Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.8 LAccepted-Finance | L1 | Accepted-Finance OK | |
| 2 | L2₹5.9 L+₹1,331.68 (0.23%)Accepted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | L2 | Accepted-Finance OK | |
| 3 | L3₹6.1 L+₹30,046.24 (5.14%)Accepted-Finance | L3 | Accepted-Finance OK |
Tender Value
Refer Docs
EMD Value
₹12,200
Closing Date
8 Sept 2021, 2:15 pmClosed
EE
CHANDRAWAL WATER WORKS
Improvement in power factor by renovation/up-graduation of existing APFC panel to 925KVAR with other allied works at old pump house no. 2 okhla water works (Re-Invited).
2021_DJB_207847_1
N.I.T. NO. 06(2021-22)
Open Tender
Miscellaneous Works
Works
30 days
CHANDRAWAL WATER WORKS
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
DJBEMD A/c No-50448339804 THROUGH SUBPAISA GATEWAY
₹12,200
Yes
16 Oct 2021
2 Sept 2021
8 Sept 2021
2 Sept 2021
8 Sept 2021
2 Sept 2021
2 Sept 2021 - 8 Sept 2021
Dismantling of Existing Panel for all damaged switchgears,capacitors, measuring instruments, indicating lights, relay & removing / replacing defective wiring and mechanical connection at site & cleaning the Panel by CRC.
Supply of Shunt Power Capacitors 3 Ph, 415V AC 50 Hz MPP Heavy Duty in suitable banking for PF improvement. Make: - Siemens/L&T/BHEL/Crompton/Khatau/ABB/Any DJB aproved make.
MCCB of following ratings as back up to Capacitors to be fixed in Panel: 3.1) Supply of 20A TP MCCB (36KA) for 5 KVAR rating, Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C7S/Any DJB approved make.
3.2) Supply of 32A TP MCCB (36KA) for 10 KVAR rating,Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C7S/Any DJB approved make.
3.3) Supply of 40A TP MCCB (36KA) for 15 KVAR rating,Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C7S/Any DJB approved make.
3.4) Supply of 60A TP MCCB (36KA) for 20 KVAR rating,Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C7S/Any DJB approved make.
3.5) Supply of 80A TP MCCB (36KA) for 25 KVAR rating,Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C7S/Any DJB approved make.
Capacitors of following ratings Capacitors to be fixed in Panel: 4.1) Supply of Capacitor Duty Contactors MO C type for 5 KVAR rating, Any DJB approved make
4.2) Supply of Capacitor Duty Contactors MO C type for 10 KVAR rating, Any DJB approved make
4.3) Supply of Capacitor Duty Contactors Mo C type for 15 KVAR rating, Any DJB approved make
4.4) Supply of Capacitor Duty Contactors for MO C type 20 KVAR rating, Any DJB approved make
4.5) Supply of Capacitor Duty Contactors MO C type for 25 KVAR rating, Any DJB approved make
Supply of On/Off Indicating Lights 22.5 mm. (Gen next pro LED Indicator 22.5 ,4 digit colour, Blue & white)for capacitor banks
Start / Stop Push Buttons 22.5 mm. for capacitor banks
Control Contactors with Control wiring
Installation of Capacitors
Power Wiring fo all the above capacitors from Bus bar to MCCB, MCCB to Cap. Duty Contactors & from Contcators to Capacitors with Proper size Copper flexible cables
APFC (Automatic Power Factor Correction Relay),415 V,digital type with Display of Power Factor 12 Step, Any DJB approved make
Wiring of New APFC Relay with Existing APFC relay (to work in series)
Supply and fixing of Exhaust Fan in the Panel Controlled thru' Thermostate, Control MCB, wiring etc.
Modification/Upgradation & Painting in existing Panel & fixing additional panel to match with existing panel with Bus bars.
Replacement of weak /damage capacitor in existing panel with new MPP Heavy Duty Capacitors of respective banks (IF FOUND WEEK DURING WORK EXECUTION). Make:- Siemens/L&T/BHEL/Crompton/Khatau/ABB/Any DJB aproved make.
Testing & Commissioning of the APFC Panel with relavent IS Standard, Checking continuity, Earthing, MCCB Mechanism, alignment, Checking all functional Test, Setting APFC Relay parameters to achieve PF between 0.98-1.00.
CAPACITOR PANEL 2 (EXISTING 325 KVAR TO BE UPGRADED TO 425 KVAR) Dismantling of Existing Panel for all damaged switchgears, capacitors, measuring instruments, indicating lights, relay & removing / replacing defective wiring and mechanical connection at site & cleaning the Panel by CRC.
Supply of Additional Shunt Power Capacitors 3 Ph, 415V AC 50 Hz MPP Heavy Duty in suitable banking for PF improvement.
Supply of 20A TP MCCB (36KA) for 5 KVAR rating, Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C&S/Any DJB approved make.
Supply of 32A TP MCCB (36KA) for 10 KVAR rating, Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C&S/Any DJB approved make.
supply of 40A TP MCCB (36KA) for 15 KVAR rating Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C&S/Any DJB approved make.
Supply of 60A TP MCCB (36KA) for 20 KVAR rating Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C&S/Any DJB approved make.
Supply of 80A TP MCCB (36KA) for 25 KVAR rating Make:-L&T/Siemens/Havells/Indocop//MDS/Cutler Hammer/C&S/Any DJB approved make.
Capacitors of following ratings Capacitors to be fixed in Panel: Supply of Capacitor Duty Contactors MO C type for 5 KVAR rating, Any DJB approved make
Supply of Capacitor Duty Contactors MO C for 10 KVAR rating, Any DJB approved make
Supply of Capacitor Duty Contactors MO C type for 15 KVAR rating,Any DJB approved make
Supply of Capacitor Duty Contactors MO C type for 20 KVAR rating,Any DJB approved make
Supply of Capacitor Duty Contactors for MO C type 25 KVAR rating,Any DJB approved make
On/Off Indicating Lights 22.5 mm. for capacitor banks
Start / Stop Push Buttons 22.5 mm. for capacitor banks
Control Contactors with Control wiring
Installation of Capacitors
Power Wiring fo all the above capacitors from Bus bar to MCCB, MCCB to Cap. Duty Contactors & from Contcators to Capacitors with Proper size Copper flexible cables
APFC (Automatic Power Factor Correction Relay),415 V,digital type with Display of Power Factor 12 Step,Any DJB approved make
Wiring of New APFC Relay with Existing APFC relay (to work in series)
Supply and fixing of Exhaust Fan in the Panel Controlled thru' Thermo state, Control MCB, wiring etc.
Modification/Upgradation & Painting in existing Panel & fixing additional panel to match with existing panel with Bus bars.
Replacement of weak /damage capacitor in existing panel with new MPP Heavy Duty Capacitors of respective banks (IF FOUND WEEK DURING WORK EXECUTION). Make:- Siemens/L&T/BHEL/Crompton/Khatau/ABB/Any DJB aproved make.
Testing & Commissioning of the APFC Panel with relavent IS Standard, Checking continuity, Earthing, MCCB Mechanism, alignment, Checking all functional Test, Setting APFC Relay parameters to achieve PF between 0.98-1.00.
Premier Engineering Company
STANDARD CAPACITORS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .