Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.0 LAccepted-Finance | L1 | Accepted-Finance Technically Qualified | |
| 2 | L2₹10.7 L+₹70,701 (7.07%)Accepted-Finance | L2 | Accepted-Finance Technically Qualified | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 4 | Not Admitted-Fee/PreQual/Technical HOUSE NO 214 WARD NO 2 TEHSIL SUJANPUR DISTT HAMIRPUR HP | HAMIRPUR | HIMACHAL PRADESH | 174304 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹10.0 L
EMD Value
₹20,000
Closing Date
28 Oct 2020, 5:00 pmClosed
Executive Engineer
Elect. Division HPPWD Palampur
Providing and installation of online UPS 40KVA for additional power back-up along with wiring in operation theatres 1 to 5, 2nd floor of 500 bedded hospital Dr.RPGMC Kangra at Tanda
2020_PWD_41600_2
Elect. Division, HPPWD Palampur
Open Tender
Electrical Works
Item Rate
30 days
Kangra at Tanda
Please refer Tender documents.
9 documents required · 9 mandatory
₹350
Executive Engineer
₹20,000
7 Dec 2020
14 Oct 2020
29 Oct 2020
14 Oct 2020
28 Oct 2020
14 Oct 2020
Amount
Supplying, erection, testing and commissioning of 40 kVA/40 kW online pure sine wave UPS with enclosure suitable for 3 phase AC input and 3 phase AC output with battery backup one hour with (min. VAH = 46800 VAH). The UPS should be of Microprocessor control double conversion, PWM (Pulse Width Modulation)/IGBT (Insulated-Gate Bipolar Transistor) based invertor with touch screen display for monitoring of its status and complete with closed battery rack. The UPS should be complete with input 415 V AC 3 ph + N (± 15%) and Output 400 V /415 V AC (± 1%) 3 Ph (380 V Optional), Manual by-pass facility, harmonics distortion at output: <2 % for Linear Load and <5% for Non-Linear Load, Power Factor Handling Capacity 0.6 to Unity within KVA and KW rating, Over load: 110% for 60 min, 125% for 10 min, 150% for 60 sec. including the cost of carriage, rack and connection etc. as required complete in all respects and to the best satisfaction of Engineer-in-charge.
40 KVA Online UPS System
Make:- Numeric/Emerson-Virtiv/APC/Microtek/ Zebronics/Delta/Fuji Electic-Consul Neowatt.
Battery bank minimum VAH 46800 (Makes: Exide/Quanta/Panasonic/APC/Zebronics)
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No. HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.
2x6.0 Sq. mm.
Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Single pole. Cat-A.
Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Double pole. Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 Amps. Cat-A.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-
Double door-8 way
Supplying and fixing Per Phase Isolation (PPI) box 4 Way including connections, testing & commissioning of the respective accessories of the same as required complete in all respects and to the best satisfaction of Engineer-in-charge.
PPI 4 Way Make: L&T (Cat. No. DBPGL004DD) or equivalent.
M/s Jamwal nxt gen energy solutions
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .