 6" dia (150mm) as per IS: 456-1978 or latest in existing trench under Railway track including jointing and all required accessories etc.
Supply & fabrication of LT Distribution panel suitable for outdoor use with canopy and double door type with stand as under, INCOMING CIRCUIT-01 No. MCCB 4 pole 400 Amp. 50 KA MP 38 based LSIG Adj. O/L Adj. S/C. Ampere meter with selector switch -01 no., voltmeter with selector switch -01 no., indication lamp RYB 03 nos., Change over 01 no., Energy meter - 01 no., CT 400/5- 03 nos., Copper busbar 400 Amp. rating- 01 set, MCB 6A SP C 10KA - 04 nos.. OUTPUT CIRCUIT - 04 no. MCCB 3pole 200 Amp. 36 KA TMD, 02 no. MCCB 3pole 100 Amp. 36 KA TMD. All MCCB in incoming and outgoing circuit will provided with HRC Fuse etc. as per attached detailed specification.
Installation, testing & commissioning of LT Distribution panel suitable for outdoor use with canopy and double door type with stand as under, INCOMING CIRCUIT-01 No. MCCB 4 pole 400 Amp. 50 KA MP based LSIG Adj. O/L Adj. S/C. Ampere meter with selector switch -01 no., voltmeter 39 with selector switch -01 no., indication lamp RYB 03 nos., Change over 01 no., Energy meter - 01 no., CT 400/5- 03 nos., Copper busbar 400 Amp. rating- 01 set, MCB 6A SP C 10KA - 04 nos.. OUTPUT CIRCUIT - 04 no. MCCB 3pole 200 Amp. 36 KA TMD, 02 no. MCCB 3pole 100 Amp. 36 KA TMD. All MCCB in incoming and outgoing circuit will provided with HRC Fuse etc. as per attached detailed specification.
Supply & fabrication of LT distribution board fabricated with MS angle Size 40X40X5 mm with door and locking arrangement duly painted red oxide and power coated enamel paint consisting of following items - IN COMING - MCCB TPN 4P 250 Amp. Breaking capacity 35 KA - 01 NO. 40 , Ampere meter with selector switch 0-300 Amp.-01 no., voltmeter with selector switch 0-500 volt - 01 NO., indication lamp RYB 03 nos., fuse for indication 05 nos., CT 300/5- 03 nos., busbar 400 Amp. rating- 01 set. & busbar insulator-1 set, Changeover 4P 400 Amp. - 01. OUT GOING - MCCB 200 Amp. 4P breaking capacity 25 KA- 02 nos. and MCCB 100 Amp. 4P breaking capacity 25 KA- 02 nos. Complete in all respect. All MCCB in incoming and outgoing circuit will provided with HRC Fuse etc. as per attached detailed specification.
Installation, testing & commissioning of LT distribution board fabricated with MS angle Size 40X40X5 mm with door and locking arrangement duly painted red oxide and power coated enamel paint consisting of following items - IN COMING - MCCB TPN 4P 250 Amp. Breaking 41 capacity 35 KA - 01 NO. , Ampere meter with selector switch 0-300 Amp.-01 no., voltmeter with selector switch 0-500 volt -01 NO., indication lamp RYB 03 nos., fuse for indication 05 nos., CT 300/5- 03 nos., busbar 400 Amp. rating- 01 set. & busbar insulator-1 set, Changeover 4P 400 Amp. - 01. OUT GOING - MCCB 200 Amp. 4P breaking capacity 25 KA- 02 nos. and MCCB 100 Amp. 4P breaking capacity 25 KA- 02 nos. Complete in all respect. All MCCB in incoming and outgoing circuit will provided with HRC Fuse etc. as per attached detailed specification.
Supply of octagonal galvanized steel pole 5 mtr long with foundation bolts, Double arm type etc. with junction box and cover complete. (a)Pole ID-BOP 5030 (b)Height-5 meter ©Top- 42 7 0 m m (d)Bottom-130mm (e)Thickness-3mm (f)Base plate-200x200x12 mm (g)Foundation bolts- PCD-200 : bolt size 4x16mmx600mm long (IS:1367,Part-III) (h)Double arm brackets (i) Foundation size (WxLxH) 500x500x1000 mm. Note:-1. Octagonal steel poles with foundation bolts should be confirming to std. 35 grade. Base Plate IS 226/IS 2062. Grade of PCC should be M-20 2. All material will be supplied by contractor.
Erection, testing & commissioning of octagonal galvanized steel pole 5 mtr long with foundation bolts, Double arm type etc. with junction box and cover complete. (a)Pole ID-BOP 5030 43 (b)Height-5 meter ©Top-70mm (d)Bottom-130mm (e)Thickness-3mm (f)Base plate-200x200x12 mm (g)Foundation bolts-PCD-200 : bolt size 4x16mmx600mm long (IS:1367,Part-III) (h)Double arm brackets (i) Foundation size (WxLxH) 500x500x1000 mm. Note:-1. Octagonal steel poles with foundation bolts should be confirming to std. 35 grade. Base Plate IS 226/IS 2062. Grade of PCC should be M-20 2. All material will be supplied by contractor.
Supply of LED Street light fitting 30 watt suitable for 230 V AC.
Installation, testing & commissioning of LED Street light fitting suitable for 230 V AC.
Supply of 'B' class GI pipe fitting made for 40mm dia for fixing of CFL fittings with all required accessories i.e. MS clamps, nut bolt washers etc.
Fixing of 'B' class GI pipe fitting made for 40mm dia for fixing of CFL fittings with all required accessories i.e. MS clamps, nut bolt washers etc.
Supply and erection of concrete for foundation and plinth in other than hard soil & rock as per explanatory notes.
Supply and erection of fencing panel & gates at sub-station .
Supply and erection of fencing up right.
Supply and spreading of gravels/ballast.
Filling with supply of soil to make even surface.
Dismantling, Erection, testing & commissioning (including transportation) of 53 Transformer / LT Panel including civil work complete in all aspect as per attached detailed. All material regarding civil work & other will be provided by contractor. Note : Transformer will be installed on the Structure provided by railway.
Fabrication of suitable size covered shed by supply of material for protection of LT Panel from rain.
Supply & fixing of 4 pole ON Load Changeover Switch in Steel Sheet Enclosure, Rating-400 Amps., 415V, 50Hz, confirming to IS/IEC 60947-3 Door Interlock and Padlock facility as per detailed specification attached.
Supply of LED tube light Box type Luminaire 20 watt complete with tube suitable for 230 V AC.
Fixing, testing & commissioning of LED tube light Box type Luminaire 20 watt complete with tube suitable for 230 V AC.
Supply of BEE 5 star rated energy efficient BLDC ceiling fan, sweep size : 1200mm, complete with wiring connection etc. as per detailed specification attached.
Erection and fixing of BEE 5 star rated energy efficient BLDC ceiling fan, sweep size : 1200mm, complete with wiring connection etc. as per detailed specification attached.
Supply of Recess mounting fitting LED Panel 36 Watt in 2' x 2' size.Optics diffuse for 230 Volt, 50 hz cut out size 595 x 595 mm.
Fixing, testing & commissioning of Recess mounting fitting LED Panel 36 Watt in 2' x 2' size.Optics diffuse for 230 Volt, 50 hz cut out size 595 x 595 mm.
Supply of exhaust fan sweep size 300 mm suitable for 230 volt AC 50 Hz complete with accessories.
Fixing, testing & commissioning of exhaust fan sweep size 300 mm suitable for 230 volt AC 50 Hz complete with accessories.
Supply of wall mounted bracket fan sweep 400 mm suitable for 230 volts , 50 hz moving type with regulator and control switch on & off with accessories.
Fixing of wall mounted bracket fan sweep 400 mm suitable for 230 volts , 50 hz moving type with regulator and control switch on & off with accessories.
Supply of Flykill-LITE Insect killer machine approximate:26 Inch L X 4.5 Inch W X 12.5 Inch H. Two tubes 18W X 2 ,Aluminium Body.
Installation, testing & Commissioning of Flykill-LITE Insect killer machine approximate:26 Inch L X 4.5 Inch W X 12.5 Inch H. Two tubes 18W X 2 ,Aluminium Body.
Supply of Bulkhead fitting with wiremesh suitable for 7/8/9 watts LED lamp with LED lamp 07 watts suitable for 230 Volts AC.
Fixing of Bulkhead fitting with wiremesh suitable for 7/8/9 watts LED lamp with LED lamp 07 watts suitable for 230 Volts AC.
Supply, installation, testing & commissioning of concealed wiring of light/Fan/Bell points in PVC rigid conduit pipe size 25mm dia medium class minimum thickness approx. 1.6mm to 70 1.8mm of ISI mark with 1.5 sq.mm. multistrand PVC insulated copper conductor cable confirming to IS:694-1990 or latest with one holder/ceiling rose on junction box with round plate with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing alongwith connection etc. including stone wall cutting, replaster, painting and other civil work
Supply, installation, testing & commissioning of concealed wiring of sub main phase & 71 neutral in PVC rigid conduit pipe size 25mm dia medium class minimum thickness approx. 1.6mm to 1.8mm of ISI mark with 4 sq.mm. PVC insulated single core multistrand copper cable with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing & connection etc. Separate PVC pipe to be provided for this item.
Supply, installation, testing & commissioning of concealed wiring of sub main phase & 72 neutral in PVC rigid conduit pipe size 25mm dia medium class minimum thickness approx. 1.6mm to 1.8mm of ISI mark with 6 sq.mm. PVC insulated single core multistrand copper cable with 2.5 sq.mm. PVC insulated copper wire green coloured for earthing & connection etc. Separate PVC pipe to be provided for this item.
Supply of material, wiring, testing & commissioning of light /fan point in PVC casing caping size 38/40mm, ISI mark with 1.5 sq.mm. multistrand PVC insulated unsheathed copper cable with 2.5 sq.mm. PVC insulated stranded copper wire green colour for earthing with connection etc.
Supply of material & wiring of sub main phase and neutral in PVC casing caping 25 74 mm. with 4 mm² single core multistrand copper cable and 2.5 sq.mm PVC insulated copper stranded green colour wire for earthing alongwith wiring and connections Note- (i) Separate PVC casing caping to be provided for this item. (ii) All material needed for this item are to be supplied by the contractor.
Supply of material & wiring of sub main phase and neutral in PVC casing caping 25 75 mm. with 6 mm² single core multistrand copper cable and 2.5 sq.mm PVC insulated copper stranded green colour wire for earthing alongwith wiring and connections Note- (i) Separate PVC casing caping to be provided for this item. (ii) All material needed for this item are to be supplied by the contractor.
Supply of flush metal box of 12-Module with connection used for concealed modular flush metal box wiring.
Erection & fixing of flush metal box of 12-Module with connection used for concealed modular flush metal box wiring.
Supply of plate Inner & Outer 12-Module used for concealed modular wiring.
Erection & fixing of plate Inner & Outer 12-Module used for concealed modular wiring.
Supply of flush metal box of 8-Module with connection used for concealed modular flush metal box wiring.
Erection & fixing of flush metal box of 8-Module with connection used for concealed modular flush metal box wiring.
Supply of material & fixing of plate Inner & Outer 8-Module used for concealed modular wiring.
Supply of material & fixing of plate Inner & Outer 8-Module used for concealed modular wiring.
Supply of flush metal box of 6-Module with connection used for concealed modular flush metal box wiring.
Erection & fixing of flush metal box of 6-Module with connection used for concealed modular flush metal box wiring.
Supply of plate Inner & Outer 6-Module used for concealed modular wiring.
Erection & fixing of plate Inner & Outer 6-Module used for concealed modular wiring.
Supply of flush metal box of 4-Module with connection used for concealed modular flush metal box wiring.
Erection & fixing of flush metal box of 4-Module with connection used for concealed modular flush metal box wiring.
Supply of plate Inner & Outer 4-Module used for concealed modular wiring.
Erection & fixing of plate Inner & Outer 4-Module used for concealed modular wiring.
Supply of flush metal box of 2-Module with connection used for concealed modular flush metal box wiring.
Erection & fixing of flush metal box of 2-Module with connection used for concealed modular flush metal box wiring.
Supply of plate Inner & Outer 2-Module used for concealed modular wiring.
Erection & fixing of plate Inner & Outer 2-Module used for concealed modular wiring.
Supply of S.P. switch 6 / 10 Amp. one way (1-Module).
Erection & fixing of S.P. switch 6 / 10 Amp. one way (1-Module).
Supply of 6 Amp. 5-pin socket (2-Module).
Erection & fixing of 6 Amp. 5-pin socket (2-Module).
Supply of fan regulator 5-step (2-Module) used for concealed modular wiring.
Erection & fixing of fan regulator 5-step (2-Module) used for concealed modular wiring.
Supply of S.P. switch 16 Amp. one way (1-Module) used for concealed modular wiring.
Erection & fixing of S.P. switch 16 Amp. one way (1-Module) used for concealed modular wiring.
Supply of 6/16 Amp. 6-pin combined shuttered socket (2-Module) used for concealed modular wiring.
Erection & fixing of 6/16 Amp. 6-pin combined shuttered socket (2-Module) used for concealed modular wiring.
Supply of blank plates (1-Module) used for concealed modular wiring.
Erection & fixing of blank plates (1-Module) used for concealed modular wiring.
Supply of material of Surface type PVC board of 12-Module with connection used for PVC casing caping wiring.
Erection & fixing of Surface type PVC board of 12-Module with connection used for PVC casing caping wiring.
Supply of material of Surface type PVC board of 6-Module with connection used for PVC casing caping wiring.
Erection & fixing of Surface type PVC board of 6-Module with connection used for PVC casing caping wiring.
Supply of Surface type PVC board of 4-Module with connection used for PVC casing caping wiring.
Erection & fixing of Surface type PVC board of 4-Module with connection used for PVC casing caping wiring.
Supply of Surface type PVC board of 2-Module with connection used for PVC casing caping / PVC rigid conduit pipe wiring.
Erection & fixing of Surface type PVC board of 2-Module with connection used for PVC casing caping / PVC rigid conduit pipe wiring.
Supply of distribution box as per model no. DBDD 12 or similar ans separate neutral 116 link with one MCB triple pole 63 Amp. Rating in the incoming and five nos. single pole 25 Amp. And 6 Amp. MCB for outgoing circuit. The internal wiring from 63 Amp. MCB to 25 Amp. MCB should be done with 10 sq.mm. copper PVC insulated conductor by distributing all three phase etc.
Installation, testing & commissioning of distribution box as per model no. DBDD 12 or 117 similar ans separate neutral link with one MCB triple pole 63 Amp. Rating in the incoming and five nos. single pole 25 Amp. And 6 Amp. MCB for outgoing circuit. The internal wiring from 63 Amp. MCB to 25 Amp. MCB should be done with 10 sq.mm. copper PVC insulated conductor by distributing all three phase etc.
Supply of MCB distribution board double door Wall mounted having MCCB 100 Amp TPN on incoming & 12 Nos MCB SP 06-32 Amp braking capacity 10 KA,on outgoing connected through busbar & equally distributed on 3- phase complete with connection.
Installation, testing & commissioning of MCB distribution board double door Wall 119 mounted having MCCB 100 Amp TPN on incoming & 12 Nos MCB SP 06-32 Amp braking capacity 10 KA,on outgoing connected through busbar & equally distributed on 3- phase complete with connection.
Supply of main distribution box 10 way suitable for housing MCB and ELCB with copper busbar and neutral link. Distribution box should be fixed on wooden taper plug or steel 120 fasteners etc. with providing and fixing of 01 no. MCB DP 32 Amp. breaking capacity 6 KA and 06 Nos. MCB SP 6-32 Amp. breaking capacity 6 KA with 01 No. ELCB 40 Amp. DP, sensitivity 100 m.Amp. and connections etc. The distribution board is to be fixed on wall with the help of rag bolt /fastener or on board and connecting the same with suitable size of wire duly crimped lugs.
Erection and fixing, testing, commissioning of main distribution box 10 way suitable for housing MCB and ELCB with copper busbar and neutral link. Distribution box should be fixed on 121 wooden taper plug or steel fasteners etc. with providing and fixing of 01 no. MCB DP 32 Amp. breaking capacity 6 KA and 06 Nos. MCB SP 6-32 Amp. breaking capacity 6 KA with 01 No. ELCB 40 Amp. DP, sensitivity 100 m.Amp. and connections etc. The distribution board is to be fixed on wall with the help of rag bolt /fastener or on board and connecting the same with suitable size of wire duly crimped lugs.
Supply of main distribution box 4+2 way suitable for housing MCB and ELCB with neutral link. Distribution box should be fixed on wooden taper plug or steel fasteners etc. with supply and fixing of 01 no. MCB SPN 16 Amp. breaking capacity 10 KA and 02 Nos. MCB SP 6-32 Amp. breaking capacity 10 KA with 01 No. ELCB 25 Amp. DP, sensitivity 30 m.Amp. and connections etc. The distribution board is to be fixed on wall with the help of rag bolt /fastener or on board and connecting the same with suitable size of wire duly crimped lugs.
Erection and fixing, testing, commissioning of main distribution box 4+2 way suitable for housing MCB and ELCB with neutral link. Distribution box should be fixed on wooden taper plug 123 or steel fasteners etc. with supply and fixing of 01 no. MCB SPN 16 Amp. breaking capacity 10 KA and 02 Nos. MCB SP 6-32 Amp. breaking capacity 10 KA with 01 No. ELCB 25 Amp. DP, sensitivity 30 m.Amp. and connections etc. The distribution board is to be fixed on wall with the help of rag bolt /fastener or on board and connecting the same with suitable size of wire duly crimped lugs.
Supply of material and wiring , testing and commissioning of light/fan point in PVC 124 rigid conduit pipe size 19/20 mm medium class with 1.5 sqmm multistrand PVC insulated copper conductor cable confirming to IS: 694-1990 or latest amd 2.5 sqmm PVC insulated copper wire coloured for earthing alongwith connections etc.
Supply of material and wiring , testing and commissioning of sub main phase and 125 neutral in PVC rigid conduit pipe size 25 mm dia. Medium class mark with 4 sq.mm. PVC insulated single core multistransd copper cable with 2.5 sq.mm. PVC insulated copper wire freen coloured for earthing and connection etc. Separate PVC pipe to be provided for this item.
Supply, Installation, Testing & Commissioning of Online UPS 2 KVA with battery and rack.
Supply of MCB DP 16Amp.
Erection & fixing of MCB DP 16Amp.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Clarification for Annexure V
ATTACHMENT
GCC_April-2022_Final.pdf
ATTACHMENT
Annexure of LC
ATTACHMENT
MakeinIndiapolicylatestamendment.pdf Make in India policy latest amendme
ATTACHMENT
500KVACSS12Specifictions.pdf
ATTACHMENT
Technical Specifications of LED
ATTACHMENT
GCCAdvanceCorrectionSlipNo11.pdf
ATTACHMENT
TenderSch.EL50-3262026-27_2.pdf
ATTACHMENT
Annexure-E.pdf
ATTACHMENT
DempoymentofEngineers.pdf
ATTACHMENT
CorrectionslipofGCC.pdf
ATTACHMENT
AnnexureLC-Inclusionofletterofcredit.pdf
ATTACHMENT
Clarification-Annexure-VofGCCwithTenders..pdf
ATTACHMENT
SpecificationofLEDLuminare-2026-1.pdf
ATTACHMENT
MakeinIndiapolicylatestamendment.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].