| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.1 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical HARIPAD VENDOR VIJAYAMMA HARIPAD 690 314 | 690314 | - | Rejected-Technical Higher | |
| 3 | Rejected-Technical | - | Rejected-Technical Higher | |
| 4 | Rejected-Technical | - | Rejected-Technical Higher |
Tender Value
₹10.4 L
EMD Value
₹15,580
Closing Date
24 Dec 2021, 11:00 amClosed
Assistant Engineer
Assistant Engineer, LSGD Section, chettikulangara Grama Panchayat
136/21Old panchayath Office Building Electrification
2021_LSGD_460884_5
2/E-Tend/AE/LSGD/CGP/2021-22
Open Tender
Electrical Works
Item Rate
90 days
chettikulangara Grama Panchayat
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,500
Yes
₹15,580
Yes
18 Jan 2022
16 Dec 2021
29 Dec 2021
16 Dec 2021
24 Dec 2021
16 Dec 2021
Amount
PART - I - ELECTRIFICATON (List of Materials approved by the Technical Committee to be used for the work, attached separately)
90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.3 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.4 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.5 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).
90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
90.2.1.7 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
90.10.3.15 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )
90.10.3.17 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.33 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )
90.10.3.32 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
90.3.20.3 : Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.
od1495580/2021_2022 : Supply and fixing angle / straight brass lined skirt type, bakelite batten holder with 200mm polished shade with 9W LED and giving connection etc. as required
od1495645/2021_2022 : Supply and fixing cast aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy powder coated, heat resistant prismatic glass cover with 9 W LED to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor fle x wire conforming to relevant ISS or extending the original wiring and making good the surface as required.(Mepro /Philips/Crompton/Bajaj make)
90.15.4.1 : Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.2 : Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.1 : Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.2 : Supply and installation of suitable size MS belt type fan clamp fabricated from flat iron 40 x 6 mm, 150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required.
od1501630/2021_2022 : Supplying and installation of supports, anchor bolts etc made out of suitable size single section sqare tube, iron rods etc as required including welding painting with 2 coats of synthetic enamel paint
od1495774/2021_2022 : Supply and installation of 1200mm sweep ceiling fan with standard accessories with out regulator including giving connection with 16/0.20mm, 3 core round copper conductor flexible chord etc as required.(Crompton (High speed)/Havells(SS-390)
od1505152/2021_2022 : Supply and installation of 900mm sweap ceiling fan with standard accessories with out reglator including giving connection with 16/0.20 mm 3core round copper conductor flexible chord etc as required.(Crompton /Havells)
od1495799/2021_2022 : Supply and providing every additional length of down rod of suitable size heavy gauge GI / WI pipe with 16/0.20 mm 3core round copper conductor flexible chord etc. as required.
90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
od1495818/2021_2022 : Supply and installation of 225 mm medium duty 1350 rpm, 4 leaf exhaust fan in metal frame (Almonard/Crompton make) in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20 mm 3 core round copper conductor flexible chord etc as required.
90.5.1.3 : Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.
90.5.1.4 : Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.13 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm
1.17.15 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.22 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.23 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 4 sq. mm
1.17.24 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.30 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
90.6.4.63 : Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.
90.12.7.27 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.7.2 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.5.2 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.
90.12.9.2 : Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench
9.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.20 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)
90.11.1.18 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
90.11.1.11 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
2.16 : Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
od1503156/2021_2022 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof FP enclosure for independent mounting of MCB including DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess etc. as required.
2.3.1 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator6 way, Double door
2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.3.4 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
od1495859/2021_2022 : Supply and installation of 25 A double pole mini break isolator suitable for 50 Hz, AC supply conforming to IS 8828-1995/ IEC 60898 in the existing enclosure and giving connections as required.
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
od1495860/2021_2022 : Supply and installation of 40A, 10KA, TP MCB ( C curve) suitable for 50 Hz , AC supply conforming to IS 8828-1995/ IEC 60898 in the existing enclosure and giving connections as required.
od1495902/2021_2022 : Supply and installation of 50A and 63A, 10KA, TP MCB( C curve) suitable for 50 Hz , AC supply conforming to IS 8828-1995/ IEC 60898 in the existing enclosure and giving connections as required.
2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.2.1 : Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required100 Amp, 16 KA, TPMCCB
od1503868/2021_2022 : Supply and installation of 125 A, 415 V, 50 Hz, AC 23 A duty, 4 pole on-load change over switch in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required.
od1495864/2021_2022 : Earthing with G.I. earth pipe 2 metre long 40 mm dia (medium class) including providing 12 mm dia drilled holes minimum 20 nos along the entire length in alternate arrangement providing 40x25 mm GI reducer at top and test joint using 2 nos ,25x3mm GI Strip minimum size 25 cm suitably shaped and tightly clamped to the pipe electrode using 25x6 mm steel bolts nut and washer and providing 2 nos, 6 mm dia drilled holes for clamping and bolting earth lead , and making masonry champer with cover plate having locking arrangement and etc. ( charcoal and salt as required shall be filled at 30 cm dia around the earth electrode)
90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.1.4 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required
90.16.2.2 : Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
90.16.5.2 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
90.16.5.4 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.
od1495866/2021_2022 : Supply & Providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.
od1495871/2021_2022 : Supply and providing 12x3 mm of brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
od1495872/2021_2022 : Supply and providing 12 x 6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.
90.16.3.8 : Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)20 x 3 mm copper strip
od1503925/2021_2022 : Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.
od1495873/2021_2022 : Supply and Installation of Outdoor type HENSEL make meter box (600X300x214 mm Mi 2410) suitable to fix 3 Phase Energy Meter with provision to fix in the box / base plate with 1 set (3 Nos.) of bakelite HRC fuse fitting and 1 No. 2 way neutral link, LV CTs etc. complete and with 3 Nos. 100 A, 415V DIN Type HRC fuse holder and fuse link and 1 No. 100A, 2 way Neutral Link, fixed in SMC/ DMC base.
od1495897/2021_2022 : Supply and providing suitable size anchor bolt hook grouted on wall for service wire
od1500548/2021_2022 : Charges for dismantling the existing electrical installation and conveying as directed at site without further damages including plastering holes and grooves in the surface of wall etc.
od1495900/2021_2022 : Charges for preparation of KSEB service connection documents for availing new 3 phase service connection/conversion of existing single phase to 3 phase including preparation of drawing of existing load etc and producing to the consumer
NETWORKING
od1495913/2021_2022 : Supply and Fixing 19", 9U, 500mm Wall Mounting Rack with Front Glass door, cooling fan 90cm, NVRS - 1 No, Power Distribution Unit Rack mounting type - 1 no, for switches with cable manager and hardware mounting kit - Make: D Link/HCL/Valark/Netrack.
od1495921/2021_2022 : Supply, Installation, Testing and Commissioning of 24 port Gigabit Ethernet Switch with 10/100/1000 ports - Preferred make: D Link.
od1495922/2021_2022 : Supply and fixing CAT-6 24 Port, Enhanced Modular type Patch Panel for interconnecting servers and clients, including termination charges - Preferred Make: Molex/D-Link.
od1495923/2021_2022 : Supply and fixing CAT-6 Information Outlet with spring shutter, front access for inter connection of nodes and switches, including termination charges - Preferred make: Molex/D-Link.
od1495924/2021_2022 : Supply, laying, testing, certification and documentation of CAT 6, 1Mtr standard factory crimped patch chord - Preferred make:- Molex/D-Link.
od1495926/2021_2022 : Supply, laying, testing, certification and documentation of CAT 6, 2 Mtr standard factory crimped patch cord - Preferred make:- Molex/D-Link.
od1495927/2021_2022 : Supply, laying, certification and documentation of CAT-6, 4 pair UTP cable through the existing conduit / casing and capping as required. <br>Make: Molex/ D-Link.
od1495928/2021_2022 : Supply and fixing of 25 mm PVC conduits/ casing and capping with specials confirming to ISI standard on surface using suitable size fixtures, spacing not exceeding 50cm including making good the damage colour washing etc. as required.
od1495929/2021_2022 : Cutting of concrete floor having 1.0mx.05mx.05m(LxBxH) size for laying 25mm PVC conduit including reconditioning of the floor with ceramic tile/ concrete as required.
od1495930/2021_2022 : Testing of new node points and making permanent labeling on the I/O box and on the patch panel.
SUPPLY & PROVIDING UPS UNIT
od1501585/2021_2022 : Supply, installation testing and commissioning of BIS certified 6 KVA, True Online UPS Unit (120V) along with 10 No. of 12V, 150 AH Battery of superior quality with battery stand and a warranty of 1 year for UPS Unit & 3 years for Battery - Hykon or other equivalent superior make.
Kollamparampil
MONYS ELECTRICALS
USHA HARIKUMAR
Bidder Name
MONYS ELECTRICALS
Kollamparampil
USHA HARIKUMAR
K G UNNIKRISHNAN NAIR
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_659708.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .