| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹6.9 LAccepted-AOC HIMACHAL PRADESH HP | L-1 | Accepted-AOC Quoted rates are lowest | |
| 2 | L-2₹7.4 L+₹49,176 (7.15%)Rejected-Finance 82 10 POST OFFICE ROAD MANDI DISTT MANDI H P | L-2 | Rejected-Finance Quoted rates are above |
Tender Value
₹6.8 L
EMD Value
₹13,517
Closing Date
23 Feb 2023, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Superintending Engineer IIT Mandi HP 175075
Providing and fixing Three phase power points and foundation work for machines in Product Realization Lab (PRL) at (A14.03.04 and A14.03.11) at A14 ground floor, North Campus of IIT Mandi
2023_IITMD_736649_2
IIT Mandi (CW)/SE-1326/2022-23/5890-92 dt.23-01-23
Open Tender
Electrical Works
Item Rate
45 days
North Campus of IIT Mandi
please refer to NIT
2 documents required · 2 mandatory
₹1,180
The Registrar IIT Mandi
₹13,517
18 May 2023
14 Feb 2023
24 Feb 2023
14 Feb 2023
23 Feb 2023
14 Feb 2023
14 Feb 2023 - 22 Feb 2023
Amount
Supplying and drawing 5x4 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit/Casing/Wall Trunk as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Providing and fixing 125 A,36KA,FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Supplying and fixing of 8 way (4 + 24), Double door surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Supplying and fixing Triple pole 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of Single pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A "C" curve, FPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Supplying and installing 300 mm width X 50 mm depth X 1.6 mm thickness size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40X3 mm MS flat clamp) as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 120 sq. mm (45mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Supplying of 3.5 Core x 120 Sq. mm of 1.1 KV Aluminium conductor XLPE Insulated,PVC extruded inner-sheathed, round wired unarmoured, overall PVC outer-sheathed (as per IS 7098 Part 1) with latest amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Providing and fixing 10 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Civil items:- Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within all lead of 50 m. All kinds of soil as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : Concrete of M25 grade with minimum cement content of 300 kg /cum as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.
M/s Texas Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .